Operating Instructions SINGLE SBC - Controller
Operating Instructions SINGLE SBC - Controller
SBC_EN_15_06
Contents
1 Configuration and operation of the controller .................................................................................................. 2
1.1 Operating elements ................................................................................................................................. 2
1.2 Control panel ........................................................................................................................................... 2
1.3 Alarm panel and display information ....................................................................................................... 3
2 Parameter description ...................................................................................................................................... 4
2.1 Working level ........................................................................................................................................... 4
2.2 Parameter level ........................................................................................................................................ 6
2.3 Configuration level ................................................................................................................................... 7
2.4 Setting the control parameter ................................................................................................................10
2.4.1 Determining the parameters with closed control circuit .................................................................10
2.4.2 Self-optimisation ............................................................................................................................11
3 Connecting diagram .......................................................................................................................................12
4 Technical data ................................................................................................................................................12
1 Configuration and operation of the controller
1.1 Operating elements
-button (P)
Button P gives access to the parameters of each level.
For accessing the individual processing levels:
- button (Enter)
All changes must be confirmed with this button. (set-point and
parameter)
- button (+)
The (+) button is used to increase the set-point and parameter values.
Each change must be confirmed by pressing the ↵ button.
- button (Off)
All systems are “off”. If power is still present the start screen is displayed.
- button (On)
The system is “working”, the pump and controller are “active”.
- button (–)
The (-) button is used to decrease the set-point and parameter values.
Each change must be confirmed by pressing the ↵ button.
Display SET
Display of the current or programmed set-values.
Display of numerical values or parameter values when at working-, parameter- and configuration-level.
1.3 Alarm panel and display information
Symbol Designation LED glows because: Rectification / explanation
Water: with manual filling:
replenish with heat transfer medium
with automatic filling:
Minimum level Minimum level not made
open cooling water supply, wait till
filled
Oil: fill or replenish with oil
Not up to temperature, or outside band-
Limit-comparator outside spread (limit)
Limit-comparator band-spread, limiting Band-spread too narrow or limiting value
value exceeded made. Turn OFF at working level, parameter
AL, or set band-spread.
Check set limiting value;
Pre-run temperature up
Pre-run insufficient heat dissipation by consumer.
to limiting value
temperature Subsequent to cooling by 5 K, heating comes
Heating switches OFF
ON again
Heating Heating on -
Cooling Cooling on -
The first display shown after pressing button P is the status display. If an error has occurred, this will be
displayed:
ALAr FLO = flow error
ALAr PUMP = motor contactor triggered
ALAr FILL = filling time exceeded
ALAr niv.H = max level. exceeded (only with oil units)
Parameter description:
Parameter Set-values range Signifying
OFF OFF Alarm outputs selected.
Alarm output programmed as signal contact max. OFF-ON.
OFF, -99 100 The setting-value corresponds to the alarm’s response value,
relative to the set point-value.
Alarm output programmed as limiting contact max OFF-ON.
MR*-start MR*-end The set point-value corresponds to the absolute response-value of
the alarm.
Alarm output programmed as limit comparator OFF-ON-OFF.
OFF, 0 100
The set point-value corresponds to the set point’s tolerance-value.
Alarm output, programmed as signal contact max. ON-OFF.
AL OFF, -99 100 The setting-value corresponds to the alarm’s response value,
relative to the set point-value.
Alarm output programmed as limiting contact max ON-OFF.
MR-start MR-end The set point-value corresponds to the absolute response-value of
the alarm.
Alarm output programmed as limit comparator ON-OFF-ON.
OFF, 0 100
The set point-value corresponds to the set point’s tolerance-value.
Alarm output programmed as limit comparator ON-OFF-ON
(with stand-by response).
OFF, 0 100
The set point-value corresponds to the set point’s tolerance-value.
No alarm during initial start-up, until the input range is made.
nd
Programmed value corresponds to 2 set-value.
nd
Set-value Change-over to 2 set-value takes place via parameter SET =
SP2 MR-start
limiting SP.2 at working level.
Also refer to configuration level.
Programmed value corresponds to the response temperature of
AP.I MR-start MR-end the inlet-temperature limitation. If up to end of measuring range is
programmed, the value end of measuring range +5°C is displayed.
Aquatimer:
Ati OFF=0 40 set point-value corresponds to the max. permissible filling cycles
after 1 hour of operation.
Change time; evacuation / vacuum time on units with automatic
Cti OFF, 10 900 mold draining. Set point-value corresponds to the compressed-air
assisted evacuation time or else the vacuum-time in seconds.
Turning the leak-stop mode ON and OFF.
LS OFF on ON means leak-stop mode turned ON.
OFF means leak-stop mode turned OFF.
rEMo OFF on Turning the remote function ON and OFF at units with interface.
*MR = metering range
Parameter Set-values range Signifying
Hand = manual filling of the unit
niv Hand Auto Auto = automatic filling of the unit
Auto not possible for heat transfer units with oil
no.Ch mould draining not active
Chg mould draining active.
CHG no.Ch Chg
Only for units with mould draining!
Change-over must be set free in the configuration level!
indi = Cooling via heat exchanger
dir = direct Cooling
dir indi dir
Direct cooling only possible at units with water
Change-over must be set free in the configuration level!
Vent after switching on
bLEd OFF, 1 240
Setting in seconds
OFF means, that the unit is turned OFF directly with the „0“ key.
C.OFF OFF Co.OF Co.OF means, that when pushing the "0" key, the unit is cooled
down first, before it is turned OFF. (Pump lag control)
Change-over
SEt SP.1 SP.2 SP.1 = internal set-value active
SP.2 = second set-value active
Input of unit addressing.
Adr 1 255 If several units are operated by the same interface, different
addresses must be chosen.
AL2 Compare with parameter AL
t.out Shows the pre-run temperature in the SET-display
2.2 Parameter level
Pushing the buttons P and ↵ will access the parameter level. Individual parameters are accessed by pushing
the P-button. The PROCESS-display shows the parameter. The SET-display shows the parameter value.
Please note!
When changing the LOC-parameters, ENTER must be kept
depressed, until the moving illumination has passed-through for
the second time (about 5 s )!
Configuration of external contact
ECO OFF on OFF: Pin 10 = inlet flow monitor
on: Pin 10 = switch-over setpoint value 1 / setpoint value 2
Enabling the filling modes „AUTOMATIC/MANUAL“
• on = change-over facility of the key marked LEVEL is enabled
niv on LOC
• LOC = change-over facility of the key marked LEVEL is
blocked.
Enabling or locking the software-key of the pump-lag control
c60 OFF, 10 100 • OFF = „OFF“-key blocked
• 10...100 °C = adjustable switch-OFF temp.
AQUA = water unit
C.OIL AqUA OIL
OIL = oil unit
Interlocking of the “direct cooling” key
(unit must be equipped with hydraulics)
cdi OFF on
• on = change-over to direct cooling is enabled
• OFF = no direct cooling allowed
Configuration of the alarm output port
• OFF = Alarm has been turned OFF
• = Signal contact OFF-ON
• = Limiting contact OFF-ON
• = Limit comparator OFF-ON-OFF
C.AL OFF 7 • = Signal contact ON-OFF
• = Limiting contact ON-OFF
• = Limit comparator ON-OFF-ON
• = Limit comp. with stand-by response
In the ON-position, output port is open.
In OFF-position, output-port is closed.
Configuration group interrupt
C.SA oP cL • oP = n/c contact
• cL = n/o contact
Parameter Set-values range Signifying
Change-logic configuration
The change sequence will have to be preselected as a function of
the unit’s hydraulic and electrical specifications.
• dd = Mold evacuation by compressed air
ChL dd Ldd • LS = Mold evacuation by vacuum suction (leak stop-function)
• Ldd = at present as per dd
• 8-9 = Mold evacuation with compressed air, when units with
“System shut-off in cooling water return” are employed, e.g.
STW 1-HTK and STW 150/1-HK + HN
Interlocking of “LS” leak-stop parameter at working level (when
hydraulic prerequisite is missing).
• ON = Changing of the “LS”-parameter enabled at working
E.LS on LOC
level
• LOC = Changing of the „LS“-parameter blocked at working-
level
Aquatimer-Start-time (min)
Aquatimer (filling-impulse-counter) becomes active following the
ASt 5 min 120 time set in the "ASt".
Previously not monitored random filling cycles.
Renewed start of the "AST" time, following the On/Off.
Monitoring of filling time
FiLL OFF; 1 99
Setting in minutes
Restart lockout after power reset
off = Restart lockout not active
on = Restart lockout active
X
(°C)
Δx
t (sec.)
T = oscillation period
Δx = oscillation amplitude of the actual value
1
Delay time: Tu = ∗T
4
4
Lead time: Tv = ∗ Tu
10
Reset time: Tn = 5 ∗ Tv
∆x ∗ 2
Proportional range: xp = ∗ 100%
Meßbereichsumfang
Span SC: 430 K
We recommend setting the proportional range “cooling“ to two times the value.
2.4.2 Self-optimisation
The optimisation algorithm with closed control circuit ascertains the characteristics of the controlled system and
calculates the feedback parameters (Xp, Tv, Tn) and the switching cycle time (C = 0.3 x Tv) for a PD/I controller
valid over a wide range.
If the controller is operated as a “heating-off-cooling” controller then the parameter values determined under
“heating” are used for “cooling”.
The optimisation is carried out during start-up shortly before the setpoint. This must be at least 5 % of the span.
During the optimisation to a setpoint that has already been reached, the temperature is reduced by approx. 5%
of the span in order to accurately determine the controlled system gain.
The optimisation algorithm can be triggered at any time by selecting “Self-optimisation = ON” and confirming
with the “Enter” button. During the optimisation process “Opt. Activ” is shown in the display. With 3-point
controllers (heating-off-cooling) the temperature reduction is accelerated via short-term activation of the cooling.
After the feedback parameters have been calculated the controller maintains the actual value at the current
setpoint.
X X
w w
y y
OPT on t OPT on t
Optimisation during heating Optimisation to setpoint
of the controlled system already "attained”
By selecting “Self-optimisation = OFF” and pressing the “Enter” button, the optimisation process can be
interrupted.
3 Connecting diagram
Interface optional! St3 PIN
GND 85
TTY 20 mA- RxTxP 86
RxTxN 87
TTY 20 mA+ Vp +5V 88
St1 PIN
draining 17 18 leak-stop
system closing 15 16 pilot contact heating
pump 13 14 filling
heating 11 12 cooling
motor protection 9 10 flow watchdog
level min. 7 8 level max.
5 6 Pt 100 temperature
Pt 100 control
3 4 monitoring
0V 1 2 24 V
St2 PIN
4 Technical data
Power supply 24V DC 0,1A
Outputs 24V DC
0,5A
2A max.
SMD fuse 4A
Short circuit proof, suitable for inductive loads