1. Scope
1.1. This specification covers the design, manufacture, testing, supply, delivery of three
phase pole mounted Hermetically sealed outdoor Distribution Transformers with
natural or air cooling.
1.2. The transformers shall be suitable for Operation in outdoor exposed locations.
1.4. The transformer shall conform in all respects to the highest standards of engineering,
design, workmanship of this specification and the latest revisions of IEC standards at
the time of offer and the purchase will have full right to reject any work or material
which are not in full accordance therewith. The offered equipment shall be complete
with all components necessary for effective and trouble-free operation. Such
components shall be deemed to be within the scope of the bidder’s supply irrespective
of whether those are specifically mentioned or not.
1.5. This Specification may not include all the necessary provisions of the contract
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
S. N Item Parameter
Minimum -50c
Maximum 500c
6 Wind Velocity:
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
3. Reference Standard
The transformer shall comply in all respects to relevant international standards with the
latest editions or amendments thereof. In the event that no reference to Standard is made
herein, all components and parts shall be fabricated, inspected, tested and preserved, so as
to ensure their fitness for designed use and purpose. The bid shall include typical
dimensional and sectional drawings of the transformers and accessories.
Relevant
Standard Title
Identifications
IEC 60071 Insulation co-ordination
IEC 60076 Power Transformers
IEC 60137 Insulating bushings for alternating voltages above 1000 V
IEC 60214 On-Load Tap Changers
IEC 60296 Specification for unused mineral insulating oils for
transformers and switchgear
IEC 60317-0-1-2013 Specifications for particular types of winding wires-Part 0:
General Requirements-Section 1: Enameled round Copper
wire
IEC 60354 Loading guide for oil-immersed power transformers
IEC 60529 Degrees of protection provided by enclosures (IP Code)
IEC 60551 Determination of Transformer and reactor sound level
IEC 60554-3-1 Specification for cellulosic paper for electrical purposes-
Part 3: Specifications for individual materials, sheet 1-
General purpose electrical paper.
IEC 60567 Guide for sampling of gases and oil from oil filled
electrical equipment and analysis of free and dissolved
gases
IECITR 60616 Terminal and tapping markings for power transformers
IEC 60071-2 Insulation co-ordination Part 2 Application guide
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Standard Title
Identifications
IEC 60722 Guide to the lightning impulse and switching impulse
testing of power transformers and reactors
In the event of direct conflict between various order documents, the precedence of authority of
documents shall be as follows –
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
4. DESIGN OF TRANSFORMERS
4.1 General
4.1.1 The transformers shall be three phase or single-phase units of the hermetically
sealed tank type with oil immersed copper windings and shall be naturally cooled
(ONAN). They shall be suitable for operation in outdoor exposed locations. All
the active parts shall be completely submerged in oil and a pressure relief valve
and oil gauge mounted on the LV side of the top cover without overextended pipe
above the cover surface. The tank design shall allow for oil expansions under
normal and fault conditions as per service conditions.
4.1.2 The transformers shall be capable of operating continuously with rated power, and
at 30 °C average yearly temperature and at 50 °C maximum yearly temperature of
the external cooling medium, their specified temperature rise limits, i.e., the
maximum permissible temperature rise of the oil (top oil) shall not exceed 50° C,
the average temperature rise of the winding is to be limited to 55°C, and the
winding hot spot temperature rise shall not exceed 68°C as per IEC 60076-2.
If the annual temperature varies from 20°C, we will apply correction factors as
per IEC60076-2 Clause 6.3.2 (Table 2).
4.1.3 The transformers shall be capable of withstanding external short circuits for at
least 3 seconds following application of loading conditions specified in IEC
60076-7. The transformer shall have a minimum insulation life of 20.55 years and
service life at least 25 years
4.1.5 All specific schedules of guaranteed characteristics are stipulated in the technical
schedule. The transformers shall be designed and tendered in full compliance with
all further applicable sections, articles and drawings of the Specification.
Furthermore, each transformer shall comply with the stipulations mentioned
hereunder.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
4.1.6 All outdoor apparatus, including bushing insulators with their mountings, shall be
designed so as to avoid any accumulation of water.
4.1.7 The transformers of ratings 25kVA, 50kVA, 100kVA, 200kVA, 315kVA and
400KVA shall be pole mounted type
The transformers shall be core type oil immersed ONAN cooled, for outdoor
application, designed for continuous operation in the prevailing site conditions.
The design shall be based on site and service conditions as specified in this
specification.
The design of the magnetic circuit shall be of non-ageing, Cold Rolled Grain
Oriented (CRGO) Silicon steel of minimum of M3 Grade (Nominal thickness of
0.23mm and maximum total loss at 1.7T to be 0.85w/Kg or better as per IEC
60404-8-7) high permeability without burrs and such as to avoid static
discharges, development of short circuit paths within itself or to the earthed
clamping structure and production of flux components at right angles to the plane
of laminations which may cause local heating.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Each lamination shall be insulated with high quality insulation coating. The core
and its Clamping plates shall form a rigid unit structure, which shall maintain its
form and position under the severe stresses encountered during shipment,
installation and short circuits.
All parts of the cores shall be of robust design capable of withstanding any
shocks to which they may be subjected during lifting, transport installation and
service.
All structural members of the assembled cores shall be of steel. All castings shall
be fettled and structural steel adequately cleaned and painted before being built
into the structure any non-magnetic or high resistance alloy used shall be subject
to approval.
Adequate fitments shall be provided to enable the core and windings to be lifted
out of the transformer tank.
The supporting frame work of the cores shall be designed so as to avoid the
presence of pockets which would prevent complete emptying of the tank through
the drain valve or cause trapping of air during filling.
Prepared by Sign Checked by Sign Approved by Sign Rev.No. Date Page
Abebaw Belay Elias Azene Chala Aman 03/2021 Aug 13,2021 No. 7
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
The framework and core bolts shall be effectively insulated from the core so as to
reduce circulating currents to a minimum.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
4.4 Windings
4.4.1 General
The HV and LV windings shall be made of continuous smooth high-grade
electrolytic copper as per IEC 60317. The characteristics of copper required shall
be as per IEC 60076-5. The Purchaser will inspect the quality of copper material
used: size of copper, number of turns, weight of copper and density…etc.
The three medium voltage windings of the transformer shall be identical in order
to allow interchangeability.
Terminals of all windings shall be brought out of the tank through Bushings for
external connections.
The windings Shall be uniformly insulated and the LV neutral points Shall be
insulated for full voltage.
The completed core and coil assemble shall be dried in vacuum at not more than
0.5mm of mercury absolute pressure and shall be immediately impregnated with
oil after the drying process to ensure the elimination of air and moisture within
the insulation. Vacuum may be applied in either vacuum over or in the
transformer tank.
The stacks of windings shall receive adequate shrinkage treatment before final
assembly.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
All leads or bars from the windings shall be brought out of the tank through
bushings for connection shall be rigidly supported. Stresses on coils and
connections must be avoided.
The coil clamping arrangement and the finished dimensions of any oil ducts shall
be such that they will not impede the free circulation of oil through the ducts.
Any metal pieces in contact with end rings shall be so designed and secured that
they do not weaken the electrical or the mechanical properties of the rings.
There shall be double layer enamel insulation for the copper winding conductor. The
insulation shall be of class A with temperature class of 105oC as per IEC 60085.
Grade K- Diamond dotted Press Paper (Thermopox): is a press paper with qualities
to improve the mechanical strength of oil immersed transformer windings without
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
reducing partial discharge levels in accordance with IEC standards 60641-2 and
60243-1
Crepe Paper: Crepe Papers shall be of type 3.2-130-100F or better in accordance with
IEC 60554-3-3. It shall have high elongation insulating properties useful for joining
and forming tapping leads of transformers. They shall have low dissipation factor
suitable for high voltage bushings of transformers, wire wrapping, and shielded rings
placed within end sections of Power transformer windings. Crepe papers shall be made
from high quality electrical grade Kraft base papers (100% sulphate wood pulp). The
technical characteristics of the paper according to IEC standards 60554-2 and 60243-1.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
4.6 MV Bushings
4.6.1 General design
Bushings shall be outdoor type, easily replaceable and shall be located on the
top. Bushing Material Shall be Porcelain material. Cemented in type bushing
shall not be accepted. The Bushing Shall be manufactured and tested in
accordance with IEC 60137 and DIN 42530, DIN 42532, DIN 42534 and
DIN42539.
MV bushings shall be rated to withstand the highest system voltage and the
maximum fault current of the windings when connected to the 15kV network
and for the same period of time.
It shall be possible to change the bushings without removing the transformer lid.
Each bushing shall be marked with the name of the manufacturer and type. The
marking shall be visible after assembly of the fittings.
4.6.2 The bushings shall be equipped with line clamps suitable for the connection of
aluminum (up to 240mm2) or copper (up to 120mm2) conductors of medium
voltage line. The clamps shall be complete with necessary screws, washers and
nuts.
Clearance
Voltage Phase to Phase Phase to Earth and Phase to Neutral Creepage Distance
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
The outer creepage distance for outdoor bushings shall not be less than
31mm/kV. The insulation levels of the bushings shall conform to the given in the
technical schedule.
The Bidder shall submit to the Purchaser Type tests reports of medium voltage
bushings, for approval of the bushings in the proposed transformers. The type tests
shall be performed according to the latest published International Standard IEC 60137
and shall include the following type tests:
Wet power-frequency voltage withstand test
Dry lightning impulse voltage withstand test
Temperature-rise test
Verification of thermal short-time current withstand test
Cantilever load withstand test
Verification of dimensions
The MV Rod diameter shall be greater than or Equal to M20 depending the current.
4.7 LV Bushings
The position of each LV bushing shall be permanently and legibly marked on the tank
or lid with a label corresponding to the rating plate designation. The LV neutral
connection shall have a permanent, special marking, different from the phase
connections.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
bracket may be provided that can be attached to the tank of the transformer, to offer
support to ensure no damage of the bushings because of movement of the AB cable.
The LV bushings shall be equipped with line clamps suitable for connecting
aluminium and copper conductors as follows. LV bushings shall have phase clamp up
to 185 mm2, neutral clamp 120 mm2. A suitable LV clamps and/or a terminal pad to
take multiple conductors shall be provided. The clamps shall be complete with
necessary screws, washers and nuts.
The LV Rod diameter shall be greater than or Equal to M20 depending the current.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Every care shall be taken to ensure that the design and manufacture of all transformers
and auxiliary plant shall be such as to reduce noise and vibration to the level of that
obtained in good modern practice.
The Transformer shall be capable of carrying its normal rating continuously at any tap
without undue stress and Overheating.
All transformers shall be capable of withstanding for three seconds without damage
any external short-circuit.
Any wiring liable to come in contact with oil shall have suitable oil resisting
insulation. The ends of stranded conductors shall be treated to prevent creepage of
oil inside the wire. There shall be no possibility of oil entering connection boxes
for cables or wiring.
Where the use of conduits is agreed the runs shall be laid with suitable falls and the
lowest parts of the run shall be external to the kiosks or boxes. All conduit-runs
shall be adequately drained and ventilated. Conduits shall not be run at or below
ground level. The external cabling on transformers shall be armored or alternatively
protected from mechanical damage in an approved manner.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Rated short
duration power Rated lightning
Highest voltage frequency impulses
System for equipment withstand voltage, withstand voltage,
Voltage(kV) Um kV (rms.) kV(rms.) kV (peak.)
15 24 50 125
4.13.3 Rated Power
The rated output at +50 °C maximum ambient temperature shall be one of the
preferred ratings 25, 50, 100, 200, 315 and 400 Rated Voltage
The transformers are required to operate from the 15kV network as follows:
((15/.22)
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE (Phase
BEFORE USE to Neutral)) KV
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
All secondary voltage ratings shall be at full load current at nominal tap.
KVA
Rating 25 50 100 200 315 400
The off-load tap changer shall have an externally operated mechanism for manual
operation. The selector switch shall be gang-operated by an accessible single
handle from the ground at convenient floor height Tap positions shall be clearly
identified. The operating mechanism shall have an effective locking device for
locking the tap changer in any desired position. All transformers shall be capable of
operation continuously without injurious sheathing when operating on any tapping
position and at 150% continuous loading and over-voltage surges.
4.15 Losses
The bid shall be accompanied with Type test reports (Short circuit test and Impulse
test) conducted at independent third-party testing Laboratories for the offered
transformers including the surge arrestor within five years from the date of the bid.
Type tests shall be conducted on the Transformers of identical design to prove that
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
the offered transformers satisfy all the design requirements set out in this
specification.
In case of any doubts, Ethiopian Electric Utility (EEU) reserves the right to verify
the original type test reports of the independent third-party testing Laboratory or
ask the supplier to conduct the type tests at an independent third-party independent
testing laboratory which is approved by EEU Type test without ADDITIONAL
COST to the employer (EEU)
The maximum Load losses and No-Load losses at rated load and conditions shall
be as given below:
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
The above losses are the maximum allowable and there should not be any positive
tolerance. Bids with higher losses than the above specified values would be treated
as non-responsive and will be rejected automatically.
Bidders are required to submit their guaranteed No losses and Load losses (at
75oC) for each proposed transformer type.
However, the manufacturer/Supplier can offer losses less than the above stated
values. The utility will evaluate offers with losses lower than the maximum
allowable losses on total owning cost basis in accordance with IEC 60076-20-2017
Appendix A.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
In comparing Bidder’s proposal and for Penalty losses will be capitalized at the
rates given Below:
If the Bid currency is other than US$ the exchange rate at the time of bid
submission will be used.
If, on delivery, the tested losses exceed the guaranteed losses up to 20% then losses
in excess of the guaranteed values shall be capitalized at the evaluation rate and the
amount deducted from the contract price. If the measured value of loss is above
20% of the quoted value, the purchaser shall reject the transformer.
There will be no credit for losses less than the guaranteed value other than for
evaluation purposes.
The tank design shall be such that the core coil assembly can be lifted freely.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Lifting lugs shall be available for lifting the core and coils out of the tank. The
hooks that will be used for anchoring the core shall be so located as not to foul with
the core coil assembly.
Gaskets used shall be oil resistant and made of such a material that no serious
deterioration occurs under service conditions. Rubber gaskets used for flange
connections of the various oil compartments shall be laid in grooves. Gaskets of
neoprene and/or such material which can be easily damaged by over-pressing (e.g.,
any kind of impregnated/ bonded cork) are not acceptable. Use of hemp as gasket
material is also prohibited.
All transformers shall be capable of giving their continuous rated output without
exceeding the specified temperature rise.
The smaller parts such as brackets, etc. shall be hot-dip galvanized. Fasteners
mounted on hot-dip galvanized or ready painted part shall be galvanized or made of
stainless-steel ISO class F1 or A2.
All steel surfaces shall be sand blasted in accordance with DIN 55928 Part 4 and
shall then be painted in the following sequences.
Prepared by Sign Checked by Sign Approved by Sign Rev.No. Date Page
Abebaw Belay Elias Azene Chala Aman 03/2021 Aug 13,2021 No. 21
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Layer
Coatings Kind Thickness
One (1) primer two-component epoxy zinc phosphate 60µm
coat
One (1) Two-component epoxy micaceous 60µm
intermediate coat iron oxide
One top coat (1) Two-component polyurethane 40µm
Total coatings thickness (dry film) 160µm
The final coat of painting shall be of pore free and homogeneous quality and shall
be of a uniform shade of code RAL 7032(silica grey) paint for the outside surfaces.
Manufactures are free to select the inner transformer paint color.
If any hot dipped galvanized parts are provided the same painting method shall be
applied, however instead of two primer coats one adhesive coat and one base coat
shall be applied. In this case the mean thickness of galvanizing shall be 70 µm.
Mechanical damage shall be repaired at site with original paint as above.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Each transformer shall be supplied with standard insulating oil conforming to the
requirements of IEC 60156 and the oil shall have a high dielectric strength
(breakdown voltage >70KV).
The type of insulating liquid, e.g., “Mineral oil-based insulating oil pursuant to
DIN VDE 0370”/relevant IEC is to be indicated on the rating plate of each
transformer.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
The fixing arrangement for the surge arresters shall be universal type to accept a
wide range of Lightning/Surge arresters and shall be subject to approval by
Ethiopian Electric Utility before manufacture.
All ferrous parts of mounting brackets shall be protected against corrosion by the
hot dip galvanizing to ISO 1461.
The bid shall be accompanied with Type test reports conducted at independent
third-party testing Laboratories for the offered Lightning Arrester within five years
from the date of the bid.
4.19 Undercarriage
The following undercarriage shall be provided as specified in the technical
schedules.
Transformers shall be fitted with an under frame suitable for bolting the
transformer to a pole mounted platform in case of pole mounted transformers.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
A grounding sign shall be put next to the grounding screw. The marking shall be
stamped and red color painted on tin plates which shall be fastened with
transformer.
1) Rating and diagram plates bearing the data specified in the appropriate IEC
recommendations.
2) Oil filling and drain valves. It shall only be possible to open these valves with a
special key/spanner to discourage tampering.
3) Tank earthing terminal. M12 size screws -2 Nos. one on the tank cover and another
on the base frame suitable for copper earthing wires.
5) Oil level indicator: This shall be readable by an operator standing at ground level at
distance of up to 5 meters away from the transformer. It shall have maximum and
minimum oil level markings which shall fall within range.
8) Pressure relief Device: The pressure relief device shall have a flow rate of 16.5
litres/sec at 100KN/sqm operating pressure shall be 40KN/m2
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
15) Galvanized steel plates (for installation of lightning/Surge arresters and fuses)
1. Type Tests,
3. Acceptance Tests.
Prior to the tests the supplier shall submit an outline of the procedures and tests in its plans,
to demonstrate fulfilment of the requirements specified in subsequent sections of the
detailed technical specification.
Before regular manufacturing commences, samples of the equipment i.e. The transformers
shall be made available for testing to ensure compliance with the design.
The Buyer reserves the right to call for type tests on the equipment at the Supplier’s
expense, on samples selected at random at the Manufacturer's Works and witness these
tests at an approved independent third-party standard Laboratory. Failure to meet the
conditions of test could result in the rejection of a complete batch of equipment’s.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
The Buyer will have the authority to delay delivery of any items of equipment, which have
not been tested and approved in accordance with the Contract.
The Supplier shall report on progress and will compare the Supplier’s production program
with actual progress and shall report in a timely manner to the Employer the reason for any
delays.
The Supplier shall submit copies of the Routine test reports of the equipment/ material
along with the inspection offer.
The inspection and acceptance tests shall be carried out in accordance with the provisions
in the applicable standard, supplemented by the specific requirements indicated in the
technical specifications free of cost to the Employer.
At least 15 days’ notice of the date, time and place of all tests shall be given to the Buyer so
that arrangements can be made to have the test witnessed.
In addition to the above requirements, the following requirements shall apply and take
precedence.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
3) Measurement of short circuit impedance and load loss (IEC 60076-1, clause 11.4)
8) Leak testing with pressure for liquid immersed transformers (IEC 60076-clause
11.8).
9) Tightness tests and pressure tests for tanks for gas filled transformers (IEC 60076-
15).
10) Check of core and frame insulation for liquid immersed transformers with core or
frame insulation (IEC 60076-clause 11.12).
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
1) Visual Inspection
3) Voltage ratio measurement and check of polarity or vector group symbol - at all tap
positions. Bushing positions shall have permanent markings at this stage of
production.
8) Dielectric test
9) Induced over voltage withstand test - 30kV and 66kV for 60 seconds on the 15kV
and 33kV windings respectively.
11) Coordination test for LV circuit breaker and HV Fuse links, if applicable.
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
6. Marking
Each transformer shall be provided with a rating plate showing the information stated in the
IEC standards. The plate shall be in both Amharic and English. The words "Property of
Ethiopian Electric Utility", the EEU logo, the contract number and loan number and a
unique identification number (to be advised by the Employer) shall also be engraved on the
rating plate.
1) A rating plate bearing the data specified in IEC 76 or other approved standard.
Indicating the following shall be fixed on the same side as LV bushings,
2) Name of manufacturer,
4) Year of manufacture,
5) Rated power,
6) Rated frequency,
7) Rated voltages,
8) Rated currents,
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
17) Each bushing shall be marked with the name or trademark of the manufacturer,
18) A diagram plate showing the internal connections and also the voltage vector
relationship of the several windings. In addition, a plan view of the transformer
giving the correct physical relationship of the terminals shall be given. When links
are provided for changing the transformer group symbol and/or ratio, then means
shall be provided for clearly indicating in which mode the transformer is
connected. The transformer ratio shall be indicated for each tap,
20) The above plates shall be of anodized sheet aluminium OR stainless steel or of
other material capable of withstanding continuous outdoor service and shall all be
suitably mounted to prevent vibration, rattling or corrosion.
7. TRANSPORT
Irrespective of the actual method approved for transport to the individual site, all
transformers shall be suitable for transport with the transformers full of oil unless otherwise
approved.
The Supplier shall be responsible for ascertaining the methods and limitations of transport
to site and designs affected by these factors be subject to agreement.
8. PACKAGING
Each Packaging Shall be clearly marked in Print (Capital Letters) with the following data in
each transformer:
Manufacturer/Supplier Name and Trademark
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
9. QUALITY PLANS
The bidder shall draw up for each section of the work quality plans which shall be
submitted to the Purchaser for approval at least two weeks prior to the commencement of
work on the particular section. Each quality plan shall set out the activities in a logical
sequence and, unless advised otherwise, shall include the following:
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
16 Frequency Hz 50
17 Principal tapping KV 15
Maximum Continuous System
18 withstand Voltage KV 17.5
19 Rated Voltage of the equipment KV 24
20 Impedance voltage at rated power % 4
III. WINDINGS
20 HV Windings
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
25.3 Maximum Winding Hotspot °C 68
V. TRANSFORMER LOSSES AND ENERGY PERFORMANCE
No-load loss at rated voltage and
26 frequency (@75 °C) W 70
27 Full load loss (@75 °C) W 900
28 Rated voltage at full load (P.F=0.95) KV
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
16 Frequency Hz 50
17 Principal tapping KV 15
Maximum Continuous System
18 withstand Voltage KV 17.5
19 Rated Voltage of the equipment KV 24
20 Impedance voltage at rated power % 4
III. WINDINGS
20 HV Windings
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
25.3 Maximum Winding Hotspot °C 68
V. TRANSFORMER LOSSES AND ENERGY PERFORMANCE
No-load loss at rated voltage and
26 frequency (@75 °C) W 90
27 Full load loss (@75 °C) W 1000
28 Rated voltage at full load (P.F=0.95) KV
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
16 Frequency Hz 50
17 Principal tapping KV 15
Maximum Continuous System
18 withstand Voltage KV 17.5
19 Rated Voltage of the equipment KV 24
20 Impedance voltage at rated power % 4
III. WINDINGS
20 HV Windings
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
25.3 Maximum Winding Hotspot °C 68
V. TRANSFORMER LOSSES AND ENERGY PERFORMANCE
No-load loss at rated voltage and
26 frequency (@75 °C) W 145
27 Full load loss (@75 °C) W 1700
28 Rated voltage at full load (P.F=0.95) KV
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
16 Frequency Hz 50
17 Principal tapping KV 15
Maximum Continuous System
18 withstand Voltage KV 17.5
19 Rated Voltage of the equipment KV 24
20 Impedance voltage at rated power % 4
III. WINDINGS
20 HV Windings
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
25.3 Maximum Winding Hotspot °C 68
V. TRANSFORMER LOSSES AND ENERGY PERFORMANCE
No-load loss at rated voltage and
26 frequency (@75 °C) W 250
27 Full load loss (@75 °C) W 2300
28 Rated voltage at full load (P.F=0.95) KV
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
16 Frequency Hz 50
17 Principal tapping KV 15
Maximum Continuous System
18 withstand Voltage KV 17.5
19 Rated Voltage of the equipment KV 24
20 Impedance voltage at rated power % 4
III. WINDINGS
20 HV Windings
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
25.3 Maximum Winding Hotspot °C 68
V. TRANSFORMER LOSSES AND ENERGY PERFORMANCE
No-load loss at rated voltage and
26 frequency (@75 °C) W 360
27 Full load loss (@75 °C) W 3800
28 Rated voltage at full load (P.F=0.95) KV
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
16 Frequency Hz 50
17 Principal tapping KV 15
Maximum Continuous System
18 withstand Voltage KV 17.5
19 Rated Voltage of the equipment KV 24
20 Impedance voltage at rated power % 4
III. WINDINGS
20 HV Windings
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
25.3 Maximum Winding Hotspot °C 68
V. TRANSFORMER LOSSES AND ENERGY PERFORMANCE
No-load loss at rated voltage and
26 frequency (@75 °C) W 430
27 Full load loss (@75 °C) W 4500
28 Rated voltage at full load (P.F=0.95) KV
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
Bid
No Item Unit Requirement Offer
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
APPENDIX C: DRAWING
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
LV Bushing
PLEASE MAKE SURE THAT THIS IS THE CORRECT ISSUE BEFORE USE
Document No.
ETHIOPIAN ELECTRIC UTILITY EEU/EQ/TS-04-212
MV Bushing