VNIV.

EX5985 - Sprinklers, Automatic and Open

Sprinklers, Automatic and Open


See General Information for Sprinklers, Automatic and Open

TYCO FIRE & BUILDING PRODUCTS EX5985


1400 PENNBROOK PKWY
LANSDALE, PA 19446-3840 USA
Sprinkler Identification Numbers (SIN) TY1121, TY1221, TY1281, TY1282, TY1381, TY1382, TY3101, TY3103, TY3121,
TY3123, TY3210, TY3221, TY3281, TY3282, TY3290, TY3301, TY3321, TY3322, TY3381, TY3382, TY3390, TY4101, TY4103,
TY4121, TY4123, TY4210, TY4321, TY4322, TY4801, TY4910, TY9128 Fusible Element Type.

Sprinkler Identification Numbers (SIN) TY313, TY315, TY323, TY325, TY363, TY365, TY1131, TY1151, TY1231, TY1251,
TY1331, TY2131, TY2231, TY3104, TY3131, TY3133, TY3151, TY3153, TY3187, TY3191, TY3201, TY3230, TY3231, TY3250,
TY3251, TY3291,TY3296, TY3331, TY3332, TY3351, TY3391, TY3431, TY3451, TY3530, TY3535, TY3539, TY3532, TY3537,
TY3550, TY3555, TY3631, TY3651, TY4131, TY4133, TY4151, TY4153, TY4191, TY4231, TY4251, TY4292, TY4232, TY4282,
TY4332, TY4631, TY4651, TY4831, TY4851, TY4931, TY4951, TY5131, TY5137, TY5151, TY5153, TY5231, TY5237, TY5251,
TY5332, TY5337, TY5339, TY5831, TY5851, TY6137, TY6237, TY7103, TY7153, TY8131, TY8151, TY8181, TY8191, TY8231,
TY8151, TY8281, TY8291, TY8331, TY8351, TY9131, TY9151, TY9181, TY9191, TY9231, TY9251, TY9281, TY9291 glass bulb
type.

Sprinkler Identification Numbers (SIN) TY3111, TY3113, TY3211, TY3311, TY4113, TY4211, TY4811 and TY4911 are center
strut type sprinklers. Chrome plated sprinklers are identified by an unplated area where the deflector is staked to the frame
and/or unplated ends of the center strut. Telfon coated sprinklers are identified by the chrome plated operating mechanism.

Sprinkler Identification Numbers (SIN) TY3135, TY3155, TY3230, TY3235, TY3250, TY3255, TY3335, TY3337, TY3339,
TY3355, TY3338, TY3357, TY3358, TY3735, TY3835, TY3935, TY5255, TY5235, TY5238, dry sprinkler glass bulb type.

Sprinkler Identification Numbers (SIN) TY3187, TY4180, TY4181, TY4182, TY2180, TY2181, TY2182 are plain brass glass bulb
type attic sprinklers.

Sprinkler Identification Numbers (SIN) TY3180, TY3181, TY3182, TY3183, TY3184, TY3185, TY3521, TY4522, TY5521,
TY5522, TY9128 are fusible link type sprinklers.

Sprinkler Identification Numbers (SIN) TY1189, TY2189, TY2190, TY3189, TY3190, TY2199, TY3199 are plain brass glass bulb
type quick response sprinklers for concealed spaces.

Sprinkler Identification Numbers (SIN) TY5111, TY5211, TY5811 are center strut type sprinklers.

Sprinkler Identification Numbers (SIN) SA1131, SA1132, SA1151, SA1152 glass bulb type.

UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS


NOMINAL 5.6 K-FACTOR
Response System Working
SIN Type Type Pressure, psig Temp Rating, °F

TY313 QR Upright 250 135, 155, 175, 200, 286

TY315 SR Upright 250 135, 155, 175, 200, 286, 360


:
TY323 QR Pendent 250 135, 155, 175, 200, 286

TY325 SR Pendent 250 135, 155, 175, 200, 286, 360

TY3231 QR Pendent 250 135, 155, 175, 200, 286

TY3201 QR Pendent 175 135, 155, 175, 200, 286

TY3221 QR Pendent, Rec. Pendent 175 165, 212

TY3131 QR Upright 250 135, 155, 175, 200, 286

TY3121 QR Upright 175 165, 212

TY3211 SR Pendent 175 135, 165, 212, 280, 360, 500

TY3251 SR Pendent 250 135, 155, 175, 200, 286, 360, 500

TY3111 SR Upright 175 135, 165, 212, 286, 360

TY3151 SR Upright 250 135, 155, 175, 200, 286, 360, 500

TY3101 SR Upright 175 135,165,212,280,360

TY3210 SR Pendent 175 135,165,212,280,360

SA1131 QR Pendent 175 155, 175, 200, 286

SA1132 QR Upright 175 155, 175, 200, 286

SA1151 SR Pendent 175 155, 175, 200, 286

SA1152 SR Upright 175 155, 175, 200, 286

TY3296 SR Pendent 175 400, 500

TY3191 SR Upright 175 400, 500

TY8131 QR Upright 250 135, 155, 175, 200, 286, 360

TY8151 SR Upright 250 135, 155, 175, 200, 286, 360

TY8231 QR Pendent 250 135, 155, 175, 200, 286, 360

TY8251 SR Pendent 250 135, 155, 175, 200, 286, 360

TY8331 QR HSW 250 135, 155, 175, 200, 286, 360

TY8351 SR HSW 250 135, 155, 175, 200, 286, 360

TY9131 QR Upright 250 135, 155, 175, 200, 286, 360

TY9151 SR Upright 250 135, 155, 175, 200, 286, 360

TY9231 QR Pendent 250 135, 155, 175, 200, 286, 360

TY9251 SR Pendent 250 135, 155, 175, 200, 286, 360


:
NOMINAL 1.4 TO 4.2 K-FACTOR
Nom System
Response K- Working
SIN Type Type Factor Pressure, psig Temp Rating, °F

TY1231 QR Pendent 2.8 175 135, 155, 175, 200, 286

TY2231 QR Pendent 4.2 175 135, 155, 175, 200, 286

TY1221 QR Pendent, Rec. 2.8 175 165, 212


Pendent

TY1131 QR Upright 2.8 175 135, 155, 175, 200, 286

TY1121 QR Upright 2.8 175 165, 212

TY2131 QR Upright 4.2 175 135, 155, 175, 200, 286

TY1251 SR Pendent 2.8 175 135, 155, 175, 200, 286,


360

TY1151 SR Upright 2.8 175 135, 155, 175, 200, 286,


360

NOMINAL 8.0 K-FACTOR


Response Inlet System Working
SIN Type Type Thread NPT Pressure, psig Temp Rating, °F

TY4231 QR Pendent 3/4 175 135, 155, 175, 200, 286

TY4131 QR Upright 3/4 175 135, 155, 175, 200, 286

TY4121 QR Upright 3/4 175 165, 212

TY4221 QR Pendent 3/4 175 165, 212

TY4911 SR Pendent 1/2 175 135, 165, 212, 286, 360

TY4211 SR Pendent 3/4 175 135, 165, 212, 280, 286

TY4251 SR Pendent 3/4 175 135, 155, 175, 200, 286, 360

TY4951 SR Pendent 1/2, 3/4 175 135, 155, 175, 200, 286, 360

TY4811 SR Upright 1/2 175 135, 165, 212, 280, 360

TY4111 SR Upright 3/4 175 135, 165, 212, 280, 360

TY4151 SR Upright 3/4 175 135, 155, 175, 200, 286, 360

TY4831 QR Upright 1/2 175 135, 155, 175, 200, 286

TY4851 SR Upright 1/2, 3/4 175 135, 155, 175, 200, 286, 360

TY4931 QR Pendent 1/2 175 135, 155, 175, 200, 286


:
TY4101 SR Upright 3/4 175 135, 165, 212, 280, 360

TY4801 SR Upright 1/2 175 135, 165, 212, 280, 360

TY4210 SR Upright 3/4 175 135, 165, 212, 280, 360

TY4910 SR Upright 1/2 175 135, 165, 212, 280, 360

TY4292 SR Pendent 3/4 175 400, 500

TY4191 SR Upright 3/4 175 400, 500

STANDARD SIDEWALL SPRAY SPRINKLERS


Response Nom System Working
SIN Type Type K-Factor Pressure, psig Temp Rating, °F

TY1381+, ++ QR Flush HSW 5.6 175 165

TY3331+, ++ QR HSW 5.6 250 135, 155, 175, 200, 286

TY3321 QR HSW 5.6 175 165, 212

TY3331+, ++ QR Rec. HSW 5.6 250 135, 155, 175, 200

TY3431 QR VSW 5.6 175 135, 155, 175, 200, 286

TY3311 SR HSW 5.6 175 135, 165, 212, 280, 360

TY3351+, ++ SR HSW 5.6 250 135, 155, 175, 200, 286, 360

TY3351+, ++ SR Rec. HSW 5.6 250 135, 155, 175, 200

TY3381+, ++ QR Flush HSW 5.6 175 165

TY3390+, ++ SR Flush HSW 5.6 175 140

TY3390 SR Flush HSW 5.6 175 165

TY3391+, ++ QR Flush HSW 5.6 175 135, 155, 175, 200

TY3451 SR VSW 5.6 175 135, 155, 175, 200, 286, 360

TY3301 SR HSW 5.6 175 135, 165, 212, 280, 360

+ Ordinary hazard occupancies.

++ Installation 4 to 12 in. below the ceiling.

FLUSH, RECESSED AND CONCEALED SPRINKLERS

Nom System Temp Rating, °F


Response K- Working
SIN Type Type Factor Pressure, psig Cover Sprinkler
:
TY1281 QR Flush Pendent 5.6 175 — 165

TY323 QR Rec. Pendent 5.6 250 — 135, 155, 175, 200

TY325 SR Rec. Pendent 5.6 250 — 135, 155, 175, 200

TY3531 QR Concealed 5.6 250 139, 155, 200


165

TY3281 QR Flush Pendent 5.6 175 — 165

TY3291 QR Flush Pendent 5.6 175 — 135, 155, 175, 200

TY1231 QR Rec. Pendent 2.8 175 — 135, 155, 175, 200

TY3201 QR Rec. Pendent 5.6 175 — 135, 155, 175, 200

TY3231 QR Rec. Pendent 5.6 250 — 135, 155, 175, 200,


286

TY4231 QR Rec. Pendent 8.0 175 — 135, 155, 175, 200,


286

TY3290 SR Flush Pendent 5.6 175 — 140, 165, 212

TY3390 SR Flush HSW 5.6 175 — 140, 165

TY1251 SR Rec. Pendent 2.8 175 — 135, 155, 175, 200

TY3211 SR Rec. Pendent 5.6 175 — 135, 165, 212, 280,


360

TY3251 SR Rec. Pendent 5.6 250 — 135, 155, 175, 200,


286

TY4211 SR Rec. Pendent 8.0 175 — 135, 165, 212, 280,


360

TY4951 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200

TY4251 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200,


286

TY3551 SR Concealed 5.6 250 139, 155, 200


165

TY5521 QR Concealed 11.2 175 139, 160, 212


Pendent 165

TY3530 QR Concealed 5.6 175 139, 155, 200


Pendent 165

TY3550 SR Concealed 5.6 175 139, 155, 200


Pendent 165

TY3521 QR Concealed HSW 5.6 250 139, 160, 212


165
:
DRY SPRINKLERS
System
Max Working
Response Length, Pressure, Nom K- Temp Rating,
SIN Type Type in. psig Factor F

TY3535# QR Concealed 48 175 5.6 155, 200

TY3335* QR HSW 48 175 5.6 135, 155, 175, 200,


286

TY3235 QR Pendent 48 175 5.6 135, 155, 175, 200,


286

TY5235 QR Pendent 48 175 11.2 135, 155, 175, 200,


286

TY3235 QR Rec. Pendent 48 175 5.6 135, 155, 175, 200,


286

TY5235 QR Rec. Pendent 48 175 11.2 135, 155, 175, 200,


286

TY3135# QR Upright 48 175 5.6 135, 155, 175, 200,


286

TY3555 SR Concealed 48 175 5.6 155, 200

TY3355* SR HSW 48 175 5.6 135, 155, 175, 200,


286, 360

TY3255 SR Pendent 48 175 5.6 135, 155, 175, 200,


286, 360

TY5255 SR Pendent 48 175 11.2 135, 155, 175, 200,


286, 360

TY3255 SR Rec. Pendent 48 175 5.6 135, 155, 175, 200,


286

TY5255 SR Rec. Pendent 48 175 11.2 135, 155, 175, 200,


286

TY3155 SR Upright 48 175 5.6 135, 155, 175, 200,


286, 360

TY3230 QR Pendent, Rec. 48 175 5.6 135, 155, 175, 200,


Pendent 286

TY3250 SR Pendent 48 175 5.6 135, 155, 175, 200,


286, 360

TY3250 SR Rec. Pendent 48 175 5.6 135, 155, 175, 200,


286
:
TY3337 QR Pendent, Rec. 48 175 5.6 135, 155, 175, 200,
Pendent 286

TY3357* SR HSW 48 175 5.6 135, 155, 175, 200,


286, 360

TY3357* SR Rec. HSW 48 175 5.6 135, 155, 175, 200,


286

TY3735+ QR HSW 48 175 5.6 135, 155, 175, 200,


286

TY3835+ QR Upright 48 175 5.6 135, 155, 175, 200,


286

TY3935+ QR Pendent 48 175 5.6 135, 155, 175, 200,


286

TY3935+ QR Rec. Pendent 48 175 5.6 135, 155, 175, 200,


286

* For ordinary hazard occupancies when installed 4 to 12 in. below ceiling.

# The 155°F sprinkler utilizes a 135°F coverplate and the 200°F sprinkler utilizes a 155°F coverplate

+ 3/4 in. NPT

CONVENTIONAL (OLD STYLE) SPRINKLERS


Response Nom
SIN Type K-Factor Temp Rating, °F

TY363 QR 5.6 135, 155, 175, 200, 286

TY365 SR 5.6 135, 155, 175, 200, 286

TY3631 QR 5.6 135, 155, 175, 200, 286

TY4631 QR 8.0 135, 155, 175, 200, 286

TY3651 SR 5.6 135, 155, 175, 200, 286, 360, 500

TY4651 SR 8.0 135, 155, 175, 200, 286, 360

STANDARD RESPONSE - (SR) - EXTENDED COVERAGE SPRINKLER -


LIGHT HAZARD
Max Max Min Distance
Width Length Flow Nom Below
SIN Type (A) Ft (B) Ft GPM K-Factor Ceiling In. Temp Rating, °F

TY3302 HSW, Rec. HSW 16 18 29 5.6 4 to 12 155, 200

TY3302 HSW, Rec. HSW 16 20 32 5.6 4 to 12 155, 200

TY3302 HSW 16 24 39 5.6 4 to 18 135


:
TY3332 HSW, Rec. HSW 16 20 32 5.6 4 to 6 155

TY3332 HSW, Rec. HSW 16 22 35 5.6 4 to 6 155, 175

TY4322 HSW 16 22 37 8.0 4 to 6 165

TY4322 HSW 16 24 44 8.0 4 to 6 165

TY4322 HSW 16 20 45 8.0 4 to 18 165

TY4332 HSW, Rec. HSW 16 20 33 8.0 4 to 12 135

TY4332 HSW, Rec. HSW 16 22 35 8.0 4 to 6 155, 175

TY4332 HSW, Rec. HSW 16 22 36 8.0 4 to 12 155, 175

TY4332 HSW, Rec. HSW 16 24 39 8.0 4 to 6 155, 175

TY4332 HSW, Rec. HSW 16 24 40 8.0 4 to 12 155, 175

TY3232 Pendent, Rec. pendent 20 20 40 5.6 — 155

TY5522* Concealed Pendent 20 20 40 11.2 — 160, 212

Dimension of wall on which a sidewall sprinkler is installed.

(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.

* Utilizes A 135 or 165°F Coverplate.

QUICK RESPONSE - (QR) - EXTENDED COVERAGE SPRINKLERS -


LIGHT HAZARD

System Distance
Max Max Min Working Nom Below
Width Length Flow Pressure, K- Ceiling Temp
SIN Type (A) Ft (B) Ft GPM psig Factor In. Rating, °F

TY1282 Flush Pendent 16 16 26 175 5.6 — 165

TY1382 Flush HSW 16 16 26 175 5.6 4 to 12 165

TY3232 Pendent, Rec. 16 16 26 175 5.6 — 135, 155


pendent

TY3232 Pendent, Rec. 18 18 33 175 5.6 — 135, 155


pendent

TY3232 Pendent, Rec. 20 20 40 175 5.6 — 135


pendent

TY3282 Flush Pendent 16 16 26 175 5.6 — 165

TY3382 Flush HSW 16 16 26 175 5.6 4 to 12 165

TY6237 Pendent 18 18 37 175 14.0 — 135, 155,


:
175, 200,
286

TY6237 Pendent 20 20 40 175 14.0 — 135, 155,


175, 200,
286

TY6237 Rec. Pendent 18 18 37 175 14.0 — 135, 155,


175, 200

TY6237 Rec. Pendent 20 20 40 175 14.0 — 135, 155,


175, 200

TY5237 Pendent, Rec. 16 16 30 175 11.2 — 135, 155,


pendent 175, 200,
286

TY5237 Pendent, Rec. 18 18 33 175 11.2 — 135, 155,


pendent 175, 200,
286

TY5237 Pendent 20 20 40 175 11.2 — 135, 155,


175

TY5237 Rec. pendent 20 20 40 175 11.2 — 135, 175

TY3532* Concealed 16 16 26 175 5.6 — 155, 200

TY3532* Concealed 20 20 40 175 5.6 — 155, 200

TY3532* Concealed 18 18 33 175 5.6 — 155, 200

TY3537* Concealed 16 16 26 175 5.6 — 155, 200

TY3537* Concealed 20 20 40 175 5.6 — 155, 200

TY3537* Concealed 18 18 33 175 5.6 — 155, 200

TY4232 Pendent, Rec. 16 16 26 175 8.0 — 135


Pendent

TY4232 Pendent 16 16 26 175 8.0 — 155

TY4232 Pendent, Rec. 18 18 33 175 8.0 — 135


Pendent

TY4232 Pendent 18 18 33 175 8.0 — 155

TY4232 Pendent, Rec. 20 20 40 175 8.0 — 135


Pendent

TY4232 Pendent 20 20 40 175 8.0 — 155

TY4332+ Concealed HSW 16 16 26 250 8.0 4 to12 155

TY3539* Dry Concealed 16 16 26 175 175 — 155, 200


:
TY3539* Dry Concealed 18 18 33 175 175 — 155, 200

TY3302 HSW, Rec. HSW 16 16 26 175 5.6 4 to 12 200

TY3302 HSW, Rec. HSW 16 16 26 175 5.6 4 to 18 135, 155

TY3302 HSW, Rec. HSW 16 18 29 175 5.6 4 to 18 135, 155

TY3302 HSW, Rec. HSW 16 20 32 175 5.6 4 to 18 135, 155

TY3302 HSW 16 22 36 175 5.6 4 to 18 135

TY3338, Dry HSW 16 16 26 175 5.6 4 to 12 135, 155


TY3339

TY3338, Dry HSW 16 18 29 175 5.6 4 to 12 135, 155


TY3339

TY3338, Dry HSW 18 16 29 175 5.6 4 to 12 135, 155


TY3339

TY3338, Dry HSW 16 20 32 175 5.6 4 to 12 135, 155


TY3339

TY3358 Dry HSW 16 16 26 175 5.6 4 to 12 135, 155

TY3358 Dry HSW 16 18 29 175 5.6 4 to 12 135, 155

TY3358 Dry HSW 16 20 32 175 5.6 4 to 12 135, 155

TY3358 Dry HSW 18 16 29 175 5.6 4 to 12 135, 155

TY5238 Dry Pendent 18 18 33 175 11.2 — 135, 155,


175, 200

TY5238 Dry Pendent, Rec. 16 16 30 175 11.2 — 135, 155,


Pendent 175, 200

TY3322 HSW 16 16 29 175 5.6 4 to 12 165

TY3322 HSW 18 16 29 175 5.6 4 to 12 165

TY3322 HSW 16 20 33 175 5.6 4 to 12 165

TY4322 HSW 16 16 26 175 8.0 4 to 6 165

TY4322 HSW 16 18 29 175 8.0 4 to 6 165

TY4322 HSW 18 16 31 175 8.0 4 to 6 165

TY4322 HSW 18 18 33 175 8.0 4 to 6 165

TY4322 HSW 16 20 34 175 8.0 4 to 6 165

TY4322 HSW 20 16 35 175 8.0 4 to 6 165

TY4322 HSW 16 22 37 175 8.0 4 to 6 165


:
TY4322 HSW 16 18 38 175 8.0 4 to 18 165

TY3332 HSW, Rec. HSW 16 16 26 250 5.6 4 to 12 135, 155,


175

TY3332 HSW, Rec. HSW 16 18 29 250 5.6 4 to 12 135, 155,


175

TY3332 HSW, Rec. HSW 16 20 32 250 5.6 4 to 6 135, 155,


175

TY3332 HSW, Rec. HSW 16 22 35 250 5.6 4 to 6 135

TY4332 HSW, Rec. HSW 16 16 26 250 8.0 4 to 12 135, 155,


175

TY4332 HSW, Rec. HSW 16 18 29 250 8.0 4 to 12 135, 155,


175

TY4332 HSW, Rec. HSW 16 20 32 250 8.0 4 to 6 135

TY4332 HSW, Rec. HSW 16 20 33 250 8.0 4 to 12 135

TY4332 HSW, Rec. HSW 16 22 35 250 8.0 4 to 6 135

TY4332 HSW, Rec. HSW 16 22 36 250 8.0 4 to 12 135

TY4332 HSW, Rec. HSW 16 24 39 250 8.0 4 to 6 135

TY4332 HSW, Rec. HSW 16 24 40 250 8.0 4 to 12 135

TY4522+ Concealed HSW 14 22 31 175 8.0 4 to 6 160

TY4522+ Concealed HSW 14 22 36 175 8.0 6 to 12 160

TY4522+ Concealed HSW 14 24 34 175 8.0 4 to 6 160

TY4522+ Concealed HSW 14 24 38 175 8.0 6 to 12 160

TY4522+ Concealed HSW 16 16 26 175 8.0 4 to 6 160

TY4522+ Concealed HSW 16 16 27 175 8.0 6 to 12 160

TY4522+ Concealed HSW 16 18 29 175 8.0 4 to 12 160

TY4522+ Concealed HSW 16 20 32 175 8.0 4 to 12 160

TY4522+ Concealed HSW 16 22 36 175 8.0 4 to 12 160

TY4522+ Concealed HSW 16 24 39 175 8.0 4 to 12 160

TY4522+ Concealed HSW 18 18 33 175 8.0 4 to 12 160

TY4522+ Concealed HSW 18 20 36 175 8.0 4 to 12 160

TY4522+ Concealed HSW 18 22 40 175 8.0 4 to 12 160

TY5522* Concealed Pendent 16 16 30 175 11.2 — 160, 212


:
TY5522* Concealed Pendent 18 18 33 175 11.2 — 160, 212

* The 155 or 160°F sprinkler utilizes a 135°F coverplate and the 200 or 212°F sprinkler utilizes a 165°F coverplate.

+ Utilizes a 135°F coverplate.

Dimension of wall on which a sidewall sprinkler is installed.

(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.

STANDARD RESPONSE - (SR) - EXTENDED COVERAGE SPRINKLERS -


ORDINARY HAZARD
Ordinary
Max Width x Hazard Min Sprinkler Nom K- Temp Rating
SIN Type Length FtxFt Group Flow Rate GPM Factor °F

TY5332 HSW 16x16 1 38 11.2 155, 200

TY5332 HSW 16x16 2 51 11.2 155, 200

TY5332 HSW 16x18 1 43 11.2 155, 200

TY5332 HSW 16x18 2 58 11.2 155, 200

TY5332 HSW 16x20 1 48 11.2 155, 200

TY5332 HSW 16x20 2 64 11.2 155, 200

TY5337 HSW 16x22 1 53 11.2 200

TY5337 HSW 16x22 2 71 11.2 200

TY5337 HSW 16x24 1 58 11.2 200

TY5337 HSW 16x24 2 77 11.2 200

TY5339 Dry HSW 16x16 1 38 11.2 155, 200

TY5339 Dry HSW 16x16 2 51 11.2 155, 200

TY5339 Dry HSW 16x18 1 43 11.2 155, 200

TY5339 Dry HSW 16x18 2 58 11.2 155, 200

TY5339 Dry HSW 16x20 1 48 11.2 155, 200

TY5339 Dry HSW 16x20 2 64 11.2 155, 200

TY5237+ Pendent, 16x16 1 39 11.2 135, 155,


Rec. 175, 200,
Pendent 286

TY5237+ Pendent, 16x16 2 51 11.2 135, 155,


Rec. 175, 200,
Pendent 286
:
TY5238 Pendent, 16x16 1 39 11.2 155, 175,
Rec. 200, 286
Pendent

TY5238+ Pendent, 16x16 2 51 11.2 155, 175,


Rec. 200, 286
Pendent

TY5237+ Pendent, 18x18 1 49 11.2 135, 155,


Rec. 175, 200,
Pendent 286

TY5237+ Pendent, 18x18 2 65 11.2 135, 155,


Rec. 175, 200,
Pendent 286

TY5237+ Pendent, 20x20 1 60 11.2 135, 155,


Rec. 175, 200,
Pendent 286

TY5237+ Pendent, 20x20 2 80 11.2 135, 155,


Rec. 175, 200,
Pendent 286

TY6237+ Pendent, 16x16 1 39 14.5 135, 155,


Rec. 175, 200,
Pendent 286

TY6237+ Pendent, 16x16 2 51 14.0 135, 155,


Rec. 175, 200,
Pendent 286

TY6237+ Pendent, 18x18 1 49 14.0 135, 155,


Rec. 175, 200,
Pendent 286

TY6237+ Pendent, 18x18 2 65 14.0 135, 155,


Rec. 175, 200,
Pendent 286

TY6237+ Pendent, 20x20 1 60 14.0 135, 155,


Rec. 175, 200,
Pendent 286

TY6237+ Pendent, 20x20 2 80 14.0 135, 155,


Rec. 175, 200,
Pendent 286

TY5137+ Upright 16x16 1 39 11.2 135, 155,


175, 200,
286

TY5137+ Upright 16x16 2 51 11.2 135, 155,


175, 200,
286
:
TY5137+ Upright 18x18 1 49 11.2 135, 155,
175, 200,
286

TY5137+ Upright 18x18 2 65 11.2 135, 155,


175, 200,
286

TY5137+ Upright 20x20 1 60 11.2 135, 155,


175, 200,
286

TY5137+ Upright 20x20 2 80 11.2 135, 155,


175, 200,
286

TY6137+ Upright 16x16 1 39 14.5 135, 155,


175, 200,
286

TY6137+ Upright 16x16 2 51 14.5 135, 155,


175, 200,
286

TY6137+ Upright 18x18 1 49 14.5 135, 155,


175, 200,
286

TY6137+ Upright 18x18 2 65 14.5 135, 155,


175, 200,
286

TY6137+ Upright 20x20 1 60 14.5 135, 155,


175, 200,
286

TY6137+ Upright 20x20 2 80 14.5 135, 155,


175, 200,
286

+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13.

QUICK RESPONSE (QR) - EXTENDED COVERAGE SPRINKLERS -


ORDINARY HAZARD
Min
Max Sprinkler
Width x Ordinary Flow Temp
Length Hazard Rate Nom Rating,
SIN Type Ft x Ft Group GPM K- °F
Factor

TY5137 Upright 14 x 1 30 11.2 135, 155, 175, 200,


14 286
:
TY5137 Upright 14 x 2 39 11.2 135, 155, 175, 200,
14 286

TY5237+ Pendent, Rec. 14 x 1 30 11.2 135, 155, 175, 200,


Pendent 14 286

TY5237+ Pendent, Rec. 14 x 2 39 11.2 135, 155, 175, 200,


Pendent 14 286

TY5238 Pendent, Rec. 14 x 1 30 11.2 135, 155, 175, 200,


Pendent 14 286

TY5238 Pendent, Rec. 14 x 2 39 11.2 135, 155, 175, 200,


Pendent 14 286

TY6137 Upright 14 x 1 39 14.0 135, 155, 175, 200,


14 286

TY6137 Upright 14 x 2 51 14.0 135, 155, 175, 200,


14 286

TY6237 Pendent 14 x 1 39 14.0 135, 155, 175, 200,


14 286

TY6237 Pendent 14 x 2 51 14.0 135, 155, 175, 200,


14 286

TY6237 Rec. Pendent 14 x 1 39 14.0 135, 155, 175, 200


14

TY6237 Rec. Pendent 14 x 2 51 14.0 135, 155, 175, 200


14

+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13-1999.

CORROSION RESISTANT SPRINKLERS


Nom Coating
SIN Type K-Factor Type Temp Rating, °F

TY313 Upright 5.6 Polyester 135, 155, 175, 200, 286

TY323 Pendent 5.6 Polyester 135, 155, 175, 200, 286

TY315 Upright 5.6 Polyester 135, 155, 175, 200, 286

TY325 Pendent 5.6 Polyester 135, 155, 175, 200, 286

TY363 Conventional 5.6 Polyester 135, 155, 175, 200, 286

TY365 Conventional 5.6 Polyester 135, 155, 175, 200, 286

TY3631 Conventional 5.6 Polyester 135, 155, 175, 200 ,286

TY4631 Conventional 8.0 Polyester 135, 155, 175, 200, 286


:
TY3311 HSW 5.6 Lead 165, 212

TY3332 HSW 5.6 Polyester 135, 155, 175

TY4332 HSW 8.0 Polyester 135, 155, 175

TY3351 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3331 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3311 HSW 5.6 Wax 165, 212

TY3311 HSW 5.6 Wax over lead 165, 212

TY3351 HSW 5.6 Wax, Wax over lead 135, 155, 175, 200

TY5332 HSW 11.2 Polyester 155, 200

TY5337 HSW 11.2 Polyester 155, 200

TY5131 Upright 11.2 Polyester 155, 200, 250, 286

TY5231 Pendent 11.2 Polyester 155, 200, 250, 286

TY3211 Pendent 5.6 Lead 165, 212

TY3251 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3231 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3211 Pendent 5.6 Wax 165, 212

TY3211 Pendent 5.6 Wax over lead 165, 212

TY3251 Pendent 5.6 Wax, Wax over lead 135, 155, 175, 200

TY4911 Pendent 8.0 Lead 165, 212

TY4211 Pendent 8.0 Lead 165, 212

TY4251 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286, 360

TY4231 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286

TY4911 Pendent 8.0 Wax 165, 212

TY4211 Pendent 8.0 Wax 165, 212

TY4911 Pendent 8.0 Wax over lead 165, 212

TY4211 Pendent 8.0 Wax over lead 165, 212

TY4251 Pendent 8.0 Wax, Wax over lead 135, 155, 175, 200

TY5237 Pendent 11.2 Lead 135, 155, 175, 200, 286

TY5237 Pendent 11.2 Polyester 135, 155, 175, 200, 286


:
TY6237 Pendent 14 Lead 135, 155, 175, 200, 286

TY6237 Pendent 14 Polyester 135, 155, 175, 200, 286

TY7251 Pendent 16.8 Polyester 155, 200, 286

TY3111 Upright 5.6 Lead 165, 212

TY3133 Upright 5.6 Lead 135, 155, 175, 200, 286

TY3153 Upright 5.6 Lead 135, 155, 175, 200, 286, 360

TY3151 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3131 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3111 Upright 5.6 Wax 165, 212

TY3111 Upright 5.6 Wax over lead 165, 212

TY3151 Upright 5.6 Wax, Wax over lead 135, 155, 175, 200

TY4811 Upright 8.0 Lead 165, 212

TY4111 Upright 8.0 Lead 165, 212

TY4133 Upright 8.0 Lead 135, 155, 175, 200, 286

TY4153 Upright 8.0 Lead 135, 155, 175, 200, 286, 360

TY4151 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286, 360

TY4131 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286

TY4811 Upright 8.0 Wax 165, 212

TY4111 Upright 8.0 Wax 165, 212

TY4811 Upright 8.0 Wax over lead 165, 212

TY4111 Upright 8.0 Wax over lead 165, 212

TY4151 Upright 8.0 Wax, Wax over lead 135, 155, 175, 200

TY5137 Upright 11.2 Lead 135, 155, 175, 200, 286

TY5137 Upright 11.2 Polyester 135, 155, 175, 200, 286

TY6137 Upright 14 Lead 135, 155, 175, 200, 286

TY6137 Upright 14 Polyester 135, 155, 175, 200, 286

TY7151 Upright 16.8 Polyester 155, 200, 286

TY3431 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3451 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
:
TY3451 VSW 5.6 Wax, Wax over lead 135, 155, 175, 200

TY9281 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286

TY8181 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286

TY8281 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286

TY9181 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286

TY8291 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY8191 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY9291 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY9191 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY3230 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286

TY3250 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360

TY3337 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286

TY3357 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286, 360

TY3339 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286

TY3296 Pendent 5.6 Lead 400, 500

TY4292 Pendent 8.0 Lead 400, 500

TY3191 Upright 5.6 Lead 400, 500

TY4191 Upright 8.0 Lead 400, 500

TY8131 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8151 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8231 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8251 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8331 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8351 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360

TY9131 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360

TY9151 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360

TY9231 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360

TY9251 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360

HIGH TEMPERATURE, WAX COATED SPRINKLERS


:
Max Sprinkler
Nom Ambient Temp
SIN Type K-Factor Temp, F Rating, F

TY3351 HSW 8.0 150 286

TY4251 Pendent 8.0 150 286

TY3251 Pendent 8.0 150 286

TY4151 Upright 8.0 150 286

TY3151 Upright 8.0 150 286

TY3451 VSW 8.0 150 286

TY9281 Pendent 8.0 150 286

TY8181 Upright 5.6 150 286

TY8281 Pendent 5.6 150 286

TY9181 Upright 8.0 150 286

TY8291 Pendent 5.6 150 286

TY8191 Upright 5.6 150 286

TY9291 Pendent 8.0 150 286

TY9191 Upright 8.0 150 286

INTERMEDIATE LEVEL SPRINKLERS


Response Nom
SIN* Type Type K-Factor Temp Rating, °F

TY313 QR Upright 5.6 135, 155, 175, 200, 286

TY315 SR Upright 5.6 135, 155, 175, 200, 286

TY323 QR Pendent 5.6 135, 155, 175, 200, 286

TY325 SR Pendent 5.6 135, 155, 175, 200, 286

TY3231 QR Pendent 5.6 135, 155, 175, 200, 286

TY3221 QR Pendent 5.6 165

TY4231 QR Pendent 8.0 135, 155, 175, 200, 286

TY4221 QR Pendent 8.0 165

TY3133 QR Upright 5.6 135, 155, 175, 200, 286

TY3123 QR Upright 5.6 165


:
TY4133 QR Upright 8.0 135, 155, 175, 200, 286

TY4123 QR Upright 8.0 165

TY3251 SR Pendent 5.6 135, 155, 175, 200, 286, 360

TY4251 SR Pendent 8.0 135, 155, 175, 200, 286, 360

TY3113 SR Upright 5.6 135, 165, 212, 280, 360

TY3153 SR Upright 5.6 135, 155, 175, 200, 286, 360

TY4111 SR Upright 8.0 135, 165, 212, 280, 360

TY4113 SR Upright 8.0 135, 165, 212, 280, 360

TY4153 SR Upright 8.0 135, 155, 175, 200, 286, 360

TY4211 SR Upright 8.0 135, 165, 212, 280, 360

TY4210 SR Pendent 8.0 135, 165, 212, 280, 360

TY3210 SR Pendent 5.6 135, 165, 212, 280, 360

TY3211 SR Pendent 5.6 135, 165, 212, 280, 360

TY3103 SR Upright 5.6 135, 165, 212, 280, 360

TY4103 SR Upright 8.0 135, 165, 212, 280, 360

* These sprinklers are available with or without sprinkler guards Models G1 and G4 as covered under File MS26602.

SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY


AREA)
Response Nom
SIN Type Type K-Factor Temp Rating, °F

TY5231 QR Pendent 11.2 155, 200, 286

TY5131 QR Upright 11.2 155, 200, 286

TY5111 SR Upright 11.2 165, 212, 286

TY5211 SR Pendent 11.2 165, 212, 286

TY5151 SR Upright 11.2 155, 200, 286

TY5831A QR Upright 11.2 155, 200

TY5851 SR Upright 11.2 155, 200, 286

TY5251 SR Rec. Pendent, Pendent 11.2 155, 200, 286

TY7151 SR Upright 16.8 155, 200, 286

TY7251 SR Pendent 16.8 155, 200, 286


:
A- For retrofit only, not to be installed in new systems.

EXTENDED COVERAGE SPRINKLERS FOR STORAGE PROTECTION


(CONTROL MODE DENSITY AREA)
Max
Response Width x Length Nom
SIN Type Ft x Ft Type K-Factor Temp Rating, F

TY9128 SR 14 x 14 Upright 25.2 165, 212

These sprinklers have not been investigated for use as a Control Mode Specific Application (CMSA) sprinkler in accordance
with NFPA 13.

SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE SPECIFIC


APPLICATION)
Response Nom Temp
SIN Type Type K-Factor Rating, °F

TY5153 SR Upright 11.2 155, 200, 286

TY7103 SR Upright 16.8 286

TY7153 SR Upright 16.8 200

SPECIFIC APPLICATION SPRINKLERS


Attic Sprinklers
Min
Roof Flow
Response Fire Pitch Max Max Rate Nom Temp
SIN Type Risk (In./In.) Width Ft Length Ft GPM K-Factor Rating, F

TY2180 QR ++ 3/12 to 7/12 6 20 13 4.2 155

TY2180 QR ++ 3/12 to 7/12 6 20 13 4.2 200

TY2181 QR ++ 7/12 to 12/12 6 20 13 4.2 155

TY2181 QR ++ 7/12 to 12/12 6 20 13 4.2 200

TY2182 QR ++ 10/12 to 12/12 6 20 13 4.2 155

TY2182 QR ++ 10/12 to 12/12 6 20 13 4.2 200

TY3180 QR ++ 4/12 to 6/12 6 60 38 5.6 212

TY3180 QR ++ 4/12 to 6/12 6 40 25 5.6 212

TY3181 QR ++ 7/12 to 9/12 6 60 38 5.6 212

TY3181 QR ++ 7/12 to 9/12 6 40 25 5.6 212

TY3182 QR ++ 10/12 to 12/12 6 60 38 5.6 212


:
TY3182 QR ++ 10/12 to 12/12 6 40 25 5.6 212

TY3183 QR ++ 4/12 to 6/12 6 40 35 5.6 212

TY3183 QR ++ 4/12 to 6/12 6 30 25 5.6 212

TY3184 QR ++ 7/12 to 9/12 6 40 35 5.6 212

TY3184 QR ++ 7/12 to 9/12 6 30 25 5.6 212

TY3185 QR ++ 10/12 to 12/12 6 40 35 5.6 212

TY3185 QR ++ 10/12 to 12/12 6 30 25 5.6 212

TY3187 QR ++ 4/12 to 12/12 6 28 34 5.6 200

TY3187 QR ++ 4/12 to 12/12 6 20 25 5.6 200

TY3183 QR ++ 4/12 to 6/12 6 10 19 5.6 212

TY3184 QR ++ 7/12 to 9/12 6 10 19 5.6 212

TY3185 QR ++ 10/12 to 12/12 6 10 19 5.6 212

TY4180 QR ++ 4/12 to 6/12 6 60 38 8.0 200

TY4181 QR ++ 7/12 to 9/12 6 60 38 8.0 200

TY4182 QR ++ 10/12 to 12/12 6 60 38 8.0 200

++ For protection of Light Hazard attic spaces of wood truss or open wood joist construction with saddle type roofs in
buildings 20 to 60 ft in width and not exceeding a protection area of 400 sq ft per sprinkler when installed in accordance with
the manufacturer' s installation and design parameter instructions.

Window Sprinklers
Min
Distance Flow
Response Fire Nom Between Rate Temp
SIN Type Risk Type K-Factor Sprinklers, Ft GPM Rating, F

TY3388 QR *, % HSW 5.6 6 to 8 20 155, 200

TY3388 QR *, % HSW 5.6 + 15 155, 200

TY3488 QR *, % VSW 5.6 6 to 8 20 155, 200

TY3488 QR *, % VSW 5.6 + 15 155, 200

TY3498 QR *,% Concealed VSW 5.6 6 to 8 20 160, 212

TY3498 QR *,% Concealed VSW 5.6 ++ 20 160, 212

+ Located between Mullions and not greater than 6 ft apart.

++ Located between Mullions and not greater that 8 ft apart.


:
* For use on heat-strengthened or tempered glass windows without horizontal mullions having a maximum height of 13 ft.
Combustibles must be maintained at a minimum distance of 2 in. from the glass. This may be accomplished by use of a 3 ft.
pony wall or any other method acceptable to the authority having jurisdiction when installed in accordance with the
manufacturer's installation and design parameter instructions.

% For use on UL certified FireLite Plus ceramic glass (by Technical Glass Products) without horizontal mullions having a
maximum height of 8 ft. Combustibles are not required to be maintained at any minimum distance from the glass when the
sprinklers are installed in accordance with the manufacturer's installation and design parameter instructions.

Authorities having jurisdiction shall be consulted to determine the hydraulic requirements for each installation.

Concealed Space Sprinklers


Max
Height of Space, In.
Response Coverage Nom Temp
SIN Type Type Min Max Area, Ft2 K-Factor Rating, F

TY1189+ QR Upright 12 36 100 2.8 175

TY1189++ QR Upright 6* 54 100 2.8 175

TY2189+ ** QR Upright 12 36 144 4.2 175

TY2189++ ** QR Upright 6* 54 144 4.2 175

TY3189+ ** QR Upright 12 36 144 5.6 175

TY3189++ ** QR Upright 6* 54 144 5.6 175

TY2190% QR Upright 6 480 120 4.2 200

TY3190% QR Upright 6 480 120 5.6 200

TY2199+ **b QR Upright 6* 84 196 4.2 200

TY2199++ ** QR Upright 6* 84 196 4.2 200

TY3199+ ** a QR Upright 6* 84 256 5.6 200

TY3199++ ** QR Upright 6* 84 256 5.6 200

* Minimum distance between upper and lower joists.

** Wet or Dry pipe systems using steel pipe.

+ For use in light hazard flat concealed spaces incorporating noncombustible or wood truss construction. The Manufacturers
Installation and Design Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and
hydraulic design requirements.

++ For use in combustible solid wood and composite wood joist construction.

% For use in attic areas outside the scope of application for the BB, SD or HIP sprinklers.

a - For use in combustible solid wood joists with baffle spaced at 2000 Ft2. The Manufacturers Installation and Design
Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and hydraulic design
requirements. The sprinklers can be used with Tyco's Listed LFP antifreeze solution (VDUV) with no limit to the system size.

b- The sprinklers can be used with Tyco's Listed LFP antifreeze solution (VDUV) with no limit to the system size.

Corridor/Hallway Sprinklers
:
SIN Type Max Max Min System Working Nom K- Temp
Width, ft Length, ft Flow, Pressure, psig Factor Rating,
(A) (B) gpm °F

TY4282+ Pendent, 28 8 23 250 8.0 155,200


Recessed
Pendent

TY4282+ Pendent, 28 10 28 250 8.0 155,200


Recessed
Pendent

+ For use in corridors and hallways of light hazard occupancies. The Manufacturer's Installation and Design Parameter
Instructions should be consulted for specific installation parameters, obstruction criteria, and hydraulic design requirements.

Trademark and/or Tradename: "CSC"

Last Updated on 2020-09-28

The appearance of a company's name or product in this database does not in itself assure that products so identified have
been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be
Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions:
1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their
entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from
the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the
reprinted material must include a copyright notice in the following format: "© 2020 UL LLC"
:

You might also like