4-Loop Panel No.2
4-Loop Panel No.2
Current Draw
Model Description Qty REFERENCE
Standby Alarm
AA504 Control Panel 1 0.420 2.700
DD501 Smoke Detector 181 0.127 0.362 NFPA 72 : 2007 ; 4.4.1.5.30* Capacity
DD502 Heat Detector 0 0.000 0.000 1. The Fire Alarm Systems require 24 Hours of Standby
CP312 Manual Call Point 17 0.012 0.051 time and in alarm for 5 minutes (Evacuate)
SA340A Sounder 2 0.001 0.006 2. The Fire Alarm Systems require 24 Hours of Standby
SA340 Sounder -W/P 1 0.001 0.003 time and in alarm for 15 minutes (Emergency Voice/Alarm
ST805 Sounder base 148 0.104 0.444 3. Auxiliary and Remote Station Fire Alarm System require
S-A4045 Input/Output Module 0 0.000 0.000 60 Hours of Standby time
0 0.000 0.000
0 0.000 0.000 BS 5839 Part 1
0 0.000 0.000 1. The Fire Alarm Systems require 24 Hours of Standby
0 0.000 0.000 time and in alarm for 30 minutes (Evacuate/ Emergency
0 0.000 0.000 Voice)
0 0.000 0.000
0 0.000 0.000
Total Standby Current (Amps) 0.664 3.566 Total Alarm Current (Amps)
Standby Time In Hours 24 0.250 Alarm Time In Minutes / 60 (15 Mins)
Total Standby AH Require d 15.943 0.892 Total Alarm AH Required
Total Combined AH Required 16.83
Multiply By The Derating Factor 1.20
Minimum Battery AmpHours Required 20.20
Wire resistance is taken from Chapter 9 Table 8 of the National Electric Code (NFPA70).