ACB Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Air Circuit Breakers

About us

Larsen & Toubro is a technology-driven company that infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering, Construction, Electrical & Automation, Machinery and Information Technology. L&T Switchgear, which forms part of the Electrical & Automation business, is India's largest manufacturer of low voltage switchgear, with the scale, sophistication and range to meet global benchmarks. With over five decades of experience in this field, the Company today enjoys a leadership position in the Indian market with growing presence in international markets. It offers a complete range of products including controlgear, powergear, motor starters, energy meters, wires and host of other accessories. Most of our product lines conform to international standards, carry markings and are certified.

Switchgear Factory, Mumbai

Switchgear Factory, Ahmednagar

Air Circuit Breakers

L&Ts Air Circuit Breakers (ACBs) are specially designed for extreme tropical conditions and have a proven track record more than 30 years. Presently more than 3,00,000 Air Circuit Breakers supplied by L&T are being used for diverse applications. The Air Circuit Breakers provide technologically driven solutions to meet customer needs. Complete selectivity Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures complete selectivity for system with time based discrimination. Perfect for Indian conditions Inherent design to perform in extreme tropical conditions. Typical site conditions like high ambient temperature, humidity and dusty environment are best handled by ACBs without compromising on performance and safety. Optimal compactness Designed to ensure l inherent temperature rise Low l Adequate interface clearances Widest choice of over current protection releases l Advance micro-controller based with option of communication & metering-SR71 l processor based releases-SR21i/SR18/SR18G Micro l Thermo-magnetic release-DN1 Elegant design & rugged construction l Common door cutout for entire range l aligned cutout for all ratings Left l Uniform height and depth for ACBs up to 4000 Amp Range to meet every customers need Various options to choose from l Breaking capacity from 35kA to 100kA l 3 Pole or 4 Pole configuration l or Drawout version Fixed l or Manual reset mechanism Auto l Independent manual or stored energy type manual or electrically operated mechanism l Different terminal orientations : Flat, Horizontal and Vertical

User friendly features Front accessible over current release settings, telescopic racking handle and various racking interlocks; no need to open the panel door l Unique Maintenance position in drawout type ACBs to facilitate maintenance & inspection without removing ACB from the panel l Multitap CTs for enhancing protection range for example: 3200A. ACB can be set to have a thermal protection from 800A l variety of Amperemetric and Voltmetric releases Wide l rated neutral pole for the entire range Fully l Lockable sliding shutters to prevent unauthorized access to TRIP and CLOSE push buttons l be used as an ON / OFF Load Isolator Can l Extendable Electrical Life: - By replacing the arcing contacts at site, for all ratings - Without changing pole assembly l Programmable SICs: Auxiliary contacts in drawout ACBs are programmable for only Service, Only Test, Test and Service, and All Positions l Unique gasket for IP54 protection l Protection releases are easily interchangeable at site l Facility for site conversion of manually operated ACBs to electrically operated ACBs
l

Safety marked for C, S & H ranges l Superior quality engineering grade plastics used for insulation purpose; conforms to Glow wire test (Ref: IEC 60695-2-1) l In-built mechanical anti-pumping for electrically operated ACBs prevent auto reclosing of ACB on fault l In-built rating error preventor in drawout ACBs ensure correct rating of drawout porton in corresponding cradle l Safety shutters prevent accidental contact with live cradle terminals l Variety of Safety Interlocks (Refer to page no. 14) l Easily removable arc chutes without use of any tool l Operating voltage ranges from 10% Un to 110% Un for shunt release ensures intentional tripping even at high voltage drops during short circuit
l

Conformance to standards IEC - 60947 (Part 1 & 2) IS/IEC - 60947 (Part 1 & 2) l 60695 - 2 - 1 IEC l BS EN 60947 - 2
l l

Product Certification

Technical Data Sheet

Rating (A) Type Designation Rated current (A) at 50C Rated operational voltage (V), 50/60Hz Rated insulation voltage (V), 50/60Hz No. of poles Rated ultimate short circuit breaking capacity 50/60Hz (kA rms) Rated service short circuit breaking capacity 50/60Hz (kA rms) Rated short time withstand capacity 50/60Hz (kA rms) Rated making capacity 50/60Hz (kA peak) Rated impulse withstand voltage of main circuit (kV) Rated impulse withstand voltage of aux. circuit (kV) Typical opening time (ms) Typical closing time (ms) Utilization category Suitability for isolation Fixed Draw out Manual Electrical Electrical & Mechanical life (operating cycles) Electrical life without maintenance Dimensions (in mm) Fixed H 3 Pole W 4 Pole D Draw out H 3 Pole W 4 Pole D Uimp Uimp Icm I
** cw

400 E In U
* e

630 E 630 415 1000 3 50 50 50 50 105 8 3/4 50 50 50 50 105 12 3 50 50 50 50 105 8 50 50 50 50 S1 E S1

800 C 800 415 1000 3/4 50 35 50 35 50 50 35 105 73.5 12 65 50 65 50 65 65 50 143 105 12 3 50 50 50 50 105 8 50 50 50 50 H E

1000 S1 1000 415 1000 3/4 50 35 50 35 50 50 35 105 73.5 12 65 50 65 50 65 65 50 143 105 12 3 50 50 50 50 105 8 50 50 50 50 C H E

1250 S1 C H E

1600 S1 1600 415 1000 3 65 50 65 50 65 65 50 143 105 12 50 50 50 50 105 8 50 50 50 50 105 12 3/4 50 35 50 35 50 50 35 105 73.5 12 65 50 65 50 65 65 50 143 105 12 3 50 50 50 50 105 8 50 50 50 50 C H E S1

2000 C 2000 415 1000 3/4 55 40 55 40 55 55 50 121 84 12 75 65 75 65 75 75 65 165 143 12 60 60 60 55 132 12 H S1

2500 C 2500 415 1000 3/4 60 40 60 40 60 60 55 132 84 12 75 65 75 65 75 75 65 165 143 12 60 60 60 60 132 12 H S1

3200 H0 3200 415 1000 3/4 75 65 75 65 75 75 70 165 143 12 100 85 100 85 100 100 85 220 187 12 H1

4000 H0 4000 415 1000 3/4 75 65 75 65 75 75 70 165 143 12 100 85 100 85 100 100 85 220 187 12 H

5000 6300 C C

400 415 1000 3

1250 415 1000 3/4 50 35 50 35 50 50 35 105 73.5 12

5000 6300 415 415

Ui

1000 1000 3/4 95 3/4 95

Icu

380/415/500V 660/690V

50 50 50 50 105 8

95 95

Ics

380/415/500V 660/690V 0.5 sec 1 sec 3 sec 380/415/500V 660/690V

95 95 95 95

209 209

105 12

105 12

105 12

105 12

12 12

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

40 60 B

P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P x x x P x P P P x P P x P P P P x P P P x x P P P P x x x x x x x

x P

P P P x

x P P P

P P P x

P P x P

P P P P P P P P P P P P P

P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P x x x P P P P x 20000 15000 6000 385 316 423.5 8000 x P P P 20000 8000 8000 6000 385 316 423.5 P P P x 20000 7000 7000 468 399 487 587

P P x P 20000

P P P P P P P P P P P P P 20000 20000 5000 10000 10000 5000 5000

15000 15000 20000 15000

6000 6000 8000 6000 8000 8000 8000 385 316 385 316 468 399 487 587 385 316 423.5 394 326 414 431 468 399 487 587

7000

6000 385 316 423.5 -

7000 7000 468 399 487 587

7000

4500 385 316 423.5 -

5000 468 399 487 587

5000

5000 5000 5000 5000 5000 5000 5000 5000 2500 2500 394 482 628 431 468 555 701 587 468 555 701 587 468 701 909 587 468 701 909 587 583 913 1182 691 583 913 1182 691

394 326 414 431 468 399 487 587

394 326 414 431

394 326 414 431

394 482 628 431 468 555 701 587

423.5 423.5 -

* Please consult us for application at dc voltages & higher operational voltage upto 1000V ac ** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than Ics / Icu at the point of installation.

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear. consult us. Please

Protection releases

Microprocessor-based, Communication-capable Release - SR71


Salient Features Micro-controller based RMS sensing Offers comprehensive protection for overload, short circuit, instantaneous, earth fault and neutral overload l resolution backlit LCD display High l Intelligent Pre-trip alarm to prevent system shutdown l Password protected setting and commands l MODBUS RTU protocol l Intrinsic RS 485 port l breaker control and monitoring through PC Total l indication for POWER ON, different faults and Pre-trip alarm LED l 2 sets of storable protection setting l Non-volatile memory to store last 5 trips l Event recording with time & date stamping 128 3 programmable contacts-1 for micro controller failure, 2 for basic l fault annunciation l 4 relay contacts for indication of exceeding maximum demand, Pretrip alarm and control on breaker (closing and opening) l Auto-doubling features to prevent nuisance tripping l Selectable I2t based current for short-time and earth fault zones l Thermal reflectivity enables faster tripping on recurrent overloads l Intelligent discrimination l Self-diagnostic and monitoring with tri-colour LED indication l Conformance to EMC standards
l l

Parameter Overload (Phase) Current Settings (A), Ir = In x .... Time Delay, Tr (sec) at 6 x Ir Pre-trip Alarm Settings Thermal Reflectivity Function Neutral Fault Short Circuit Current Settings (A), In = Irx .... Time Delay (sec) Current Settings (A), Is = In x .... Time Delay, Ts (msec) at 10 x In l2t OFF l t ON Pre-trip Alarm Settings l 2t Cold-load Pickup Cold-load Pickup Delay Instantaneous Earth Fault Function Current Settings (A), Ip = In x .... Function Current Settings (A), Ig = In x .... Time Delay (sec), Td Pre-trip Alarm Settings l 2t Cold-load Pickup
2

Screen Abbreviation PICKUP TMS-tr PREALAR THM-MEM FUNC PICKUP DELAY PICKUP DELAY DELAY PREALAR l2t COLDPIC CP_DLY FUNC PICKUP FUNC PICKUP DELAY PREALAR l2t COLDPIC

Details 0.4 to 1.0 In in steps of 0.05 In 0.5-1-2-4-6-12-18-24-30 0.5 to 0.95 Ir in steps of 0.05 Ir ON / OFF Enable / Disable 0.5-1.0 Same as 'Overload (Phase)' 2 to 10 In in steps of 0.5 In 20-100-200-300-400 20-100-200-300-400 0.5 to 0.95 Is in steps of 0.05 Is ON / OFF Enable / Disable 0.1 to 10 sec in steps of 0.1 sec Enable / Disable 2 to 16 In in steps of 0.1 In Enable / Disable 0.1 to 0.6 in steps of 0.05 In for l2t ON 0.1 to 0.6 in steps of 0.01 In for l2t OFF 100 to 400 msecs in steps of 100 msec for l2t ON 0.1 to 5 sec in steps of 100 msec for l t OFF 0.5 to 0.95 Ig in steps of 0.05 Ig ON / OFF Enable / Disable
2

Factory Settings 1.0 In 30 sec 0.95 Ir OFF 1.0 Ir 30 sec 10 In 400 msec 400 msec 0.95 Is Disable 0.1 sec Enable 16 In Enable 0.6 In 3 sec 0.95 Ig OFF Disable
Note: Both Protection Groups 1 & 2 carry the same factory settings.

Additional Protections

Parameter Under Current Function Current Setting (A) x In Time Delay (secs) Trip / Alarm Current Unbalance Function Current Setting (A) x In Time Delay (secs) Over Voltage# Function Voltage Setting (V) Vs = Vn x .. Time Delay (secs) Reset Voltage Trip / Alarm Under Voltage# Function Voltage Setting (V) Vn x .. Time Delay (secs) Reset Voltage Trip / Alarm Under Frequency# Function Frequency Setting (Hz) Time Delay (secs) Drop Off Frequency Trip / Alarm Over Frequency# Function Frequency Setting (Hz) Time Delay (secs) Drop Off Frequency Trip / Alarm Reverse Power# Function Settings (kW) Time Delay (secs) Trip Alarm Phase Sequence# Function Settings Time Delay (secs) Trip / Alarm Breaker Failure Function Time Delay (secs) Maximum Demand Exceed Function Settings (kW) Step i -Discrimination

Screen Abbreviation FUNC PICKUP DELAY MODE FUNC PICKUP DELAY FUNC PICKUP DELAY RSTSET MODE FUNC PICKUP DELAY RSTSET MODE FUNC PICKUP DELAY DRPOFF MODE FUNC PICKUP DELAY DRPOFF MODE FUNC PICKUP DELAY MODE FUNC PICKUP DELAY MODE FUNC DELAY FUNC PICKUP DELAY i -Discrimination

Details Enable / Disable 15% to 80% in steps of 5% In 1 to 255 in steps of 1 second Either / Both Enable / Disable 10% to 95% in steps of 5% In 1 to 10 in steps of 5 secs Enable / Disable 105% to 150% in steps of 5% Vn 0.1 to 100 in steps of 0.1 secs 85% to 98% in steps of 1% Vs Either / Both Enable / Disable 45% to 65% in steps of 5% Vn 0.1 to 5 in steps of 0.1 secs 102% to 115% in steps of 1% Vs Either / Both Enable / Disable 45 to 50Hz for 50Hz in steps of 0.01Hz 57 to 60Hz for 60Hz in steps of 0.01Hz 0.1 to 100 secs in steps of 0.1 Second 0.02 to 0.10Hz in steps of 0.1Hz Either / Both Enable / Disable 50 to 55Hz for 50Hz in steps of 0.01Hz 60 to 62Hz for 60Hz in steps of 0.01Hz o.1 to 100 secs in steps of 0.1 second 0.02 to 0.10Hz in steps of 0.1Hz Either / Both Enable / Disable 0.02 to 0.4 in steps of 0.01 Pn 1 to 100 in steps of 0.1 secs Either / Both Enable / Disable 123 - 132 0 to 5 in steps of 0.5 secs Either / Both Enable / Disable 0.05 to 2 secs in steps of 0.01 secs Enable / Disable 40 kW - 1600 kW 10 kW - 1000 kW

Factory Settings Disable 0.8 In 1 second Alarm Disable 0.2 In 2.0 secs Disable 1.2 Vn 5.0 secs 0.95 Vs Alarm Disable 0.6 Vn 1 second 1.02 Vs Alarm Disable 48.0Hz 59.0Hz 0.2 secs 0.1Hz Alarm Disable 52.0Hz 61.0Hz 0.2 secs 0.1Hz Alarm Disable 0.2 Pn 2.0 secs Alarm Disable 123 2 secs Alarm Disable 1.0 second Disable 100 kW 10 kW Disable

# Requires SR71-PM module

Metering

Parameter Current I

Screen Abbreviation

Details Phase, Earth and Neutral Maximum running Current per Phase Percent Loading Phase-Neutral Phase-Phase System Frequency System Power Factor Active Power per Phase and Total (kW) Reactive Power per Phase and Total (kVAr) Apparent Power per Phase and Total (kVA) Maximum Demand (kW) Total Active Energy (kWh) Total Reactive Energy (kVArh) Total Apparent Energy (kVAh) R-Phase Current Harmonics Y-Phase Current Harmonics B-Phase Current Harmonics R-Phase Voltage Harmonics Y-Phase Voltage Harmonics B-Phase Voltage Harmonics High Resolution Backlit LCD

Imax %Load Voltage# V Vph-Vph Frequency# Power Factor# Power# F PF kW kVAr kVA kW Energy# kWh kVArh kVAh Harmonic-Current I1HAR I2HAR I3HAR Harmonic-Voltage# V1HAR V2HAR V3HAR Display # Requires SR71-PM module

Additional Features
Parameter LED Indications Auxiliary Power ON Overload Short Circuit Instantaneous Earth Fault Neutral Fault Trip Alarm Auxiliary Supply Digital Inputs Output Relays P P P P P P P P 24V DC 4 Nos. 3 Internal + 4 External Relays 240V AC / 5A, 30V DC / 5A (resistive load) Rating Plug Communication In Multiplier Protocol Link used Maintenance Indication Event Records Trip Records 630-800-1000-1250-2000-3200-5000 MODBUS RTU RS 485 I2t based Pickup, Alarm, Trip, Date, Time and Cause of Event Last 5 records with date and time stamping, voltage and current readings in all phases Testing Self-Diagnostic Test Relay Module Supplementary Modules Power Supply Module Communication Module No. of Storable Settings P 4 Relay Outputs 24V DC Output MODBUS RTU 2 Details

Protection releases

Microprocessor Based Release - SR21i


Salient Features
l

Self-powered True RMS sensing Zone selective interlocking on short circuit and ground faults reduces dynamic and thermal stress on the system Self-diagnostic and self-correcting facility to monitor its own performance Facility for default protection setting Switchable thermal memory takes care of residual heat in case of repetitive overloads

Multi-state LED to indicate - Power ON condition - Test mode - Microprocessor unhealthy condition Individual fault annunciation through LEDs On load testing release possible through TEST button (without tripping the breaker) AN1 module for remote fault indication through LEDs with changeover contact for each kind of fault Direct tripping of breaker-reliable tripping with minimum time delay test kit available for testing the release (SRT-2)

Realistic hot and cold curves which take into account integrated heating effect

Conformance to EMI/EMC standards

Type of Protection

Setting Range Pick-up Current Ir - 0.5 to 1.0 times In Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1.00 2 to 10 times In Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 2 to 16 times In Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, MAX (infinity) 0.2 to 0.6 times In Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Time Delay 0.2 to 30 sec. at 6 times Ir Steps : 0.2, 0.5, 1, 1.5, 2, 3.5, 6, 12, 17, 30 Sec 20 ms to 600 ms Steps : 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms 100 to 400 ms Steps : 100, 200, 300, 400 ms & infinity

Long Time

Short Time

Instantaneous

Ground Fault

In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.

Protection releases

Microprocessor Based Release - SR18 & SR18G


Salient Features
l

Self-powered

True RMS sensing

Comprehensive protection - SR18; Long Time and Short Time - SR18G; Long Time, Short Time and Ground fault protection

True Hot & Cold characteristics

Switchable thermal memory takes care of residual heat in case of repetitive overloads

Facility to have default protection settings

Suitable for 800A to 6300A

Multi-state LED to indicate - Power ON condition - Test mode - Microprocessor unhealthy condition

Individual fault annunciation through LEDs

On load testing of release possible through TEST button (without tripping the breaker)

Test kit (SRT-2) available for testing the releases

Direct tripping of breaker-Reliable tripping with minimum time delay

Conformance to EMI/EMC standards

Type of Protection Long Time

Setting Range Pick-up Current Ir - 0.5 to 1.0 times In Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1.00 2 to 10 times Ir Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 6 & 12 In 0.2 to 0.6 times In Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Time Delay 2.5 sec at 6 times Ir

Short Time

20 to 600 ms Steps: 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms 100 to 400 ms Steps : 100, 200, 300, 400 ms & OFF

Instantaneous Ground Fault*

* Available in SR18G release only In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.

10

Protection releases

Thermo-magnetic Over Current Release Type - DN1

DN1 is CT-operated thermo-magnetic release, which offers reliable protection against overload, short circuit and ground faults.

Protection
Overload Protection l Continuous & individual phase adjustable dial settings from 75% to 100% of CT tap
l

Inverse Time Characteristics

Short Circuit Protection l taps available to select operating threshold Two Ground Fault Protection l Offered with auxiliary earth fault release (20% to 50% In)

Salient Features
l

True RMS sensing

Ambient temperature compensated from -50C to 500C

Wide range of overload & short circuit settings possible with multitap CTs

Each phase can be individually adjusted for overload & short circuit settings Fixed minimum impulsion time of 25 ms on short circuit to prevent nuisance tripping due to transients Trip test facility available

11

Accessories

Locks/Interlocks
Type Lockable Trip Push Button (LTPB) Data

Mounted in place of normal trip push button. With this, ACB can be locked in trip condition. For interlocking, LTPBs are offered in the following combinations: l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 incomers and 1 bus coupler schemes l Combination of L, M, N, LM and MN locks, which are suitable for three incomer and two bus coupler schemes l Combination of K, L, MN, KL, LM and MN locks, which are suitable for four incomer and three bus coupler schemes l Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are suitable for five incomer and four bus coupler schemes

View of the Cradle

Locking in Isolated Position (LIP) The facility of locking the ACB in Isolated position is available in Drawout ACBs. This is useful to achieve interlocking between Main & Standby source. Similar lock is available as LOCK IN ANY POSITION. Door Interlock This ensures: l Unless the panel door is closed, breaker cannot be racked in or out l Unless the breaker is in Isolated Position, it is not possible to open the panel door Racking Interlock This ensures that breaker cannot be racked in/out unless the ACB is in tripped/open condition.

Door Interlock

Racking Inerlock

Locking in Isolated Position

Mechanical Interlock

It is possible to provide Mechanical Interlock between two breakers of the same or different ratings in vertical or horizontal configurations. Mechanical interlock is available for ACBs up to 4000A. Mechanical interlocking for ACBs in vertical configuration can be provided by links or by flexible cables. Same for horizontal configuration can be provided by flexible cables.

12

Accessories

Signaling
Type
C1

Data

Common indication of tripping due to overload, short circuit and ground faults. l Provided by micro-switch C1 fitted inside the ACB l Available as an option in all releases

C2

Separate indication of tripping due to overload, short circuit and ground faults. lrelease type DN1, this is provided by micro-switch C1 & For C2 (C2 fitted inside release) l Available through in-built fault indicators in SR18, SR18G, SR21i & SR71 releases

AN1-Annunciator Module

Remote indication of tripping due to overload, short circuit and ground faults. Can l be used with releases type SR18/SR18G/SR21i l Individual fault indication provided by three separate LEDs for - Long time faults - Short time fault/instantaneous fault - Ground fault one potential free contact rated 5A at 230V AC available for each type of fault l mounting on panel (H-W-D=92mm x 46mm x 105mm) Flush l Operating voltage: 240V AC/110V DC/220V DC (other Voltages available on request)

C5

Indication for operation of shunt release or under voltage release. l Provided by micro-switch C5 fitted on the shunt release

13

Accessories

Control
Type Shunt Release Data For remote tripping of the breaker l Shunt release coil is short time rated and is disconnected from the circuit by an auxiliary contact when the ACB trips (Refer to wiring diagram) l power consumption Low l types available: Two - EA for DC application - EA1 for AC application
l

Technical Data
Type Nominal Power Operation of voltage consumLimit Release Uc (V) ption at 50Hz pick up EA1 240 AC 415 AC 24V DC 48V DC 110 DC 220 DC 800 VA 800 VA 32 W 125 W 45 W 30 W 10-130% Uc 65-130% Uc

EA

Note : Other voltages available on request

Undervoltage Release

Two types available: Type l MV With no intentional time delay Notes: When undervoltage release is provided, the ACB can be closed only when supply is available to the undervoltage release.

Parameter Nominal voltage (Uc) Pick up (V) Drop OFF (V) Consumption (VA)

Specification 240V & 415V: 50Hz 220V & 415V: 60Hz 80% Uc 35-65% Uc Pick up - 23 VA Hold on - 10 VA 6W

Watt loss

Auxiliary Contacts

Two combinations available: l + 2 NC 2 NO l + 6 NC 6 NO

Electrical circuit Resistive

Voltage (V) 24 to 415 AC 250V AC 24 to 415 AC 250V AC

Rated current (A) 16 1.2 16 1.0 #

Nonresistive

# L/R = 15ms with two contacts in series

Operation Counter

l l

Operates mechanically Display total number of breaker operation cycles

14

Overall Dimensions

Fixed Breakers
For 630A to 2500A 3P/4P C/H
for Metallic Components 340 min for Insulating Sheet 140 min 100 min 20 min 9 to Remove Arc Chute 7 Door Bezel 27 26

36 min A 26 58 264

36 min

385

200 min

33

394 309

22 16 27 104 Earthing Terminal 2 Holes-6.3 30 35 20 405 230 301 2.6 min 86 10 54 68.8

21

16

Ratings CN - CS 630/800/1000A 1250/1600A 630/800/1000A 1250/1600A 2000/2500A 2000/2500A C/H C/H C/H C/H C/H C/H 3P 3P 4P 4P 3P 4P

Dimensions (mm) A 326 D 57 E 102

Weight (kg.) Manual 50 51 Electrical 57 58 61 62 76 84

F -

414

56

98

98

54 55

482 628

83 82

154 150

156

69 77

For CN-CS...E 400A-2000A 3P


340 min Insulator 100 min 40 min 58 102 316
+1.0

40 min 56

20 min 23.5

102

Rating Type 400E 1250E 1600/ 2000E


X 227

X 5 15

Y 150 140

X 4 Holes 12 385

325

286

32

20 22 137.5

20

216 298 402 21

179.5 Note : All Dimensions are in mm.

256

15

Overall Dimensions

Fixed Breakers
Terminal

2 Holes-13 30 15 30

3 Holes-13 15

25 50

12.5

25

50 100

25

400 to 2000E & 800/1000/1250/1600C/H

2000/2500C/H

Terminal Connections
23.5

23.5 10 15

10 227 227

15

Terminal for 800/1000C/H

145

Terminal for 1250/1600/2000/2500C/H

Bezel Fixing Plan for all Fixed Breakers

12 Holes-4

305 101

140

332

112

112

Hinge

Hinge

325

112

5.5

91

11 min

59

294

15 min

Door Cutout

Door Drilling for Bezel Fixing Plan

363

Bezel

Note: All dimensions are in mm.

16

Overall Dimensions

Drawout Breakers
For 630A to 3200A C/H/S1 3P/4P 3200H1/4000H 3P ,
for Metallic Components A 122 94.5 264 40 max 40 64.5 *5 75 Isolated Position 200 min 380 min for Insulating Sheet
100 min

51 Test Position Service Position 26 Door 7 Bezel

468

397.5

404

46 6 199.5 6

M 10 4 17.5 min. 18.9 max. 8.9 min. 18 20 245 74

28

10

54

538

*Terminal For 630/800/1000 C/H/S1, 1250/2500S1 & 2000C/H


D E F E D 64.5 Earthing Terminal 5 15 40 25 65 15 15 60

308.5

308.5

221.5

221.5

308.5

*Terminal for 1250/1600/2500C/H & 800/1000H Ratings CN - CS 630/800/1000A 2000A 1250/1600A 630/800/1000A 2000A 1250/1600A 2000/2500A 2500/3200A 2000/2500A 2500/3200A 3200A 4000A 3200A 4000A
Note : All Dimensions are in mm.

*Terminal for for 3200S1

*Terminal for 3200H0/H1 & 4000H0/H

Dimensions (mm) A C/H/S1 S1 C/H/S1 C/H/S1 S1 C/H/S1 C/H S1 C/H S1 H0/H1 H0/H H0/H1 H0/H 3P 3P 3P 4P 4P 4P 3P 3P 4P 4P 3P 3P 4P 4P 909 151.5 202 202 701 148.5 202 701 122.5 150 156 555 123.5 154 487 96.5 98 98 399 97.5 102 D E F

221.5

68.8

160

256

17

Overall Dimensions

Drawout Breakers
Flat Terminal Connections
50 25 19 12.5 4 slots 8.5 x 9.5 8.5 10.2 58.4 38 4 Slots 8.5 x 9.5 8.5 10.2 58.4 6 Slots 8.5 x 9.5 20 63 25 100 30 30 10.2 58.4 6 Holes-14 68.8 10 199.5 10 5 615 17.5 min 18.9 max. 8.9 min. 18 20 245 54 256 467 46 6 5 74 28 D E F E D 217 8 Holes-14 28 17.5 40 42
64.5

38

8.5

630 - 1000C & 630 - 1250S1


106 33 20 6 Holes-14 43 67 33 12 100

800 - 1000H, 1250/1600C/H & 1600 - 2000S1


106 33 20 6 Holes-14 43 38 62 67 33 12 70 50 25 17.5

2000C
160 25 25 25 25

38

2500C/H & 2000H

2500S1

3200S1

3200H0/H & 4000H0/H1

For 5000C/6300C 3P
for Metallic Components 75 A 124 96.5 264 20 max 102 200 min 400 min for Insulating Sheet
100 min

Isolated Position

51 Test Position Service Position 26

Door

7 Bezel

404

683

50

40

43.5

Earthing Terminal

Terminal Connections 5000C/6300C

63

160

M 10

Ratings A 5000A 6300A 5000A 6300A C 3P C 3P C 4P C 4P 913 913 1182 1182

Dimensions (mm) D 187.5 187.5 187.5 187.5 E 269 269 269 269 F 269 269

Note: All Dimensions are in mm.

18

12.5

25

Overall Dimensions

Mounting Details
For Horizontal Mounting of all Draw-out Breakers
For 630A to 3200A C/H/S1 3P/4P 3200 H0/H1, 4000 H0/H 3P/4P
107.5 367.5 40 10 Holes-11 24

Ratings 800A - 1600A


*G

Type 3P 3P 4P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P C/H S1 C/H S1 C/H C/H S1 S1 H0/H1 H0/H1 H0/H H0/H C C

G (mm) 280.3 280.3 368.3 368.3 436.3 582.3 436.3 582.3 582.3 790.3 582.3 790.3 863 1132

Front

630A - 2000A 800A - 1600A 630A - 2000A

24 64.1

2000/2500A 2000/2500A 2500/3200A

20

481

37

2500/3200A 3200A 3200A

For 5000C/6300C 3P/4P


592 522 10 Holes-11 25

4000A 4000A 5000/6300A 5000/6300A

25

50 108.5 184.5

Bezel Fixing Plan for all Draw-out Breakers


12 Holes-4 Hinge Hinge 305 332

412

224

199

Base of Cradle

5.5

20.5 min

294

5 min

Door Cutout
Note: For 5000C/6300C 3P ACB, A = 81.5 For other Drawout Breakers A = 79.5

450

19

Overall Dimensions

Terminals
Horizontal Terminals
80 80 80 80

Rear Side

10

15

10

308.5

800 - 1000C

1250 - 1600C/H & 800/1000H

2000C

221.5

15

2500C/H & 2000H

2 Holes-14 12.5 15

3 Holes-14 12.5

4 Holes-14 20 12.5 25 33 33 160

6 Holes-14

16.5

12.5

25

12.5

30 12 43

Vertical Terminals
V U 4 Holes-T O P R 40.0 Top S W

387.5

221.5

308.5

25 25 25

63 16.5

100

50

25

Side View Ratings 800/1000A 1250/1600A 800/1000A 2000A 2500A 2000A C C/H H C C/H H M 10.2 20 20 20 N 38 40 40 40 P 20 20 20 20 Q 25 25 40 40 R 29.2 29.2 29.2 33.5

Rear View S 5 5 22.5 7.5 T 9 9 14 14 U 65 65 80 80 V 95 95 110 110 W 10 10 15 15 X 58.4 80 80 80

Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.

20

Switchgear Training Centres

Pune

Lucknow

Coonoor

Train & Gain - This concept underlies L&Ts commitment to its customers and the Indian switchgear industry. To this end, L&T has set up Switchgear Training Centers equipped with a wide range of education facilities at Pune, Lucknow & Coonoor. Specially designed Hands-On training programs on the operation & maintenance of switchgear are conducted for engineers and technicians from different industry segments. The centers have state-of-the-art training facilities, well-equipped workshops and testing systems.

21

Notes

Electrical Standard Products (ESP) Branch Offices:


REGISTERED OFFICE AND HEAD OFFICE L&T House, Ballard Estate P. O. Box 278 Mumbai 400 001 Tel: 022-67525656 Fax: 022-67525858 Website: www.Larsentoubro.com ELECTRICAL STANDARD PRODUCTS (ESP) 501, Sakar Complex I Opp. Gandhigram Rly. Station Ashram Road Ahmedabad 380 009 Tel: 079-66304007-11 Fax: 079-26580491 / 66304025 e-mail: [email protected] 38, Cubbon Road, P. O. Box 5098 Bangalore 560 001 Tel: 080-25020100 Fax: 080-25580525 e-mail: [email protected] 131/1, Zone II Maharana Pratap Nagar Bhopal 462 011 Tel: 0755-4098721 / 7 / 8 / 9 Fax: 0755-2769264 e-mail: [email protected] Plot No. 559, Annapurna Complex Lewis Road Bhubaneswar 751 014 Tel: 0674-6451342, 2436696 Fax: 0674-2537309 e-mail: [email protected] SCO 32, Sector 26-D Madhya Marg, P. O. Box 14 Chandigarh 160 026 Tel: 0172-4646840, 4646853 Fax: 0172-4646802 e-mail: [email protected] 10, Club House Road Chennai 600 002 Tel: 044-28462072 / 4 / 5 / 2109 Fax: 044-28462102 / 3 e-mail: [email protected] 67, Appuswamy Road Post Bag 7156 Opp. Nirmala College Coimbatore 641 045 Tel: 0422-2588120 / 1 / 5 Fax: 0422-2588148 e-mail: [email protected] L&T House, Group MIG-5 Padmanabhpur Durg 491 001 Tel: 0788-2213833 / 14 / 21 / 29 Fax: 0788-2213820 Khairasol, Degaul Avenue Durgapur 713 212 Tel: 2559848, 2559849, 2559844 Fax: 0343-2553614 e-mail: [email protected] Milanpur Road, Bamuni Maidan Guwahati 781 021 Tel: 0361-2550568 Fax: 0361-2551308 e-mail: [email protected] II Floor, Vasantha Chambers 5-10-173, Fateh Maidan Road Hyderabad 500004 Tel: 040-66720250 Fax: 040-23296468 e-mail: [email protected] D-24, Prithvi Raj Road, C-Scheme Jaipur 302 001 Tel: 0141-2385915 / 16 / 17 / 18 Fax: 0141-2373280 e-mail: [email protected] Akashdeep Plaza, 2nd Floor P. O. Golmuri Jamshedpur 831 003 Jharkhand Tel: 0657-2340864 / 387 Fax: 0657-2341250 e-mail: [email protected] Skybright Bldg; M. G. Road Ravipuram Junction, Ernakulam Kochi 682 016 Tel: 0484-4409420 / 4 / 5 / 7 Fax: 0484-4409426 e-mail: [email protected] 3-B, Shakespeare Sarani Kolkata 700 071 Tel: 033-44002572 / 3 / 4 Fax: 033-22822589 e-mail: [email protected] A28, Indira Nagar, Faizabad Road Lucknow 226 016 Tel: 0522-2312904 / 5 / 6 Fax: 0522-2311671 e-mail: [email protected] No: 73, Karpaga Nagar, 8th Street K. Pudur Madurai 625007 Tel: 0452-2537404, 2521068 Fax: 0452-2537552 e-mail: [email protected] EBG North Wing Office-Level 2 Gate 7, Powai Campus Mumbai 400 072 Tel: 022-67052874 / 2737 / 1156 Fax: 022-67051112 e-mail: [email protected] #12, Shivaji Nagar North Ambazari Road Nagpur 440 010 Tel: 0712-2260012 / 3 Fax: 0712-2260020 / 30 e-mail: [email protected] 32, Shivaji Marg P. O. Box 6223 New Delhi 110 015 Tel: 011-41419514 / 5 / 6 Fax: 011-41419600 e-mail: [email protected] L&T House P. O. Box 119 191/1, Dhole Patil Road Pune 411 001 Tel: 020-26135048 Fax: 020-26124910, 26135048 e-mail: [email protected] 3rd Floor Vishwakarma Chambers Majura Gate, Ring Road Surat 395 002 Tel: 0261-2473726 Fax: 0261-2477078 e-mail: [email protected] Radhadaya Complex Old Padra Road Near Charotar Society Vadodara 390 015 Tel: 0265-6613610 / 1 / 2 Fax: 0265-2336184 e-mail: [email protected] 48-8-16, Dwarakanagar Visakhapatnam 530 016 Tel: 0891-6620411-2 / 3 Fax: 0891-6620416 e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products Larsen & Toubro Limited Powai Campus, Mumbai 400 072 Customer Interaction Center (CIC) BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858 Tel : 022 6774 5858 Fax : 022 6774 5859 E-mail : [email protected] Website : www.LNTEBG.com

SP 50437(R2)

270111

You might also like