39214-048/Issue 7

Note
1. All circuits are power limited except for relay contacts. If the relay contacts are connected
to a non power limited source, remove the lower portion of the power limited label along the
kiss cut. Use only limited energy cable types FPL, FPLR or FPLP on power limited circuits.

Specifications
Part No 55000-820
Compatibility Identifier 55000-820
Type Switch Monitor Input/Output Module
Style Fascia plate with wiring terminals
Dimensions 4½” x 4½” x 1”
Temperature Range 32ºF to 120ºF (0ºC to 49ºC)
Humidity 10 to 93% RH Non-condensing
Wiring Size 24AWG - 14AWG
Signal Line Circuit (SLC) Supervised Power Limited
Working Voltage 17-28V dc
Modulation Voltage 5-9V (peak to peak)
Operating Current Supervisory Current 2.5mA
Surge Current
Maximum Alarm Current
7.5mA
6.0mA (LED on)
XP95A Switch Monitor Input/Output Module
Functional States Analog Level (Normal)
Analog Level (Alarm)
16
64
Installation Instructions
Analog Level (Trouble) 4
Initiating Device Circuit (IDC) General
Wiring styles Supervised power limited Class A and Class B The XP95A Switch Monitor Input/Output Module, part no 55000-820, is a loop-powered device
Voltage 10V dc which incorporates a monitored input circuit for connection to remote switches. It also has an
Current 1.7mA max unmonitored opto-coupled input and volt-free relay output. It is mounted on a plastic fascia
Line impedance 100Ω max plate for use with a 4" square or 2 gang electrical backbox (minimum depth 2⅛”).
End-of-Line Resistors 47KΩ (A UL listed end-of-line resistor is available from Apollo and
can be ordered under part number 44251-146). A red LED flashes in synchronization with the current pulse reply from the device. If output bit 2
Open Collector Input Not supervised is set, the LED is illuminated continuously.
Logic 1 is > 4V dc
Logic 0 is < 1V dc Note: the XP95A Switch Monitor Input/Output Module is designed for indoor use only.
Relay Output Non supervised, programmable, dry contact
24V dc, 1A:30V ac, 0.5A (resistive) Control Panel Compatibility
The module has been listed by Underwriters Laboratories Inc. For details of compatible control
Functional Test Data panels contact Apollo Fire Detectors Limited. Please check fi re control panel literature for com-
Output Bit Function Input Bit Function patible Apollo devices.
2 Alarm LED 2 Alarm LED Confi rmation Installation
1 = On 1 = On These products must be installed in accordance with the applicable NFPA standards, local
0 = Off 0 = Off codes and jurisdictional authorities. Failure to follow these instructions may result in failure
of devices to report an alarm condition. Apollo Fire Detectors Limited is not responsible for
1 Not Used 1 Indicates Class Wiring devices which are improperly installed, maintained and tested.
1 = Class B*
0 = Class A Before installing these products, check the continuity, polarity and insulation resistance of all
wiring. Check that siting is in accordance with the fi re system drawings and conforms to all
0 Relay Control 0 Opto-isolated Input Status applicable local codes such as NFPA 72.
1 = On 1 = Input low
0 = Off 0 = Input high 1. Mount the electrical box as required and install all cables for termination. Where applica-
ble ensure that cable shield/earth continuity is maintained.
* Note: Toggles to ‘0’ in alarm.
2. Drill holes in the fascia plate corresponding to the holes on the mounting box selected (Fig. 1).

3. Terminate all cables in compliance with local codes and regulations.


©Apollo Fire Detectors Ltd 2017
4. Set the address of the module as shown on page 3.
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754 5. Gently push the completed assembly towards the mounting box and align the fi xing holes.
Email: [email protected] Website: www.apollo-fire.co.uk Secure the unit with the screws provided. Do not overtighten the screws.
In the USA: Apollo America Inc., 25 Corporate Drive, Auburn Hills, Michigan, 48326, USA 6. Commission the module.
Tel: (248) 332-3900 Fax: (248) 692-0888
Email: [email protected] Website: www.apollo-fire.com

4 1
Relay Functionality
The relay is operated by setting output bit 0. If the supply voltage is removed, the relay will not
change state. When the Switch Monitor Input/Output Module is powered up, the relay will be WIRING CLASS
in the same state as it was prior to the module being switched off but the module will respond
to output bit 0 four seconds after power has been applied. If the module has not been interro- 0 A
gated, a relay reset will automatically be applied.
ON

1 2 3 4 5 6 7 8

1 2 4 8 16 32 64

1 B
ADDRESS
© Apollo Fire Detectors Limited 2004-2009/JDR/TP

Fig. 3- DIL Switch


Address Setting
Segments 1-7 of the DIL Switch are used to select the address of the module. Each of the seven
segments must be set to ‘0’ (ON) or ‘1’ (OFF) using a small screwdriver or similar tool. A com-
plete list of address settings is shown below (The eighth segment of the switch is used to select
Class A or B wiring).
© Apollo Fire Detectors Limited 2004/JDR/JLC

DIL switch DIL switch DIL switch DIL switch DIL switch
Fig. 1- Mounting the XP95A Switch Monitor Input/Output Module addr setting addr setting addr setting addr setting addr setting
1234567 1234567 1234567 1234567 1234567

1 1000000 11 1101000 21 1010100 31 1111100 41 1001010


NON-POLARIZED 2 0100000 12 0011000 22 0110100 32 0000010 42 0101010
30V dc max
OPTO-ISOLATED All circuits are power limited. Use only limited 3 1100000 13 1011000 23 1110100 33 1000010 43 1101010
Logic 1 is > 4V dc
INPUT
energy cable types FPL, FPLR or FPLP on power 4 0010000 14 0111000 24 0001100 34 0100010 44 0011010
Logic 0 is < 1V dc limited circuits. 5 1010000 15 1111000 25 1001100 35 1100010 45 1011010
Any number of UL contact devices may be used. 6 0110000 16 0000100 26 0101100 36 0010010 46 0111010
Do not mix fire alarm, supervisory or security 7 1110000 17 1000100 27 1101100 37 1010010 47 1111010
devices on the same monitor module. 8 0001000 18 0100100 28 0011100 38 0110010 48 0000110
9 1001000 19 1100100 29 1011100 39 1110010 49 1000110
OPTO N/C
INPUT 10 0101000 20 0010100 30 0111100 40 0001010 50 0100110
COM 1 Amp 30V dc
N/O
Class B wiring method 51 1100110 61 1011110 71 1110001 81 1000101 91 1101101
L2 47K, 52 0010110 62 0111110 72 0001001 82 0100101 92 0011101
+ ½W,
A/B + 53 1010110 63 1111110 73 1001001 83 1100101 93 1011101
5% EOL
A+
54 0110110 64 0000001 74 0101001 84 0010101 94 0111101
A–
L1 Initiating devices 55 1110110 65 1000001 75 1101001 85 1010101 95 1111101
A/B –
– 56 0001110 66 0100001 76 0011001 86 0110101 96 0000011
Class A wiring method 57 1001110 67 1100001 77 1011001 87 1110101 97 1000011
58 0101110 68 0010001 78 0111001 88 0001101 98 0100011
59 1101110 69 1010001 79 1111001 89 1001101 99 1100011
60 0011110 70 0110001 80 0000101 90 0101101 100 0010011
© Apollo Fire Detectors Limited 2007-8/TP

Incoming 101 1010011 111 1111011 121 1001111


communications 102 0110011 112 0000111 122 0101111
loop 103 1110011 113 1000111 123 1101111
104 0001011 114 0100111 124 0011111
105 1001011 115 1100111 125 1011111
Outgoing
communications 106 0101011 116 0010111 126 0111111
loop 107 1101011 117 1010111
108 0011011 118 0110111
Fig. 2- Wiring Diagram for XP95A Swtich Monitor Input/Output Module 109 1011011 119 1110111
110 0111011 120 0001111

2 3