HT33-TX Series Tower Online UPS: 10-40kVA (380V/400V/415V)

The document provides specifications for the HT33-TX series tower online UPS, including its system capacity, input/output voltage and frequency ranges, efficiency, battery specifications, temperature operating range, and optional features like parallel capability and interface cards.

Uploaded by

dhafer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views1 page

HT33-TX Series Tower Online UPS: 10-40kVA (380V/400V/415V)

The document provides specifications for the HT33-TX series tower online UPS, including its system capacity, input/output voltage and frequency ranges, efficiency, battery specifications, temperature operating range, and optional features like parallel capability and interface cards.

Uploaded by

dhafer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Specification

Specification
HT33-TX Series Tower Online UPS
10-40kVA (380V/400V/415V) MODEL HT33010X-TX HT33020X-TX HT33030X-TX HT33040X-TX
System Capacity 10kVA 20kVA 30kVA 40kVA
HT33-TX series in-built transformer three phase UPS applies advanced technology that increases performance and reliability: two
Dual Input Standard
high speed DSPs with completed digital control fully ensure high quality of power supply, high input power factor and low input
Phase 3 Phase+Neutral+Ground, 380V/400V/415V(line-line)
current distortion. With in-built transformer, the HT33-TX is providing more safety to critical load.
304~478Vac (line-line),full load;
Input Voltage Range
228V~304Vac (line-line),load decreases linearly according to the min phase voltage
Input
Rate Frequency 50/60Hz
Input Frequency Range 40Hz~70Hz
Input PF >0.99
Input THDi <4% <3%
Rate Voltage 380/400/415Vac (line-line)
Rate Frequency 50/60Hz
Bypass Input Voltage Range Settable, -40%~+25%
Bypass Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
Bypass Overload 125% long term operation; 130% for 10 mins; 150% for 1 min
Rate Voltage 380/400/415Vac (line-line)
Voltage Regulation 1% for balance load; 1.5% for unbalance load
Rate Frequency 50/60Hz
Frequency Precision 0.1%
Output
Output PF 0.9
Output THDu <1% , Linear load; <5.5%, Non-linear load
Crest Factor 3:1
Inverter Overload 110% for 1 hour; 125% for 10 mins ;150% for 1 min; >150% for 200 ms
Application Voltage ±240Vdc
Battery Number 40pcs (Settable: even number from 32 to 44)
IDC(Internet Data center),ISP,IT Room, Service Center Precision instruments,Intelligent equipments Battery Voltage Precision ±1%
Charge Power up to 20% * Output active power
Battery Cold Start Optional
Features AC Mode 92.0%
Efficiency ECO Mode 95.0%
In-built galvanic isolation transformer Battery cold start Battery Mode 92.0%
Display LCD + LED + keyboard
High input PF>0.99;Input current THDi<4% Battery management: smart charging control, auto
IP Class IP 20
maintenance, greatly extend the battery life
Muti-protection, over-temperature protection with 8 sensors, Interface RS232,RS485
System
over-load, battery under voltage, fan failures, short-circuit Parallel up to 8 units Option SNMP Card, Parallel kit, USB, Programmable Dry Contact

Friendly operation interface, high-resolution LCD screen Temperature Operation: 0~ 40 ℃ Storge: -40 ~70 ℃
Four circuit breakers, providing full protection when fault
happens Relative Humidity 0 ~95% Non-condensing
Altitude <1000m. Within 1000m to 2000m, power derate 1% for every 100m rise
Noise (1 meter) 55dB @ 50% load
Applicable Standards Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3
Weight (kg) 200 220 240 300
Physical
Dimension W*D*H (mm) 350*738*1335 500*840*1400