Inael: Laboratorio de Alta Tensión High Voltage Laboratory

The test report summarizes the results of a temperature-rise test on a 36kV ceramic cut-out. The test was conducted according to IEC 60282-2 and measured the temperature rise of the cut-out under test when a 100A fuse link and 200A sectionalizer blade were installed and carrying constant currents of 100A and 200A respectively. All qualification criteria were met, with maximum temperature rises of 22.4°C for the fuse link and 37.3°C for the sectionalizer blade, below the limits specified in the standard. Therefore, the cut-out passed the temperature-rise test.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views11 pages

Inael: Laboratorio de Alta Tensión High Voltage Laboratory

The test report summarizes the results of a temperature-rise test on a 36kV ceramic cut-out. The test was conducted according to IEC 60282-2 and measured the temperature rise of the cut-out under test when a 100A fuse link and 200A sectionalizer blade were installed and carrying constant currents of 100A and 200A respectively. All qualification criteria were met, with maximum temperature rises of 22.4°C for the fuse link and 37.3°C for the sectionalizer blade, below the limits specified in the standard. Therefore, the cut-out passed the temperature-rise test.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

INAEL – High Voltage Laboratory INLAT 003-08

INAEL
Laboratorio de Alta Tensión
High Voltage Laboratory

INALAT omnia disce, videbis postea nihil esse superfluum


Jarama 5 – 45007 Toledo – Spain ● +34 925 233511 ●[email protected] page 1 of 11
TEST REPORT INLAT 003-08

Client CHANGSHA RICH

Object under test 36kV Ceramic Cut-out

Test description Temperature-rise test

Test certified by Mr. Silvestre Cerda


IEC 60282-2
Normative references

Test date from Feb 18, 2008 to Feb 20, 2008

Pages Protocol 8 Annexes 3

Test Report date Feb 22, 2008

Result

The measured values and the general behaviour of the Objects under Test were realized
according to the conditions defined in the normative references and their characteristics
are accepted by the client and supplier.

Test Values voltage : ±5% ; current : ±5% ; time: ±5%


Uncertainties Description Max values 2 levels.
Mr.Rafael De La Fuente
Test team
Laboratory Mr. Rubén Maestro
Test station LAT-01

Revised and Accepted Mr. Silvestre Cerda


HV Lab Manager

36 kV Ceramic Cut-out Page 2 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

Contents Page

General Characteristic of the Object under Test 4

Test realized 5

Normative references 5

Identification of the Object under Test 5

Test Procedure 5

Test criteria and evaluation results 7

Test result table with Fuse-link 8

Test result table with Sectionalizer blade 9

Annex 1 : Cut-out during the test 10

Annex 2 : Temperature-rise Test Circuit 11

36 kV Ceramic Cut-out Page 3 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

General Characteristic of the Object Under Test

Description CERAMIC CUT-OUT

Supplier CHANGSHA RICH

Rated Voltage 36 kV

Rated Current 200 A

Frequency 50/60 Hz

To earth 70 kV
Power Frequency withstand voltage, 1 min
Sectionalizer
80 kV
distance
To earth 170 kV
Lightning impulse withstand voltage 1,2/50 µs Sectionalizer
195 kV
distance
Insulators Material Ceramic

36 kV Ceramic Cut-out Page 4 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

Test realized

Test description Samples tested

Temperature-rise test 1

Normative references

• IEC 60282-2

Identification of the Object under Test

Description Object under test Test sample identification

36 kV CERAMIC CUT-OUT No Identification

Test Procedure.

• The Object under Test equipped with upper and lower standard contacts was
mounted on a mechanical structure fixed by its middle support and connected to
the Current Generator through 1m long 150 mm2 copper conductors .
• A constant 100 Arms power frequency current flew through the Object under
Test mounted with a 100A link fuse. The temperature was measured with
thermocouples K connected to the different parts of the circuit. After some hours
of temperature stabilization, the temperature was measured over the last 3 hours,
taking into account that the temperature difference was lower than 1 º K / hour.
• A constant 200 Arms power frequency current flew through the Object under
Test mounted with a 200A sectionalizer blade. Following the same procedure as
the previous one with the fuse link, the temperature was measured with
thermocouples K connected to the different parts of the circuit. After some hours
of temperature stabilization, the temperature was measured over the last 3 hours,
taking into account that the temperature difference was lower than 1 º K / hour.

36 kV Ceramic Cut-out Page 5 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

36 kV Ceramic Cut-out Page 6 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

Test Results and Evaluation Criteria.

Qualification Criteria

• The ambient air temperature during the tests shall be between 10ºC and 40ºC.
• During the last quarter of the test period, the change of ambient air temperature
shall not exceed 1ºK in 1h.
• The temperature rise measured after temperature stabilization shall not exceed
the limits specified in table 17 of standard IEC 60282-2

Final Conclusion

All the Qualification Criteria were fulfilled, therefore the sample with fuse link and
sectionalizer blade is deemed to pass the test.

36 kV Ceramic Cut-out Page 7 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

TEMPERATURE-RISE TEST

TEST REPORT

Object under Test : CUT-OUT 36KV WITH 100A FUSE-LINK


Supplier : CHANGSHA RICH

THERMOCOUPLE
MEASURING POINT
NR.
1 Upper current generator connection
2 Upper contact
3 Upper Junction Fuse holder
4 Fuse holder
5 Lower Junction Fuse holder
6 Lower contact
7 Lower current generator connection

TERMOCOUPLE TEMPERATURE (ºC) TEMPERATURE-RISE


NR. 16h 17h 18h (ºK)

1 21.5 20.5 19.9 4


2 24.8 23.6 23.1 7.2
3 33.7 31.5 30.8 14.9
4 41.7 38.1 38.3 22.4
5 28.1 26.4 26.2 10.3
6 23.1 21.9 21.6 5.7
7 17.9 17.8 17.6 1.7
Ambient Temperature 15.4 16.1 15.9

36 kV Ceramic Cut-out Page 8 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

TEMPERATURE-RISE TEST

TEST REPORT

CUT-OUT 36KV WITH 200A SECTIONALIZER


Object under Test :
BLADE
Supplier : CHANGSHA RICH

THERMOCOUPLE
MEASURING POINT
NR.
1 Upper current generator connection
2 Upper contact
3 Upper Junction Fuse holder
4 Fuse holder
5 Lower Junction Fuse holder
6 Lower contact
7 Lower current generator connection

TERMOCOUPLE TEMPERATURE (ºC) TEMPERATURE-RISE


NR. 16h 17h 18h (ºK)

1 31.9 31.4 31.1 12.8


2 38.8 38.2 37.8 19.5
3 48.5 47.6 46.8 28.5
4 56.7 55.8 55.6 37.3
5 47.1 45.9 45.5 27.2
6 40.7 39.9 39.7 21.4
7 31.3 31.1 31.0 12.7
Ambient Temperature 17.8 18.4 18.3

36 kV Ceramic Cut-out Page 9 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

Annex 1 : Cut-out during the test with K 100A fuse-link

36 kV Ceramic Cut-out Page 10 of 11


– Temperature-Rise Test
TEST REPORT INLAT 003-08

Annex 2 : Power Frequency Current Test Circuit

Tr = Step-down Transformer
A = Amperemeter
O1 = Object under Test

36 kV Ceramic Cut-out Page 11 of 11


– Temperature-Rise Test