1. The fire alarm system for the Accommodation Block-E project has a 4-loop addressable fire alarm panel that requires a minimum of 20.2 amp-hours of battery backup. 2. The system includes 181 smoke detectors, 17 manual call points, and 148 sounder bases, and requires 24 hours of standby time and 15 minutes of alarm time. 3. Standards and calculations referenced include NFPA 72: 2007, BS 5839 Part 1, and the National Electric Code for determining wire resistance and derating factors for the battery size calculation.

Uploaded by

Roni Philip
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
118 views1 page

4-Loop Panel No.2

1. The fire alarm system for the Accommodation Block-E project has a 4-loop addressable fire alarm panel that requires a minimum of 20.2 amp-hours of battery backup. 2. The system includes 181 smoke detectors, 17 manual call points, and 148 sounder bases, and requires 24 hours of standby time and 15 minutes of alarm time. 3. Standards and calculations referenced include NFPA 72: 2007, BS 5839 Part 1, and the National Electric Code for determining wire resistance and derating factors for the battery size calculation.

Uploaded by

Roni Philip
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project Name: Camp-2,Galfar IN-House Project Standby Hours: 24

Project ID: CAMP-2-SLD-FA Alarm Mins: 15


Prepared By: Viswanath Derating Factor: 1.2
Date: 23-Mar-2022 Number of Loop: 4

Addressable Fire Alarm Panel


Panel ID: AA504 Model: AA504 (4-Loop Panel)
Location: Accommodation Block-E

Current Draw
Model Description Qty REFERENCE
Standby Alarm
AA504 Control Panel 1 0.420 2.700
DD501 Smoke Detector 181 0.127 0.362 NFPA 72 : 2007 ; 4.4.1.5.30* Capacity
DD502 Heat Detector 0 0.000 0.000 1. The Fire Alarm Systems require 24 Hours of Standby
CP312 Manual Call Point 17 0.012 0.051 time and in alarm for 5 minutes (Evacuate)
SA340A Sounder 2 0.001 0.006 2. The Fire Alarm Systems require 24 Hours of Standby
SA340 Sounder -W/P 1 0.001 0.003 time and in alarm for 15 minutes (Emergency Voice/Alarm
ST805 Sounder base 148 0.104 0.444 3. Auxiliary and Remote Station Fire Alarm System require
S-A4045 Input/Output Module 0 0.000 0.000 60 Hours of Standby time
0 0.000 0.000
0 0.000 0.000 BS 5839 Part 1
0 0.000 0.000 1. The Fire Alarm Systems require 24 Hours of Standby
0 0.000 0.000 time and in alarm for 30 minutes (Evacuate/ Emergency
0 0.000 0.000 Voice)
0 0.000 0.000
0 0.000 0.000
Total Standby Current (Amps) 0.664 3.566 Total Alarm Current (Amps)
Standby Time In Hours 24 0.250 Alarm Time In Minutes / 60 (15 Mins)
Total Standby AH Require d 15.943 0.892 Total Alarm AH Required
Total Combined AH Required 16.83
Multiply By The Derating Factor 1.20
Minimum Battery AmpHours Required 20.20

Wire resistance is taken from Chapter 9 Table 8 of the National Electric Code (NFPA70).