Product Data: CH16NA 018 - 060 Single - Stage Heat Pump With Puronr Refrigerant
Product Data: CH16NA 018 - 060 Single - Stage Heat Pump With Puronr Refrigerant
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S 14.0 -- 16.0 SEER/11.5 -- 13.0 EER/8.2 -- 9.0 HSPF
S Microtube Technologyt refrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 68 dBA
S Sound level as low as 67 dBA with accessory sound blanket.
Reliability
S Non--ozone depleting Puronr refrigerant
S Scroll compressor
S Front seating service valves
S Internal pressure relief valve
S Internal thermal overload
S Filter drier
S High pressure switch
S Loss of charge switch
S Balanced refrigeration system for maximum reliability
Durability
WeatherArmort protection package:
Carrier’s CH16NA has been designed utilizing Carrier’s
non--ozone depleting Puron refrigerant. S Solid, durable sheet metal construction
This product has been designed and manufactured to meet Energy S Dense wire coil guard
Starr criteria for energy efficiency when matched with appropriate Applications
coil components. Refer to the combination ratings in the AHRI S Long--line -- up to 250 feet (76.20 m) total equivalent
Directory for system combinations that meet Energy Star r length, up to 200 feet (60.96 m) condenser above
guidelines. evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)
NOTE: Ratings contained in this document are subject to S Low ambient (down to --10_F/--23_C)) with accessory
change at any time. Always refer to the AHRI directory kit
(www.ahridirectory.org) for the most up--to--date ratings
information.
MODEL NUMBER NOMENCLATURE
B A
CH16 N A 018 00G
Variations
Electrical Supply
N --- 208/230 ---60 ---1 00G --- Variations
Nominal Capacity
018 --- 1 ---1/2 Ton
024 --- 2 Tons
030 --- 2 ---1/2 Tons
A --- Puron 036 --- 3 Tons
042 --- 3 ---1/2 Tons
048 --- 4 Tons
060 --- 5 Tons
STANDARD FEATURES
Feature 18 24 30 36 42 48 60
Puron Refrigerant X X X X X X X
Scroll Compressor X X X X X X X
Crankcase Heater X X
Field Installed Filter Drier X X X X X X X
X = Standard
2
PHYSICAL DATA
UNIT SIZE SERIES 018--- A 024--- B 030--- B 036--- B 042--- B 048--- B 060--- B
Compressor Type Scroll
REFRIGERANT Puron (R---410A)
Outdoor Heating Piston # TXV TXV TXV 55 59 TXV 65
Control TXV (Puron Hard Shutoff)
Charge lb (kg) 7.00 (3.18) 7.60 (3.45) 9.75 (4.42) 11.20 (5.08) 9.92 (4.50) 9.87 (4.48) 13.00 (5.90)
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM) 2233 3223 3223 3223 3770 4046 4400
Motor HP 1/12 1/12 1/12 1/12 1/3 1/4 1/3
Motor RPM 810 810 810 810 700 810 767
COND COIL
Face Area (Sq ft) 19.30 20.10 20.10 20.10 20.10 20.10 35.47
Fins per In. 20 20 20 20 20 20 20
Rows 1 1 2 2 2 2 2
Circuits 5 5 6 8 8 8 12
VALVE CONNECT. (In. ID)
Vapor 5/8 3/4 7/8
Liquid 3/8”
REFRIGERANT TUBES* (In. OD)
Vapor (0 ---80 Ft Tube Length) 5/8 3/4 7/8 1 1/8
Max Liquid Line 3/8”
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
Vapor Line Sizing and Cooling Capacity Losses -- Puronr Refrigerant 1-- Stage Heat Pump Applications
Cooling Capacity Loss (%)
Maximum Total Equivalent Line Length ft. (m)
Unit Liquid Line Vapor Line
Standard
Nominal Diameters Diameters Long Line Application Requires Accessories
Application
Size (Btuh) (In. OD) (In.) OD
26--- 50 51--- 80 81--- 100 101--- 125 126--- 150 151--- 175 176--- 200 201--- 225 226--- 250
(7.9--- 15.2) (15.5--- 24.4) (24.7--- 30.5) (30.8--- 38.1) (38.4--- 45.7) (46.0--- 50.3) (53.6--- 60.0) (61.3--- 68.6) (68.9--- 76.2)
18,000 1/2 1 2 3 4 6 7 8 9 10
1--- Stage
3/8
HP with
5/8 0 0 1 1 1 2 2 3 3
Puron
24,000 5/8 0 1 1 2 3 3 4 4 5
1--- Stage
3/8
HP with
3/4 0 0 0 0 1 1 1 1 1
Puron
30,000 5/8 1 2 3 3 4 5 6 7 8
1--- Stage
3/8 3/4 0 0 1 1 1 2 2 2 3
HP with
Puron 7/8 0 0 0 0 1 1 1 1 1
36,000 5/8 1 2 4 5 6 7 9 10 11
1--- Stage
3/8 3/4 0 0 1 1 2 2 3 3 4
HP with
Puron 7/8 0 0 0 0 1 1 1 1 2
42,000 3/4 0 1 2 2 3 4 4 5 6
1--- Stage
3/8
HP with
7/8 0 0 1 1 1 2 2 2 3
Puron
48,000 3/4 0 1 2 3 4 5 5 6 7
1--- Stage
3/8
HP with
7/8 0 0 1 1 2 2 2 3 3
Puron
60,000 3/4 1 2 4 5 6 7 9 10 11
1--- Stage
3/8 7/8 0 1 2 2 3 4 4 5 5
HP with
Puron 1 ---1/8 0 0 0 1 1 1 1 1 1
Standard Length = 80 ft. (24.4 m) or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica-
tion Guidelines
3
REFRIGERANT PIPING LENGTH LIMITATIONS
Maximum Line Lengths:
The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for
allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.
4
ACCESSORY THERMOSTATS
Capabilities Heat Cooling
Part Number Description
Gas Electric Heat Pump Stages Stages
TP---WEM01 CôR™, Wi---Fi Programmable Relative Humidity Thermostat X X X 4 2
TP---PRH01 ---A edge™ Programmable Relative Humidity Thermostat X X X 3 2
TP---PHP01 edge™ Programmable Thermostat (HP or AC) X X 3 2
TP---NRH01 edge™ Non ---Programmable Relative Humidity Thermostat X X X 3 2
TP---NHP01 edge™ Non ---Programmable Thermostat (HP or AC) X X 3 2
TC ---WHS01 Wi---Fi® Programmable X X X 3 2
TC ---PHP01 Programmable Thermostat (HP or AC) X X 3 2
TC ---NHP01 Non ---Programmable Thermostat (HP or AC) X X 3 2
TB---PHP01 Programmable Thermostat (HP or AC) X X 2 1
TB---NHP01 Non ---Programmable Thermostat (HP or AC) X X 2 1
Thermostat Accessories
Part Number Description Used With
TP---EXP EXP Card for Programmable Thermostats TP---Pxx
TSTATCCSEN01 ---B Outdoor Air Temperature Sensor TP---Pxx, TP---Nxx
TSTATXXCNV10 Thermostat Conversion Kit (4 to 5 wire) 10 pack All Carrier branded thermostats
TX ---LBP01 Large Decorative Backplate TP---Pxx, TP---Nxx, TC ---Pxx
TX ---MBP01 Medium Decorative Backplate TC ---Nxx, TB---Pxx
ACCESSORIES
Unit Size
Accessory No. Description
018 024, 030 036 042 048 060
KHAFM0101AAA{ PSC Fan MOTOR KIT X X
KAACH1601AAA CRKC HTR KIT X X
KAACH1701AAA CRKC HTR KIT X X
KAACS0201PTC KIT PTC X X X X X X
KAATD0101TDR TIME DELAY KIT X X X X X X
KHAIR0201AAA ISLN RELAY KIT X X X X X X
KHALS0401LLS SOL VALVE KIT X X X X X X
KHASS0606MPK* SNOW STAND KIT X X X X X X
KSACY0101AAA CYCLE PROTR KIT X X X X X X
KSAFT0101AAA FRZ THERM KIT X X X X X X
KSAHS1501AAA HARD START KIT X X
KSAHS2401AAA HARD START KIT X X X X
KSALA0301410 LOW AMBIENT KIT X X X X X X
KSALA0601AAA MOTORMASTER KIT X X X X X X
KSASF0201AAA SPRT FEET KIT X X X X X X
KSASH2301COP SOUND BLANKET X X X
KSASH2401COP SOUND BLANKET X X X
KSATX0201PUR TXV KIT; Copper X X
KSATX0301PUR TXV KIT; Copper X X
KSATX0401PUR TXV KIT; Copper X X
KSBTX0201PUR TXV KIT; Aluminum X X
KSBTX0301PUR TXV KIT; Aluminum X X
KSBTX0401PUR TXV KIT; Aluminum X X
x = Accessory
{Required for use with low ambient or motor master kits. Efficiency will not be met with this accessory installed.
* Available from RCD
5
ACCESSORY USAGE GUIDELINE
Table 1 – Accessory Usage
REQUIRED FOR LOW–AMBIENT REQUIRED FOR
REQUIRED FOR
Accessory COOLING APPLICATIONS SEA COAST APPLICATIONS
LONG LINE APPLICATIONS*
(Below 55F / 12.8C) (Within 2 miles / 3.22 km)
Accumulator Standard Standard Standard
Ball Bearing Fan Motor Yes{ No No
Compressor Start Assist Capacitor and
Yes Yes No
Relay
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Yes No No
Hard Shutoff TXV Yes Yes Yes
Isolation Relay Yes No No
Liquid Line Solenoid Valve No See Long–Line Application Guideline No
Motor Master Control or
Yes} No No
Low Ambient Switch
Support Feet Recommended No Recommended
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline.
{ Additional requirement for Low–Ambient Controller (full modulation feature) MotorMasterr Control.
} In units equipped with ECM OD motor, motor needs to be replaced per unit accessory guide to work properly. This motor kit comes with a new defrost
board that also needs to be installed. Unit will not meet AHRI rated efficiency once motor and control board are replaced to use this accessory.
Accessory Description and Usage (Listed Alphabetically)
1.Ball Bearing Fan Motor A Low--Ambient Pressure Switch must be used when
A fan motor with ball berings which permits speed reduction while cooling operation is used at outdoor temperatures
maintaining bearing lubrication. below 55_F (12.8_C).
Usage Guideline: 7.Liquid--Line Solenoid Valve (LLS)
Required on all units when using MotorMaster® An electrically operated shutoff valve which stops and starts
refrigerant liquid flow in response to compressor operation. It is to
2.Compressor Start Assist -- Capacitor and Relay be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.
Start capacitor and relay gives a “hard” boost to compressor motor
at each start up. Usage Guideline:
Usage Guideline: 8. MotorMaster® Low--Ambient Controller
Required for 2--stage non--communicating units in the A
following applications: Fan--speed control device activated by a temperature sensor,
Long line designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
Low ambient cooling mode only. For outdoor temperatures down to --10_F (--23_C), it
Suggested for all compressors in areas with a history of maintains condensing temperature at 100_F ±10_F (37.8_C
low voltage problems. ±6.5_C)
3. Crankcase Heater Usage Guideline:
An electric resistance heater which mounts to the base of the A MotorMaster Low--Ambient Controller or
compressor to keep the lubricant warm during off cycles. Improves Low--Ambient Pressure Switch must be used when
compressor lubrication on restart and minimizes the chance of cooling operation is used at outdoor temperatures
liquid slugging. below 55_F (12.8_C).
Usage Guideline: An LLS is required in all long line heat pump
Required in low ambient cooling applications. applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.
Required in long line applications.
9.Snow Stand
Suggested in all commercial applications.
Coated wire rack which supports unit 18 in. (457.2 mm) above
4. Evaporator Freeze Thermostat mounting pad to allow for drainage from unit base.
An SPST temperature--actuated switch that stops unit operation Usage Guideline:
when evaporator reaches freeze--up conditions. Suggested in the following applications:
Usage Guideline: Heat pump installations in heavy snowfall areas.
Required when low ambient kit has been added. Heat pump installations in snow drift locations.
5. Isolation Relay Heat pump installations in areas of prolonged
An SPDT relay which switches the low ambient controller out of subfreezing temperatures.
the outdoor fan motor circuit when the heat pump switches to All commercial installations.
heating mode. 10.Thermostatic Expansion Valve (TXV) Bi--Flow
Usage Guideline: A modulating flow--control valve which meters refrigerant liquid
Required in all heat pumps where low ambient kit has flow rate into the evaporator in response to the superheat of the
been added. refrigerant gas leaving the evaporator.
6. Low--Ambient Pressure Switch Usage Guideline:
A long life pressure switch which is mounted to outdoor unit
Accessory required to meet AHRI rating and system
service valve. It is designed to cycle the outdoor fan motor in order
to maintain head pressure within normal operating limits. The reliability, where indoor not equipped.
control will maintain working head pressure at low--ambient Required in all heat pump applications designed with
temperatures down to 0_F (--17.8_C) when properly installed. Puron refrigerant.
Usage Guideline:
6
ELECTRICAL DATA
MAX
OPER VOLTS* COMPR FAN FUSE**
UNIT SIZE V/PH MCA or CKT
MAX MIN LRA RLA FLA BRK
AMPS
18 56.3 10.5 0.5 13.6 20
24 62.9 11.9 0.6 15.5 25
30 72.5 15.4 0.6 19.9 30
36 208/230/1 253 197 75.0 16.8 0.6 21.6 35
42 123.9 20.0 2.8 27.8 40
48 130.0 24.4 1.3 31.8 45
60 152.5 24.9 2.8 33.9 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
7
DIMENSIONS
SHIPPING
OPERATING SHIPPING SHIPPING
ELECTRICAL A B C D E F G H I J K LENGTH / WIDTH
UNIT SERIES WEIGHT WEIGHT HEIGHT
CHARACTERISTICS (Sq.)
INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM Lbs Kgs Lbs Kgs INCH MM INCH MM
CH16NA01800GAAAA A Y N N N 31 3/16 792.5 35 1/16 890.7 5/8 15.9 6 9/16 166.1 24 11/16 626.3 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 15 3/4 400.1 16 406.4 16 1/4 412.8 167 75.7 199 90.3 32 3/16 817.9 36 11/16 931.3
CH16NA02400GABAA B Y N N N 35 889.0 32 1/16 815.1 5/8 15.9 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 17 1/2 444.5 17 7/8 454.0 15 5/8 396.9 172 78.0 189 85.7 36 914.9 33 3/4 857.6
CH16NA03000GABAA B Y N N N 35 889.0 32 1/16 815.1 3/4 19.1 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 17 1/4 438.2 16 7/8 428.6 15 3/4 400.1 207 93.9 228 103.4 36 914.9 33 3/4 857.6
CH16NA03600GABAA B Y N N N 35 889.0 32 1/16 815.1 3/4 19.1 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 17 3/8 441.3 17 1/2 444.5 13 3/4 349.3 215 97.5 237 107.5 36 914.9 33 3/4 857.6
CH16NA04200GABAA B Y N N N 35 889.0 32 1/16 815.1 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 16 1/4 412.8 17 7/8 454.0 15 7/8 403.2 233 105.7 256 116.1 36 914.9 33 3/4 857.6
CH16NA04800GABAA B Y N N N 35 889.0 32 1/16 815.1 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 16 1/8 409.6 18 457.2 14 7/8 377.8 238 108.0 262 118.8 36 914.9 33 3/4 857.6
CH16NA06000GABAA B Y N N N 35 889.0 45 11/16 1160.5 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 1 1/8 28.2 3 13/16 97.4 17 7/8 454.0 16 1/4 412.8 19 482.6 288 130.6 317 143.8 36 914.9 47 3/8 1203.2
Y=YES NOTES:
N=NO
460-3-60
575-3-60
208/230-3-60
208-230-1-60
1. CENTER OF GRAVITY .
8
"X" "Y"
UNIT SIZE MINIMUM GROUND MOUNTING MINIMUM ROOF-TOP MOUNTING
PAD APPLICATION DIMENSIONS PAD APPLICATION DIMENSIONS
Wall Wall
6”
(152.4) 24”
(609.6)
24” Service
12”
(609.6) (304.8)
Service
12” 6”
Wall
(304.8) (152.4)
12”
(304.8)
12”
(304.8)
9
Wall
24” 24” 24”
(609.6) (609.6) (609.6)
Service Service Service
Note: Numbers in ( ) = mm
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
CH16NA BALANCE POINT WORKSHEET
OUTDOOR TEMPERATURE, 0C
-23 -18 -13 -8 -3 2 7 12 17 22
80 23.4
060 Size
70 20.5
60 17.6
048 Size
042 Size
50 14.6
036 Size
40 11.7
10
kW
030 Size
MBTUH
30 8.8
024 Size
018 Size
20 5.9
10 2.9
BASED ON INDOOR RATED
COMBINATION WITH ENT. AIR AT 70 ºF
AND AT RATED CFM
0 0.0
OUTDOOR TEMPERATURE, ºF
TESTED AHRI COMBINATION RATINGS
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at: www.MyCarrierRatings.com
For performance data at specific application &/or design conditions with various indoor unit combinations, the
equipment performance calculator can be accessed at : http://rpmob.wrightsoft.com/
11
DETAILED COOLING CAPACITIES#
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
EVAPORATOR AIR
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
Capacity MBtuh† Total Capacity MBtuh† Total Capacity MBtuh† Total Capacity MBtuh† Total Capacity MBtuh† Total Capacity MBtuh† Total
EWB
CFM System System System System System System
° F (° C) Total Sens‡ Total{ Sens‡ Total{ Sens‡ Total{ Sens‡ Total{ Sens‡ Total{ Sens‡
KW** KW** KW** KW** KW** KW**
CH16NA018---A Outdoor Section With FX4DNF019L Indoor Section
72 (22.2) 21.64 11.38 0.99 20.62 10.99 1.17 19.56 10.60 1.37 18.43 10.19 1.60 17.23 9.75 1.87 15.94 9.29 2.19
67 (19.4) 19.65 13.99 1.00 18.73 13.61 1.18 17.76 13.21 1.38 16.74 12.79 1.61 15.65 12.35 1.88 14.49 11.89 2.20
545 63 (17.2)†† 18.21 13.45 1.01 17.36 13.07 1.18 16.46 12.67 1.39 15.51 12.26 1.62 14.50 11.81 1.89 13.42 11.35 2.21
62 (16.7) 17.90 16.53 1.01 17.08 16.13 1.18 16.22 15.71 1.39 15.34 15.19 1.62 14.47 14.47 1.89 13.59 13.59 2.21
57 (13.9) 17.36 17.36 1.01 16.70 16.70 1.19 16.01 16.01 1.39 15.26 15.26 1.62 14.45 14.45 1.89 13.57 13.57 2.21
72 (22.2) 21.94 11.80 0.99 20.90 11.42 1.17 19.80 11.02 1.38 18.65 10.60 1.61 17.41 10.16 1.88 16.09 9.69 2.20
67 (19.4) 19.95 14.67 1.00 19.00 14.28 1.18 18.00 13.87 1.38 16.95 13.45 1.62 15.83 13.00 1.89 14.64 12.53 2.21
600 63 (17.2)†† 18.50 14.08 1.01 17.62 13.69 1.19 16.70 13.29 1.39 15.72 12.87 1.63 14.69 12.42 1.90 13.58 11.94 2.22
62 (16.7) 18.24 17.42 1.01 17.40 16.99 1.19 16.56 16.43 1.39 15.72 15.72 1.62 14.87 14.87 1.90 13.95 13.95 2.21
57 (13.9) 17.92 17.92 1.01 17.22 17.22 1.19 16.49 16.49 1.39 15.70 15.70 1.63 14.85 14.85 1.90 13.93 13.93 2.21
72 (22.2) 22.28 12.35 1.00 21.21 11.97 1.18 20.07 11.56 1.38 18.88 11.14 1.62 17.60 10.69 1.89 16.26 10.22 2.21
67 (19.4) 20.28 15.56 1.01 19.30 15.16 1.19 18.26 14.74 1.39 17.18 14.31 1.63 16.04 13.85 1.90 14.82 13.36 2.22
675 63 (17.2)†† 18.83 14.91 1.02 17.91 14.51 1.20 16.96 14.10 1.40 15.96 13.67 1.64 14.88 13.20 1.91 13.76 12.71 2.23
62 (16.7) 18.66 18.49 1.02 17.85 17.85 1.20 17.08 17.08 1.40 16.24 16.24 1.63 15.34 15.34 1.90 14.36 14.36 2.22
57 (13.9) 18.57 18.57 1.02 17.83 17.83 1.20 17.05 17.05 1.40 16.22 16.22 1.63 15.32 15.32 1.90 14.35 14.35 2.22
CH16NA024---B Outdoor Section With FX4DNF025L Indoor Section
72 (22.2) 28.14 14.70 1.30 26.53 14.04 1.51 24.88 13.37 1.74 23.19 12.70 2.02 21.40 12.00 2.34 19.51 11.26 2.70
67 (19.4) 25.57 18.15 1.31 24.12 17.45 1.52 22.62 16.74 1.75 21.06 16.02 2.03 19.44 15.27 2.35 17.73 14.49 2.72
700 63 (17.2)†† 23.72 17.45 1.32 22.36 16.76 1.53 20.97 16.06 1.76 19.54 15.34 2.04 18.02 14.60 2.35 16.46 13.84 2.72
62 (16.7) 23.33 21.49 1.32 22.02 20.72 1.53 20.70 19.92 1.76 19.48 18.74 2.04 18.07 18.07 2.35 16.74 16.74 2.72
57 (13.9) 22.69 22.69 1.33 21.60 21.60 1.53 20.47 20.47 1.76 19.29 19.29 2.04 18.04 18.04 2.35 16.72 16.72 2.72
72 (22.2) 28.65 15.44 1.32 26.99 14.77 1.52 25.29 14.09 1.76 23.52 13.39 2.03 21.68 12.68 2.35 19.74 11.94 2.72
67 (19.4) 26.07 19.36 1.33 24.55 18.63 1.53 23.00 17.90 1.77 21.39 17.14 2.04 19.72 16.37 2.36 17.98 15.55 2.73
800 63 (17.2)†† 24.19 18.57 1.34 22.79 17.86 1.54 21.35 17.13 1.78 19.85 16.38 2.05 18.31 15.61 2.37 16.69 14.81 2.74
12
62 (16.7) 23.91 23.02 1.34 22.58 22.36 1.54 21.30 21.30 1.78 20.04 20.04 2.05 18.71 18.71 2.37 17.30 17.30 2.74
57 (13.9) 23.64 23.64 1.34 22.47 22.47 1.54 21.27 21.27 1.78 20.01 20.01 2.05 18.69 18.69 2.37 17.28 17.28 2.74
72 (22.2) 29.05 16.16 1.33 27.34 15.47 1.54 25.58 14.77 1.77 23.77 14.06 2.05 21.88 13.33 2.37 19.90 12.58 2.74
67 (19.4) 26.44 20.51 1.34 24.88 19.76 1.55 23.28 18.99 1.79 21.65 18.21 2.06 19.94 17.40 2.38 18.16 16.54 2.75
900 63 (17.2)†† 24.56 19.64 1.35 23.12 18.90 1.56 21.63 18.14 1.79 20.10 17.36 2.07 18.53 16.56 2.39 16.89 15.71 2.76
62 (16.7) 24.64 23.75 1.35 23.23 23.23 1.56 21.96 21.96 1.79 20.63 20.63 2.07 19.24 19.24 2.38 17.76 17.76 2.75
57 (13.9) 24.42 24.42 1.35 23.20 23.20 1.56 21.93 21.93 1.79 20.61 20.61 2.07 19.21 19.21 2.38 17.74 17.74 2.75
CH16NA030---B Outdoor Section With FX4DN(B,F)037L Indoor Section
72 (22.2) 34.74 18.39 1.78 33.09 17.76 1.98 31.33 17.09 2.20 29.42 16.38 2.45 27.35 15.63 2.74 25.12 14.82 3.08
67 (19.4) 31.56 22.65 1.78 30.07 22.02 1.98 28.48 21.35 2.20 26.78 20.65 2.46 24.93 19.90 2.75 22.94 19.09 3.08
875 63 (17.2†† 29.27 21.78 1.78 27.89 21.15 1.98 26.43 20.49 2.21 24.87 19.80 2.46 23.18 19.06 2.75 21.36 18.26 3.08
62 (16.7) 28.78 26.78 1.78 27.46 26.13 1.98 26.07 25.42 2.21 24.61 24.42 2.46 23.19 23.19 2.75 21.67 21.67 3.08
57 (13.9) 27.94 27.94 1.78 26.87 26.87 1.98 25.74 25.74 2.21 24.51 24.51 2.46 23.15 23.15 2.75 21.64 21.64 3.08
72 (22.2) 35.24 19.11 1.82 33.54 18.47 2.02 31.70 17.79 2.24 29.73 17.07 2.49 27.59 16.30 2.78 25.29 15.48 3.11
67 (19.4) 32.04 23.83 1.82 30.49 23.19 2.02 28.85 22.51 2.24 27.08 21.79 2.49 25.18 21.02 2.78 23.13 20.18 3.11
975 63 (17.2†† 29.72 22.87 1.82 28.30 22.24 2.02 26.78 21.56 2.24 25.17 20.85 2.49 23.44 20.09 2.78 21.56 19.27 3.11
62 (16.7) 29.32 28.34 1.82 27.97 27.61 2.02 26.69 26.47 2.24 25.26 25.26 2.49 23.81 23.81 2.78 22.21 22.21 3.11
57 (13.9) 28.87 28.87 1.82 27.74 27.74 2.02 26.53 26.53 2.24 25.23 25.23 2.49 23.78 23.78 2.78 22.18 22.18 3.11
72 (22.2) 35.72 19.87 1.83 33.95 19.23 2.02 32.06 18.54 2.24 30.04 17.81 2.50 27.84 17.03 2.79 25.49 16.20 3.12
67 (19.4) 32.48 25.03 1.83 30.89 24.39 2.02 29.20 23.70 2.25 27.34 22.93 2.50 25.45 22.16 2.79 23.35 21.30 3.12
1075 63 (17.2†† 30.16 24.00 1.83 28.69 23.35 2.02 27.13 22.66 2.25 25.48 21.94 2.50 23.70 21.15 2.79 21.79 20.29 3.12
62 (16.7) 29.89 29.78 1.83 28.59 28.59 2.02 27.33 27.32 2.25 25.93 25.93 2.50 24.41 24.41 2.79 22.73 22.73 3.12
57 (13.9) 29.73 29.73 1.83 28.55 28.55 2.02 27.28 27.28 2.25 25.90 25.90 2.50 24.39 24.39 2.79 22.71 22.71 3.12
13
62 (16.7) 41.74 39.72 2.46 39.86 38.75 2.78 37.93 37.64 3.13 36.02 36.02 3.54 34.04 34.04 4.01 31.85 31.85 4.55
57 (13.9) 40.98 40.98 2.46 39.43 39.43 2.77 37.77 37.77 3.13 35.97 35.97 3.54 33.99 33.99 4.01 31.82 31.82 4.55
72 (22.2) 50.60 27.99 2.52 48.12 27.08 2.84 45.50 26.14 3.19 42.72 25.15 3.60 39.73 24.09 4.07 36.58 22.99 4.59
67 (19.4) 46.20 35.36 2.51 44.00 34.46 2.82 41.65 33.51 3.18 39.18 32.51 3.59 36.50 31.42 4.05 33.64 30.25 4.59
1575 63 (17.2†† 43.05 33.97 2.49 41.00 33.06 2.81 38.85 32.12 3.17 36.57 31.12 3.57 34.10 30.04 4.04 31.46 28.86 4.58
62 (16.7) 42.62 42.11 2.49 40.79 40.79 2.81 39.03 39.03 3.17 37.11 37.11 3.58 35.00 35.00 4.05 32.69 32.69 4.58
57 (13.9) 42.38 42.38 2.49 40.73 40.73 2.81 38.98 38.98 3.17 37.06 37.06 3.58 34.96 34.96 4.05 32.66 32.66 4.58
CH16NA048---B Outdoor Section With FX4DN(B,F)061L Indoor Section
72 (22.2) 58.07 29.24 2.80 55.36 29.79 3.22 52.51 30.20 3.71 49.43 30.41 4.27 46.11 30.42 4.93 42.57 30.23 5.67
67 (19.4) 53.00 36.08 2.79 50.57 37.01 3.21 48.00 37.79 3.69 45.23 38.38 4.26 42.21 38.75 4.91 38.97 38.89 5.65
1420 63 (17.2†† 49.29 34.76 2.78 47.05 35.64 3.19 44.69 36.36 3.68 42.13 36.89 4.24 39.35 37.20 4.89 36.34 37.26 5.64
62 (16.7) 48.39 42.71 2.78 46.26 43.99 3.19 43.97 45.08 3.68 41.55 45.90 4.24 39.34 45.23 4.89 36.61 36.61 5.64
57 (13.9) 46.84 46.84 2.77 45.13 45.13 3.19 43.29 43.29 3.67 41.27 41.27 4.24 39.04 39.04 4.89 36.56 36.56 5.64
72 (22.2) 59.07 30.58 2.83 56.23 31.18 3.25 53.24 31.63 3.74 50.06 31.90 4.31 46.62 31.95 4.96 42.99 31.81 5.70
67 (19.4) 53.94 38.22 2.82 51.41 39.25 3.24 48.73 40.13 3.73 45.85 40.80 4.29 42.74 41.25 4.95 39.40 41.46 5.69
1600 63 (17.2†† 50.21 36.77 2.81 47.88 37.73 3.23 45.42 38.54 3.72 42.77 39.14 4.28 39.90 39.52 4.93 36.79 39.63 5.68
62 (16.7) 49.44 45.54 2.81 47.22 46.87 3.23 45.37 46.67 3.72 42.73 42.73 4.28 40.34 40.34 4.93 37.71 37.71 5.68
57 (13.9) 48.62 48.62 2.81 46.78 46.78 3.23 44.83 44.83 3.71 42.67 42.67 4.28 40.29 40.29 4.93 37.66 37.66 5.68
72 (22.2) 59.90 31.99 2.87 56.96 32.65 3.29 53.86 33.16 3.78 50.55 33.48 4.35 47.05 33.60 5.00 43.33 33.52 5.74
67 (19.4) 54.77 40.52 2.85 52.13 41.65 3.28 49.35 42.61 3.77 46.39 43.38 4.33 43.18 43.90 4.99 39.78 44.18 5.73
1800 63 (17.2†† 51.02 38.91 2.85 48.60 39.95 3.26 46.06 40.85 3.75 43.32 41.54 4.32 40.36 41.97 4.97 37.19 42.14 5.72
62 (16.7) 50.90 47.27 2.85 48.40 48.40 3.26 46.31 46.31 3.75 44.01 44.01 4.32 41.48 41.48 4.98 38.71 38.71 5.73
57 (13.9) 50.29 50.29 2.84 48.34 48.34 3.26 46.25 46.25 3.75 43.96 43.96 4.32 41.43 41.43 4.98 38.67 38.67 5.73
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240--- 08. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB — Entering Wet Bulb
14
HEAT PUMP HEATING PERFORMANCE
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
INDOOR AIR
---3 ( ---19.4) 7 ( ---13.9) 17 ( ---8.3) 27 ( ---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
Total
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Capacity MBtuh Total Capacity MBtuh Total
EDB Sys-
CFM Sys. Sys. Sys. Sys. Sys. Sys. Sys.
° F (° C) tem
Total{ Integ* KW† Total{ Integ* KW† Total{ Integ* KW† Total{ Integ* KW† Total{ Integ* KW† Total{ Integ* KW† Total{ Integ* KW† Total{ Integ* KW†
15
875 11.78 10.84 1.87 14.40 13.23 1.90 17.36 15.83 1.95 20.71 18.39 2.00 24.42 22.23 2.05 28.49 28.49 2.10 32.85 32.85 2.16 37.43 37.43 2.22
70
975 11.81 10.86 1.86 14.42 13.25 1.89 17.38 15.85 1.94 20.72 18.40 1.97 24.46 22.26 2.01 28.55 28.55 2.06 32.95 32.95 2.11 37.62 37.62 2.16
(21.1)
1075 11.77 10.83 1.87 14.44 13.27 1.89 17.40 15.86 1.92 20.74 18.42 1.95 24.49 22.28 1.99 28.60 28.60 2.03 33.05 33.05 2.07 37.93 37.93 2.11
875 11.68 10.74 1.95 14.26 13.10 1.99 17.18 15.67 2.04 20.49 18.19 2.10 24.17 21.99 2.15 28.17 28.17 2.21 32.47 32.47 2.27 36.94 36.94 2.33
75
975 11.70 10.76 1.94 14.28 13.12 1.98 17.20 15.68 2.03 20.50 18.20 2.07 24.18 22.00 2.12 28.22 28.22 2.16 32.57 32.57 2.22 37.28 37.28 2.27
(23.9)
1075 11.73 10.79 1.94 14.30 13.14 1.98 17.22 15.70 2.02 20.51 18.22 2.05 24.21 22.03 2.09 28.27 28.27 2.13 32.66 32.66 2.17 37.35 37.35 2.22
CH16NA036-B Outdoor Section With FX4DN(B,F)049L Indoor Section
1050 12.02 11.06 1.86 16.26 14.95 1.99 20.98 19.12 2.10 25.06 22.25 2.18 29.70 27.03 2.27 35.13 35.13 2.40 41.72 41.72 2.57 49.55 49.55 2.76
65
1200 12.24 11.26 1.87 16.51 15.17 1.98 21.20 19.33 2.09 25.34 22.51 2.16 30.05 27.35 2.24 35.66 35.66 2.36 42.37 42.37 2.50 50.02 50.02 2.69
(18.3)
1350 12.42 11.43 1.88 16.74 15.38 1.99 21.41 19.52 2.08 25.57 22.71 2.15 30.35 27.62 2.22 35.96 35.96 2.33 42.75 42.75 2.46 50.20 50.20 2.65
1050 11.39 10.48 1.95 15.69 14.42 2.08 20.56 18.74 2.20 24.66 21.91 2.29 29.23 26.60 2.38 34.55 34.55 2.51 40.96 40.96 2.68 48.73 48.73 2.87
70
1200 11.59 10.67 1.96 15.94 14.64 2.08 20.80 18.96 2.19 24.92 22.13 2.27 29.56 26.90 2.35 35.00 35.00 2.47 41.59 41.59 2.62 49.25 49.25 2.80
(21.1)
1350 11.78 10.84 1.97 16.15 14.84 2.08 21.01 19.15 2.19 25.14 22.33 2.26 29.85 27.16 2.33 35.36 35.36 2.44 42.06 42.06 2.57 49.49 49.49 2.76
1050 10.74 9.88 2.03 15.11 13.89 2.17 19.47 17.75 2.28 24.28 21.56 2.40 28.76 26.17 2.50 33.99 33.99 2.62 40.52 40.52 2.81 47.92 47.92 3.00
75
1200 10.95 10.08 2.04 15.35 14.11 2.17 19.83 18.08 2.28 24.51 21.77 2.38 29.09 26.47 2.46 34.42 34.42 2.58 41.14 41.14 2.74 48.46 48.46 2.92
(23.9)
1350 11.12 10.23 2.06 15.56 14.30 2.18 20.57 18.75 2.29 24.73 21.97 2.37 29.36 26.72 2.45 34.77 34.77 2.55 41.32 41.32 2.69 48.74 48.74 2.88
CH16NA042-B Outdoor Section With FX4DN(B,F)049L Indoor Section
1240 17.06 15.70 2.29 21.26 19.54 2.42 25.65 23.38 2.51 30.43 27.03 2.63 35.69 32.48 2.76 41.43 41.43 2.90 47.26 47.26 3.06 53.52 53.52 3.22
65
1400 17.13 15.76 2.29 21.31 19.59 2.41 25.67 23.41 2.49 30.46 27.06 2.60 35.80 32.58 2.71 41.54 41.54 2.84 47.45 47.45 2.97 53.86 53.86 3.11
(18.3)
1575 17.21 15.83 2.29 21.38 19.64 2.39 25.71 23.44 2.47 30.51 27.09 2.57 35.91 32.68 2.68 41.66 41.66 2.79 47.65 47.65 2.91 54.19 54.19 3.04
1240 16.95 15.59 2.41 20.99 19.29 2.55 25.40 23.16 2.64 30.14 26.77 2.77 35.29 32.11 2.90 41.00 41.00 3.05 46.69 46.69 3.21 52.84 52.84 3.37
70
1400 17.03 15.67 2.41 20.84 19.15 2.53 25.43 23.18 2.61 30.17 26.79 2.73 35.34 32.16 2.85 40.87 40.87 2.98 46.88 46.88 3.12 53.33 53.33 3.27
(21.1)
1575 17.12 15.75 2.41 20.90 19.21 2.52 25.47 23.22 2.60 30.21 26.83 2.70 35.39 32.21 2.81 40.97 40.97 2.93 47.07 47.07 3.05 53.65 53.65 3.19
1240 16.67 15.34 2.53 20.55 18.89 2.67 25.15 22.93 2.78 29.84 26.50 2.91 34.92 31.78 3.06 40.36 40.36 3.20 46.14 46.14 3.36 52.31 52.31 3.54
75 1400 16.73 15.39 2.53 20.60 18.93 2.65 25.18 22.96 2.75 29.87 26.53 2.87 34.96 31.81 3.00 40.44 40.44 3.13 46.32 46.32 3.27 52.63 52.63 3.43
(23.9)
1575 16.81 15.47 2.53 20.66 18.99 2.65 25.21 22.99 2.74 29.91 26.56 2.84 35.01 31.86 2.96 40.54 40.54 3.08 46.50 46.50 3.20 52.94 52.94 3.34
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
} The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
16
{ The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.
EDB — Entering Dry Bulb
GUIDE SPECIFICATIONS AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
CH16NA
GENERAL 1--1/2 TO 5 NOMINAL TONS
17
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C).
3. Maximum outdoor operating air temperature for cooling mode is 125_F (51.7_C).
4. Minimum outdoor operating air temperature for heating mode is –10_F (–23_C).
5. Maximum outdoor operating air temperature for heating mode is 66_F (18.9_C).
6. For reliable operation, unit should be level in all horizontal planes.
7. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or elevation differences between indoor and outdoor units
greater than 20 ft (6.1 m), consult Residential Piping and Longline Guideline and Service Manual available from equipment distribut-
or.
8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
10. Do not apply capillary tube indoor coils to these units.
11. Factory--supplied filter drier must be installed.
Copyright 2018 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 07/18 Catalog No:CH16NA ---02PD
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: CH16NA--- 01PD
18