UserManual For VMwareESXi RS232 or USB

This document provides instructions for configuring Winpower software for VMware ESXi via USB or RS232 communication. It discusses installing Winpower on guest operating systems or a separate physical computer, then configuring USB, serial port, or USB-RS232 devices. It also explains how to start Winpower, set shutdown conditions, and add ESXi hosts for remote shutdown. The goal is to use Winpower to remotely shutdown VMs and ESXi hosts in the event of a power failure.

Uploaded by

sergiocoseg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views17 pages

UserManual For VMwareESXi RS232 or USB

This document provides instructions for configuring Winpower software for VMware ESXi via USB or RS232 communication. It discusses installing Winpower on guest operating systems or a separate physical computer, then configuring USB, serial port, or USB-RS232 devices. It also explains how to start Winpower, set shutdown conditions, and add ESXi hosts for remote shutdown. The goal is to use Winpower to remotely shutdown VMs and ESXi hosts in the event of a power failure.

Uploaded by

sergiocoseg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

Winpower for VMware ESXi via USB/RS232 (paid version)

1 Over viewer ............................................................................................................................ 2

1.1 Topological structure....................................................................................................... 2

1.2 Shutdown Sequence ........................................................................................................ 3

2 Configuring for critical guest OS(only need to be done for case1) ........................................ 4

2.1 USB Communication ........................................................................................................ 4

2.1.1 Earlier than ESXi 6.5:................................................................................................. 4

2.1.2 Later than ESXi 6.5: ................................................................................................... 5

2.2 RS232 Communication .................................................................................................... 7

2.2.1 Earlier than ESXi 6.5:................................................................................................. 7

2.2.2 Later than ESXi 6.5: ................................................................................................... 7

2.3 USB TO RS232 Communication ....................................................................................... 9

2.3.1 Earlier than ESXi 6.5:................................................................................................. 9

2.3.2 Later than ESXi 6.5: ................................................................................................. 10

3 Configuring for Winpower .................................................................................................... 12

3.1 Winpower installation ................................................................................................... 12

3.1.1 Winpower installation on Windows OS.................................................................. 12

3.1.2 Winpower installation on Linux OS ........................................................................ 12

3.2 Winpower start.............................................................................................................. 12

3.2.1 Winpower start on windows OS ............................................................................. 12

3.2.2 Winpower start on Linux OS ................................................................................... 12

3.3 Winpower communication ............................................................................................ 13

3.3.1 RS232 or USB .......................................................................................................... 13

3.3.2 USB TO RS232 ......................................................................................................... 14

3.4 Set the shutdown condition .......................................................................................... 14

3.5 Add the ESXi hosts ......................................................................................................... 15


1 Over viewer

1.1 Topological structure

 Case 1:
Winpower can be installed on any of the Guest OS, just as windows, Linux, Mac OSX, Solaris.
Please make sure the “VMware tools” are installed for all the Guest OS.
The guest OS that is installed Winpower is the Critical VM.

 Case 2:
Winpower can be installed on the other physical Computer at the same network with
VMware ESXi, just like Windows, Linux, Mac OSX, Solaris.
Please make sure the “VMware tools” are installed for the all the Guest OS.
1.2 Shutdown Sequence

Case 1(Case 1 has two Instances):


 Winpower shut down the VMs and Hosts(Host disable Autostart)

UPS Power Fail No-critical VMs Critical VM ESXi Hosts


Shutdown condition is met shutdown shutdown shutdown

 Winpower only shut down the Hosts(Host enable Autostart)

UPS Power Fail All the VMs ESXi hosts


Shutdown condition is met shutdown shutdown

Case 2:

UPS Power Fail All the VMs ESXi hosts Local Winpower
Shutdown condition is met shutdown shutdown physical PC shutdown
2 Configuring for critical guest OS(only need
to be done for case1)

2.1 USB Communication

2.1.1 Earlier than ESXi 6.5:

 Choose the critical guest OS that Winpower is installed , Add the USB controller by the
“Summary”->”Edit setting”->”add”->”USB Controller”

 Choose the critical guest OS that Winpower is installed, Add the USB device by the
“Summary”->”Edit setting”->”add”->”USB device”, make sure the UPS is connected.
 The UPS USB can be added successfully as below image

 Restart the guest OS after adding the USB controller and USB device

2.1.2 Later than ESXi 6.5:

 Choose the critical guest OS that Winpower is installed, Add the USB device by the ”Edit
settings”->”add other device”->”USB device”
 The UPS USB can be added successfully as below image
2.2 RS232 Communication

2.2.1 Earlier than ESXi 6.5:

 Power off the critical guest OS that Winpower is installed, right click it. Add the serial port
by the “Summary”->”Edit setting”->”add”->”Serial Port”->”Use physical serial port”, the
serial port name is “/dev/char/serial/uart0” as default.

 Restart the guest OS after adding the serial port

2.2.2 Later than ESXi 6.5:

 Power off the critical guest OS that Winpower is installed, right click it. Add the serial port
by the ”Edit settings”->”add other device”->”Serial Port”->
 Choose “Use physical serial port”

 Restart the guest OS after adding the serial port


2.3 USB TO RS232 Communication

2.3.1 Earlier than ESXi 6.5:

 Choose the critical guest OS that Winpower is installed, Add the USB controller by the
“Summary”->”Edit setting”->”add”->”USB Controller”

 Choose the critical guest OS that Winpower is installed, Add the USB device by the
“Summary”->”Edit setting”->”add”->”USB device”, Choose “prolific USB-Serial
Controller”, make sure the UPS is connected.
 The UPS can be added successfully as below image

2.3.2 Later than ESXi 6.5:

 Choose the critical guest OS that Winpower is installed ,Add the USB device by the
“Summary”->”Edit settings”->”add other device”->”USB device”
 The UPS USB-RS232 can be added successfully as below image
3 Configuring for Winpower

3.1 Winpower installation

Winpower can be installed on any of the OS, just like Windows, Linux, MACOSX, Solaris
For more simply, just give the windows and Linux samples.
Please check the Winpower user manual for more information.

3.1.1 Winpower installation on Windows OS

 Right click the “setup.exe”, choose “Run as administrator” to complete the installation.
 The Winpower agent will be running automatically when the Windows boots

3.1.2 Winpower installation on Linux OS

 Download the software (Winpower_setup_LinuxAMD64.tar.gz) from the Website or from


the CD attached. Upload the software from Windows to the Linux using WinSCP tools.
 Extract the software, there are two files including LinuxAMD64 and InstallerData.
 Enter the LinuxAMD64 and then enter the following command to install the software:
cd LinuxAMD64
./setup.bin (if the Linux is GUI Mode)
./setup_console.bin (if the Linux is CUI mode)
 Go to the installation path and enter the following command to start the Winpower agent
manually:
cd /opt/MonitorSoftware
./agent start
Note:The Winpower agent will be running automatically when the Linux boots, you don’t
need to enter the command for every time.

3.2 Winpower start

3.2.1 Winpower start on windows OS

 Winpower agent will be started automatically, you can right click the green icon choose
“start monitor” to start the Winpower manager.

3.2.2 Winpower start on Linux OS

 Winpower agent will be start automatically, you can input the command “./monitor” under
the “/opt/MonitorSoftware” to start the Winpower manager

3.3 Winpower communication

3.3.1 RS232 or USB

 If the Winpower communication with UPS via USB or RS232, just auto search it by
“System” ->”Auto search device”
Windows OS:

Linux OS:
3.3.2 USB TO RS232

 If the Winpower communication with UPS via USB-RS232:


On the Windows OS, you should install the USB-RS232 driver, then restart the system and
auto search the device.
On the Linux OS, you don’t need to install the USB-RS232 driver, you should add the serial
port name by “System” ->”Com port Setting”, add the serial port name “/dev/ttyUSB0”,
then auto search the device

3.4 Set the shutdown condition

 Open Winpower manager, Click “Device” -> ”Shutdown Parameter”, Set the shutdown
condition

3.5 Add the ESXi hosts

 Open Winpower manager, Click “Device” -> ”Shutdown Parameter”, choose the
“Shutdown ESXi hosts and VMs before Shutdown”

 Click “ESXi Configure”->”Add”, Enter the ESXi hosts IP, user name, password
You can input multi-ESXi hosts.

 If you have disabled the “Autostart” as below image:


Please check the Winpower box “Shutdown all the VMs before host shutdown” ,
Winpower will shut down all the no-critical VMs firstly, then shutdown the critical VMs
and hosts.

 If you have enable the “Autostart” as below image:

Please don’t check the box “Shutdown all the VMs before host shutdown”, so Winpower
only shut down the hosts. The VMs will be shut down before host shutdown by the
“Autostart” function.