Elsa 3L-DF-SP & SM50 Catalogue-Mar 2019

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 2

GENERAL FEATURES:

• 3L-DF/SP is a Supervising panel to monitor and directly power each 3L-DF/SM50 sensor modules linked (up to 40 units).

• Each 3L-DF/SM50 is an independent sensor module (no length association) and connected with cut-to-length
liquid leak detection sensing cable (3L-LS, 3L-AS and/or 3L-AD).

• Reliable frequency modulation is used for the digital communication between the panel and the modules.

• Precision to locate leak location : +/-1m or 0.5%

 Redundancy :Fail-Safe Loop Back or Token Ring connection feature built-in.


(Able to detect leak even cable break at 1st meter location).

• LCD Display : Backlight with LCD of 4 lines x 20 English characters

• Sound Alarm : 90dB max. buzzer with silencing button

• System Menu : Access to Event Log, System Reset, Configuration Mode

• Multiple leak alarms simultaneously : Yes (No. of simultaneously leak = No. of 3L-DF/SM50 sensor modules in use).

• Max accumulated length of sensing cable : up to 2,000m :


o eg: 40 units of 3L-DF/SM50 x [ 50m of Sensing cable connected on each 3L-DF/SM50 unit] .
(Note: 3L-LS or 3L-AS Sensing cables comes with standard length of 1m; 3m; 7m and 15m.)

• 3L-DF/SP Box dimensions : Rugged ABS UL-VO case of L222 x W146 x H55mm.
3L-DF/SM50 Box dimensions : Moulded in ABS case of L50 x W38 x H25mm. IP67 rated.

 Zone names setup : By PC-software (input each zone name up to 35 characters).


 Event Log : 896 Time-stamped Events stored in non-volatile memory,
First-In-First-Out (in case overflow)
ENVIRONMENTAL RATINGS
Operating temperature : 0°C to 40 °C (indoor installation only)
Storage temperature : : -20 °C to 70 °C
Humidity : : 5% to 95% non-condensing

POWER REQUIREMENTS
Power supply : 100 - 240VAC
Optional input : 12 - 24VAC/DC
Power consumption : 8 VA/3 W maximum

POWER RELAYS SWITCHING CHARACTERISTICS


Cable break/power failure by contact : Operation – SPDT
Switching current – 0.5 A at 250 VAC, 1A at 30 VDC

Liquid leakage dry contact : Operation – SPDT


Switching current – 0.5 A at 250 VAC, 1A at 30 VDC

SERIAL COMMUNICATION INTERFACE


Physical support : Opto-isolated RS485-two-wire, ESD and surge protected as per IEC 61000-4-2
Protocol : Modbus
Optional GSM/GPRS transmitter interfacing
Optional Modbus over TCP/IP (allow world-wide remote supervision through Internet connection)
Optional BACnet/IP interface
Optional Profibus interface
Optional LONworks interface

COMPLIANCE TO INTERNATIONAL STANDARDS


EMC emission : IEC61000-6-3(2001) –
Electromagnetic compatibility
Generic emission standard for residential,
commercial and light industrial environment

EMC immunity : IEC61000-6-1(2001) –


Electromagnetic compatibility
Generic immunity standard for residential,
commercial and light industrial environment