0% found this document useful (0 votes)
139 views84 pages

Sequence Manager

Uploaded by

Jose Sierra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
139 views84 pages

Sequence Manager

Uploaded by

Jose Sierra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 84

Quick Start Guide

SequenceManager™
1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix,
1789 SoftLogix, Studio 5000 Logix Emulate
Important user information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment
before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions
in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by
suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer,
the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated
with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this
manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to
personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

Important: Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be
present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous
temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc
Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work
practices and for Personal Protective Equipment (PPE).

Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of contents

Preface Studio 5000 environment ..................................................................................... 7


Additional resources............................................................................................... 7
Legal Notices ........................................................................................................... 8

Chapter 1

System requirements
Chapter 2

Install SequenceManager
Event Components
Chapter 3

SequenceManager and Logix Designer, Sequence Editor, and Sequence Monitor ............................ 20
related components ControlLogix Firmware ...................................................................................... 21
SequenceManager Controls................................................................................ 21
overview
SequenceManager Event Handling applications ............................................ 22

Chapter 4

Equipment Sequence Editor Equipment Sequence Editor ............................................................................... 24


overview Steps to create Equipment Sequence diagrams................................................ 25
Equipment Sequence diagrams and Sequential Function Chart routines
differences .............................................................................................................. 25
Equipment Sequence Diagrams ......................................................................... 27
Create an Equipment Sequence program ......................................................... 27
Define a new Equipment Sequence ................................................................... 28
Configure Equipment Sequence properties ..................................................... 30
Create a Sequence Parameter using the New Parameter or Tag dialog box31
Example: Construct an Equipment Sequence diagram ................................. 33
Prepare the Equipment Sequence diagram ...................................................... 34
Configure simultaneous branches to add and mix material .......................... 35
Converge the simultaneously executed paths .................................................. 38

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 3


Table of contents

Chapter 5

Sequence Execution & The Equipment Sequence Monitor .................................................................. 41


Monitoring Sequence Tag Monitor ........................................................................................ 42
Step states in an Equipment Sequence .............................................................. 42
Step execution in an Equipment Sequence ...................................................... 43
Step execution in a selective sequence ............................................................... 43
Step execution in a simultaneous sequence ...................................................... 45
Transition display states ...................................................................................... 47
Transition firing states ......................................................................................... 48
Transition execution ............................................................................................ 48
Quality of Data ..................................................................................................... 48
How sequence output parameter and step input tag expressions evaluate . 50
How step tags update ........................................................................................... 50
How sequence parameters update ..................................................................... 51
Pause, auto pause, and resume commands ....................................................... 51
Ownership ............................................................................................................. 52
Change modes effect on sequence and step commands ................................. 54
Equipment Sequence failures.............................................................................. 54

Chapter 6

SequenceManager event SequenceManager events ..................................................................................... 57


handling applications SequenceManager Event Services Console overview ..................................... 59
SequenceManager Event Services Console commands.................................. 60
Configure Mircosoft SQL Server for Reporting Services for
SequenceManager Events .................................................................................... 61
Configure settings for the SequenceManager Event Archiving
Service ..................................................................................................................... 62
SequenceManager Event Archiving Service settings ...................................... 65
Configure settings for the SequenceManager Event Client Service ............ 66
SequenceManager Event Client Service settings............................................. 68

Chapter 7

The SequenceManager
Controls
Chapter 8

Sequence Summary Control Configure the Sequence Summary Control .................................................... 71


Sequence Summary command controls ............................................................ 71

4 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Table of contents

Chapter 9

Sequence Detail Control Configure the Sequence Detail Control........................................................... 73


Sequence Detail Control command controls .................................................. 73
Sequence Detail Control status header area .................................................... 75
Sequence Detail Control status footer area ..................................................... 76
A monitored step in the Sequence Detail Control ......................................... 77
A monitored transition in the Sequence Detail Control .............................. 78

Chapter 10

Sequence Parameters Control Configure the Sequence Parameters Control .................................................. 81


Modify step tags or sequencing parameters using the Sequence Parameters
Control ................................................................................................................... 81
Index

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 5


Preface

Studio 5000 environment The Studio 5000 Automation Engineering & Design Environment™ combines
engineering and design elements into a common environment. The first element is
the Studio 5000 Logix Designer™ application. The Logix Designer application is
the rebranding of RSLogix™ 5000 software and will continue to be the product to
program Logix5000™ controllers for discrete, process, batch, motion, safety, and
drive-based solutions.

The Studio 5000® environment is the foundation for the future of


Rockwell Automation® engineering design tools and capabilities. The Studio 5000
environment is the one place for design engineers to develop all elements of their
control system.

Additional resources These documents contain additional information concerning related Rockwell
Automation products.

Resource Description
Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell
1770-4.1 Automation industrial system.

Product Certifications webpage, available at Provides declarations of conformity, certificates, and other
http://ab.rockwellautomation.com certification details.

You can view or download publications at


http://www.rockwellautomation.com/literature. To order paper copies of
technical documentation, contact your local Rockwell Automation distributor or
sales representative.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 7


Preface

Legal Notices Copyright notice

© 2016 Rockwell Automation, Inc. All rights reserved. Printed in USA.

This document and any accompanying Rockwell Software products are


copyrighted by Rockwell Automation, Inc. Any reproduction and/or distribution
without prior written consent from Rockwell Automation, Inc. is strictly
prohibited. Please refer to the license agreement for details.

End User License Agreement (EULA)

You can view the Rockwell Automation End-User License Agreement ("EULA")
by opening the License.rtf file located in your product's install folder on your hard
drive.

Other Licenses

Botan (http://botan.randombit.net/) is distributed under these terms:

Copyright (C) 1999-2013, 2014 Jack Lloyd

2001 Peter J Jones


2004-2007 Justin Karneges
2004 Vaclav Ovsik
2005 Matthew Gregan
2005-2006 Matt Johnston
2006 Luca Piccarreta
2007 Yves Jerschow
2007-2008 FlexSecure GmbH
2007-2008 Technische Universitat Darmstadt
2007-2008 Falko Strenzke
2007-2008 Martin Doering
2007 Manuel Hartl
2007 Christoph Ludwig
2007 Patrick Sona
2010 Olivier de Gaalon
2012 Vojtech Kral
2012 Markus Wanner
2013 Joel Low

All rights reserved.

Redistribution and use in source and binary forms, with or without modification,
are permitted provided that the following conditions are met:

1. Redistributions of source code must retain the above copyright notice, this
list of conditions, and the following disclaimer.

8 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Preface

2. Redistributions in binary form must reproduce the above copyright notice,


this list of conditions, and the following disclaimer in the documentation
and/or other materials provided with the distribution.

THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND


CONTRIBUTORS "AS IS" AND ANY EXPRESS OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL
THE COPYRIGHT HOLDER OR CONTRIBUTORS BE LIABLE FOR
ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR
CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO,
PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF
USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER
CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING
NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE
USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF
SUCH DAMAGE.

The package GNU Compiler Collection (GCC) is licensed under the following
licenses:

GNU General Public License v3.0, the text of which is available at


http://www.gnu.org/licenses/gpl-3.0-standalone.html . Copyright © 2007 Free
Software Foundation, Inc.

MIT License, the text of which is available at


http://www.opensource.org/licenses/MIT.

GNU General Public License v3.0 with GCC Runtime Library exception (v3.1),
the text of which is available at https://olex-
secure.openlogic.com/licenses/base_license/gpl-gcc-v3-license-base. Copyright
(C) 2009 Free Software Foundation, Inc.

GNU Lesser General Public License v2.1, the text of which is available at
http://www.gnu.org/licenses/old-licenses/lgpl-2.1-standalone.html..Copyright
(C) 1991, 1999 Free Software Foundation, Inc.

GNU General Public License v2.0, the text of which is available at


http://www.gnu.org/licenses/old-licenses/gpl-2.0-standalone.html. Copyright
(C) 1989, 1991 Free Software Foundation, Inc.

Mozilla Public License 1.1, the text of which is available at


http://www.mozilla.org/MPL/MPL-1.1.html.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 9


Preface

Unicode, Inc. License Agreement, the text of which is available at


http://www.unicode.org/copyright.html. Copyright © 1991-2009 Unicode, Inc.

GNU Library General Public License v2.0, the text of which is available at
http://www.gnu.org/licenses/old-licenses/lgpl-2.0-standalone.html. Copyright
(C) 1991 Free Software Foundation, Inc

BSD 3-clause New or Revised License, the text of which is available at


http://www.opensource.org/licenses/BSD-3-Clause.

BSD 2-clause (FreeBSD License), the text of which is available at


http://www.freebsd.org/copyright/freebsd-license.html. Copyright 1992-2012
The FreeBSD Project.

GNU Free Documentation License v1.3, the text of which is available at


http://www.gnu.org/licenses/fdl-1.3.txt. Copyright © 2000, 2001, 2002, 2007,
2008 Free Software Foundation, Inc.

GNU General Public License v2.0 w/ServerHandler library exception, the text of
which is available at https://olex-secure.openlogic.com/licenses/gpl-serverhandler-
exception. Copyright (C) 1989, 1991 Free Software Foundation, Inc

GNU Lesser General Public License v3.0, the text of which is available at
http://www.gnu.org/licenses/lgpl-3.0-standalone.html. Copyright © 2007 Free
Software Foundation, Inc.

Creative Commons Attribution 3.0, the text of which is available at


http://creativecommons.org/licenses/by/3.0/legalcode.

Independent JPEG Group License, the text of which is available at https://olex-


secure.openlogic.com/licenses/ijg-license.

Boost Software License 1.0, and BSD 3-clause (University of California Regents),
the text of which is available at http://www.boost.org/LICENSE_1_0.txt.

The package Newlib is licensed under the following licenses:

GNU General Public License v2.0 w/Autoconf exception, the text of which is
available at http://spdx.org/licenses/GPL-2.0-with-autoconf-exception.
Copyright (C) 1989, 1991 Free Software Foundation, Inc.

GNU General Public License v3.0 w/Autoconf exception, the text of which is
available at http://spdx.org/licenses/GPL-3.0-with-autoconf-exception.
Copyright © 2009 Free Software Foundation, Inc.

OpenSSL distributed under these terms:

Copyright (c) 1998-2011 The OpenSSL Project. All rights reserved.

10 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Preface

Redistribution and use in source and binary forms, with or without modification,
are permitted provided that the following conditions are met:

1. Redistributions of source code must retain the above copyright notice, this
list of conditions and the following disclaimer.

2. Redistributions in binary form must reproduce the above copyright notice,


this list of conditions and the following disclaimer in the documentation
and/or other materials provided with the distribution.

3. All advertising materials mentioning features or use of this software must


display the following acknowledgment: "This product includes software
developed by the OpenSSL Project for use in the OpenSSL Toolkit.
(http://www.openssl.org/)"

4. The names "OpenSSL Toolkit" and "OpenSSL Project" must not be used to
endorse or promote products derived from this software without prior
written permission. For written permission, please contact openssl-
[email protected].

5. Products derived from this software may not be called "OpenSSL" nor may
"OpenSSL" appear in their names without prior written permission of the
OpenSSL Project.

6. Redistributions of any form whatsoever must retain the following


acknowledgment: "This product includes software developed by the
OpenSSL Project for use in the OpenSSL Toolkit
(http://www.openssl.org/)"

THIS SOFTWARE IS PROVIDED BY THE OpenSSL PROJECT ``AS IS''


AND ANY EXPRESSED OR IMPLIED WARRANTIES, INCLUDING, BUT
NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
ARE DISCLAIMED. IN NO EVENT SHALL THE OpenSSL PROJECT OR
ITS CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL
DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT
OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR
PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND
ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT
LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE)
ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN
IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

=================================================
===================

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 11


Preface

This product includes cryptographic software written by Eric Young


([email protected]). This product includes software written by Tim Hudson
([email protected]).
/

Original SSLeay License

-----------------------

/Copyright (C) 1995-1998 Eric Young ([email protected])

All rights reserved.

This package is an SSL implementation written by Eric Young


([email protected]).

The implementation was written so as to conform with Netscapes SSL.

This library is free for commercial and non-commercial use as long as the
following conditions are aheared to. The following conditions apply to all code
found in this distribution, be it the RC4, RSA, lhash, DES, etc., code; not just the
SSL code. The SSL documentation included with this distribution is covered by
the same copyright terms except that the holder is Tim Hudson
([email protected]).

Copyright remains Eric Young's, and as such any Copyright notices in the code are
not to be removed.

If this package is used in a product, Eric Young should be given attribution as the
author of the parts of the library used. This can be in the form of a textual message
at program startup or in documentation (online or textual) provided with the
package.

Redistribution and use in source and binary forms, with or without modification,
are permitted provided that the following conditions are met:

1. Redistributions of source code must retain the copyright notice, this list of
conditions and the following disclaimer.

2. Redistributions in binary form must reproduce the above copyright notice,


this list of conditions and the following disclaimer in the documentation
and/or other materials provided with the distribution.

3. All advertising materials mentioning features or use of this software must


display the following acknowledgement: "This product includes
cryptographic software written by Eric Young ([email protected])" The
word 'cryptographic' can be left out if the rouines from the library being
used are not cryptographic related :-).

12 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Preface

4. If you include any Windows specific code (or a derivative thereof) from the
apps directory (application code) you must include an acknowledgement:
"This product includes software written by Tim Hudson
([email protected])"

THIS SOFTWARE IS PROVIDED BY ERIC YOUNG ``AS IS'' AND ANY


EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT
LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN
NO EVENT SHALL THE AUTHOR OR CONTRIBUTORS BE LIABLE
FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY,
OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS
OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION)
HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT
(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY
OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE
POSSIBILITY OF SUCH DAMAGE.

The licence and distribution terms for any publically available version or derivative
of this code cannot be changed. i.e. this code cannot simply be copied and put
under another distribution licence [including the GNU Public Licence.]

Trademark Notices

Allen-Bradley, ControlBus, ControlFLASH, Compact GuardLogix, Compact


I/O, ControlLogix, CompactLogix, DCM, DH+, Data Highway Plus,
DriveLogix, DPI, DriveTools, Explorer, FactoryTalk, FactoryTalk Administration
Console, FactoryTalk Alarms and Events, FactoryTalk Batch, FactoryTalk
Directory, FactoryTalk Security, FactoryTalk Services Platform, FactoryTalk
View, FactoryTalk View SE, FLEX Ex, FlexLogix, FLEX I/O, Guard I/O, High
Performance Drive, Integrated Architecture, Kinetix, Logix5000, Logix5550,
MicroLogix, DeviceNet, EtherNet/IP, PLC-2, PLC-3, PLC-5, PanelBuilder,
PowerFlex, PhaseManager, POINT I/O, PowerFlex, Rockwell Automation,
RSBizWare, Rockwell Software, Studio 5000 Logix Emulate, Historian,
RSFieldbus, RSLinx, RSLogix, RSNetWorx for DeviceNet, RSNetWorx for
EtherNet/IP, RSMACC, RSView, RSView32, Rockwell Software Studio 5000
Automation Engineering & Design Environment, Studio 5000 View Designer,
SCANport, SLC, SoftLogix, SMC Flex, Studio 5000, Ultra 100, Ultra 200,
VersaView, WINtelligent, XM, SequenceManager are trademarks of Rockwell
Automation, Inc.

Any Rockwell Automation logo, software or hardware product not mentioned


herein is also a trademark, registered or otherwise, of Rockwell Automation, Inc.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 13


Preface

Other Trademarks

CmFAS Assistant, CmDongle, CodeMeter, CodeMeter Control Center, and


WIBU are trademarks of WIBU-SYSTEMS AG in the United States and/or
other countries. Microsoft is a registered trademark of Microsoft Corporation in
the United States and/or other countries. ControlNet is a trademark of
ControlNet International. DeviceNet is a trademark of the Open DeviceNet
Vendors Association (ODVA). Ethernet/IP is a trademark of ControlNet
International under license by ODVA.

All other trademarks are the property of their respective holders and are hereby
acknowledged.

Warranty

This product is warranted in accordance with the product license. The product’s
performance may be affected by system configuration, the application being
performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in
this document do not cover all the details or variations in the equipment,
procedure, or process described, nor do they provide directions for meeting every
possible contingency during installation, operation, or maintenance. This
product’s implementation may vary among users.

This document is current as of the time of release of the product; however, the
accompanying software may have changed since the release. Rockwell Automation,
Inc. reserves the right to change any information contained in this document or
the software at any time without prior notice. It is your responsibility to obtain the
most current information available from Rockwell when installing or using this
product.

Environmental compliance

Rockwell Automation maintains current product environmental information on


its website at http://www.rockwellautomation.com/rockwellautomation/about-
us/sustainability-ethics/product-environmental-compliance.page

Contact Rockwell Automation

Customer Support Telephone — 1.440.646.3434

Online Support — http://www.rockwellautomation.com/support/

14 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Chapter 1

System requirements

The following are the minimum and recommended system requirements to


successfully install, configure, and run SequenceManager Event Console. These
requirements assume that no other application is running on the computer, unless
it is an application that is listed in the Tested third-party software section.

• Ensure that all selected hardware is on the compatibility list for any one of
the following:
• Microsoft® Windows™ Server 2008 Service Pack 2 (32-bit)
Microsoft Windows Server 2008 R2 Service Pack 1 (64-bit)
• Microsoft Windows Server 2012
Microsoft Windows Server 2012 R2
• Windows 7 Service Pack 1 (64-bit)
Windows 8.1 (32-bit and 64-bit)
• SQL Server 2008 R2
SQL Server 2012 R2

Systems that do not meet the minimum requirements for the version of
software being used are not covered under warranty.

Important: For more information about supported operating systems and other Rockwell Software
product version support, refer to the Product Compatibility and Download Center (PCDC).

Tested third-party software

The following new software has been tested with the current version of
SequenceManager Event Console.

Adobe

• Acrobat Reader XI (11)

Rockwell Software

• Logix Designer (formerly RSLogix 5000) version 28


• RSLinx Classic version 3.60

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 15


Chapter 1 System requirements

• RSLinx Enterprise version 5.74


• FactoryTalk Activation version 3.60 or later
• FactoryTalk Services Platform version 2.80.0.4 or later
• FactoryTalk View Site Edition (SE) version 8.1

16 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Chapter 2

Install SequenceManager Event Components

Install SequenceManager Event Components to start the event handling services.

Important: If this install is an upgrade to the Batch system and the BatchHistoryEx SQL
database is already being used, back up the database before installing the
SequenceManager Event Components.

To install SequenceManager Event Components:

1. Access the Product Compatibility and Download Center (PCDC) to


download the SequenceManager Event Install.exe.

2. Run the SequenceManager Event Install.exe file to install the


SequenceManager Event Components.

3. To read the end-user license agreement, select license terms and


conditions. Then select the check box to accept the terms and conditions.
Select Next.

4. Select the SequenceManager Event Components to install:

• Batch History Database and Reports


Important: The database is selected to migrate by default. If Overwrite is selected,
the existing Batch history database will be deleted.

• If SQL authentication is being used, select Use SQL Authentication


and then enter the SQL Username and the SQL Password.

5. Select Install.

Close the installation window when the installation has complete.

See also

SequenceManager and related components overview on page 19

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 17


Chapter 3

SequenceManager and related components


overview

Use the SequenceManager to model and execute sequential manufacturing


processes using the ControlLogix features described in the following tasks:

• Configure the coordination of Equipment Phase execution using the


Equipment Sequence Editor.
• Execute Equipment Sequence programs using ControlLogix.
• Monitor and manage running Equipment Sequences using the Logix
Designer application.
• Enable operators to monitor and manage running Equipment Sequences
and Equipment Phases by adding SequenceManager ActiveX controls to
FactoryTalk View SE displays.
• Subscribe and collect generated sequence events using SequenceManager
Event Client Service and SequenceManager Event Archiving Service.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 19


Chapter 3 SequenceManager and related components overview

The following diagram illustrates the components that are part of the
SequenceManager and their responsibilities.

See also

Logix Designer, Sequence Editor, and Sequence Monitor on page 20

ControlLogix Firmware on page 21

SequenceManager Controls on page 21

SequenceManager Event Handling applications on page 22

Logix Designer, Sequence The Equipment Sequence Editor is used to create Equipment Sequence programs.
The sequence diagram defines a sequence of Equipment Phases to be run, the
Editor, and Sequence order of execution, and their parameter data necessary to make the product. Input
Monitor and output parameters are defined in the Equipment Sequence using the
Sequence Tag Editor. Equipment Sequence programs and their tags are fully
integrated with all Logix program and tag authoring capabilities.

The Equipment Sequence Monitor is the online version of the Equipment


Sequence Editor and is used to monitor and interact with Equipment Sequences

20 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


SequenceManager and related components overview Chapter 3

that have been downloaded to the controller. The control engineer can do the
following:

• Command the Equipment Sequence.


• Change the value of parameters and attributes.
• Interact with the executing sequence.

See also

SequenceManager and related components overview on page 19

ControlLogix Firmware The Equipment Sequence program firmware implements all the code necessary to
manage the use of Equipment Phase programs, shares data between a sequence
program and one or more Equipment Phase programs, and coordinates execution
of the Equipment Phases.

When an Equipment Sequence or sequence element changes status or an operator


interacts with the Equipment Sequence, the firmware generates an event. Once an
event is generated, it is published for external applications to receive.

See also

SequenceManager and related components overview on page 19

The SequenceManager ActiveX controls provide operator visualization of the


SequenceManager Controls
Equipment Sequence program. There are three operator controls for viewing and
interacting with the Equipment Sequences.

The Sequence Detail Control provides the operator with a detailed view of an
Equipment Sequence, including its chart structure, steps, and transitions. The
runtime status of the sequence program and its sequence elements are also shown.
The operator can command the Equipment Sequence from this control.

The Sequence Summary Control displays the sequence program status for each
of the Equipment Sequences downloaded to the controller. The Sequence
Summary Control also allows the operator to view and command a selected
Equipment Sequence.

The Sequence Parameters Control displays a table of all sequence parameters


and step tags of a specified Equipment Sequence, and allows the operator to
command a selected sequence parameter or step tag. To refine the display,
configure the table to filter the information displayed.

See also

SequenceManager and related components overview on page 19

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 21


Chapter 3 SequenceManager and related components overview

Logix Designer, Sequence Editor, and Sequence Monitor on page 20

ControlLogix Firmware on page 21

SequenceManager Event The SequenceManager Event Services Console provides the user interface for
performing the following tasks:
Handling applications
• Start, stop, pause, and resume the SequenceManager Event Client Service
and the SequenceManager Event Archiving Service.
• Display the status of the SequenceManager Event Client Service and the
SequenceManager Event Archiving Service
• Configure the SequenceManager Event Client Service settings and
SequenceManager Event Archiving Service settings.

The SequenceManager Event Client, a service external to the controller, receives


the event from the general event log. The Event Client saves generated raw events
into a temporary file.

The SequenceManager Archiving Service processes the raw event files, localizing,
translating, and assembling data into the formats used by PlantPAx Historian and
reporting applications. This data is written to an .EVT file and there is an option
to write to a SQL Server database.

PlantPAx applications read the generated events and process them.

Tip: The SequenceManager Event Handling applications are installed separately from
the Logix Designer installation process.

See also

SequenceManager and related components overview on page 19

Logix Designer, Sequence Editor, and Sequence Monitor on page 20

ControlLogix Firmware on page 21

SequenceManager Controls on page 21

22 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Chapter 4

Equipment Sequence Editor overview

The following image identifies the main areas of the Equipment Sequence Editor.

Item Name Description


Equipment Sequence Editor Use to add sequence elements to the Equipment Sequence
toolbar diagram.
Equipment Sequence Diagram Use to construct and configure Equipment Sequence diagrams.
workspace
Sequence Tag Editor Use to add and configure parameters for the equipment phase
steps in the Equipment Sequence diagram.
Equipment Sequence tabs Use to select and navigate different Equipment Sequence
diagrams under the tasks.

See also

Equipment Sequence Editor on page 24

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 23


Chapter 4 Equipment Sequence Editor overview

Equipment Sequence Editor The Equipment Sequence Editor is contained within the routine window in the
main Logix Designer application window. Use this editor to edit Equipment
Sequence diagram routines. The routine window contains tabs for all open
routines, a view for each routine, and the Equipment Sequence toolbar. When a
new sequence diagram is first shown, it contains an initial step, linked to a
transition with the default expression TRUE, linked to a terminal step.

The Equipment Sequence Editor layout consists of the Equipment Sequence


Element toolbar, the Equipment Sequence Diagram workspace, and the Sequence
Tag Editor.

Equipment Sequence Element toolbar - When offline and editing an


Equipment Sequence, the Equipment Sequence Element toolbar adds steps,
transitions, and branch structures to the sequence diagram.

Equipment Sequence Diagram workspace - Use to construct and configure


Equipment Sequence diagrams.

Sequence Tag Editor - Use the Sequence Tag Editor to add and configure
sequence parameters and configure step tag properties. All sequence parameters
and step tags are listed in a table format. The Sequence Tag Editor is the grid that
displays at the bottom of the Equipment Sequence diagram.

See also

Create an Equipment Sequence program on page 27

24 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

Steps to create Equipment An Equipment Sequence diagram is a graphical representation of a sequence that
coordinates the execution of equipment. Each diagram comprises basic sequence
Sequence diagrams elements such as steps, links, and transitions structured in a specific topology.
Each Equipment Sequence has one routine that is configured by adding elements
and applying branch structures using buttons available from the Equipment
Sequence Element toolbar in the Equipment Sequence Editor.

Perform these steps to create the Equipment Sequence.

Step How
Identify and create Equipment Phases Considering the equipment associated with an operational unit of equipment,
identify the actions that equipment can perform.

Identify the manufacturing procedure to Analyze the manufacturing process and break it into a series of
be automated manufacturing actions or steps that are performed serially, conditionally, or
simultaneously. Identify the conditions when one manufacturing step should
stop and the next be started.
Configure the Sequence Diagram Construct the diagram routine to model the manufacturing process. Each step
represents one use of an Equipment Phase to perform an action. Code the
conditions for starting and stopping actions as transition expressions.
Configure Sequence Parameters and Step Analyze the materials and ingredients used by each manufacturing action.
Tags The sequence input parameters provide data to the Equipment Sequence
program. The data provided is available to the Equipment Phase input
parameters via step input tags.
Analyze the reporting requirements. Generated actual values should be
stored into the Equipment Phase output parameters. The value of the
Equipment Phase output parameter is copied to its associated step output tag
when requested to do so or automatically when the phase becomes STOPPED,
ABORTED, or COMPLETE. Sequence output parameters evaluate their
expressions when the sequence becomes STOPPED, ABORTED, or COMPLETE.

An Equipment Sequence diagram is intended to control a specific piece of


equipment. All steps within the sequence refer to existing Equipment Phase
instances within the same controller.

See also

Equipment Sequence diagrams and Sequential Function Chart routines


differences on page 25

Equipment Sequence Use the following table to guide when to use an Equipment Sequence diagram
instead of a Sequential Function Chart routine.
diagrams and Sequential
Function Chart routines Sequential Function Chart routine Equipment Sequence diagram
Is a single routine. Coordinates the execution of independent programs.
differences No concept of state beyond inhibited. Has an internal state machine to manage sequence
execution and display states that are useful to operators.
A step contains a list of structured text actions to perform. A step has an internal state machine managing
interactions between a sequence and the step's
associated Equipment Phase.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 25


Chapter 4 Equipment Sequence Editor overview

Transitions enable and disable scanning of a step's Transitions have an internal state machine managing
actions. when steps are activated, deactivated, and automatically
commanded.
Operators specify tag values but do not expect to run the Operators expect to interact with the sequence, the steps,
program interactively. the parameters, and the transitions.
Program runs after download, unless inhibited. Sequences wait to be commanded after download.

See also

Equipment Sequence Editor on page 24

26 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

Equipment Sequence An Equipment Sequence diagram is a graphical representation of a sequence that


coordinates the execution of equipment. Each diagram comprises basic sequence
Diagrams elements such as steps, links, and transitions structured in a specific topology.
Each Equipment Sequence has one routine that is configured by adding elements
and applying branch structures using buttons available from the Equipment
Sequence Element toolbar in the Equipment Sequence Editor.

See also

Steps to create Equipment Sequence diagrams on page 25

Create an Equipment Equipment Sequence programs:

Sequence program • Describes the order in which Equipment Phases run and when they are
started and stopped.
• Run as a program containing only one routine—the sequence diagram.
• Use sequence input parameters and sequence output parameters.
• Displays the same states as a phase. The current state is based on active
sequence elements.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 27


Chapter 4 Equipment Sequence Editor overview

Add steps, transitions, links, divergent and convergent branches to manually


construct Equipment Sequences. Equipment Sequences are created in either
simple series, loop, simultaneous, or selective structures.

To create Equipment Sequence programs:

1. Define a new Equipment Sequence.

2. Configure Equipment Sequence properties.

3. Construct Equipment Sequence diagrams. See Equipment Sequence


Diagrams.

4. Create a Sequence Parameter using the New Parameter or Tag dialog box.

Important: When the Equipment Sequence scan rate is significantly longer than the
Equipment Phase scan rate, sequence events triggered by step state
changes may not be generated. It is advisable to avoid phase state
changes occurring in less than the sequence scan rate, if having those
event records is necessary.

See also

Define a new Equipment Sequence on page 28

Configure Equipment Sequence properties on page 30

Equipment Sequence Diagrams on page 27

Create a Sequence Parameter using the New Parameter or Tag dialog box
on page 31

Define a new Equipment In New Equipment Sequence, define the properties of an Equipment Sequence.

Sequence Before you begin:

• Go offline with the controller.

To define a new Equipment Sequence:

1. Go to File > New Component > Equipment Sequence to enter properties


for the new Equipment Sequence.

2. In Name, enter a name for the Equipment Sequence.

3. (Optional) In Description, enter a description for the Equipment


Sequence.

28 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

4. (Optional) To make the Equipment Sequence program a child of an


existing program in the logical model, select the Parent program.
Otherwise, select None.

5. From Schedule In, choose the task to schedule the Equipment Sequence.

The list contains only tasks in which the Equipment Sequence can be
scheduled. If you created the Equipment Sequence by right-clicking a task in
the Controller Organizer, that task is selected by default.

6. (Optional) To give the Equipment Sequence a version string for event


reporting purposes, select from the menus for Major and Minor, and enter
text in Extended Text.

• Major: The major revision number of the Equipment Sequence. The


default value is 1.
• Minor: The minor revision number of the Equipment Sequence. The
default value is 0.
• Extended Text: Enter additional revision information. For example,
entering c in this field, makes the Equipment Sequence version 1.0c.
The maximum number of displayable characters is 40. Any characters
exceeding the limit are ignored.

7. (Optional) To continue describing the Equipment Sequence revision, use


the Revision Note.

For example, list the changes made to the Equipment Sequence since the
last revision.

8. (Optional) To inhibit this Equipment Sequence and prevent it from being


owned or commanded, select Inhibit Sequence. The check box is cleared by
default.

An Equipment Sequence’s icon displays in the Controller Organizer with


the inhibited indicator:

9. (Optional) To open the Equipment Sequence Editor upon creation of a


sequence, select Open Sequence Diagram. The check box is selected by
default.

10. To configure additional Equipment Sequence attributes upon creation of a


sequence, select Open properties. The check box is clear by default. Click
OK to open Equipment Sequence Properties.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 29


Chapter 4 Equipment Sequence Editor overview

See also

Configure Equipment Sequence properties on page 30

Configure Equipment Configure Equipment Sequence properties in the Equipment Sequence


Properties dialog box, Configuration tab.
Sequence properties
Before you begin:

• Go offline with the controller.

All transitions following the selective divergence are active and evaluate their
expressions with every scan of the sequence.

To configure Equipment Sequence properties:

1. Open the Equipment Sequence Properties dialog box by right-clicking the


Equipment Sequence name in the Controller Organizer or Logical
Organizer and selecting Properties.

2. Click the Configuration tab and revise the properties as necessary.

a. (Optional) Select Retain sequence ID when resetting sequence to


retain the sequence ID when resetting the Equipment Sequence. If this
option is not selected, a RESET command clears the Sequence ID value
of an Equipment Sequence.

b. (Optional) Select the Generate sequence events option to generate


sequencing events recording the manufacturing process. This includes
operator commands, changes in sequence attributes, and changes in
sequencing parameters and step tag values.

c. (Optional) If you selected the Generate sequence events option, enter


a number for the Unit ID option. The Unit ID is an integer value
assigned to represent the equipment unit the sequence is coordinating.
This value is recorded with sequence events to identify the equipment
coordinated.

d. (Optional) When starting sequence, there are two options:

• Use initial value of the tag: Select this option to reinitialize all
sequencing parameter and step tag value fields with their
configured Initial Value field when a START command is sent to
the Equipment Sequence.

30 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

• Use current value of the tag: Select this option to retain the value
of all sequencing parameter and step tag valuefields when a START
command is sent to the Equipment Sequence.
e. (Optional) When resetting sequence, there are two options:

• Restore the tag to its initial value: Select this option to reinitialize
all sequencing parameter and step tag value fields with their
configured Initial Value field when a RESET command is sent to
the sequence.
• Maintain current value of the tag: Select this option to retain the
value of all sequencing parameter and step tag value fields when a
RESET command is sent to the sequence.

See also

Equipment Sequence Diagrams on page 27

Create a Sequence Sequence input parameters define the set of parameters that must be provided to
an Equipment Sequence program to coordinate manufacturing a product. The
Parameter using the New sequence output parameters record process variables set during execution.
Parameter or Tag dialog
Before you begin:
box
• Go offline with the controller.

To create a sequence parameter:

1. In the Equipment Sequence, right-click Parameters and Local Tags.

2. Select New Parameter.

3. In Name, enter the name of the sequence parameter.

4. (optional) In Description, enter a description of the sequence parameter.

5. In Usage, select one of the following:

• Input Parameter
• Output Parameter

6. In Data Type, click to access the Select Data Type dialog box and
select one of the sequence parameter data types.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 31


Chapter 4 Equipment Sequence Editor overview

Sequence parameters only allow these system provided data types:


SEQ_DINT, SEQ_SINT, SEQ_INT, SEQ_REAL, SEQ_BOOL, and
SEQ_STRING.

7. (optional) In Parameter Connection, choose a single connection for the


sequence parameter.

8. Scope shows the new Equipment Sequence where the new parameter is
created.

9. In External Access, choose whether the sequence parameter will have


Read/Write, Read Only, or no (None) access from external applications
such as HMIs.

Tip: It is recommended to have input parameters use Read/Write access, and output
parameters use Read Only access. Often, inputs are assigned by an operator and
outputs need to maintain the integrity of the value assigned to it by the sequence.

10. Verify the Sequencing check box is selected. This is the default.

11. Click Create for create options. Select:

• Create and Close to close the dialog box after creating a tag (default).
• Create and Open New to save the tag created and open another empty
New Tag dialog box.
• Create and Keep Open to save the tag created and keep the dialog box
open with the values still showing.

12. To configure or change the following sequence parameter attributes, go to


the Tag Editor:

• Sequencing flag
• Data Type
• Description
• External Access
• Connections
For each sequence parameter, the Description and Connections may be
configured for Value, Valid, and Initial Value.

13. To configure or change the following sequence parameter attributes, go to


the Sequence Tag Editor:

• Value

32 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

• Initial Value
• Expression (only available on sequence output parameters)
• Description
Tip: The following boxes in the New Parameter and Tag dialog box are not
configurable, because they do not apply to sequence parameters:
• Base Tag
• Alias
• Style
• Constant

See also

Example: Construct an Equipment Sequence diagram on page 33

Example: Construct an Following is an example of how to create an Equipment Sequence diagram. In this
example, the Equipment Sequence adds material, mixes material, and empties the
Equipment Sequence mixer by doing the following:
diagram
• Prepares for mixing by adding 25% of Material_A from Tank 1 at 500
gallons per minute.
• Adds and mixes material through three different execution paths,
simultaneously:
• Finishes adding Material_A from Tank 1 at 25 gallons per minute,
using a transfer of control.
• Adds Material_B from Tank 2 or Tank 3, using a selective divergence.
• Mixes Material_A with Material_B.
• Empties the mixer after all materials are added and the mixing is complete.

In the following example, an Equipment Sequence diagram is constructed to add


material quickly from a tank, then simultaneously continues to add material and
mix material, then empties the mix.

To construct this example of an Equipment Sequence diagram:

1. Prepare the Equipment Sequence diagram.

2. Prepare for mixing.

3. Configure simultaneous branches to add and mix material.

4. Converge the simultaneously executed paths.

5. Empty the tank after materials are added and mixed.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 33


Chapter 4 Equipment Sequence Editor overview

6. Finish the Equipment Sequence diagram.

See also

Prepare the Equipment Sequence diagram on page 34

Configure simultaneous branches to add and mix material on page 35

Converge the simultaneously executed paths on page 38

Prepare the Equipment Prepare the Equipment Sequence diagram.

Sequence diagram To prepare the Equipment Sequence diagram:

1. In the Equipment Sequence that was created, delete the link between
Tran_000 and the end step .

2. Move the end step above the transition, so you can find it later.

3. Create sequence input parameters to specify how much Material_A and


Material_B are to be added in later steps.

34 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

4. To prepare for mixing, configure the step and transition to begin adding
Material_A.

See also

Configure simultaneous branches to add and mix material on page 35

Converge the simultaneously executed paths on page 38

Use simultaneous and selective branches to add and mix material.


Configure simultaneous
branches to add and mix To configure simultaneous branches to add and mix material:
material
1. On the Equipment Sequence toolbar, click Add Simultaneous divergence
with elements branch to add the ingredients and mix the ingredients. This
adds two out of the three required steps, so you must add a disconnected
step and link it to the simultaneous divergence branch.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 35


Chapter 4 Equipment Sequence Editor overview

This creates three simultaneous paths: one to add Material_A, one to add
Material_B, and one to mix the ingredients.

2. For each step, rename the default step name and then select the Equipment
Phase.

The Equipment Sequence must choose to add Material_B from either Tank
2 or Tank 3.

3. Add a selective divergence to choose between two paths.

36 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

The transition expressions test a tag to determine which path to use and run
the correct Equipment Phase. The tank to be used is a sequence input
parameter, Add_B_From_Tank. The value 2 means add material from
Tank 2 and the value 3 means to add material from Tank 3. The sequence
input parameter is created and configured in a later step.

4. Add the selective convergence branch to bring the two separate tank paths
back together.

See also

Converge the simultaneously executed paths on page 38

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 37


Chapter 4 Equipment Sequence Editor overview

Converge the Converge simultaneously executed paths.

simultaneously executed To converge the simultaneously executed paths:


paths
1. Add a step underneath the selective convergence so all three paths can be
merged back together. The simultaneous convergence branch requires all
preceding branches to end in steps.

2. After adding and configuring the additional step, add the simultaneous
convergence branch.

3. Now that the three separate paths are merged back together with materials
added and mixed, empty the tank and dump the mixture by adding and
configuring a disconnected transition and a step and transition pair.

38 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Equipment Sequence Editor overview Chapter 4

4. To finish the Equipment Sequence diagram, move the end step below the
Empty_Mixer_1 step. Then automatically align the sequence elements in
the diagram so that the layout is less cluttered and clearly visible.

See also

Example: Construct an Equipment Sequence diagram on page 33

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 39


Chapter 5

Sequence Execution & Monitoring

Sequence execution is responsible for coordinating:

• The execution of phases in the order specified by the sequence diagram.


• The transition expressions to specify when steps are attached to phases,
started, stopped, reset, and attached.
• The step activation to trigger passing Equipment Sequence input data to the
Equipment Phase.
• The COMPLETE, STOPPED, or ABORTED triggers passing output data
from the Equipment Phase to the Equipment Sequence.
• Generating events to record changes in status and operator interactions.

Equipment Sequence programs are IDLE until they are started. Resetting an
Equipment Sequence returns them to an IDLE state. Sequence parameters and
step tags can be initialized manually or configured as a sequence property.

Monitoring is performed from the Logix Designer application and the


SequenceManager Controls. The Equipment Sequence Monitor is the equivalent
of the Sequence Detail Control and the Sequence Parameter Control. The
rendering of status is the same. Command interactions are the same with the
exception of ownership; the Logix Designer application overrides ownership of the
Equipment Sequence and the SequenceManager Controls request ownership.

The Equipment Sequence Open the Equipment Sequence Monitor by opening an Equipment Sequence
diagram from the Controller Organizer or Logical Organizer, and going on line
Monitor with the controller. The Equipment Sequence Monitor is the routine window.

The Equipment Sequence Monitor is the online version of the Equipment


Sequence Editor and is used to monitor and interact with Equipment Sequences
that have been downloaded to the controller. The control engineer can do the
following:

• Command the Equipment Sequence.


• Change the value of parameters and attributes.
• Interact with the executing sequence.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 41


Chapter 5 Sequence Execution & Monitoring

See also

SequenceManager and related components overview on page 19

Equipment Sequence Editor on page 24

Sequence Tag Monitor Open the Sequence Tag Monitor by opening an Equipment Sequence diagram
from the Controller Organizer or Logical Organizer, and going on line with the
controller. The Sequence Tag Monitor is the grid in the bottom of the diagram.

Use the Sequence Tag Monitor to view and edit sequence parameters and assign
step tag values while the controller is online. All sequence parameters and step tags
are listed in a table format.

The attributes that can be edited in the Sequence Tag Monitor are: Value,
InitialValue, and Description, based on the tag's External Access configuration.
In the Sequence Tag Monitor, parameter expressions can be enabled, disabled, or
forced to evaluate.

See also

Sequence Execution & Monitoring on page 41

Step states in an Equipment When a step is not active, the step state is inactive. When a step is active, and
attached to an Equipment Phase, the step state mirrors the state of the Equipment
Sequence Phase. The step state is also represented by the color of the step.

Steps with a Do Nothing phase only have two displayed step states: RUNNING
and IDLE.

Step States Description


ABORTING ABORTING means the Equipment Phase's ABORTING routine is executing.
ABORTED ABORTED means the Equipment Phase's ABORTING routine is finished.
HOLDING HOLDING means the Equipment Phase's HOLDING routine is executing.
HELD HELD means the Equipment Phase's HOLDING routine is finished.
RESETTING RESETTING means the RESETTING logic is executing.
RESTARTING RESTARTING means the RESTARTING routine is executing.
RUNNING RUNNING means the RUNNING routine is executing.
STOPPING STOPPING means the STOPPING routine is executing.
STOPPED STOPPED means the STOPPING routine is finished.
COMPLETE COMPLETE means the RUNNING routine is finished.
IDLE IDLE means the step is active and attached to the associated Equipment Phase, but the Equipment Phase is not executing a routine.
INACTIVE INACTIVE means that the step is not active and is not attached to its associated Equipment Phase.

42 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

Step execution in an Each step in an Equipment Sequence diagram represents a specific action. Step
types include initial steps, Equipment Sequence steps, No phase steps, and end
Equipment Sequence steps.

Each step executes differently.

Initial step - The initial step is activated when the Equipment Sequence starts
execution and immediately becomes COMPLETE. The initial step may be
activated or deactivated with a change active step command.

Equipment Sequence step execution- The Equipment Sequence step


automatically loads step input tag values into the phase input parameters when the
Equipment Sequence attaches to the step, depending on the configuration of the
Equipment Phase. The step commands the Equipment Phase to start and shows
status changes of the Equipment Phase in the status of the step. The step
automatically copies phase output parameter values into step output tags when the
Equipment Phase becomes COMPLETE, STOPPED, or ABORTED, depending
on the configuration of the Equipment Phase.

No phase step - The step immediately becomes COMPLETE when executed.

End step - The end step is activated when the preceding transition starts it and
immediately becomes COMPLETE. The end step may be activated or deactivated
with an active step change command.

See also

Step execution in a selective sequence on page 43

Step execution in a simultaneous sequence on page 45

Step execution in a In a selective branch, only the step in the path or branch under the first transition
to evaluate as TRUE is executed. Other paths or branches are ignored. Sequence
selective sequence execution continues in the selected path until that path's final transition.

Step execution in a selective branch

The following table describes how and when steps in a selective sequence execute -
the active step is shaded in gray. This sequence execution example uses a simple
step (A-F) sequence with one selective branch.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 43


Chapter 5 Sequence Execution & Monitoring

Active step Sequence example Description


Initial step When the sequence is commanded to START, the initial step becomes active.

Step A After Transition 0 becomes TRUE, the initial step is STOPPED, RESET, and deactivated. Control is passed to Step
A, which is made active and is STARTED. Transition 0 becomes inactive and Transition 1 becomes active.

Step B After Transition 1 becomes TRUE, Step A is STOPPED, RESET, and deactivated. Control is passed to Step B,
which is made active and is STARTED. Transition 1 becomes inactive and both Transition 2 and Transition 4
become active.

Step C If Transition 2 becomes TRUE first, Transition 4 is deactivated. Step B is STOPPED, RESET, and deactivated.
Control is passed to Step C, which is made active and is STARTED. Transition 2 becomes inactive, and Transition
3 becomes active.

44 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

Step E After Transition 3 becomes TRUE, Step C is STOPPED, RESET, and deactivated. Control is passed to Step E, which
is made active and is STARTED. Transition 6 is made active, and Transition 3 is deactivated.

Step F After Transition 6 becomes TRUE, Step E is STOPPED, RESET, and deactivated. Control is passed to Step F, which
is made active and is STARTED. Transition 7 is made active, and Transition 6 is deactivated.

End step After Transition 7 becomes TRUE, Step F is STOPPED, RESET, and deactivated. Control is passed to the end step,
which is activated. The end step immediately becomes COMPLETE. This indicates that the entire sequence is
COMPLETE.

See also

Step execution in a simultaneous sequence on page 45

Step execution in a In a simultaneous branch, the steps immediately following a simultaneous


divergence branch start execution together. Step execution continues in all paths
simultaneous sequence until the transition following the simultaneous convergence evaluates as TRUE.
To execute across the simultaneous convergence branch, all steps immediately
preceding the convergence must be active and the transition (Transition 3 in the
example) immediately following the convergence must evaluate as TRUE.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 45


Chapter 5 Sequence Execution & Monitoring

Step execution in a simultaneous branch

The following table describes how and when steps in a simultaneous sequence
execute - the active step is shaded in gray. This sequence execution example uses a
simple five step (A-E) sequence with one simultaneous branch.

Active step Sequence example Description


Initial step When the sequence is commanded to START, this step becomes active.

Step A After Transition 0 becomes TRUE, the initial step is STOPPED, RESET, and deactivated. Control is passed to Step
A, which is made active and is STARTED. Transition 0 becomes inactive and Transition 1 becomes active.

Step B & After Transition 1 becomes TRUE, Step A is STOPPED, if it is still RUNNING, RESET and deactivated. Steps B and C
Step C become active and are STARTED at the same time. Transition 1 becomes inactive and Transition 2 becomes
active.

Step C & After Transition 2 becomes TRUE, Step B is STOPPED, RESET, and deactivated. Step D is activated and STARTED.
Step D Step C remains active. Transition 2 becomes inactive and Transition 3 becomes active, because all the steps
immediately preceding the transition are active.

46 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

Step E Steps C and D are active, so Transition 3 evaluates its expression. After Transition 3 becomes TRUE, Steps C and
D are STOPPED, RESET, and deactivated and Step E is activated and STARTED. Transition 3 becomes inactive
and Transition 4 becomes active.

End step After Transition 4 becomes TRUE, Step E is STOPPED, RESET, and deactivated. The end step is activated and
STARTED. The end step immediately becomes COMPLETE. This indicates that the entire sequence is COMPLETE.
Transition 4 becomes inactive.

See also

Step execution in a selective sequence on page 43

Transition display states Transition display states show how the transition execution relates to the overall
Equipment Sequence execution.

Transition Display State Transition Color Description


IDLE GRAY The transition is not actively executing.
ARMED GREEN The transition is actively evaluating its expression.
FIRING GREEN The transition expression has evaluated TRUE. The previous steps is STOPPED and the next steps is started.
STOPPED BLUE The transition has completed processing a STOP command and has stopped the transition's execution.
ABORTED PURPLE A Equipment Sequence transition in the ABORTED state has been disabled by an ABORT command and
will not advance an Equipment Sequence chart.
HELD YELLOW/BROWN An Equipment Sequence transition in the HELD state has been halted by a HOLD command or HELD
because of an Equipment Sequence failure and will not initiate or advance the Equipment Sequence
transition firing process until issued a RESTART command. If the transition has been HELD due to an
Equipment Sequence failure, the failure should be cleared before issuing a RESTART command.
HOLDING YELLOW/BROWN An Equipment Sequence transition in the HOLDING state is advancing the Equipment Sequence transition
firing process. This transitional state is only visible until the scan processing the HOLD command has
finished.

See also

Transition firing states on page 48

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 47


Chapter 5 Sequence Execution & Monitoring

Transition firing states The firing attribute is a subset of the FIRING state and gives a visual indication of
the current state.

This firing attribute is visible when the transition expression has evaluated TRUE.
The firing process requires several interactions with different phases and is an
asynchronous process. Some phases may have programs that can take a long time
to finish running (stopping a motor for example), so the firing object shows what
the transition is doing. The displayed Firing Attribute values are: COMMITTED,
STOPPING, RESETTING, PENDING, and PAUSED.

Firing Attribute Description


ACQUIRING The Equipment Sequence is acquiring the right to command the Equipment Phase. For every step that follows the transition, the Equipment
Sequence must attach to each associated Equipment Phase before the steps can be activated.
COMMITTED The transition is committed to firing because the transition expression has evaluated TRUE, but the transition cannot activate the following
steps because it is in Manual mode or the Equipment Sequence is in the PAUSED substate.
STOPPING As part of firing, the Equipment Sequence commands all the active preceding steps to stop. The transition firing state is STOPPING until all
commanded steps are STOPPED.
RESETTING As part of firing, the Equipment Sequence commands all the preceding steps that are STOPPED to RESET. The transition firing state is RESETTING
until all the commanded steps are IDLE.
PENDING The transition is not able to fire because the Equipment Phases of the steps above or below the transition are not in the correct state to permit
the transfer of control function.
PAUSED The transition is committed to fire, but cannot because the Equipment Sequence has been PAUSED. The transition is waiting for a RESUME
command.
POST SCANNING The transition is at the end of the firing process. On the next scan of the Equipment Sequence chart, the transition advances the chart.

See also

Transition display states on page 47

Transition execution When a transition is activated, it evaluates its expression. If the expression is
TRUE, it stops all the preceding steps that are active, resets and detaches from all
the preceding steps, and attaches to the following steps. Once it attaches to the
following steps, it starts those steps.

See also

Step states in an Equipment Sequence on page 42

Transition display states on page 47

Transition firing states on page 48

Quality of Data Quality of Data is the concept that a sequence parameter or step tag can have a
value that is not known to be correct. There are three cases:

• Step output tag has not been updated yet. There are three ways the update
can occur.

48 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

• When the Equipment Phase has not requested to load a value to the
step output tag (PXRQ instruction).
• The Equipment Phase has not run to a COMPLETE, STOPPED, or
ABORTED state for a configured automatic update to occur.
• The step output has read/write external access (inherited from the
Equipment Phase output parameter) and the operator assigns a value.
• Sequence output parameter has not been updated yet. There are three ways
the update can occur.
• The sequence enters the COMPLETE, STOPPED, or ABORTED
state, causing the sequence parameter's expression to evaluate.
• The operator commands the parameter expression to evaluate.
• The output has read/write external access and the operator assigns a
value.
• An expression contains a tag with an invalid quality of data.
• Step input tags and sequence output parameters can have a configured
expression that may reference a sequence parameter or step tag whose
Valid member is FALSE.

If your application needs to discern data integrity, use Quality of Data to test the
validity of sequence parameter data.

These system provided data types implement the Quality of Data concept:

• Valid – Specifies the validity of the contents of the sequence parameter or


step tag’s Value member as a BOOL: 1 = Valid and 0 = Invalid. When
the Valid attribute is 1, then the Value member of the parameter or
sequence is known to be correct. When it is 0, the Value member is not
known to be correct. If the Value is known not to be valid, the invalid
symbol is shown.
• InitializeAsValid - When an Equipment Sequence is initialized, the Valid
attribute is set to the value of the InitializeAsValid attribute.

The Valid attribute is the quality of data of the sequence input parameter. Because
these parameters may not have expressions, the Valid attribute is always TRUE.

See also

How sequence output parameter and step input tag expressions evaluate on
page 50

How step tags update on page 50

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 49


Chapter 5 Sequence Execution & Monitoring

How sequence parameters update on page 51

How sequence output Step tag input expressions evaluate at the beginning of each scan, sequence output
parameter expressions evaluate when the sequence enters a terminal (STOPPED,
parameter and step input ABORTED, COMPLETE) state. Step tag input expression and sequence output
tag expressions evaluate parameter expressions can be commanded to evaluate using the Force Expression
Evaluation command.

See also

How step tags update on page 50

How sequence parameters update on page 51

How step tags update Step input tags

Step input tags update by directly assigning a value using Logix Designer or the
Sequence Parameter Control, depending on the configured External Access
value. Then a sequence’s tags are initialized by moving the Initial Value attribute
value into the Value attribute, by using either the START or RESET command in
Logix Designer or the Initialize Parameters command in Logix Designer or the
Sequence Parameter Control. The configured parameter expression is evaluated
on each scan. The step input tag’s expression must be enabled for evaluation to
update the Value attribute.

Step output tags

Step output tags update by directly assigning a value using Logix Designer or the
Sequence Parameter Control, depending on the configured External Access
value. Then a sequence’s tags are initialized by moving the Initial Value attribute
value into the Value attribute, by using either the START or RESET command in
Logix Designer or the Initialize Parameters command in Logix Designer or the
Sequence Parameter Control. Then the associated Equipment Phase output
parameter value is loaded when one of the following occurs:

• The phase is configured to update the state to change to a terminal state


(COMPLETE, STOPPED, or ABORTED)
• The scanning Equipment Phase routine executes a Equipment Phase
External Request (PXRQ) instruction requesting the output parameter
value be copied to the step output tag.

See also

How sequence parameters update on page 51

Sequence Parameters Control on page 81

50 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

How sequence parameters Sequence input parameters

update Sequence input parameters update by executing a configured Connection,


performed by the firmware every scan. Then by directly assigning a value using
Logix Designer or the Sequence Parameter Control, depending on the
configured External Access value. Then a sequence’s tags are initialized by moving
the Initial Value attribute value into the Value attribute, by using either the
START or RESET command in Logix Designer or the Initialize Parameters
command in Logix Designer or the Sequence Parameter Control.

Sequence Output Parameters update:

Sequence output parameters update by directly assigning a value using Logix


Designer or the Sequence Parameter Control, depending on the configured
External Access value. Then a sequence’s tags are initialized by moving the Initial
Value attribute value into the Value attribute, by using either the START or
RESET command in Logix Designer or the Initialize Parameters command in
Logix Designer or the Sequence Parameter Control. The associated Equipment
Phase output parameter value is loaded when the phase is configured to update to
the state to change to a terminal state (COMPLETE, STOPPED, or
ABORTED). The sequence output parameter’s expression must be enabled to
update the Value attribute after evaluation.

See also

How step tags update on page 50

Sequence Parameters Control on page 81

Pause, auto pause, and Use the Pause and Auto Pause buttons to test and troubleshoot Equipment
Sequence or Equipment Sequence step execution.
resume commands
The Pause and Auto Pause button commands:

• The Equipment Sequence to pause execution of the sequence when active


transition expressions evaluate TRUE.
• The Equipment Sequence step and its associated phase to enable pausing
when a PPD instruction is executed.

When the Pause and Auto Pause buttons are toggled on, the button background
is a light blue with a dark blue outline.

The Resume button commands:

• The Equipment Sequence to resume execution of the sequence.


• The Equipment Sequence step and its associated phase to resume execution.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 51


Chapter 5 Sequence Execution & Monitoring

See also

Change modes effect on sequence and step commands on page 54

Ownership is having the right to command an Equipment Sequence or an


Ownership
Equipment Phase.

Both Equipment Sequences and Equipment Phases must be owned to be


commanded. The ownership commands are Attach (SATT) and Detach (SDET).

Internal sequencers (programs), external sequencers (FactoryTalk Batch), and


operators always use an Attach instruction to command an Equipment Sequence.
Logix Designer always uses an Override (SOVR) instruction to command an
Equipment Sequence. A program might successfully attach an Equipment
Sequence but be unable to command it because Logix Designer has overridden
ownership.

The ownership override commands are:

• Attach: Operators, internal sequencers, and external sequencers attach to


an Equipment Sequence or Equipment Phase to control it.
• Override: A Logix Designer application always takes ownership of an
Equipment Sequence or Equipment Phase by overriding an existing Attach.
• Detach: Operators, internal sequencers, external sequencers, and Logix
Designer Detach to release the right to control the Equipment Sequence or
Equipment Phase.

If the Equipment Sequence is attached by another sequencer, an external


sequencer, or an operator, an Override takes precedence without waiting for other
owners to release the Equipment Sequence. Any existing attachment remains and
resumes control once the Override is gone.

If the Equipment Phase is attached by an Equipment Sequence, an Override


interrupts the Equipment Sequence's ability to coordinate the Equipment Phase.
This is a sequencing failure condition and the Equipment Sequence is HELD.

Only one attachment is allowed on an Equipment Phase or Equipment Sequence.


If the Equipment Phase or Equipment Sequence is not already attached to,
attaching will grant the attaching sequencer ownership (and commanding
privilege). If the Equipment Phase or Equipment Sequence is already attached to,
then other potential owners trying to attach to the same Equipment Phase or
Equipment Sequence fail.

52 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

Ownership types

Ownership types are the ways a sequence or phase may be owned--enabling the
owner to command them. Each ownership type is stored independently on the
phase or sequence so one type of ownership does not remove another.

Relative Priority Ownership Type # Allowed Description


First Logix Designer Override Up to 15 Logix Designer application always takes ownership
by overriding all other potential users. Up to 15
different Logix Designer applications may attach to a
single Equipment Phase or Equipment Sequence at
one time.
Second Attach 1 A request to attach fails if the Equipment Sequence
or Equipment Phase is already attached.

Ownership user types

There are four user types: Logix Designer, External Sequencer, Internal Sequencer,
and Operator. The attachment type accompanies an attach request to take
ownership.

Types of users Description Examples


Logix Designer A control engineer using Logix Designer overrides ownership Equipment Phase Monitor within Logix Designer
of the Equipment Phase or Equipment Sequence. Sequence Editor within Logix Designer
Internal Sequencer A program running within a ControlLogix controller. Programs, Equipment Sequences, Equipment
Phases
Operator An operator logged into a FactoryTalk View Site Edition Sequence Detail, Sequence Summary
display interacting with Equipment Sequence through the
SequenceManager Controls.
When an attachment of Operator type exists, all operator
displays may command the Equipment Sequence.
External Sequencer An application outside ControlLogix that interacts with FactoryTalk Batch Server
sequenced objects.

See also

The SequenceManager Controls on page 69

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 53


Chapter 5 Sequence Execution & Monitoring

Change modes effect on Use the change mode to toggle an Equipment Sequence between Automatic and
Manual mode.
sequence and step
commands Mode effect on sequence commands

The following table shows the mode effect on sequence commands.

Command Automatic Mode Manual Mode


Start, Hold, Stop, Abort, Restart, Reset Allowed Ignored
Pause, Auto Pause, Resume Allowed Ignored
Clear Failures on a sequence Allowed Allowed
Force Transition Expression to Evaluate TRUE Allowed Ignored
Change Active Step Ignored Allowed

Mode effects on step commands

Commanding a step is the same as commanding the Equipment Phase, except it is


done through the sequence. The following table shows the mode effect on step
commands.

Command Automatic Mode Manual Mode


Start, Hold, Stop, Abort, Restart, Reset Ignored Allowed
Pause, Auto Pause, Resume Ignored Allowed
Clear Failures on a sequence Ignored Allowed
Force Transition Expression to Evaluate TRUE Allowed Allowed

See also

Equipment Sequence failures on page 54

Equipment Sequence Failures originate from two sources, Equipment Phases and Equipment
Sequences. An Equipment Phase generates a failure by executing a Phase Failure
failures (PFL) instruction, maintained by the Failure attribute. The Equipment Sequence
generates a failure by detecting a problem that impairs its ability to coordinate
active sequence elements, maintained by the Internal Failure attribute.

A failure propagates up the hierarchy of sequence elements from the point it


originated; Equipment Phases notify steps and steps notify the Equipment
Sequence. Failure status is maintained at each of these layers:

• The Equipment Phase backing tag has a Failure member.


• The step backing tag has a Failure member and an Internal Failure member.
• The Equipment Sequence backing tag has a Failure member and an Internal
Failure member.

54 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Execution & Monitoring Chapter 5

A failure is considered a serious problem that warrants holding the execution of


the sequence, all active elements, and any phases to which they are attached until
the cause of the failure is corrected. This can occur in either Automatic or Manual
mode.

Phase-generated failures

Phase-generated failures are the result of the phase logic executing a PFL
instruction. The instruction includes a failure code created and managed by the
user. The failure is stored on the Failure member of the phase’s backing tag. The
failure is detected by the step, setting the Failure member on the step's backing tag.
Finally, the failure on the step is detected by the sequence, setting the Failure
member on the sequence.

Sequence-generated failures

Sequence-generated failures are detected by the sequencing engine as it executes.


The failure is detected by the step and is stored on the Internal Failure member of
the step’s backing tag. That failure is detected by the step, setting the Internal
Failure member on its backing tag.

Clear failures

The Clear Failures command resets the failure and internal failure members of the
sequence and step backing tags. If a phase failure is being cleared, the Clear
Failures command is forwarded to the phase. Sequences, like phases, cannot be
restarted until all their failures are cleared. Note that if the cause of the failure has
not been resolved, the next scan of the Equipment Sequence engine will likely
regenerate the failure.

You need to do the following sequence of actions in order to recover from an


Equipment Sequence failure:

• Correct the cause of the failure.


• Clear the failure status from the sequence, step, and phase involved in the
failure.
• Restart the sequence.

See also

Change modes effect on sequence and step commands on page 54

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 55


Chapter 6

SequenceManager event handling applications

The event handling components are split between the controller and a supporting
PC. The sequence program, running in the firmware of the controller, generates
events. An external workstation hosts the SequenceManager Event Client Service,
which subscribes to SequenceManager events and writes them to a raw event data
file. The SequenceManager Event Archiving Service converts the raw events data
into readable form, writes the data to an .EVT file, and populates tables in a
database for PlantPAx reporting.

SequenceManager Event Console

• Start, stop, pause, and resume the SequenceManager Event Client Service
and the SequenceManager Event Archiving Service.
• Display the status of the SequenceManager Event Client Service and the
SequenceManager Event Archiving Service
• Configure the SequenceManager Event Client Service settings and
SequenceManager Event Archiving Service settings.

SequenceManager Event Client

The SequenceManager Event Client receives events from multiple controllers.


Each event received is written directly to a raw event file.

SequenceManager Event Archiving Service

SequenceManager Event Archiving Service is responsible for reading events from


the raw event file. Each event is translated and localized into readable strings, then
the data is stored into sequence specific event files (.EVT files). Another option is
for data to be stored into the BatchHistoryEx data table in the SQL Server for
PlantPAx event data handling.

See also

SequenceManager and related components overview on page 19

SequenceManager events record status changes, processing actions, and user


SequenceManager events
interactions as the Equipment Sequence executes. These events have importance
at runtime because they indicate the current status of various aspects of a

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 57


Chapter 6 SequenceManager event handling applications

manufacturing process and have historical importance because the data is a record
of exactly what transpired.

The three event types recorded by the SequenceManager are:

• Sequence Command Events record commands to change state, change


pause state, change sequence mode, change ownership, clear failures, change
active step, override transition expression, and enable and disable sequence
tag expressions.
• Process Data Update Events record the value of system values updating,
including the state, pause, mode, ownership, and failure.
• Parameter Update Events record changes in value or status of sequence
parameters and step tags, including operator updates to parameters and step
tag values, operators changing the status of sequence parameter or step tag
expressions, phase updates to step tag values, and phase requests for step tag
data.

Keep the following considerations in mind when using SequenceManager events:

• Equipment Phases and Equipment Sequences should be run in a periodic


task.
• Equipment Sequence programs can be in the same periodic task as the
Equipment Phase programs, or in separate tasks.
• Generating events affects the performance of an Equipment Sequence. Only
generate events when records for executing the sequence are required.
• Avoid generating more than 60 events and alarms combined per second.
• Configure sets of sequence parameters and step tags to not exceed the
memory capacity of the controller.
• Equipment Phases can execute faster than an Equipment Sequence can
record events.
An Equipment Sequence coordinates Equipment Phases that run in
fractions of a second. But, the firmware event generation systems cannot
keep up. When it is important to reliably record events, it is best that the
phase takes at least 10 seconds to run to completion.

• When steps are started and completed, use automatic storing of input and
output data. A phase executing PXRQ instructions to read input or write
outputs from or to an Equipment Sequence faster than every 10 seconds
may lose events.

The benchmark of a fast Equipment Sequence program is tested as:

58 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


SequenceManager event handling applications Chapter 6

• 18 Steps with three parallel paths of simultaneous execution


• 225 Parameters
• Generating 334 events
• For a sequence running 60 seconds
• For an ES completing in approximately 60 seconds
With this phase and sequence configuration, events are not lost when burst
of alarms are processed.
The benchmark is primarily for testing how fast Equipment Sequence can
run without losing events. The execution speed of a sequence depends upon
the execution speed of the Equipment Phases. Phases that complete their
execution in less than 10 seconds may lose events depending upon the
number of alarms being generated.

• Equipment Phases can be configured to get Input Parameters when they


start and to store Output Parameters when they complete. This is the most
efficient way to move data between an Equipment Sequence> and an
Equipment Phase.
Important: When Generate Events is enabled, the Logix Designer application checks
that there is enough memory to generate the Sequence Parameter and
Step Tag value events. The checks occur when the sequence program is
verified, when a sequence program is imported and exported as a
component, and when the controller is online and the sequence program’s
Generate Events attribute is enabled.
If the amount of memory required is not available, the sequence does not
verify, generates an import error, and the import is not allowed or the
Generate Events attribute is not enabled, respectively.

See also

SequenceManager and related components overview on page 19

SequenceManager Event Use the SequenceManager Event Services Console dialog box to start, stop,
pause, resume, configure, and view the status of the SequenceManager Event
Services Console overview Client Service and the SequenceManager Event Archiving Service.

Once the services are started, they run until they are stopped. The cost in CPU
time for running the services is minimal because they are event-driven: the
SequenceManager Event Client Service is driven only by Equipment Sequence
events, and the SequenceManager Event Archiving Service is driven only by
end-of-sequence events.

See also

SequenceManager Event Handling applications on page 22

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 59


Chapter 6 SequenceManager event handling applications

SequenceManager Event Client Service settings on page 68

Configure settings for the SequenceManager Event Client Service on page


66

Configure settings for the SequenceManager Event Archiving Service on


page 62

SequenceManager Event Use the following options on the SequenceManager Event Services Console
dialog box to control the event services.
Services Console commands
SequenceManager Event Client Service

Name Purpose
Start Starts the SequenceManager Event Client Service.
Stop Stops the SequenceManager Event Client Service.
Pause Causes the SequenceManager Event Client Service to change from the Running to the Paused
state. The SequenceManager Event Client Service does not process raw event files when it
receives an event notification from the SequenceManager Event Archiving Service.
Resume Causes the SequenceManager Event Client Service to change from the Paused to the Running
state. When the SequenceManager Event Client Service is resumed, it causes the
SequenceManager Client Service to notify the SequenceManager Archiving Service that there
are event records to be processed.

Settings Opens the Service Settings dialog box where you configure the service settings.
Process Orphaned Sequences Opens the Process Orphaned Sequences dialog box to allow the specification of a last
modification time of the raw event files. Any raw event files not modified since the last
modification time are identified as orphaned incomplete raw event files, so the event client can
close these raw event files and pass them to the SequenceManager Archiving Service.

Service Status Identifies the status of the service. The following statuses can appear for each service:
The service is not installed – The SequenceManager Event Console is installed but it cannot
find an installation of the SequenceManager Event Client Service or the SequenceManager
Event Archiving Service.
The service is running – The service has been started and is running.
The service is starting – The service has been commanded to start and is beginning to run.
The service is stopping – The service has been commanded to stop and is in the process of
stopping.
The service is not running – The service is installed but has not been commanded to start.
The service is stopped – The service is stopped.
The service is paused – The service is paused.
The service pause is pending – The service is in the process of pausing.
The service continue is pending – The service resuming execution is pending.
Path to Executable The path where the service executable file is installed. The SequenceManager Event Client
Service executable file is SeqEventClientService.exe.

60 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


SequenceManager event handling applications Chapter 6

SequenceManager Event Archiving Service

Name Purpose
Start Starts the SequenceManager Event Archiving Service.
Stop Stops the SequenceManager Event Archiving Service.
Pause Causes the SequenceManager Event Archiving Service to change from the Running to the
Paused state. The SequenceManager Archiving Service does not process raw event files when it
receives an event notification from the SequenceManager Event Client Service.
Resume Causes the SequenceManager Event Archiving Service to change from the Paused to the
Running state. When the SequenceManager Event Archiving Service is resumed, it causes the
SequenceManager Client Service to notify the SequenceManager Archiving Service that there
are event records to be processed.
Settings Opens the Service Settings dialog box where you configure the service settings.
Service Status ldentifies the status of the service. The following statuses can appear for each service:
The service is not installed – The SequenceManager Event Console is installed but it cannot
find an installation of the SequenceManager Event Client Service or the SequenceManager
Event Archiving Service.
The service is running – The service has been started and is running.
The service is starting – The service has been commanded to start and is beginning to run.
The service is stopping – The service has been commanded to stop and is in the process of
stopping.
The service is not running – The service is installed but has not been commanded to start.
The service is stopped – The service is stopped.
The service is paused – The service is paused.
The service pause is pending – The service is in the process of pausing.
The service continue is pending – The service resuming execution is pending.
Path to Executable The path where the service executable file is installed. The SequenceManager Event Archiving
Service executable file is SeqEventArchivingService.exe.

See also

SequenceManager Event Services Console overview on page 59

Configure settings for the SequenceManager Event Client Service on page


66

Configure settings for the SequenceManager Event Archiving Service on


page 62

Configure Microsoft SQL Reporting within SequenceManager Events requires the setup of Reporting
Services.
Server for Reporting
Services for To configure the Microsoft SQL Server for Reporting Services for
SequenceManager Events:
SequenceManager Events
1. From the Windows Start menu, select All Programs > Microsoft SQL
Server 2012 (or 2008 R2) > Configuration Tools > Reporting Services
Configuration Manager.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 61


Chapter 6 SequenceManager event handling applications

2. At the prompt, select Connect. The Reporting Services Configuration


Manager opens.

3. Select Report Manager URL.

4. Select the URLs link to open the Home - Report Manager page in a web
browser. If the link is not active, select Apply to activate the link.

If this is the first time the Report Manager page is accessed, warning
messages may appear. To continue, select Close for any warning.

5. On the Home - Report Manager page, select Folder Settings.

6. On the Security page, select New Role Assignment.

7. On the New Role Assignment page:

a. In the Group or user name box, enter the domain\user name


that was used when installing SQL Server.

b. Select the Role check box to select all of the roles.

c. Select OK.

The new role is added to the list on the SQL Server Security page.

See also

Configure settings for the SequenceManager Event Archiving Service on


page 62

Configure settings for the When using the SequenceManager Event Services Console to start the event
handling services, configure the settings for the SequenceManager Event
SequenceManager Event Archiving service.
Archiving Service
Before you begin:

• Configure Microsoft SQL Server for Reporting Services for


SequenceManager Events.

To configure settings for the SequenceManager Event Archiving service:

1. Access the Product Compatibility and Download Center (PCDC) to


download the SequenceManager Event Install.exe.

2. Select the SequenceManager Event Install.exe file to install the


SequenceManager Event Services Console.

62 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


SequenceManager event handling applications Chapter 6

If reports will be run, prior to installing the SequenceManagerEvent


Components, install and configure SQL Server Reporting services.

3. From the Start menu navigate to Rockwell Software > SequenceManager


> Sequence Event Manager Components > Event Services Console,
right-click and select to Run as Administrator.

Important: If Run as administrator is not used, the settings will not be enabled and
will not be available to be configure.

4. In the SequenceManager Event Services Console dialog box, In the


SequenceManager Event Archiving Service area, if the Service Status is:
The Service is running, in the Process Event Client Service notifications
area, select Stop. The service must be stopped before you can configure the
settings.

5. Under SequenceManager Event Archiving Service, select Settings to


open the SequenceManager Event Archiving Service Settings dialog box.

6. For Output Event Directory, select Browse to navigate to the directory


where the archiving service can write the translated .EVT event data files. If
the directory is not valid, an error icon appears.

7. For Log File Directory, click Browse to choose the directory where the
archiving service writes log information about its execution. This log can be
used to track service operation. If the directory is invalid, an error icon
appears.

8. For Log Level, select the check boxes for the types of event messages that
the archiving service should log.

9. For Maximum Log File Size (Lines), enter the number of lines, starting at
1000 and up to 50000, that the log file can contain before a new log file is
started.

10. For Maximum Number of Logs (Files), enter the maximum number of log
files to keep. The oldest log file is deleted when client service reaches the
limit. The minimum value is 1, the maximum value is 1000, and the default
value is 100.

11. (Optional) Select Save Events in Database to configure the archiving


service to write the translated events into an .EVT file and into the
BatchHistoryEX database. When you select the check box, the settings
under Save Events in Database become active.

• (Optional) Delete Output Event Files after Archiving – Configures


the archiving service to delete the output event files after they are

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 63


Chapter 6 SequenceManager event handling applications

archived to a database. The number of output event files grows as


sequences execute and, if they are not deleted, they can consume a large
amount of disk space.
• Archived Output Event Directory – Select Browse to choose the
directory for archived Batch event files. When the Delete Output
Event Files after Archiving option is not selected, archived event files
are moved into this directory.
• Archiver Ini File – Select Browse to choose the directory that contains
the .ini file that describes how the archiving service should run. The .ini
file is used by the SequenceManager Event Archiving Service to keep
track of the number of records that have been successfully processed
and saved into the database. This number is needed for error recovery.
• Database Connection String – This connection string is used by the
archiving service to connect and log into the BatchHistoryEX database.
The Database Connection String can be created by selecting Browse to
open the Microsoft Data Source dialog box. From the Microsoft Data
Source dialog box:
• Create a new Machine Data Source.
• Select the SQL Server driver.
• Connect to the SQL database instance.
• Change the default database to BatchHistoryEx.
The installation package needs to configure the database connection,
create the database to store the events, and create the stored procedures
needed to process the events.
Select Browse to open the Select Data Source dialog box. Select an
existing data source or create a new data source. After you specify the
data source, the database connection string is automatically generated
for the connection.

• Table Name – Enter a name for the table where the archiving service
writes the sequence events in the BatchHistoryEX database. The
default table name is BHBatchHis.
• Maximum Records per Transaction – Enter the number of event
records, starting at 1 and up to 10000, that are written in a single
archive transaction.

See also

SequenceManager Event Archiving Service settings on page 65

SequenceManager Event Services Console overview on page 59

64 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


SequenceManager event handling applications Chapter 6

Configure settings for the Sequence Event Manager Client service on page
66

SequenceManager Event Use the following settings in the SequenceManager Event Archiving Service
Settings dialog box to configure the archiving service.
Archiving Service settings
Setting Description
Output Event Directory The directory where the archiving service can write the translated .EVT event data files. If
the directory is not valid, an error icon appears.
Log File Directory The directory where the service logs execution information that technical support can use
during troubleshooting, if necessary. If the directory is invalid, an error icon appears.
Log Level The types of event messages that the archiving service should log. Event types include
Error, Warning, Information, and Debug.
Maximum Log File Size (Lines) The maximum number of lines that each log file can contain. When the log file hits this
limit, the archiving service starts a new log file. The minimum value is 1000, the maximum
value is 50000, and the default value is 10000.
Maximum Number of Logs (Files) The maximum number of log files to keep before the service begins deleting log files as
new files are created. Enter a value starting at 1 and up to 1000. The default value is 100.
Save Events in Database Configures the archiving service to write the translated events into an .EVT file and into the
BatchHistoryEX database. If selected, the settings under Save Events in Database
become active.
Delete Output Event Files after Archiving Configures the archiving service to delete the output event files after they are archived to a
database.
Archived Output Event Directory The directory that contains the archived Batch event files.
Archiver .ini File The .ini file is used by the SequenceManager Event Archiving Service to keep track of the
number of records that have been successfully processed and saved into the database. This
number is needed for error recovery.
Database Connection String This connection string is used by the archiving service to connect and log into the
BatchHistoryEX database. The installation package needs to configure the database
connection, create the database to store the events, and create the stored procedures
needed to process the events.
Table Name A name for the table where the archiving service writes the sequence events in the
PlantPAx Historian database. The default table name is BHBatchHis.
Maximum Records per Transaction The number of event records, from1 to 10000, that are written in a single archive
transaction.

See also

Configure settings for the SequenceManager Event Archiving Service on


page 62

SequenceManager Event Services Console overview on page 59

Configure settings for the SequenceManager Event Client Service on page


66

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 65


Chapter 6 SequenceManager event handling applications

Configure settings for the Configure the settings for the SequenceManager Event Client Service before
starting the event handing services.
SequenceManager Event
Client Service To configure settings for the SequenceManager Event Client Service:

1. Access the Product Compatibility and Download Center (PCDC) to


download the SequenceManager Event Install.exe.

2. Select the SequenceManager Event Install.exe file to install the


SequenceManager Event Services Console.

3. From the Start menu navigate to Rockwell Software > SequenceManager


> Sequence Event Manager Components > Event Services Console,
right-click and select to Run as Administrator.

Important: If Run as administrator is not used, the settings will not be enabled and
will not be available to be configure.

4. In the SequenceManager Event Services Console dialog box, In the


SequenceManager Event Archiving Service area, if the Service Status is:
The Service is running, in the Process Event Client Service notifications
area, select Stop. The service must be stopped before you can configure the
settings.

5. In the SequenceManager Event Client Service area, select Settings to


open the SequenceManager Event Client Service Settings dialog box.

6. For Sequence Raw Event Directory, select Browse to choose the directory
to which the service will write raw event data files. If the directory is not
valid, an error icon appears.

7. For Log File Directory, select Browse to choose the directory to which the
service will write log files. If the directory is not valid, an error icon appears.

8. For Log Level, select the check boxes for the types of event messages that
the client service should log.

9. For Maximum Log File Size (Lines), enter the number of lines, starting at
1000 and up to 50000, that the log file can contain before a new log file is
started.

10. For Maximum Log File Size (Files), enter the number of files to be kept,
starting at 1 and up to 1000. When this number of files is reached, the
oldest log file is deleted.

11. (optional) In the Controller Connection Configuration area, select Add


to open the Browse for Controller dialog box.

66 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


SequenceManager event handling applications Chapter 6

a. Select a controller on the network tree and select OK. Repeat this step
for each controller that the client service connects to. The maximum
number of controllers that can be configured is one, three, or ten
controllers.

The controllers are added to the controllers list in the Controller


Connection Configuration area.

12. Check the controller connection status. The status can be:

Good - The controller is connected and in a good state for subscribing and
receiving events.
Bad - The controller is connected, but not in a state for subscribing and
receiving events. For instance, the controller is in Program mode, a project is
being downloaded, or there is a major fault.
Lost - The connection failed. The cause of the lost connection must be
determined and resolved.
Unknown - The connection status cannot be determined. This status is
shown only at design time and it can take up to 30 seconds to determine a
connection status.
If the controller connection fails, attempt to reestablish connection by
adjusting the values in the Timeout (Milliseconds) and Number of
Retries boxes.
Timeout - The time limit that data does not pass between the controller
and the Event Client Service before marking the connection as Lost.
Increase this value to attempt to reestablish connection.
Number of Retries - The number of times the Timeout value can expire
before the connection is determined to be lost and the status changes to
Lost. Increase this value to attempt to reestablish connection.

13. (optional) To delete a controller, select one or more controllers in the list
and select Delete.

14. (optional) To test the connection on a controller, select one or more


controllers in the list and select Test.

See also

SequenceManager Event Client Service settings on page 68

SequenceManager Event Services Console Overview on page

59 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 67


Chapter 6 SequenceManager event handling applications

Configure settings for the SequenceManager Event Archiving Service on


page 62

SequenceManager Event Use the following settings in the SequenceManager Event Client Service
Settings dialog box to configure the client service.
Client Service settings
Setting Description
Sequence Raw Event Directory The directory to which the service writes raw event data files, which have a .raw extension.
If the directory is not valid, an error icon appears. The SequenceManager Event Archiving
Service converts the raw events data into readable form, writes the data to an .EVT file,
and populates tables in a database for PlantPAx reporting.
Log File Directory The directory where the service logs execution information that technical support can use
during troubleshooting, if necessary. If the directory is invalid, an error icon appears.
Log Level The types of event messages that the client service should log. Event types include Error,
Warning, Information, and Debug.

Maximum Log File Size (Lines) The maximum number of lines that each log file can contain. When the log file hits this
limit, the client service starts a new log file. The minimum value is 1000, the maximum
value is 50000, and the default value is 10000.
Maximum Number of Logs (Files) The maximum number of log files to keep before the service begins deleting log files as
new files are created. Enter a value starting at 1 and up to 1000. The default value is 100.

Controllers Client service subscribes to controllers. The number of controllers the client service can
subscribed to is dependent on the license. The license can be for either one controller,
three controllers, or 10 controllers. The client service receives events from the controllers
and caches them in raw event data files.
Timeout (Milliseconds) The time that the service attempts to contact a controller before marking the connection as
Lost. The suggested timeout value is 8000 to 16000 milliseconds. The minimum value is
500, and the maximum value is 30000.
Number of Retries The number of attempts the service makes to contact a controller before marking the
connection as Lost. The suggested value is 4, which is also the minimum value. The
maximum value is 512.

Add Add controllers that the client service subscribes to, depending on the license: one
controller, three controllers, or 10 controllers.
Delete Delete currently selected controllers. A minimum of 1 controller must be selected or this
button is not an available option.
Test Test the connection between the SequenceManager Event Client Service and the selected
controllers. At least one controller must be selected.

See also

SequenceManager Event Services Console overview on page 59

Configure settings for the SequenceManager Event Client Service on page


66

Configure settings for the SequenceManager Event Archiving Service on


page 62

68 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Chapter 7

The SequenceManager Controls

The SequenceManager sequences a series of Equipment Phases to the Control


Logix platform. The operator views and interacts with the Equipment Sequences
downloaded to a Logix controller through three types of controls:

• Sequence Detail Control


• Sequence Summary Control
• Sequence Parameters Control

Sequence Detail Control

The Sequence Detail Control provides the operator with a detailed view of an
Equipment Sequence, including its chart structure, steps, and transitions. The
runtime status of the sequence program and its sequence elements are also shown.
The operator can command the Equipment Sequence from this control.

Sequence Summary Control

The Sequence Summary Control displays the sequence program status for each
of the Equipment Sequences downloaded to the controller. The Sequence
Summary Control also allows the operator to view and command a selected
Equipment Sequence.

Sequence Parameters Control

The Sequence Parameters Control displays a table of all sequence parameters


and step tags of a specified Equipment Sequence, and allows the operator to
command a selected sequence parameter or step tag. To refine the display,
configure the table to filter the information displayed.

See also

Sequence Detail Control on page 73

Sequence Summary Control on page 71

Sequence Parameters Control on page 81

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 69


Chapter 8

Sequence Summary Control

Use the Sequence Summary Control to see status information for the Equipment
Sequences downloaded to a controller. Select a sequence in the list and command
it.

See also

Sequence Summary command controls on page 71

Configure the Sequence Control to communicate with a controller on page


71

Configure the Sequence To configure the Sequence Summary Control to communicate with a controller
or to use VBA, customize several settings in the control Property Panel. There is
Summary Control also the option to customize display options.

Before you begin:

• Open the FactoryTalk View Site Edition (SE) application.


• Open a display. If the display already has the Sequence Summary Control
added, configure or reconfigure the Sequence Summary Control. If the
display does not have the Sequence Summary Control added, add the
Sequence Summary Control to the display and then configure it.

Sequence Summary Use the following commands to control an Equipment Sequence using the
command controls Sequence Summary Control. The availability of some commands depends on the
selected Equipment Sequence owner, state, mode, and failure status. Click More
to display all the commands on the toolbar.

Icon Command Description


Take Ownership Take ownership of the Equipment Sequence. Taking ownership means that this application now
has the right to command this Equipment Sequence; other internal sequencers, external
sequencers, and operators are not allowed to command this sequence. The Logix Designer
application can override ownership.
Release Ownership Release ownership of the Equipment Sequence. Releasing ownership makes the sequence
available to internal sequencers, external sequencers, and operators for attachment.
Set ID Opens the Set Sequence ID dialog box where you can assign an identifier to the Equipment
Sequence. This command is enabled only when an Equipment Sequence is idle.
Start Start execution of the Equipment Sequence.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 71


Chapter 8 Sequence Summary Control

Hold Halt all attached phases for the Equipment Sequence and stop evaluating transitions until the
Equipment Phase runs its HOLDING routine.
Restart Continue execution of the Equipment Sequence from the HELD state.
Stop Stop all attached phases and active transitions for the Equipment Sequence. Any attached
Equipment Phases run their STOPPING routines.
Abort Abort all attached phases and active transitions for the Equipment Sequence. Any attached
Equipment Phases run their ABORTING routines.
Reset Reset any remaining active phases for the Equipment Sequence.
Clear Failures Clear the failure flags on the Equipment Sequence.
Pause Pause execution of the Equipment Sequence. When the active transition evaluates TRUE, it does
not transition to the FIRING state until you click Resume. The Resume command resets the
Pause flag so the sequence will continue execution uninterrupted.
Auto-Pause Automatically pause the Equipment Sequence as transitions evaluate TRUE. The Resume
command resets the Pause flag. The Auto-Pause flag immediately causes the Pause flag to be
turned on again, so the sequence pauses when the next transition expression evaluates TRUE.
Resume Continue execution of the Equipment Sequence.
Automatic Put the Equipment Sequence in Automatic mode, which allows the sequencing engine to
automatically fire transitions and execute the Equipment Sequence.
Manual Put the Equipment Sequence in Manual mode, in which the sequencing engine does not
automatically fire transitions, and an operator commands the Equipment Sequence step by step.
On the toolbar, only the Release Ownership, Pause, Auto-Pause, and Automatic commands
are enabled.

See also

Sequence Summary Control on page 71

72 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Chapter 9

Sequence Detail Control

Use the Sequence Detail Control to see a detailed view of an Equipment Sequence,
including its chart structure, steps, and transitions. You can also view the runtime
status of the Equipment Sequence and the sequence elements.

See also

Sequence Detail Control status header area on page 75

Sequence Detail Control command controls on page 73

A monitored transition in the Sequence Detail Control on page 78

A monitored step in the Sequence Detail Control on page 77

Configure the Sequence To configure the Sequence Detail Control to communicate with a controller,
customize several settings in the control Property Panel.
Detail Control
Before you begin:

• Open the FactoryTalk View SE application.


• Open a display. If the display already has the Sequence Detail Control
added, configure or reconfigure the Sequence Detail Control. If the display
does not have the Sequence Detail Control added, add the Sequence
Detail Control to the display and then configure it.

See also

Sequence Detail Control on page 73

Sequence Detail Control Use the following commands to control an Equipment Sequence using the
Sequence Detail Control. The availability of some commands depends on the
command controls selected Equipment Sequence owner, state, mode, and failure status. Click More
to display all the commands on the toolbar.

The following commands are always displayed:

• Take/Release ownership
• Set ID

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 73


Chapter 9 Sequence Detail Control

• Initialize parameters
• Start
• Hold
• Restart
• Stop
• Abort
• Reset
• More/Less

These commands are available after selecting the More button and can be hidden
by selecting the Less button:

• Clear Failures
• Pause/Cancel Pause
• Auto Pause/Cancel Auto Pause
• Resume
• Enter/Exit Manual
• Step change
• Force transition
Icon Command Description
Take Ownership Take ownership of the Equipment Sequence. Taking ownership means that this application now
has the right to command this Equipment Sequence; other internal sequencers, external
sequencers, and operators are not allowed to command this sequence.
Release Ownership Release ownership of the Equipment Sequence. Releasing ownership means that internal
sequencers, external sequencers, and operators with attachments are allowed to command this
sequence.
Set ID Opens the Set Sequence ID dialog box where you can assign an identifier of up to 82 characters to
the Equipment Sequence. This command is enabled only when an Equipment Sequence is idle.
Start Start execution of the Equipment Sequence.
Hold Halt all connected phases for the Equipment Sequence and stop evaluating transitions until the
Equipment Phase runs its Hold routine.
Restart Continue execution of the Equipment Sequence from the HELD state.
Stop Stop all connected phases and active transitions for the Equipment Sequence.
Abort Abort all connected phases and active transitions for the Equipment Sequence.
Reset Reset any remaining active phases for the Equipment Sequence.
Clear Failures Clear the failure flags on the Equipment Sequence.
Pause Pause execution of the Equipment Sequence. When the active transition evaluates TRUE, it does
not transition to the FIRING state until you click Resume.

74 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Detail Control Chapter 9

Auto-Pause Automatically pause the Equipment Sequence as transitions evaluate TRUE. When you click
Resume, the next transitions fire, but the Equipment Sequence pauses again after each transition
evaluates TRUE.
Resume Continue execution of the Equipment Sequence.
Enter Manual Put the Equipment Sequence in Manual mode, in which the sequencing engine does not
automatically fire transitions, and an operator commands the Equipment Sequence step by step.
On the toolbar, only the Release Ownership, Pause, Auto-Pause, and Automatic commands
are enabled.
Exit Manual Put the Equipment Sequence in Automatic mode, which allows the sequencing engine to
automatically fire transitions and execute the Equipment Sequence.

See also

Sequence Detail Control on page 73

Sequence Detail Control The header area of the Sequence Detail Control shows live data values for the
currently loaded Equipment Sequence.
status header area

Item Name Description


Owners This box shows the current owner of the displayed Equipment Sequence and visual
indication of ownership overrides.
• Blank: No ownership.
• Logix Designer (<number>): The <number> indicates the number of Logix
Designer applications that have overridden ownership of the sequence.
• Operator: A user through the SequenceManager Detail of the SequenceManager
Summary ActiveX controls has attached to the sequence.
• Internal Sequencer: A program running within the controller has used the Attach
to Equipment Sequence (SATT) command to attach to the sequence.
• External Sequencer: An application outside the controller, the FactoryTalk Batch
Server, has attached to the sequence.

Unit ID Indicates the integer value currently assigned to the sequence. Configured on the
Sequence Properties Dialog Box, Configuration tab, that represents the
equipment unit the sequence is coordinating.
Sequence ID A string entered by the operator or control engineer using the Set ID button to specify
an identifier for this execution of the equipment sequence. Once the sequence is
executing (not in an IDLE state), the Sequence ID cannot be changed.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 75


Chapter 9 Sequence Detail Control

State Shows the current state of the displayed Equipment Sequence. States are:
• IDLE
• RESTARTING
• RUNNING
• RESETTING
• HOLDING
• STOPPING
• ABORTING
• HELD
• STOPPED
• ABORTED
• COMPLETE
Substate Displays the state of the bits in Pause Control. The following states are:
• Paused
• Pause Enabled
• Auto Pause Enabled
• Paused, Auto Pause Enabled

Mode Shows the current execution mode of the displayed Equipment Sequence, either
Automatic or Manual.

Sequence Detail Control The footer section on the Sequence Detail Control contains the following settings
and status indicators.
status footer area
The communication, failure, and unscheduled/inhibited icons are also displayed
in the upper left corner of the diagram window, in the status bar, and on any step
or tag the status is detected.

Setting or status Description


Zoom control Adjusts the zoom on the control window.
Auto-Scroll Turn Auto-Scroll on or off.
Sequence name The name of the Equipment Sequence.

76 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Detail Control Chapter 9

Status bar Displays the following status icons:

– There is a communication problem with the controller, the SequenceManager Server Service
application, the live data server, or the tags.

– No known communication problem.

– There is a failure in the Equipment Sequence.

– No known failure in the Equipment Sequence.

– The controller is in Program, Remote Program, or an unknown mode.


– The controller is in Run, Remote Run, or an unknown mode.

– The Equipment Sequence or task is inhibited, or the Equipment Sequence is unscheduled.

– The Equipment Sequence is scanning, or the status is unknown.

See also

Sequence Detail Control on page 73

A monitored step in the A monitored equipment sequence step shows several functions:

Sequence Detail Control • The user-configured step name and the Equipment Phase name.
• The step execution state.
• If the step is a source or target for a transfer of control.
• If the step has a failure.
• The step is executing.
• If the step or associated phase is paused.

Item Description
Failure Phase failure - generated by the Equipment Phase Failure (PFL)
instruction in the Equipment Phase logic.
Internal failure - the sequencing engine has encountered a problem
with the Equipment Sequence.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 77


Chapter 9 Sequence Detail Control

Step Name The name of the step as configured during creation of the Equipment
Sequence.
Pause status The symbol shows that:
• A pause of the phase logic is pending.
• An auto-pause of the phase logic is pending.
• The associated Equipment Phase is paused.
• The associated Equipment Phase is paused and auto-pause is
pending.
Equipment Phase Name Each step is configured to reference one phase. The name of the phase
is displayed so you know which equipment phase is executing.
Transfer of Control (TOC) A step that has been configured as the source to transfer ownership to
a following target step, without stopping the execution of the phase.
The symbol shows:
• When the top bar is filled, this step is the beginning of a TOC step
pair.
• When the bottom bar is filled, this step is the end of a TOC step pair.
• When both top and bottom bars are filled, this step is the end of a
TOC step pair and the beginning of another TOC step pair.
When transfer of control is not configured, the symbols are not drawn.
Step State When a step is active, and attached to its phase, the step state mirrors
the state of the phase. The set of displayed states are: INACTIVE, NOT
CONNECTED (active but not attached), IDLE, RESTARTING, RUNNING,
RESETTING, HOLDING, STOPPING, ABORTING, HELD, STOPPED,
ABORTED, and COMPLETE.
Tip: <No phase> steps have no associated phase and only
have two displayed states: RUNNING and IDLE.
The step state is also represented by the color of the step.

A monitored transition in A transition has several displayed attributes and status. The transition name and
expression are defined when the sequence is configured and static when the
the Sequence Detail Control sequence is online. The display state and firing attribute are dynamic and update
as the transition executes.

Item Description
Transition Name The name of the transition is assigned by the Equipment Sequence Editor. It
is an incremented value beginning with Tran_000.

78 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Sequence Detail Control Chapter 9

Transition Display State The transition display state is indicated by the color of the transition.
For more information about transition display states, see below for
Transition display states.

Transition Expression Transition expressions define the criteria to STOP, RESET, and detach all
preceding steps and their associated Equipment Phases and attach and START
the following Equipment Phases and steps. The expression must always
evaluate to either TRUE or FALSE.
Transition Firing Attribute The Transition Firing Attribute is only displayed when the transition is in the
FIRING state, which means the expression has evaluated TRUE. The firing
attribute is a subset of the FIRING state and gives a visual indication of the
current state.

See also

Transition display states on page 47

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 79


Chapter 10

Sequence Parameters Control

Use the Sequence Parameters Control to see a list of the step tags and sequence
parameters in an Equipment Sequence. Select tags and parameters in the list to
modify them or view more information about them.

See also

Modify step tags or sequence parameters using the Sequence Parameters


Control on page 81

Configure the Sequence To configure the Sequence Parameters Control, customize several settings in the
control Property Panel.
Parameters Control
You can configure the Sequence Parameters Control to communicate with a
controller, to use VBA scripting, or (to) change display options.

Before you begin:

• Open the FactoryTalk View Site Edition (SE) application.


• Open a display. If the display already has the Sequence Parameters
Control added, configure or reconfigure the Sequence Parameters
Control. If the display does not have the Sequence Parameters Control
added, add the Sequence Parameters Control to the display and then
configure it.

See also

Sequence Parameters Control on page 81

Modify step tags or Select a step tag or sequencing parameter from the list on the Sequence Parameters
Control to modify, disable or enable, force evaluation of, or view more
sequencing parameters information about the step tag or sequencing parameter.
using the Sequence
Tip: To modify settings for tags and parameters, the external value for the tags and parameters must be set to
Parameters Control Read/Write. Use the Tag Editor in the Logix Designer application to change the external value for a tag or
parameter.

To modify a tag or parameter:

1. Select the tag or parameter.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 81


Chapter 10 Sequence Parameters Control

2. In the Value box, type the new value for the tag or parameter.

3. To disable or enable a tag or parameter, click Expression and then click


Disable Expression or Enable Expression. When you disable a tag or
parameter, the disabled icon appears in the Expression box. To re-
enable a disabled tag or parameter, click Expression and then click Enable
Expression. When you re-enable a disabled expression, the disabled icon
disappears from the Expression box.

4. To force evaluation of a tag or parameter, click Expression and then click


Force Evaluation. The Force Evaluation button is disabled when any of
the following is true:

• The Equipment Sequence is in the IDLE state.


• The controller is in Program mode.
• The Equipment Sequence or its assigned task is disabled.
• The Equipment Sequence is unscheduled.

To view more information for a tag or parameter:

1. Select the tag or parameter.

2. Click View Expression to display the complete expression. Click View


Description to display the complete description.

See also

Sequence Parameters Control on page 81

82 Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Index

C
commands 54, 56, 76, 80

D
diagrams 27, 28, 35

E
equipment sequence 21, 26, 27, 28, 35, 43, 44, 45, 57
events 61, 62, 65, 68, 69, 71
example 35

M
mode 56

O
overview 21, 25, 49, 50, 81, 83
ownership 54

Q
quality of data 51

S
Sequence Detail Control 73, 79, 80, 81, 83, 84, 85
Sequence Parameter Control 73, 87, 88
Sequence Summary Control 73, 75, 76
sequencing parameter 52, 53
step 44, 45, 48, 52, 84
step tag 52

T
transition 49, 50, 85

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016 83


Rockwell Automation support
Rockwell Automation provides technical information on the web to assist you in using its products. At
http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You
can also visit our Support Center at https://rockwellautomation.custhelp.com for software updates, support chats and forums, technical
information, FAQs, and to sign up for product notification updates.

In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local
distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone.

Installation assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact
Customer Support for initial help in getting your product up and running.

United States or Canada 1.440.646.3434


Outside United States or Canada Use the Worldwide Locator available at http://www.rockwellautomation.com/locations, or contact your local Rockwell
Automation representative.

New product satisfaction return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if
your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to
your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Documentation feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
feedback form, publication RA-DU002.

Rockwell Automation Publication 1756-QS109C-EN-P - June 2016


Supersedes Publication 1756-QS109B-EN-P - March 2016 Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like