IRIPROx (H+V) Catalog
IRIPROx (H+V) Catalog
IRIPROx (H+V) Catalog
IRIPro
IRIPro IL1 : 000.00 A
IL2 : 000.00 A
IRIPro
Series IL1 : 000.00 A
IL2 : 000.00 A
Catalog
PMD Division
IRIPROx-(EO/3I-EI)-(H/V)-(1/5)-(1/5)
Over current protection Relay : IRIPROx
02
Over current protection Relay : IRIPROx
1) Introduction
IRIPRO Series offers a compact Over-current protection solution for distribution/feeder segment.
IRIPRO Family of protective relays are numeric relays that provides protection and monitoring with reliable and fast
protection solution in a single unit with programmable digital outputs.
2) Application
The IRIPRO relays have been designed for controlling, protecting and monitoring industrial, utility distribution
networks and substations. They can also be used as part of backup protection scheme for feeders, transformers and
generators.
3) Hardware
u Measures True RMS with DFT Filter
4) Protection Features
u Three Phase Time Over Current Protection (51)
* Model Dependent
03
Over current protection Relay : IRIPROx
5) Functional Diagram
COMMUNICATION RECORDS
Front USB
PC/Laptop
Fault Record 3 Digital Outputs
CBFP
50/51 86
50BF
64R*
50N/
50BF 86
51N
Earth 1
current
(Figure 1)
Reset Delay
This parameter introduces a delay in opening of relay contacts, when the current goes below the drop out value for over current,
short circuit and earth faults. This parameter will not work when manual reset mode is selected.
Inrush Blocking
Relay is equipped with in-built facility of Inrush blocking to avoid nuisance tripping and stable operations.
04
Over current protection Relay : IRIPROx
7) Fault Recording
IRIPRO records last 5 faults in its non volatile memory with it's time stamp. Each record has the following information:
Fault Format
IL1 / IL2 / IL3 / E : Fault Current Amplitude
FLT : Fault Type
TIME : HH:MM:SEC:mSEC
DATE : DD/MM/YY
The user can view the fault record / various parameters via the front USB interface software.
Fault Records
Number of Records to Display
Fault No Fault Date - Phase Fault Type IL1-Phase Current [Amp] IL2-Phase Current [Amp] IL3-Phase Current [Amp] Ie-Earth Current [Amp]
2 15 Apr 2021 09:45:17:451 PM Earth Fault Hi-Set 0.00 80.3 0.00 80.7
4 05, Feb 2021 10:23:11:117 AM Over current 53.70 54.3 52.7 0.1
Output Contact
No. of Digital Outputs : 3 (DO1, DO2, DO3)
Type of Outputs : Relay
Programmable (DO Assignment) : Yes
Relay Reset Type : Programmable (Auto/Manual)
05
Over current protection Relay : IRIPROx
IRIPROx
IL1 : 000.00 A
IL2 : 000.00 A
CURRENT PROTECTION RELAY
L1
L2
L3 IRIPROx
CURRENT PROTECTION RELAY
E
L1 I>
RESET
ENTER
I>
L2
IL1 : 000.00 A I>>
I>>
L3 IL2 : 000.00 A IE>
IE>
E IE>>
IE>>
9) Communication
The unit has:
Front USB port for direct connection to a PC
The entire setting, Fault is available on 'A to A' type USB (female) interface with saving & printing option.
06
Over current protection Relay : IRIPROx
3 Ph. over-current low set pickup l> 0.05xIp 2.5xIp 0.05xIp EXIT
Ph. over-current definite timing t> 0.1 Sec 150 Sec 0.01Sec 0.10 Sec
Ph. over-current inverse timing ti> 0.01 1.500 0.005 0.05
5 Earth over-cur. low set pickup Ie> 0.05xIn 2.5xIn 0.05xIn EXIT
Earth over-cur. low set definite timing te> 0.03 Sec 150 Sec 0.01Sec 0.10 Sec
Earth over-cur. low set inverse timing tie> 0.01 1.500 0.005 0.05
13.5
Very Inverse t= ti [s]
(I / IS) - 1
80
Extremely Inverse t= ti [s]
(I / IS)2 - 1
0.14/0.061/0.028
Normal Inverse 3.0/1.3 /0.6 t= ti [s]
(I / IS)0.02 – 1
DO Assignment
S.No Parameter Display DO Assign
1 Phase over-current low set I> DO1/DO2/DO3
2 Phase over-current hi-set I>> DO1/DO2/DO3
3 Earth over-current low set Ie> DO1/DO2/DO3
4 Earth over-current hi-set Ie>> DO1/DO2/DO3
5 Self supervision SlfSup DO1/DO2/DO3
6 Circuit breaker failure protection CBFP DO1/DO2/DO3
07
Over current protection Relay : IRIPROx
Common Setting (These are the settings common for all protections)
Parameter Display Setting Range Step Default
Min. Max. Size Setting
Phase CT ratio P-CTR 1 9999 1 1
Earth CT ratio E-CTR 1 9999 1 1
Reset Delay R_dly 0 20 Sec 0.1 Sec 0 Sec
Fault popup FltPop Enable Disable 1 Enable
Auxiliary Supply
Auxiliary voltage range 18-300V DC / 60-280V AC
Power consumption Quiescent approx. 3W, Operating <7W
Measurement Accuracy
08
Over current protection Relay : IRIPROx
Measuring Input
09
Over current protection Relay : IRIPROx
13a) Connection Diagram IRIPROx-3I-EI (Three Phase Over Current & Earth Fault with Residual Connection)
B7 B8
L1
L2
L3
Aux Supply
P1 S1 A1 1A/5A
A2 COM IL1
B1
P2 S2
DO-3
P1 S1 1A/5A B2
A3
Digital Output
A4 COM IL2
B3
P2 S2
DO-2
B4
P1 S1 A5 1A/5A
A6 COM IL3
B5
P2 S2
DO-1
(Trip) B6
A7 1A/5A
A8 COM IE
*
1A = Rated 1 Amp
5A = Rated 5 Amp
(Figure 5)
13b) Connection Diagram (Three Phase & Earth Fault with CBCT)
B7 B8
L1
L2
L3
Aux Supply
P1 S1 A1 1A/5A
A2 COM IL1
P2 S2
B1
P1 S1 A3 1A/5A DO-3
A4 COM IL2 B2
Digital Output
P2 S2
B3
P1 S1 A5 1A/5A DO-2
A6 COM IL3 B4
P2 S2
B5
DO-1
A7 1A/5A (Trip) B6
A8 COM IE
*
1A = Rated 1 Amp
5A = Rated 5 Amp
(Figure 6)
* Model Dependent
10
Over current protection Relay : IRIPROx
L1
B7 B8
L2
L3
N
Aux Supply
B1
DO-3
P1 S1 A7 B2
Digital Output
IE
A8 B3
P2 S2 DO-2
B4
B5
DO-1
(Trip) B6
*
1A = Rated 1 Amp
5A = Rated 5 Amp
(Figure 7)
13d) Connection Diagram (Restricted Earth Fault Scheme) available in EOR model only.
B7 B8
L1 L2 L3
P1 S1 P1 S1 P1 S1 Aux Supply
P2 S2 P2 S2 P2 S2
B1
DO-3
Rsr A7 B2
Digital Output
A8 B3
DO-2
B4
B5
DO-1
P1 S1
(Trip) B6
P2 S2
(Figure 8)
11
Over current protection Relay : IRIPROx
14a) Dimensional Details (All the dimensions are in mm, Gen. Tol. : +1.0 mm)
(HORIZONTAL MODEL - H)
Top View
Front View
137.0
131.0
125.0
151.0
31.5
(Figure 9)
151.0
70.0mm
Panel cutout
dimensions
68.5
76.2
139.0mm
(Figure 11)
(Figure 12)
12
Over current protection Relay : IRIPROx
14b) Dimensional Details (All the dimensions are in mm, Gen. Tol. : +1.0 mm)
(VERTICAL MODEL - V)
151.0
137.0
31.5
125.0
(Figure 13) 131.0
(Figure 14)
Top View
68.5
70.0mm
139.0mm
131.0
Panel cutout
dimensions
76.2
(Figure 16)
(Figure 15)
13
Over current protection Relay : IRIPROx
IRIPROx X X X X
MODEL NO. #1
3I-EI : 3 Over current with Earth fault
EO : Earth Fault with Hi-Set
EOR : REF with stabilizing resistance
#2
ENCLOSURE TYPE
H : Horizontal Mounting
V : Vertical Mounting
NOTE :
#1) Refer Model Selection Table (S.No. 12) for different model.
#2) Refer Dimension detail / Panel cutout dimension (S.No. 14a & 14b).
14
www.cselectric.co.in
IRIPROx
Revision Number
S.No. Rev.No. Details Date
Branch Address
Branch Phone Fax E-mail
Ahmedabad: +91-79-615651 22/23/24 +91-79-61565130 [email protected]
Bangalore: +91-80-305703 72/73, 30570347 +91 2558 4839 [email protected]
Bhubaneswar: +91-674-2507265 +91 674 2507265 [email protected]
Chennai: +91-44-33534501,33534521-23 ---- [email protected]
Cochin: +91-484-3071717 +91 0484 3071716 [email protected]
Delhi: +91-11-338490 00/10/11 +91 11 30838826 [email protected]
Hyderabad: +91-40-485340 80/82 ---- [email protected]
Kolkata: +91-33-392121 19-21 ---- ----
Mumbai: +91-22-241147 27/28 ---- [email protected]
Pune: +91-20-242505 18/19 +91 20 30283244 [email protected]