Inael: Laboratorio de Alta Tensión High Voltage Laboratory
Inael: Laboratorio de Alta Tensión High Voltage Laboratory
INAEL
Laboratorio de Alta Tensión
High Voltage Laboratory
Result
The measured values and the general behaviour of the Objects under Test were realized
according to the conditions defined in the normative references and their characteristics
are accepted by the client and supplier.
Contents Page
Test realized 5
Normative references 5
Test Procedure 5
Rated Voltage 36 kV
Frequency 50/60 Hz
To earth 70 kV
Power Frequency withstand voltage, 1 min
Sectionalizer
80 kV
distance
To earth 170 kV
Lightning impulse withstand voltage 1,2/50 µs Sectionalizer
195 kV
distance
Insulators Material Ceramic
Test realized
Temperature-rise test 1
Normative references
• IEC 60282-2
Test Procedure.
• The Object under Test equipped with upper and lower standard contacts was
mounted on a mechanical structure fixed by its middle support and connected to
the Current Generator through 1m long 150 mm2 copper conductors .
• A constant 100 Arms power frequency current flew through the Object under
Test mounted with a 100A link fuse. The temperature was measured with
thermocouples K connected to the different parts of the circuit. After some hours
of temperature stabilization, the temperature was measured over the last 3 hours,
taking into account that the temperature difference was lower than 1 º K / hour.
• A constant 200 Arms power frequency current flew through the Object under
Test mounted with a 200A sectionalizer blade. Following the same procedure as
the previous one with the fuse link, the temperature was measured with
thermocouples K connected to the different parts of the circuit. After some hours
of temperature stabilization, the temperature was measured over the last 3 hours,
taking into account that the temperature difference was lower than 1 º K / hour.
Qualification Criteria
• The ambient air temperature during the tests shall be between 10ºC and 40ºC.
• During the last quarter of the test period, the change of ambient air temperature
shall not exceed 1ºK in 1h.
• The temperature rise measured after temperature stabilization shall not exceed
the limits specified in table 17 of standard IEC 60282-2
Final Conclusion
All the Qualification Criteria were fulfilled, therefore the sample with fuse link and
sectionalizer blade is deemed to pass the test.
TEMPERATURE-RISE TEST
TEST REPORT
THERMOCOUPLE
MEASURING POINT
NR.
1 Upper current generator connection
2 Upper contact
3 Upper Junction Fuse holder
4 Fuse holder
5 Lower Junction Fuse holder
6 Lower contact
7 Lower current generator connection
TEMPERATURE-RISE TEST
TEST REPORT
THERMOCOUPLE
MEASURING POINT
NR.
1 Upper current generator connection
2 Upper contact
3 Upper Junction Fuse holder
4 Fuse holder
5 Lower Junction Fuse holder
6 Lower contact
7 Lower current generator connection
Tr = Step-down Transformer
A = Amperemeter
O1 = Object under Test