Transformer Test Report: Transformers Technical Data Field Service Representive

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

TRANSFORMER TEST REPORT SERVICES DIVISION

TRANSFORMERS TECHNICAL DATA Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Unit
Manufacture : Rated Power : MVA
Type : Rated voltage HV : kV
Serial No. : Rated voltage LV : kV
Year : Rated current HV : A
Standard : Rated current LV : A
O
% Impedance (85 C) : No. of phase :
Temp. rise : Rated frequency : Hz
Oil in transformer : Vector group symbol :
Total mass : No. of tap :
Cooling type : Nominal Tap :

Note :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
VISUAL INSPECTION AND MECHANICAL Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

VISUAL INSPECTION

No. Description Checked N/A In good


Condition

1 Body/Tank Condition o o o
2 Paint Condition o o o
3 Name Plate o o o
4 Rating plate o o o
5 Radiator panel/fins o o o
6 Cooling Fans o o o
7 Conservator o o o
8 Bushing HV / LV o o o
9 Termination and Cable box o o o
10 HV Cable Tightening Torque o o o
11 LV Cable Tightening Torque o o o
12 Tap Changer o o o
13 Winding Temperature indicator o o o
14 Oil Temperature Indicator o o o
15 Oil Level Indicator Main Coservator o o o
16 Leakage o o o
17 Buchholz Relay o o o
18 Pressure Relief Device Main Tank o o o
19 Radiator valve o o o
20 Oil Filling Valve o o o
21 Oil Sampling device o o o
22 Air Breather with silica Gel o o o
23 Drain Valve o o o

Tested & Reported By Witnessed By Witnessed By Approved By

Company PT. TRAFOINDO P.P.

Name

Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
INSULATION RESISTANCE MEASUREMENT AND POLARIZATION INDEX (PI) Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Insulation Resistantce & PI


Temperature : ⁰C
Test Voltage Insulation Resistance (GΩ)
Condition Condition
(Volt) 1 minute 10 minutes Polarization Index

HV – Ground

LV - Ground

HV – LV

Guidelines for evaluating transformer insulation using value: (STANDARD: WESTING HOUSE)

L-L Voltage Class Mega Ohms


1.2 32
2.5 68
5 135
8.66 230
15 410
24 670
32.5 930

Acceptance Criteria :

Guidelines for evaluating transformer insulation using index polarization value: (STANDARD: ANSI C57.125-1991)

Polarization Index Insulation Condition


Less than 1.0 Dangerous
1.0 - 1.1 Poor
1.1 - 1.25 Questionable
1.25 - 2.00 Fair
Above 2.0 Good

Test Result :

Measurement used :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TESTING AND COMMISSIONING TRANSFORMER SERVICES DIVISION

Winding Resistance Measurement Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

WINDING RESISTANCE TEST


HV Side
R Meas (mΩ) R Dev (%) R Meas (mΩ) R Dev (%) R Meas (mΩ) R Dev (%)
TAP
A A B B C C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

LV SIDE
R Meas (mΩ) R Dev (%) R Meas (mΩ) R Dev (%) R Meas (mΩ) R Dev (%)
TAP
A A B B C C
1

Acceptance Criteria : Deviation between measured within 5%


Result :
Equipment used :

Tested & Reported By Witnessed By Witnessed By Approved By

Company PT. TRAFOINDO P.P.

Name

Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
TURN TRANSFORMATION RATIO TEST / RATIO TEST & VECTOR GRUP TEST Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

TTR & Vector Grup Test

Measured Ratio
Tap HV LV Theoritical
Dev. (%) Dev. (%) Dev. (%)
Position Ratio A–B B–C C–A
Volt (± 0.5%) (± 0.5%) (± 0.5%)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

Acceptance Criteria : Deviation between theoritical ratio and measured ratio within 0.5%

Result :

Equipment used :

Tested & Reported By Witnessed By Witnessed By Approved By

Company PT. TRAFOINDO P.P.


Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
TURN TRANSFORMATION RATIO TEST / RATIO TEST & VECTOR GRUP TEST Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Tested & Reported By Witnessed By Witnessed By Approved By

Company PT. TRAFOINDO P.P.


Name
Date

Signature

Page /
Tan Delta

TRANSFORMER TEST REPORT SERVICES DIVISION


TAN DELTA REPORT Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Test TEST TEST CONNECTING TEST % DISSIPATION fACTOR Direct Insulating


INSULATION TESTED Capacitan
No MODE WINDING KV Measured 20 Coretion mA Watt Rating
PRIMARY SIDE (P)
1 P-ST (Ground) GST P-Black/S-Red, T-Blue
2a P-S (Guard) GSTg-R P-Black/S-Red
2b P-T (Guard) GSTg-B P-Black/ T-Blue
2c P-ST (Guard) GSTg-RB P-Black/S-Red, T-Blue
3a P-S UST-R P-Black/S-Red
3b P-T UST-B P-Black/ T-Blue
3c P-ST UST-RB P-Black/S-Red, T-Blue
SECONDARY SIDE (S)
1 P-ST (Ground) GST P-Black/S-Red, T-Blue
2a P-S (Guard) GSTg-R P-Black/S-Red
2b P-T (Guard) GSTg-B P-Black/ T-Blue
2c P-ST (Guard) GSTg-RB P-Black/S-Red, T-Blue
3a P-S UST-R P-Black/S-Red
3b P-T UST-B P-Black/ T-Blue
3c P-ST UST-RB P-Black/S-Red, T-Blue
Bushing
1 Phse 1U UST P-Black/S-Red
2 Phase 1V UST P-Black/S-Red
3 Phase 1W UST P-Black/S-Red

IEEE, Std C57.12.90-1993,10.10.5 PF Temp Oli °C


Temperature Correction Factors
Temperature ℃ Correction Factor
10 0.8 Acceptance Criteria : Trafo baru Max 0.5 %
15 0.9 Trafo telah Beroprasi max 1%
20 1 Result : Accept
25 1.12 Equpment Used : OMICRON – TESTRANO 600
30 1.25
35 1.4
40 1.55

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /

Page 0
TRANSFORMER TEST REPORT SERVICES DIVISION
Auxiliary Function Test Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

1. SPECIFICATION
NO Material Type / Specification Result
1 Oil Level Indicator Main Conservator
2 Oil Temperature Indicator
3 Winding Temperature Indicator
4 Buchholz Relay
5 Pressure Relief Device 1
6 Relay OLTC Trip

2. VISUAL INSPECTION
NO Construction Installed/ Not Installed Result
1 Panel Control Box
2 Teminal Block
3 Thermal Relay
4 MCB
5 Selector Switch
6 Cable Conection

3. ELECTRICAL FUNCTION
No Description Result
1 Bucholz Alarm / Trip
2 Oil Temperature Alarm / Trip
3 Winding Temperature Alarm / trip
4 Pressure Relief Device 1 Contact Trip
5 Relay OLTC Trip
6 Oil Level Indicator Main Consevator/OLTC
7 Fans Operation ON/AUTO

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
Differential Transformer Stability Test Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

STABILITY TEST
Technical Data Protection Relay
Device Identification Main Protection Relay
Identification
Manufacture
Device Type
Serial Number
Ratio CT HV
Ratio CT HV

Stability Diagram
MVA

KV KV

RELAY

Stabilty Test Main Protection


Injection Tranformer Side Current Measured

400 V

Result : Stabil Condition

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
SFRA Analyzer Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
SFRA Analyzer Field Service Representive

Object Description : Contract No : -

Plant : Project Name :

Trafindo Order No. : Customer :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
SFRA Analyzer Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
BDV Test OIL Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Type of Oil : Mineral Oil


Standard used : IEC 60156:1995
Electrode shape :
Electrode spacing : 2.5 mm
Number of Test : 6 times
Sampling position : Bottom

Before Oil Purification After Oil Purification


Oil Temperature : ⁰C Oil Temperature : ⁰C

TEST Breakdown Voltage (kV) TEST Breakdown Voltage (kV)


1 1
2 2
3 3
4 4
5 5
6 6
Average Average

WATER CONTENT
Tem OLI °C Ppm / %

Acceptance Criteria BDV :


Standard IEC 60422-2013
Highest Voltage BDV Water Content
(kV) Good Fair Poor (Ppm)
>170 kV >60 50 - 60 <50 >10
72.5 to 170 >50 40 - 50 <40 >10
<72.5 >40 30 - 40 <30 >20

Result :

Equipment used :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /
TRANSFORMER TEST REPORT SERVICES DIVISION
DGA Test OIL Field Service Representive

Object Description : Contract No :

Plant : Project Name :

Trafindo Order No. : Customer :

Tested & Reported By Witnessed By Witnessed By Approved By


Company PT. TRAFOINDO P.P.
Name
Date

Signature

Page /