Minerva Marine: M600Ex Intrinsically Safe Fire Detectors

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

PSF122UM.

qxp 02/01/2009 11:44 Page 1

MINERVA® Marine

M600Ex Intrinsically Safe Fire Detectors

Features:
Intelligent Universal Smoke/Heat/CO detector
Low profile, discreet and unobtrusive
Superior performance and reliability
Designed for fast, easy installation
Optional locking kit
May be used in systems that meet BS5839 Pt1
Integral and remote alarm LED
Certified to ATEX: Ex II1GD and Cenelec:
Ex ia IIC T5/Ex iaD 20 T100oC
Complies to EN54-7 for Smoke Detectors and
EN54-5 for Heat Detectors

M600Ex Fire Detection Range


Our sophisticated Ex system for use in hazardous
atmospheres, introduces to the market a range of
conventional I.S. fire detectors. In addition to the
unobtrusive size and styled shape, a number of
design features have been incorporated including
single visit to the ceiling installation and a service and
maintenance detector park position.

Fire Detection
PSF122UM.qxp 02/01/2009 11:44 Page 2

General Application
Included within the range is the High Performance Optical Smoke As each type of fire detector responds to a particular ‘fire product’ the
(HPO) Detector and a combined Carbon Monoxide and Heat Detector. relative speed of response of the detector is therefore dependent upon
the type of fire being detected. The range of M600Ex detectors have
The complete range has been designed to meet the requirements of been designed to provide the earliest possible warning of a fire
BS (British Standards) and EN (European Standards) for fire condition, with a minimum possibility of false/unwanted alarms.
detectors. The detectors also carry the new CE mark.
As smoke is normally present at an early stage in most fires, smoke
M600Ex Series Conventional Detectors type detectors are therefore considered the most useful. When
The M600Ex Series provides the detector part of an automatic fire considering the type of smoke detector for the application, the
detection system, as defined in BS5839 Pt1:2002. The M600Ex probable type of fuel for the fire should be considered. For general fire
Series Conventional or two state detector is one that provides two detection, where there is an equal possibility of either a ‘fast’ or ‘slow’
output states to the controller, either ‘normal’ or a ‘fire alarm’ fire developing, the intelligent high performance optical detector
condition. provides an excellent detection response.

The detectors along with callpoints are grouped into zones, with each In situations where the installation of smoke detectors would cause an
zone being connected to the control panel, by a two wire circuit. Each unacceptable level of false alarms (i.e. kitchens, laundry areas) heat
zone having a separate zone indicator at the control panel. Safety detectors may be installed. The M600Ex series provides a selection of
barriers are used to maintain the intrinsically safe status of the circuit heat detectors, from Rate of Rise to fixed temperature.
under all conditions.
Because of the wide variety of applications that fire detectors are
expected to cover, it is recommended that reference to BS5839
Pt1:2002 is made to aid selection.
PSF122UM.qxp 02/01/2009 11:44 Page 3

High Performance Optical Smoke Detector


MR601TEx
These detectors react to the whole range of fire products from slow
smouldering fires, producing visible particles to open flaming fires
producing large numbers of very hot smaller sized aerosols. It
combines optical and heat detector technology to detect clear burning
fire products which hitherto could only be easily detected by
ion-chamber detectors.

For normal ambient conditions, the high performance optical detector


behaves as a normal optical detector. Only when a rapid rise in
temperature is detected does the sensitivity of the detector increase
and the presence of smoke will confirm a fire condition which will be
transmitted as an alarm level.

Heat Detector MD601Ex and MD611Ex


These detectors use two networked thermistors in a bridge
configuration to provide a fast response, that depends both on
absolute temperature and rate of rise of temperature.

The rate of rise/fixed temperature heat detectors can be used in areas


where smoke sensors are unsuitable due to environmental conditions
(smoke, dust etc.). Such areas include kitchens, locker rooms,
canteens, garages, loading bays etc.

Enhanced Carbon Monoxide Fire and Heat Detector


MDU601Ex
The MDU601Ex detector is a combined CO and Rate-of-Rise Heat
detector where the sensitivity of the CO detector is enhanced in
response to a fast rate of change of temperature.

Maybe used in dusty environments instead of the MR601TEx Detector


PSF122UM.qxp 02/01/2009 11:44 Page 4

Technical Specifications Electromagnetic Compatibility


Mechanical ESD: to EN50130-4
Detector Material: FR110 “Bayblend” fire resistant Radiated Immuntity: to EN50130-4
Dimensions: See diagram below Fast Transient: to EN50130-4
Weight: 0.2Kg detector and base (approx) Slow High Energy: to EN50130-4
Colour: White Conducted Immunity: to EN50130-4
Emissions: to EN61000-6-3

Environmental Approvals
Operating Temp. Range: -20oC to +70oC These detectors have the following approvals:
-10oC to +55oC (MDU601Ex only) ABS: American Bureau of Shipping
Storage Temp.: -25oC to +80oC BV: Bureau Veritas
-20oC to +55oC (MDU601Ex only) DNV: Det Norske Veritas
Relative Humidity: 95% non condensing KRS: Korean Register of Shipping
90% non condensing (MDU601Ex only) LRS: Lloyds Register of Shipping
CCS: China Classification Society
Electrical NKK: Japanese Register of Shipping
Supply Voltage: 14 to 28Vd.c. GL: Germamischer Lloyd
Quiescent Current: 100µA typical MCA: Maritime and Coastguard Agency
Alarm Current: 48mA typical RMRS: Russian Maritime Register of Shipping
Reset Time: 0.5 - 5 seconds
Wiring Connections: SEM Terminal 2 x 1.5mm2

109mm
43mm

The right is reserved to modify or withdraw any product


or service without notice

Technical Information Sheet PSF122UM Issue 3