ACB Manual
ACB Manual
ACB Manual
About us
Larsen & Toubro is a technology-driven company that infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering, Construction, Electrical & Automation, Machinery and Information Technology. L&T Switchgear, which forms part of the Electrical & Automation business, is India's largest manufacturer of low voltage switchgear, with the scale, sophistication and range to meet global benchmarks. With over five decades of experience in this field, the Company today enjoys a leadership position in the Indian market with growing presence in international markets. It offers a complete range of products including controlgear, powergear, motor starters, energy meters, wires and host of other accessories. Most of our product lines conform to international standards, carry markings and are certified.
L&Ts Air Circuit Breakers (ACBs) are specially designed for extreme tropical conditions and have a proven track record more than 30 years. Presently more than 3,00,000 Air Circuit Breakers supplied by L&T are being used for diverse applications. The Air Circuit Breakers provide technologically driven solutions to meet customer needs. Complete selectivity Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures complete selectivity for system with time based discrimination. Perfect for Indian conditions Inherent design to perform in extreme tropical conditions. Typical site conditions like high ambient temperature, humidity and dusty environment are best handled by ACBs without compromising on performance and safety. Optimal compactness Designed to ensure l inherent temperature rise Low l Adequate interface clearances Widest choice of over current protection releases l Advance micro-controller based with option of communication & metering-SR71 l processor based releases-SR21i/SR18/SR18G Micro l Thermo-magnetic release-DN1 Elegant design & rugged construction l Common door cutout for entire range l aligned cutout for all ratings Left l Uniform height and depth for ACBs up to 4000 Amp Range to meet every customers need Various options to choose from l Breaking capacity from 35kA to 100kA l 3 Pole or 4 Pole configuration l or Drawout version Fixed l or Manual reset mechanism Auto l Independent manual or stored energy type manual or electrically operated mechanism l Different terminal orientations : Flat, Horizontal and Vertical
User friendly features Front accessible over current release settings, telescopic racking handle and various racking interlocks; no need to open the panel door l Unique Maintenance position in drawout type ACBs to facilitate maintenance & inspection without removing ACB from the panel l Multitap CTs for enhancing protection range for example: 3200A. ACB can be set to have a thermal protection from 800A l variety of Amperemetric and Voltmetric releases Wide l rated neutral pole for the entire range Fully l Lockable sliding shutters to prevent unauthorized access to TRIP and CLOSE push buttons l be used as an ON / OFF Load Isolator Can l Extendable Electrical Life: - By replacing the arcing contacts at site, for all ratings - Without changing pole assembly l Programmable SICs: Auxiliary contacts in drawout ACBs are programmable for only Service, Only Test, Test and Service, and All Positions l Unique gasket for IP54 protection l Protection releases are easily interchangeable at site l Facility for site conversion of manually operated ACBs to electrically operated ACBs
l
Safety marked for C, S & H ranges l Superior quality engineering grade plastics used for insulation purpose; conforms to Glow wire test (Ref: IEC 60695-2-1) l In-built mechanical anti-pumping for electrically operated ACBs prevent auto reclosing of ACB on fault l In-built rating error preventor in drawout ACBs ensure correct rating of drawout porton in corresponding cradle l Safety shutters prevent accidental contact with live cradle terminals l Variety of Safety Interlocks (Refer to page no. 14) l Easily removable arc chutes without use of any tool l Operating voltage ranges from 10% Un to 110% Un for shunt release ensures intentional tripping even at high voltage drops during short circuit
l
Conformance to standards IEC - 60947 (Part 1 & 2) IS/IEC - 60947 (Part 1 & 2) l 60695 - 2 - 1 IEC l BS EN 60947 - 2
l l
Product Certification
Rating (A) Type Designation Rated current (A) at 50C Rated operational voltage (V), 50/60Hz Rated insulation voltage (V), 50/60Hz No. of poles Rated ultimate short circuit breaking capacity 50/60Hz (kA rms) Rated service short circuit breaking capacity 50/60Hz (kA rms) Rated short time withstand capacity 50/60Hz (kA rms) Rated making capacity 50/60Hz (kA peak) Rated impulse withstand voltage of main circuit (kV) Rated impulse withstand voltage of aux. circuit (kV) Typical opening time (ms) Typical closing time (ms) Utilization category Suitability for isolation Fixed Draw out Manual Electrical Electrical & Mechanical life (operating cycles) Electrical life without maintenance Dimensions (in mm) Fixed H 3 Pole W 4 Pole D Draw out H 3 Pole W 4 Pole D Uimp Uimp Icm I
** cw
400 E In U
* e
800 C 800 415 1000 3/4 50 35 50 35 50 50 35 105 73.5 12 65 50 65 50 65 65 50 143 105 12 3 50 50 50 50 105 8 50 50 50 50 H E
1000 S1 1000 415 1000 3/4 50 35 50 35 50 50 35 105 73.5 12 65 50 65 50 65 65 50 143 105 12 3 50 50 50 50 105 8 50 50 50 50 C H E
1250 S1 C H E
1600 S1 1600 415 1000 3 65 50 65 50 65 65 50 143 105 12 50 50 50 50 105 8 50 50 50 50 105 12 3/4 50 35 50 35 50 50 35 105 73.5 12 65 50 65 50 65 65 50 143 105 12 3 50 50 50 50 105 8 50 50 50 50 C H E S1
3200 H0 3200 415 1000 3/4 75 65 75 65 75 75 70 165 143 12 100 85 100 85 100 100 85 220 187 12 H1
4000 H0 4000 415 1000 3/4 75 65 75 65 75 75 70 165 143 12 100 85 100 85 100 100 85 220 187 12 H
5000 6300 C C
Ui
Icu
380/415/500V 660/690V
50 50 50 50 105 8
95 95
Ics
95 95 95 95
209 209
105 12
105 12
105 12
105 12
12 12
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
40 60 B
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P x x x P x P P P x P P x P P P P x P P P x x P P P P x x x x x x x
x P
P P P x
x P P P
P P P x
P P x P
P P P P P P P P P P P P P
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P x x x P P P P x 20000 15000 6000 385 316 423.5 8000 x P P P 20000 8000 8000 6000 385 316 423.5 P P P x 20000 7000 7000 468 399 487 587
P P x P 20000
6000 6000 8000 6000 8000 8000 8000 385 316 385 316 468 399 487 587 385 316 423.5 394 326 414 431 468 399 487 587
7000
7000
5000
5000 5000 5000 5000 5000 5000 5000 5000 2500 2500 394 482 628 431 468 555 701 587 468 555 701 587 468 701 909 587 468 701 909 587 583 913 1182 691 583 913 1182 691
423.5 423.5 -
* Please consult us for application at dc voltages & higher operational voltage upto 1000V ac ** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than Ics / Icu at the point of installation.
Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear. consult us. Please
Protection releases
Parameter Overload (Phase) Current Settings (A), Ir = In x .... Time Delay, Tr (sec) at 6 x Ir Pre-trip Alarm Settings Thermal Reflectivity Function Neutral Fault Short Circuit Current Settings (A), In = Irx .... Time Delay (sec) Current Settings (A), Is = In x .... Time Delay, Ts (msec) at 10 x In l2t OFF l t ON Pre-trip Alarm Settings l 2t Cold-load Pickup Cold-load Pickup Delay Instantaneous Earth Fault Function Current Settings (A), Ip = In x .... Function Current Settings (A), Ig = In x .... Time Delay (sec), Td Pre-trip Alarm Settings l 2t Cold-load Pickup
2
Screen Abbreviation PICKUP TMS-tr PREALAR THM-MEM FUNC PICKUP DELAY PICKUP DELAY DELAY PREALAR l2t COLDPIC CP_DLY FUNC PICKUP FUNC PICKUP DELAY PREALAR l2t COLDPIC
Details 0.4 to 1.0 In in steps of 0.05 In 0.5-1-2-4-6-12-18-24-30 0.5 to 0.95 Ir in steps of 0.05 Ir ON / OFF Enable / Disable 0.5-1.0 Same as 'Overload (Phase)' 2 to 10 In in steps of 0.5 In 20-100-200-300-400 20-100-200-300-400 0.5 to 0.95 Is in steps of 0.05 Is ON / OFF Enable / Disable 0.1 to 10 sec in steps of 0.1 sec Enable / Disable 2 to 16 In in steps of 0.1 In Enable / Disable 0.1 to 0.6 in steps of 0.05 In for l2t ON 0.1 to 0.6 in steps of 0.01 In for l2t OFF 100 to 400 msecs in steps of 100 msec for l2t ON 0.1 to 5 sec in steps of 100 msec for l t OFF 0.5 to 0.95 Ig in steps of 0.05 Ig ON / OFF Enable / Disable
2
Factory Settings 1.0 In 30 sec 0.95 Ir OFF 1.0 Ir 30 sec 10 In 400 msec 400 msec 0.95 Is Disable 0.1 sec Enable 16 In Enable 0.6 In 3 sec 0.95 Ig OFF Disable
Note: Both Protection Groups 1 & 2 carry the same factory settings.
Additional Protections
Parameter Under Current Function Current Setting (A) x In Time Delay (secs) Trip / Alarm Current Unbalance Function Current Setting (A) x In Time Delay (secs) Over Voltage# Function Voltage Setting (V) Vs = Vn x .. Time Delay (secs) Reset Voltage Trip / Alarm Under Voltage# Function Voltage Setting (V) Vn x .. Time Delay (secs) Reset Voltage Trip / Alarm Under Frequency# Function Frequency Setting (Hz) Time Delay (secs) Drop Off Frequency Trip / Alarm Over Frequency# Function Frequency Setting (Hz) Time Delay (secs) Drop Off Frequency Trip / Alarm Reverse Power# Function Settings (kW) Time Delay (secs) Trip Alarm Phase Sequence# Function Settings Time Delay (secs) Trip / Alarm Breaker Failure Function Time Delay (secs) Maximum Demand Exceed Function Settings (kW) Step i -Discrimination
Screen Abbreviation FUNC PICKUP DELAY MODE FUNC PICKUP DELAY FUNC PICKUP DELAY RSTSET MODE FUNC PICKUP DELAY RSTSET MODE FUNC PICKUP DELAY DRPOFF MODE FUNC PICKUP DELAY DRPOFF MODE FUNC PICKUP DELAY MODE FUNC PICKUP DELAY MODE FUNC DELAY FUNC PICKUP DELAY i -Discrimination
Details Enable / Disable 15% to 80% in steps of 5% In 1 to 255 in steps of 1 second Either / Both Enable / Disable 10% to 95% in steps of 5% In 1 to 10 in steps of 5 secs Enable / Disable 105% to 150% in steps of 5% Vn 0.1 to 100 in steps of 0.1 secs 85% to 98% in steps of 1% Vs Either / Both Enable / Disable 45% to 65% in steps of 5% Vn 0.1 to 5 in steps of 0.1 secs 102% to 115% in steps of 1% Vs Either / Both Enable / Disable 45 to 50Hz for 50Hz in steps of 0.01Hz 57 to 60Hz for 60Hz in steps of 0.01Hz 0.1 to 100 secs in steps of 0.1 Second 0.02 to 0.10Hz in steps of 0.1Hz Either / Both Enable / Disable 50 to 55Hz for 50Hz in steps of 0.01Hz 60 to 62Hz for 60Hz in steps of 0.01Hz o.1 to 100 secs in steps of 0.1 second 0.02 to 0.10Hz in steps of 0.1Hz Either / Both Enable / Disable 0.02 to 0.4 in steps of 0.01 Pn 1 to 100 in steps of 0.1 secs Either / Both Enable / Disable 123 - 132 0 to 5 in steps of 0.5 secs Either / Both Enable / Disable 0.05 to 2 secs in steps of 0.01 secs Enable / Disable 40 kW - 1600 kW 10 kW - 1000 kW
Factory Settings Disable 0.8 In 1 second Alarm Disable 0.2 In 2.0 secs Disable 1.2 Vn 5.0 secs 0.95 Vs Alarm Disable 0.6 Vn 1 second 1.02 Vs Alarm Disable 48.0Hz 59.0Hz 0.2 secs 0.1Hz Alarm Disable 52.0Hz 61.0Hz 0.2 secs 0.1Hz Alarm Disable 0.2 Pn 2.0 secs Alarm Disable 123 2 secs Alarm Disable 1.0 second Disable 100 kW 10 kW Disable
Metering
Parameter Current I
Screen Abbreviation
Details Phase, Earth and Neutral Maximum running Current per Phase Percent Loading Phase-Neutral Phase-Phase System Frequency System Power Factor Active Power per Phase and Total (kW) Reactive Power per Phase and Total (kVAr) Apparent Power per Phase and Total (kVA) Maximum Demand (kW) Total Active Energy (kWh) Total Reactive Energy (kVArh) Total Apparent Energy (kVAh) R-Phase Current Harmonics Y-Phase Current Harmonics B-Phase Current Harmonics R-Phase Voltage Harmonics Y-Phase Voltage Harmonics B-Phase Voltage Harmonics High Resolution Backlit LCD
Imax %Load Voltage# V Vph-Vph Frequency# Power Factor# Power# F PF kW kVAr kVA kW Energy# kWh kVArh kVAh Harmonic-Current I1HAR I2HAR I3HAR Harmonic-Voltage# V1HAR V2HAR V3HAR Display # Requires SR71-PM module
Additional Features
Parameter LED Indications Auxiliary Power ON Overload Short Circuit Instantaneous Earth Fault Neutral Fault Trip Alarm Auxiliary Supply Digital Inputs Output Relays P P P P P P P P 24V DC 4 Nos. 3 Internal + 4 External Relays 240V AC / 5A, 30V DC / 5A (resistive load) Rating Plug Communication In Multiplier Protocol Link used Maintenance Indication Event Records Trip Records 630-800-1000-1250-2000-3200-5000 MODBUS RTU RS 485 I2t based Pickup, Alarm, Trip, Date, Time and Cause of Event Last 5 records with date and time stamping, voltage and current readings in all phases Testing Self-Diagnostic Test Relay Module Supplementary Modules Power Supply Module Communication Module No. of Storable Settings P 4 Relay Outputs 24V DC Output MODBUS RTU 2 Details
Protection releases
Self-powered True RMS sensing Zone selective interlocking on short circuit and ground faults reduces dynamic and thermal stress on the system Self-diagnostic and self-correcting facility to monitor its own performance Facility for default protection setting Switchable thermal memory takes care of residual heat in case of repetitive overloads
Multi-state LED to indicate - Power ON condition - Test mode - Microprocessor unhealthy condition Individual fault annunciation through LEDs On load testing release possible through TEST button (without tripping the breaker) AN1 module for remote fault indication through LEDs with changeover contact for each kind of fault Direct tripping of breaker-reliable tripping with minimum time delay test kit available for testing the release (SRT-2)
Realistic hot and cold curves which take into account integrated heating effect
Type of Protection
Setting Range Pick-up Current Ir - 0.5 to 1.0 times In Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1.00 2 to 10 times In Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 2 to 16 times In Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, MAX (infinity) 0.2 to 0.6 times In Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Time Delay 0.2 to 30 sec. at 6 times Ir Steps : 0.2, 0.5, 1, 1.5, 2, 3.5, 6, 12, 17, 30 Sec 20 ms to 600 ms Steps : 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms 100 to 400 ms Steps : 100, 200, 300, 400 ms & infinity
Long Time
Short Time
Instantaneous
Ground Fault
Protection releases
Self-powered
Comprehensive protection - SR18; Long Time and Short Time - SR18G; Long Time, Short Time and Ground fault protection
Switchable thermal memory takes care of residual heat in case of repetitive overloads
Multi-state LED to indicate - Power ON condition - Test mode - Microprocessor unhealthy condition
On load testing of release possible through TEST button (without tripping the breaker)
Setting Range Pick-up Current Ir - 0.5 to 1.0 times In Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1.00 2 to 10 times Ir Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 6 & 12 In 0.2 to 0.6 times In Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Time Delay 2.5 sec at 6 times Ir
Short Time
20 to 600 ms Steps: 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms 100 to 400 ms Steps : 100, 200, 300, 400 ms & OFF
* Available in SR18G release only In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.
10
Protection releases
DN1 is CT-operated thermo-magnetic release, which offers reliable protection against overload, short circuit and ground faults.
Protection
Overload Protection l Continuous & individual phase adjustable dial settings from 75% to 100% of CT tap
l
Short Circuit Protection l taps available to select operating threshold Two Ground Fault Protection l Offered with auxiliary earth fault release (20% to 50% In)
Salient Features
l
Wide range of overload & short circuit settings possible with multitap CTs
Each phase can be individually adjusted for overload & short circuit settings Fixed minimum impulsion time of 25 ms on short circuit to prevent nuisance tripping due to transients Trip test facility available
11
Accessories
Locks/Interlocks
Type Lockable Trip Push Button (LTPB) Data
Mounted in place of normal trip push button. With this, ACB can be locked in trip condition. For interlocking, LTPBs are offered in the following combinations: l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 incomers and 1 bus coupler schemes l Combination of L, M, N, LM and MN locks, which are suitable for three incomer and two bus coupler schemes l Combination of K, L, MN, KL, LM and MN locks, which are suitable for four incomer and three bus coupler schemes l Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are suitable for five incomer and four bus coupler schemes
Locking in Isolated Position (LIP) The facility of locking the ACB in Isolated position is available in Drawout ACBs. This is useful to achieve interlocking between Main & Standby source. Similar lock is available as LOCK IN ANY POSITION. Door Interlock This ensures: l Unless the panel door is closed, breaker cannot be racked in or out l Unless the breaker is in Isolated Position, it is not possible to open the panel door Racking Interlock This ensures that breaker cannot be racked in/out unless the ACB is in tripped/open condition.
Door Interlock
Racking Inerlock
Mechanical Interlock
It is possible to provide Mechanical Interlock between two breakers of the same or different ratings in vertical or horizontal configurations. Mechanical interlock is available for ACBs up to 4000A. Mechanical interlocking for ACBs in vertical configuration can be provided by links or by flexible cables. Same for horizontal configuration can be provided by flexible cables.
12
Accessories
Signaling
Type
C1
Data
Common indication of tripping due to overload, short circuit and ground faults. l Provided by micro-switch C1 fitted inside the ACB l Available as an option in all releases
C2
Separate indication of tripping due to overload, short circuit and ground faults. lrelease type DN1, this is provided by micro-switch C1 & For C2 (C2 fitted inside release) l Available through in-built fault indicators in SR18, SR18G, SR21i & SR71 releases
AN1-Annunciator Module
Remote indication of tripping due to overload, short circuit and ground faults. Can l be used with releases type SR18/SR18G/SR21i l Individual fault indication provided by three separate LEDs for - Long time faults - Short time fault/instantaneous fault - Ground fault one potential free contact rated 5A at 230V AC available for each type of fault l mounting on panel (H-W-D=92mm x 46mm x 105mm) Flush l Operating voltage: 240V AC/110V DC/220V DC (other Voltages available on request)
C5
Indication for operation of shunt release or under voltage release. l Provided by micro-switch C5 fitted on the shunt release
13
Accessories
Control
Type Shunt Release Data For remote tripping of the breaker l Shunt release coil is short time rated and is disconnected from the circuit by an auxiliary contact when the ACB trips (Refer to wiring diagram) l power consumption Low l types available: Two - EA for DC application - EA1 for AC application
l
Technical Data
Type Nominal Power Operation of voltage consumLimit Release Uc (V) ption at 50Hz pick up EA1 240 AC 415 AC 24V DC 48V DC 110 DC 220 DC 800 VA 800 VA 32 W 125 W 45 W 30 W 10-130% Uc 65-130% Uc
EA
Undervoltage Release
Two types available: Type l MV With no intentional time delay Notes: When undervoltage release is provided, the ACB can be closed only when supply is available to the undervoltage release.
Parameter Nominal voltage (Uc) Pick up (V) Drop OFF (V) Consumption (VA)
Specification 240V & 415V: 50Hz 220V & 415V: 60Hz 80% Uc 35-65% Uc Pick up - 23 VA Hold on - 10 VA 6W
Watt loss
Auxiliary Contacts
Nonresistive
Operation Counter
l l
14
Overall Dimensions
Fixed Breakers
For 630A to 2500A 3P/4P C/H
for Metallic Components 340 min for Insulating Sheet 140 min 100 min 20 min 9 to Remove Arc Chute 7 Door Bezel 27 26
36 min A 26 58 264
36 min
385
200 min
33
394 309
22 16 27 104 Earthing Terminal 2 Holes-6.3 30 35 20 405 230 301 2.6 min 86 10 54 68.8
21
16
Ratings CN - CS 630/800/1000A 1250/1600A 630/800/1000A 1250/1600A 2000/2500A 2000/2500A C/H C/H C/H C/H C/H C/H 3P 3P 4P 4P 3P 4P
F -
414
56
98
98
54 55
482 628
83 82
154 150
156
69 77
40 min 56
20 min 23.5
102
X 5 15
Y 150 140
X 4 Holes 12 385
325
286
32
20 22 137.5
20
256
15
Overall Dimensions
Fixed Breakers
Terminal
2 Holes-13 30 15 30
3 Holes-13 15
25 50
12.5
25
50 100
25
2000/2500C/H
Terminal Connections
23.5
23.5 10 15
10 227 227
15
145
12 Holes-4
305 101
140
332
112
112
Hinge
Hinge
325
112
5.5
91
11 min
59
294
15 min
Door Cutout
363
Bezel
16
Overall Dimensions
Drawout Breakers
For 630A to 3200A C/H/S1 3P/4P 3200H1/4000H 3P ,
for Metallic Components A 122 94.5 264 40 max 40 64.5 *5 75 Isolated Position 200 min 380 min for Insulating Sheet
100 min
468
397.5
404
46 6 199.5 6
28
10
54
538
308.5
308.5
221.5
221.5
308.5
*Terminal for 1250/1600/2500C/H & 800/1000H Ratings CN - CS 630/800/1000A 2000A 1250/1600A 630/800/1000A 2000A 1250/1600A 2000/2500A 2500/3200A 2000/2500A 2500/3200A 3200A 4000A 3200A 4000A
Note : All Dimensions are in mm.
Dimensions (mm) A C/H/S1 S1 C/H/S1 C/H/S1 S1 C/H/S1 C/H S1 C/H S1 H0/H1 H0/H H0/H1 H0/H 3P 3P 3P 4P 4P 4P 3P 3P 4P 4P 3P 3P 4P 4P 909 151.5 202 202 701 148.5 202 701 122.5 150 156 555 123.5 154 487 96.5 98 98 399 97.5 102 D E F
221.5
68.8
160
256
17
Overall Dimensions
Drawout Breakers
Flat Terminal Connections
50 25 19 12.5 4 slots 8.5 x 9.5 8.5 10.2 58.4 38 4 Slots 8.5 x 9.5 8.5 10.2 58.4 6 Slots 8.5 x 9.5 20 63 25 100 30 30 10.2 58.4 6 Holes-14 68.8 10 199.5 10 5 615 17.5 min 18.9 max. 8.9 min. 18 20 245 54 256 467 46 6 5 74 28 D E F E D 217 8 Holes-14 28 17.5 40 42
64.5
38
8.5
2000C
160 25 25 25 25
38
2500S1
3200S1
For 5000C/6300C 3P
for Metallic Components 75 A 124 96.5 264 20 max 102 200 min 400 min for Insulating Sheet
100 min
Isolated Position
Door
7 Bezel
404
683
50
40
43.5
Earthing Terminal
63
160
M 10
Dimensions (mm) D 187.5 187.5 187.5 187.5 E 269 269 269 269 F 269 269
18
12.5
25
Overall Dimensions
Mounting Details
For Horizontal Mounting of all Draw-out Breakers
For 630A to 3200A C/H/S1 3P/4P 3200 H0/H1, 4000 H0/H 3P/4P
107.5 367.5 40 10 Holes-11 24
G (mm) 280.3 280.3 368.3 368.3 436.3 582.3 436.3 582.3 582.3 790.3 582.3 790.3 863 1132
Front
24 64.1
20
481
37
25
50 108.5 184.5
412
224
199
Base of Cradle
5.5
20.5 min
294
5 min
Door Cutout
Note: For 5000C/6300C 3P ACB, A = 81.5 For other Drawout Breakers A = 79.5
450
19
Overall Dimensions
Terminals
Horizontal Terminals
80 80 80 80
Rear Side
10
15
10
308.5
800 - 1000C
2000C
221.5
15
2 Holes-14 12.5 15
3 Holes-14 12.5
6 Holes-14
16.5
12.5
25
12.5
30 12 43
Vertical Terminals
V U 4 Holes-T O P R 40.0 Top S W
387.5
221.5
308.5
25 25 25
63 16.5
100
50
25
Side View Ratings 800/1000A 1250/1600A 800/1000A 2000A 2500A 2000A C C/H H C C/H H M 10.2 20 20 20 N 38 40 40 40 P 20 20 20 20 Q 25 25 40 40 R 29.2 29.2 29.2 33.5
Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
20
Pune
Lucknow
Coonoor
Train & Gain - This concept underlies L&Ts commitment to its customers and the Indian switchgear industry. To this end, L&T has set up Switchgear Training Centers equipped with a wide range of education facilities at Pune, Lucknow & Coonoor. Specially designed Hands-On training programs on the operation & maintenance of switchgear are conducted for engineers and technicians from different industry segments. The centers have state-of-the-art training facilities, well-equipped workshops and testing systems.
21
Notes
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Electrical Standard Products Larsen & Toubro Limited Powai Campus, Mumbai 400 072 Customer Interaction Center (CIC) BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858 Tel : 022 6774 5858 Fax : 022 6774 5859 E-mail : [email protected] Website : www.LNTEBG.com
SP 50437(R2)
270111