UserManual For VMwareESXi RS232 or USB
UserManual For VMwareESXi RS232 or USB
2 Configuring for critical guest OS(only need to be done for case1) ........................................ 4
Case 1:
Winpower can be installed on any of the Guest OS, just as windows, Linux, Mac OSX, Solaris.
Please make sure the “VMware tools” are installed for all the Guest OS.
The guest OS that is installed Winpower is the Critical VM.
Case 2:
Winpower can be installed on the other physical Computer at the same network with
VMware ESXi, just like Windows, Linux, Mac OSX, Solaris.
Please make sure the “VMware tools” are installed for the all the Guest OS.
1.2 Shutdown Sequence
Case 2:
UPS Power Fail All the VMs ESXi hosts Local Winpower
Shutdown condition is met shutdown shutdown physical PC shutdown
2 Configuring for critical guest OS(only need
to be done for case1)
Choose the critical guest OS that Winpower is installed , Add the USB controller by the
“Summary”->”Edit setting”->”add”->”USB Controller”
Choose the critical guest OS that Winpower is installed, Add the USB device by the
“Summary”->”Edit setting”->”add”->”USB device”, make sure the UPS is connected.
The UPS USB can be added successfully as below image
Restart the guest OS after adding the USB controller and USB device
Choose the critical guest OS that Winpower is installed, Add the USB device by the ”Edit
settings”->”add other device”->”USB device”
The UPS USB can be added successfully as below image
2.2 RS232 Communication
Power off the critical guest OS that Winpower is installed, right click it. Add the serial port
by the “Summary”->”Edit setting”->”add”->”Serial Port”->”Use physical serial port”, the
serial port name is “/dev/char/serial/uart0” as default.
Power off the critical guest OS that Winpower is installed, right click it. Add the serial port
by the ”Edit settings”->”add other device”->”Serial Port”->
Choose “Use physical serial port”
Choose the critical guest OS that Winpower is installed, Add the USB controller by the
“Summary”->”Edit setting”->”add”->”USB Controller”
Choose the critical guest OS that Winpower is installed, Add the USB device by the
“Summary”->”Edit setting”->”add”->”USB device”, Choose “prolific USB-Serial
Controller”, make sure the UPS is connected.
The UPS can be added successfully as below image
Choose the critical guest OS that Winpower is installed ,Add the USB device by the
“Summary”->”Edit settings”->”add other device”->”USB device”
The UPS USB-RS232 can be added successfully as below image
3 Configuring for Winpower
Winpower can be installed on any of the OS, just like Windows, Linux, MACOSX, Solaris
For more simply, just give the windows and Linux samples.
Please check the Winpower user manual for more information.
Right click the “setup.exe”, choose “Run as administrator” to complete the installation.
The Winpower agent will be running automatically when the Windows boots
Winpower agent will be started automatically, you can right click the green icon choose
“start monitor” to start the Winpower manager.
Winpower agent will be start automatically, you can input the command “./monitor” under
the “/opt/MonitorSoftware” to start the Winpower manager
If the Winpower communication with UPS via USB or RS232, just auto search it by
“System” ->”Auto search device”
Windows OS:
Linux OS:
3.3.2 USB TO RS232
Open Winpower manager, Click “Device” -> ”Shutdown Parameter”, Set the shutdown
condition
Open Winpower manager, Click “Device” -> ”Shutdown Parameter”, choose the
“Shutdown ESXi hosts and VMs before Shutdown”
Click “ESXi Configure”->”Add”, Enter the ESXi hosts IP, user name, password
You can input multi-ESXi hosts.
Please don’t check the box “Shutdown all the VMs before host shutdown”, so Winpower
only shut down the hosts. The VMs will be shut down before host shutdown by the
“Autostart” function.