Installation Instructions
TitanPower Plus-SU2 Collector
Flush Mounting
Statics: An adequate load capacity of the roof construction must be taken in consideration, because the connection parts are fixed to the roof structure. In case of specific loads, high wind and/or snow pressures the valuation of an expert has to be obtained. Please observe the local codes and rules for roof installations.
Lightning protection: All metallic parts of the solar system must be connected to the ground by a copper cable with an area of at least 16mm2 (AWG 5). If lightning protection is already in place the collector system can be connected directly to it.
Protection against dirt and injury: Never carry collectors at the pipe ends. Keep dry and clean! Dont store collectors outdoors!
Rinsing, filling and maintenance: During installation and setup of the collectors keep them covered to prevent damages. Please consider the national rules and manufacturer instructions for the use of propylene glycol. Use only water-glycol mixtures that are appropriate for solar thermal systems.
Operating parameters, maintenance: The recommended operating pressure should be in a range between 36.3 and 43.5 PSI. The volumetric flow rate is suggested between 5.28 and 18.5 gallons per 10.76 square feet per hour. Highest approved working pressure is 47 psi. Solar collectors are usually maintenance-free but the solar system should be checked for damages and irregularities yearly by a solar thermal installer. Transport and handling: Carry collectors with the glass side facing up. Dont damage the pipe ends. Dont throw any materials at the glass plate and be careful of the glass edges. Never touch pipes in case of solar radiation to avoid the risk of a severe burn General: The references shown make no pretence on completeness. In all cases you must comply with the national rules for mounting, installing and operation of a solar system.
Technical data
2017mm / 79.4inch
TitanPower Plus-SU2:
TitanPower Plus-SU2
985mm / 38.78inch
TitanPower Plus-SU2
32mm
1.26inch
Field Length [inch] 38.78 78.82 118.86 158.89 198.94 238.98 279.02 319.06 359.09 399.13
Pressure Loss
Tm=20C Flow [l/h] Pressure Loss [Pa] 0 0 50 564 100 1168 150 1811 200 2493 250 3215
ConnectMaxx-15100096
ConnectMaxx-18000305
ConnectMaxx-74010701-2120
ConnectMaxx-74011003
ConnectMaxx-74022601
ConnectMaxx-77000500
ConnectMaxx-77000501
ConnectMaxx-72201701
ConnectMaxx-SDS25412
1c
79.41 inches
1d
Do Not exceed 48
2b
In cases where the flashing does not fit under the above shingle, it may be necessary to notch out the shingle.
2c
3a
3b
3c
3d
3e
4a
4b
4c
4d
**The Hot Supply from the collector should be the shortest pipe run**
5a
5b