Sprinkler Identification Numbers (SIN) TY313, TY315, TY323, TY325, TY363, TY365, TY1131, TY1151, TY1231, TY1251,
TY1331, TY2131, TY2231, TY3104, TY3131, TY3133, TY3151, TY3153, TY3187, TY3191, TY3201, TY3230, TY3231, TY3250,
TY3251, TY3291,TY3296, TY3331, TY3332, TY3351, TY3391, TY3431, TY3451, TY3530, TY3535, TY3539, TY3532, TY3537,
TY3550, TY3555, TY3631, TY3651, TY4131, TY4133, TY4151, TY4153, TY4191, TY4231, TY4251, TY4292, TY4232, TY4282,
TY4332, TY4631, TY4651, TY4831, TY4851, TY4931, TY4951, TY5131, TY5137, TY5151, TY5153, TY5231, TY5237, TY5251,
TY5332, TY5337, TY5339, TY5831, TY5851, TY6137, TY6237, TY7103, TY7153, TY8131, TY8151, TY8181, TY8191, TY8231,
TY8151, TY8281, TY8291, TY8331, TY8351, TY9131, TY9151, TY9181, TY9191, TY9231, TY9251, TY9281, TY9291 glass bulb
type.
Sprinkler Identification Numbers (SIN) TY3111, TY3113, TY3211, TY3311, TY4113, TY4211, TY4811 and TY4911 are center
strut type sprinklers. Chrome plated sprinklers are identified by an unplated area where the deflector is staked to the frame
and/or unplated ends of the center strut. Telfon coated sprinklers are identified by the chrome plated operating mechanism.
Sprinkler Identification Numbers (SIN) TY3135, TY3155, TY3230, TY3235, TY3250, TY3255, TY3335, TY3337, TY3339,
TY3355, TY3338, TY3357, TY3358, TY3735, TY3835, TY3935, TY5255, TY5235, TY5238, dry sprinkler glass bulb type.
Sprinkler Identification Numbers (SIN) TY3187, TY4180, TY4181, TY4182, TY2180, TY2181, TY2182 are plain brass glass bulb
type attic sprinklers.
Sprinkler Identification Numbers (SIN) TY3180, TY3181, TY3182, TY3183, TY3184, TY3185, TY3521, TY4522, TY5521,
TY5522, TY9128 are fusible link type sprinklers.
Sprinkler Identification Numbers (SIN) TY1189, TY2189, TY2190, TY3189, TY3190, TY2199, TY3199 are plain brass glass bulb
type quick response sprinklers for concealed spaces.
Sprinkler Identification Numbers (SIN) TY5111, TY5211, TY5811 are center strut type sprinklers.
Sprinkler Identification Numbers (SIN) SA1131, SA1132, SA1151, SA1152 glass bulb type.
TY3251 SR Pendent 250 135, 155, 175, 200, 286, 360, 500
TY3151 SR Upright 250 135, 155, 175, 200, 286, 360, 500
TY4251 SR Pendent 3/4 175 135, 155, 175, 200, 286, 360
TY4951 SR Pendent 1/2, 3/4 175 135, 155, 175, 200, 286, 360
TY4151 SR Upright 3/4 175 135, 155, 175, 200, 286, 360
TY4851 SR Upright 1/2, 3/4 175 135, 155, 175, 200, 286, 360
TY3351+, ++ SR HSW 5.6 250 135, 155, 175, 200, 286, 360
TY3451 SR VSW 5.6 175 135, 155, 175, 200, 286, 360
# The 155°F sprinkler utilizes a 135°F coverplate and the 200°F sprinkler utilizes a 155°F coverplate
System Distance
Max Max Min Working Nom Below
Width Length Flow Pressure, K- Ceiling Temp
SIN Type (A) Ft (B) Ft GPM psig Factor In. Rating, °F
* The 155 or 160°F sprinkler utilizes a 135°F coverplate and the 200 or 212°F sprinkler utilizes a 165°F coverplate.
+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13.
+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13-1999.
TY3351 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3331 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286
TY3351 HSW 5.6 Wax, Wax over lead 135, 155, 175, 200
TY3251 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3231 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286
TY3251 Pendent 5.6 Wax, Wax over lead 135, 155, 175, 200
TY4251 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286, 360
TY4231 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286
TY4251 Pendent 8.0 Wax, Wax over lead 135, 155, 175, 200
TY3153 Upright 5.6 Lead 135, 155, 175, 200, 286, 360
TY3151 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3131 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286
TY3151 Upright 5.6 Wax, Wax over lead 135, 155, 175, 200
TY4153 Upright 8.0 Lead 135, 155, 175, 200, 286, 360
TY4151 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286, 360
TY4131 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286
TY4151 Upright 8.0 Wax, Wax over lead 135, 155, 175, 200
TY3431 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286
TY3451 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
:
TY3451 VSW 5.6 Wax, Wax over lead 135, 155, 175, 200
TY9281 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286
TY8181 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286
TY8281 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286
TY9181 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286
TY8291 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY8191 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY9291 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY9191 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY3230 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286
TY3250 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360
TY3337 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286
TY3357 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286, 360
TY3339 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286
TY8131 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8151 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8231 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8251 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8331 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8351 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360
TY9131 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360
TY9151 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360
TY9231 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360
TY9251 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360
* These sprinklers are available with or without sprinkler guards Models G1 and G4 as covered under File MS26602.
These sprinklers have not been investigated for use as a Control Mode Specific Application (CMSA) sprinkler in accordance
with NFPA 13.
++ For protection of Light Hazard attic spaces of wood truss or open wood joist construction with saddle type roofs in
buildings 20 to 60 ft in width and not exceeding a protection area of 400 sq ft per sprinkler when installed in accordance with
the manufacturer' s installation and design parameter instructions.
Window Sprinklers
Min
Distance Flow
Response Fire Nom Between Rate Temp
SIN Type Risk Type K-Factor Sprinklers, Ft GPM Rating, F
% For use on UL certified FireLite Plus ceramic glass (by Technical Glass Products) without horizontal mullions having a
maximum height of 8 ft. Combustibles are not required to be maintained at any minimum distance from the glass when the
sprinklers are installed in accordance with the manufacturer's installation and design parameter instructions.
Authorities having jurisdiction shall be consulted to determine the hydraulic requirements for each installation.
+ For use in light hazard flat concealed spaces incorporating noncombustible or wood truss construction. The Manufacturers
Installation and Design Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and
hydraulic design requirements.
++ For use in combustible solid wood and composite wood joist construction.
% For use in attic areas outside the scope of application for the BB, SD or HIP sprinklers.
a - For use in combustible solid wood joists with baffle spaced at 2000 Ft2. The Manufacturers Installation and Design
Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and hydraulic design
requirements. The sprinklers can be used with Tyco's Listed LFP antifreeze solution (VDUV) with no limit to the system size.
b- The sprinklers can be used with Tyco's Listed LFP antifreeze solution (VDUV) with no limit to the system size.
Corridor/Hallway Sprinklers
:
SIN Type Max Max Min System Working Nom K- Temp
Width, ft Length, ft Flow, Pressure, psig Factor Rating,
(A) (B) gpm °F
+ For use in corridors and hallways of light hazard occupancies. The Manufacturer's Installation and Design Parameter
Instructions should be consulted for specific installation parameters, obstruction criteria, and hydraulic design requirements.
The appearance of a company's name or product in this database does not in itself assure that products so identified have
been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be
Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions:
1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their
entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from
the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the
reprinted material must include a copyright notice in the following format: "© 2020 UL LLC"
: