Service Manual: EUWA ( ) 40-120K (X)
Service Manual: EUWA ( ) 40-120K (X)
Service Manual: EUWA ( ) 40-120K (X)
1
3
8 T1 T2 8 12
7
9 P1 P2 9
10 11
16
14 13 11
4899
Service Manual
EUWA(*)40-120K(X)
Air-cooled waterchillers
Daikin Europe NV
ESIE98–03
Table of Contents
1
1 Introduction
Part 1
System Outline 1-1
3
1 General Outline
2 Piping Layout
5
2.1 What Is in This Chapter 1-21
2.2 Functional Diagram Refrigeration Circuit 1-22
2.3 Parts Table of the Refrigeration Circuit 1-26
3 Wiring Layout
Table of Contents i
ESIE98–03
Part 2
1 Functional Description 2-1
1 Functional Control
ii Table of Contents
ESIE98–03
Part 3
Troubleshooting 3-1 1
4
3 Checking the Inputs and Outputs
4 Troubleshooting
Part 4
1 Commissioning and Test Run 4-1
3 Refrigerant R-134a
4 3.1 What Is in This Chapter? 4-11
3.2 What Is New? 4-12
3.3 Characteristics 4-13
5 Part 5
Maintenance 5-1
1 Maintenance
Appendix A
Photo parts A-1
Appendix B
Drawings B-1
Index i
iv Table of Contents
ESIE98–03 Introduction
1 Introduction
EUWA(*)40-120K(X) The Daikin EUWA(*)40-120K(X) air-cooled water chillers are designed for outdoor installation. The
chiller types units are available in 6 standard sizes for cooling applications only.
The EUWA(*)40-120K(X) units can be combined with Daikin fan coil units or air handling units for air
3
conditioning purposes. They can also be used to supply water for process cooling.
Before starting up the unit for the first time, make sure that it has been properly installed. Consult the
check lists in ‘Pre-Test Run Checks’ on page 4-3.
You will find the following tools at the back of the manual:
■ a list of parts in function of the integrated photos. Refer to Appendix A Photo parts.
4
■ a list of drawings. Refer to Appendix B Drawings.
■ an index. Refer to Index.
Usage of the
manual
The present service manual gives you all the information you need to do the necessary repair and
maintenance tasks for these waterchillers operating with HCFC 22 (EUWA(*)40-120K) and
5
HFC 134a (EUWA(*)40-120KX). It is intended for and should only be used by qualified engineers.
It is not intended to replace technical know-how acquired through training and experience.
The basic rules of good workmanship still apply, but should be more strictly applied on
R-134a (EUWA(*)40-120KX) applications.
Approvals The asterix (*) in EUWA(*)40-120K(X) refers to B, M, T, S or D, which are abbreviations for:
Using icons Icons are used to attract the attention of the reader to specific information. The meaning of each icon
is described in the table below:
Type of
Icon Description
information
Caution A ‘caution’ is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an
unexpected result or has to restart (part of) a procedure.
v
Introduction ESIE98–03
Type of
1 Icon
information
Description
Reference A ‘reference’ guides the reader to other places in this binder or in this
manual, where he/she will find additional information on a specific
topic.
vi
ESIE98–03
1
Part 1
System Outline
Introduction The purpose of this part is to give an outline of all the relevant elements in an installation of the
EUWA(*)40-120K(X) chiller types. Once all the elements of the installation are described in short and
3
the installation set-up is understood, a functional description of all elements will be given in the
following parts of this book.
Part 1
1
1 General Outline
Introduction In this chapter you will find the outlook drawing and the installation outline of the air-cooled water
chillers EUWA(*)40-120K(X).
3
Overview This chapter covers the following topics:
Nominal cooling
capacity(1) 101 kW 129 kW 161 kW
38.5 kW 52.7 kW 59 kW
Nominal cooling input(1)
MAIN COMPONENTS
3 Compressor
type semi-hermetic single screw semi-hermetic single screw semi-hermetic single screw
speed 2880 rpm 2880 rpm 2880 rpm
crankcase heater 150 W 150 W 150 W
model x n° ZH3LSFLYE ZH5MLFLYE ZH5LLFLYE
Evaporator
type 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry
4 min.water volume system
expansion: EHS/S 155 SX BT
1700 l
expansion: EHS/S 155 SX BT
1700 l
expansion: EHS/S 220 SX BT
2100 l
water flow rate Min: 185 Max: 737 l/min Min: 187.5 Max: 750 l/min Min: 230 Max: 920 l/min
nom. water pressure drop 21 kPa 25 kPa 23 kPa
insulation material PVC nitril foam PVC nitril foam PVC nitril foam
Condenser
Piping connections
evap. water in/outlet 3’’ gas 3’’ gas flexible joint Ø 114.3
evaporator water drain 1/2” gas 1/2” gas 1/2” gas
relief device outlet compressor 1”NPT compressor 2x1”NPT compressor 2x1”NPT
Refrigerant circuit
refrigerant type R-22 R-22 R-22
refrigerant charge 33 kg 39 kg 45 kg
refrigerant control thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve
oil type SUNISO 4GSD SUNISO 4GSD SUNISO 4GSD
oil charge volume 7.5 l 10 l 10 l
n° of circuits 1 1 1
Dimensions (h x w x d) 2135 x 3980 x 1110 mm 2135 x 3980 x 1110 mm 2135 x 3980 x 1110 mm
Weight
machine weight 1205 kg 1345 kg 1530 kg
operation weight 1245 kg 1385 kg 1585 kg
Casing
material polyester painted galvanised polyester painted galvanised polyester painted galvanised
steel plate steel plate steel plate
colour ivory white / Munsell code ivory white / Munsell code ivory white / Munsell code
5Y7.5/1 5Y7.5/1 5Y7.5/1
1 EUWA(*)80-120K In the following table you will find the technical specifications of chiller types EUWA(*)80-120K:
Nominal cooling
capacity(1) 202 kW 258 kW 300 kW
77 kW 106 kW 115 kW
Nominal cooling input(1)
MAIN COMPONENTS
Compressor
type semi-hermetic single screw semi-hermetic single screw semi-hermetic single screw
speed 2880 rpm 2880 rpm 2880 rpm
3 crankcase heater
model x n°
150 W
2 x ZH3LSFLYE
150 W
2 x ZH5MLFLYE
150 W
2 x ZH5LLFLYE
Evaporator
type 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry
expansion: EHD/S 270 SX BT expansion: EHD/S 310 SX BT expansion: EHD/S 420 SX BT
min.water volume system 2400 l 3000 l 3600 l
Condenser
type cross fin coil / Hi-X-tubes and cross fin coil / Hi-X-tubes and cross fin coil / Hi-X-tubes and
chromate coated waffle louvre chromate coated waffle louvre chromate coated waffle louvre
fins fins fins
Piping connections
evap. water in/outlet flexible joint Ø 141.3 flexible joint Ø 141.3 flexible joint Ø 168.3
evaporator water drain 1/2” FPT 1/2” FPT 1/2” FPT
relief device outlet compressor 2x1”NPT compressor 2x2x1”NPT compressor 2x2x1”NPT
Refrigerant circuit
refrigerant type R-22 R-22 R-22
refrigerant charge 2x36 kg 2x40 kg 2x47 kg
refrigerant control thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve
oil type SUNISO 4GSD SUNISO 4GSD SUNISO 4GSD
oil charge volume 7.5 l 10 l 10 l
n° of circuits 2 2 2
Dimensions (h x w x d) 2156 x 3980 x 2210 mm 2156 x 3980 x 2210 mm 2156 x 3980 x 2210 mm
Weight
machine weight 2500 kg 2750 kg 2950 kg
operation weight 2595 kg 2840 kg 3085 kg
Casing
material polyester painted galvanised steel polyester painted galvanised steel polyester painted galvanised steel
plate plate plate
colour ivory white / Munsell code ivory white / Munsell code ivory white / Munsell code
5Y7.5/1 5Y7.5/1 5Y7.5/1
■
ZL: leaving water evaporator=-10 °C
OP10: anti-freeze protection kit (evaporator heatertape)
3
■ OP12: suction stopvalve
■ OP52: main isolator switch
■ OP57: ampere & voltmeter
(1):
Nominal conditions are as follows: 4
■ entering/leaving water temperature 12/7 °C
■ ambient air temperature 35 °C
■ power input is total input:
compressor + control circuit
■ leaving evaporator water temperature from 4 °C to 20 °C (pull-down condition to 25 °C). 5
1 EUWA(*)40-60KX In the following table you will find the technical specifications of chiller types EUWA(*)40-60KX:
Nominal cooling
capacity(1) 111 kW 140 kW 160 kW
39.1 kW 53.7 kW 64 kW
Nominal cooling input(1)
MAIN COMPONENTS
Compressor
type semi-hermetic single screw semi-hermetic single screw semi-hermetic single screw
speed 2880 rpm 2880 rpm 2880 rpm
3 crankcase heater
model x n°
150 W
ZHA5LLFLYE / ZHA5LLFLTE
150 W
ZHA7SLFLYE / ZHA7SLFLTE
150 W
ZHA7MLFLYE / ZHA7MLFLTE
Evaporator
type 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry
expansion: ES-185 expansion: ES-220 expansion: ES-270
min.water volume system 2400 l 2750 l 3600 l
Condenser
type cross fin coil / Hi-X-tubes and cross fin coil / Hi-X-tubes and cross fin coil / Hi-X-tubes and
chromate coated waffle louvre chromate coated waffle louvre chromate coated waffle louvre
fins fins fins
Piping connections
evap. water in/outlet flexible joint Ø 114.3 flexible joint Ø 114.3 flexible joint Ø 141.3
evaporator water drain 1/2” FPT 1/2” FPT 1/2” FPT
relief device outlet compressor 1”NPT compressor 1”NPT compressor 1”NPT
Refrigerant circuit
refrigerant type R-134a R-134a R-134a
refrigerant charge 30 kg 45 kg 50 kg
refrigerant control thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve
oil type IDEMITSU FVC68D IDEMITSU FVC68D IDEMITSU FVC68D
oil charge volume 7.5 l 10 l 10 l
n° of circuits 1 1 1
Dimensions (h x w x d) 2135 x 3980 x 1110 mm 2135 x 3980 x 1110 mm 2135 x 3980 x 1110 mm
Weight
machine weight 1391 kg 1600 kg 1705 kg
operation weight 1439 kg 1655 kg 1798 kg
Casing
material polyester painted galvanised polyester painted galvanised polyester painted galvanised
steel plate steel plate steel plate
colour ivory white / Munsell code ivory white / Munsell code ivory white / Munsell code
5Y7.5/1 5Y7.5/1 5Y7.5/1
1 EUWA(*)80-120KX In the following table you will find the technical specifications of chiller types EUWA(*)80-120KX:
Nominal cooling
capacity(1) - - -
- - -
Nominal cooling input(1)
Capacity steps - - -
MAIN COMPONENTS
Compressor
type semi-hermetic single screw semi-hermetic single screw semi-hermetic single screw
speed 2880 rpm 2880 rpm 2880 rpm
3 crankcase heater
model x n°
-
2xZHA5LLFLYE /
-
2xZHA7SLFLYE /
-
2xZHA7MLFLYE /
2xZHA5LLFLTE 2xZHA7SLFLTE 2xZHA7MLFLTE
Evaporator
type 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry 2 pass, 1 circuit, shell & tube dry
expansion: ES-360 expansion: ES-420 expansion: ES-470
Condenser
type cross fin coil / Hi-X-tubes and cross fin coil / Hi-X-tubes and cross fin coil / Hi-X-tubes and
chromate coated waffle louvre chromate coated waffle louvre chromate coated waffle louvre
Piping connections
evap. water in/outlet flexible joint Ø 141.3 flexible joint Ø 168.3 flexible joint Ø 168.3
evaporator water drain 1/2” FPT 1/2” FPT 1/2” FPT
relief device outlet - - -
Refrigerant circuit
refrigerant type R-134a R-134a R-134a
refrigerant charge 30 kg 45 kg 50 kg
refrigerant control thermostatic expansion valve thermostatic expansion valve thermostatic expansion valve
oil type IDEMITSU FVC68D IDEMITSU FVC68D IDEMITSU FVC68D
oil charge volume 7.5 l 10 l 10 l
n° of circuits 2 2 2
Dimensions (h x w x d) 2156 x 2210 x 3980 mm 2156 x 2210 x 3980 mm 2156 x 2210 x 3980 mm
Weight
machine weight 2523 kg 2884 kg 3005 kg
operation weight 2603 kg 3018 kg 3130 kg
Casing
material polyester painted galvanised polyester painted galvanised polyester painted galvanised
steel plate steel plate steel plate
colour ivory white / Munsell code ivory white / Munsell code ivory white / Munsell code
5Y7.5/1 5Y7.5/1 5Y7.5/1
Some of the data of EUWA(*)80-120KX were not available when this Service Manual was composed.
Therefore, we refer to Engineering Data to obtain this information.
Power supply Y1 Y1 Y1 Y1 Y1 Y1
Compressor
phase 3~ 3~ 3~ 3~ 3~ 3~
starting current 129 A 171 A 234 A 129 A 171 A 234 A
max. running current 87 A 111 A 133 A 87 A 111 A 133 A
starting method star-delta star-delta star-delta star-delta star-delta star-delta
voltage 400 V 400 V 400 V 400 V 400 V 400 V
voltage
phase 3~ 3~ 3~ 3~ 3~ 3~
frequency 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz
voltage 400 V 400 V 400 V 400 V 400 V 400 V
4 voltage tolerance
Control circuit
±10 V ±10 V ±10 V ±10 V ±10 V ±10 V
phase 1~ 1~ 1~ 1~ 1~ 1~
recommended fuses factory installed factory installed factory installed factory installed factory installed factory installed
voltage 230 V 230 V 230 V 230 V 230 V 230 V
Unit
(1):
Nominal conditions are as follows:
■ entering/leaving water temperature 12/7 °C
■ ambient air temperature 35 °C
■ power input is total input:
compressor + control circuit
■ leaving evaporator water temperature from 4 °C to 20 °C (pull-down condition to 25 °C).
EUWA(*)40-120KX In the following table you will find the electrical specifications of chiller types EUWA(*)40-120KX:
1
Model EUWA(*)40KX EUWA(*)50KX EUWA(*)60KX EUWA(*)80KX EUWA(*)100KX EUWA(*)120KX
Compressor
phase 3~ 3~ 3~ 3~ 3~ 3~
starting current 172 A/363 A 193 A/400 A 250 A/504 A - - -
max. running current 86.5 A/145 A 111 A/210 A 133 A/245 A - - -
starting method star-delta star-delta star-delta star-delta star-delta star-delta
voltage 400 V/230 V 400 V/230 V 400 V/230 V 400 V/230 V 400 V/230 V 400 V/230 V
nominal running current 62 A/107 A 89 A/161 A 99 A/180 A 62 A/107 A 89 A/161 A 99 A/180 A
recommended fuses factory installed factory installed factory installed factory installed factory installed factory installed
Control circuit
phase 1~ 1~ 1~ 1~ 1~ 1~
4
recommended fuses factory installed factory installed factory installed factory installed factory installed factory installed
voltage 230 V 230 V 230 V 230 V 230 V 230 V
Unit
nominal running current(1) 76 A/130 A 104 A/186 A 114 A/205 A 152 A/260 A 208 A/372 A 228 A/410 A
starting current
recommended fuses
172 A/363 A
3 x 125 aM/
193 A/400 A
3 x 160 aM/
250 A/504
3 x 160 aM/
-
3 x 200 aM/
-
3 x 250 aM/
-
3 x 315 aM/
5
3 x 200 aM 3 x 250 aM 3 x 315 aM 3 x 400 aM 3 x 500 aM 3 x 630 aM
max. running current 101 A/168 A 126 A/235 A 148 A/270 A 202 A/336 A 252 A/470 A 296 A/540 A
(1):
Nominal conditions are as follows:
■ entering/leaving water temperature 12/7 °C
■ ambient air temperature 35 °C
■ power input is total input:
compressor + control circuit
■ leaving evaporator water temperature from 4 °C to 20 °C (pull-down condition to 25 °C).
The data of EUWA(*)80-120KX were not available when this Service Manual was composed.
Therefore, we refer to Engineering Data to obtain this information.
EUWA(*)40-60K The figure below displays the outlook of the chiller type EUWA(*)40-60K:
1110
173
3980
2
2135
10 DETAIL A 13
5
376.5
236
286
100
C C
3000
Required space
around the unit for
service and air intake
For a description of the components of the outlook drawings, refer to ‘Main components table’ on
page 1-18.
Photo display of
EUWA(*)40-120K(X)
The photo below displays the outlook of the chiller type EUWA(*)40-60K(X):
1
EUWA(*)80-120K The figure below displays the outlook of the chiller type EUWA(*)80-120K:
DETAIL A (1/10)
2210
4
FOR INSTALLATION
1000
5
1000
3980
C
D
1000
1000
3000
13
2156
DETAIL A 4
19 5
Required space
around the unit for
448
446
alve
CHILLED WATER
TOESTEL A B C D IN OUT
EUWAB80K 2280 970 287 387 ø 141.3 ø 141.3
EUWAB100K 2280 970 287 387 ø 141.3 ø 141.3
EUWAB120K 2250 1013 362 512 ø 168.3 ø 168.3
For a description of the components of the outlook drawings, refer to ‘Main components table’ on
page 1-18.
1 EUWA(*)40-60KX The figure below displays the outlook of the chiller type EUWA(*)40-60KX:
1110
173
3980
2 2
2135
10 DETAIL A 13
3
376.5
236
286
100
B A
DETAIL A (1/10)
CHILLED WATER
4
1000
C
D
3000
5 Required space
around the unit for
service and air intake
For a description of the components of the outlook drawings, refer to ‘Main components table’ on
page 1-18.
EUWA(*)80-120KX The figure below displays the outlook of the chiller type EUWA(*)80-120KX:
DETAIL A (1/10)
1
2210
FOR INSTALLATION
1000
1000
3980
C
D
1000
1000
3
3000
2156
12
DETAIL A 4
19 5
Required space
around the unit f or
446
4
396
453
154
100
40 2125 334 E F E
A B
CHILLED WATER
TOESTEL A B C D E F IN OUT
EUWA*80KXY1
EUWA*100KXY1
EUWA*120KXY1
2280
2280
2250
998
998
1013
287
287
362
387
387
512
1100
950
950
1100
1400
1400
ø 141.3
ø 168.3
ø 168.3
ø 141.3
ø 168.3
ø 168.3 5
For a description of the components of the outlook drawings, refer to ‘Main components table’ on
page 1-18.
1 Main components
table
The following table introduces the different parts of the outlook drawings for EUWA(*)40-120K(X):
N° Components
1 Evaporator
2 Condenser
4 Discharge stopvalve
5 Liquid stopvalve
7 Chilled water in
3 8 Chilled water out
17 Switch box
Typical installation The illustration below shows you a typical installation outline. Some of these installation parts are not
outline necessarily included in all the chillers described in this manual.
CHILLER
5
SECONDARY WATER CIRCUIT 3
2
1
3 4
6
8 T1 12
T2 8
7 5
9 P1 P2 9
10
16 11
13 11
14
4899
Part 1
1
2 Piping Layout
Introduction In this chapter we will only explain the internal refrigeration circuit. The water piping is considered
common practice and is therefore not explained.
3
Overview This chapter covers the following topics:
Y11S
10 Y12S
SET 25 BAR
Y13S
B1P 12
S1PH S14PH
B2P
7 12
3 M1C
SUCTION
STOPVALVE
(OPTIONAL)
13 1
WATER OUT
WATER IN
R3T
R4T
8 16 16 8
SAFETY VALVE
4
AT 28 BAR
6
S3T ONLY FOR
40HP
1/2"
EVAPORATOR
18 9
SAFETY VALVE Y14S 15 5
AT 28 BAR 4
17
ONLY FOR
50 AND 60HP
1" 11
5
STRAINER
Y15S
CONDENSER
R5T
14
CHECK VALVE FLARE CONN. SCREW CONN. FLANGE CONN. PINCHED PIPE SPINNED PIPE
Functional diagram
EUWA(*)80-120K
The figure below displays the functional diagram of the refrigeration circuit of the chiller types
EUWA(*)80-120K: 1
10
8
Y11S Y21S
Water OUT
Y12S 10 Y22S
16
EVAPORATOR
R4T
Y13S Y23S
12 4 12
7 7
B1P B4P
S1HP S14HP B2P B5P S2HP S15HP
16
R3T 12
12
13
1
M1C 8
Water IN SUCTION
STOPVALVE
(OPTIONAL)
M2C
1 13
3
SUCTION
STOPVALVE
(OPTIONAL)
4
6 15 5 5 15 6
9 17 17 9 18
Condenser Condenser 5
2
R5T
14
CHECK VALVE FLARE CONN. SCREW CONN. FLANGE CONN. PINCHED PIPE SPINNED PIPE
1 Functional diagram
EUWA(*)40-60KX
The figure below displays the functional diagram of the refrigeration circuit of the chiller types
EUWA(*)40-60KX:
Y11S
10
Y12S
7 Y13S
B1P
S1HP S14HP
12 B2P
SUCTION
STOPVALVE
M1C (OPTIONAL)
13 1
1"
3 16 16
WATER OUT
WATER IN
SAFETY VALVES
AT 19 BAR
8 8
R3T
R4T
1 15
4
9
EVAPORATOR
S3T
4
Y14S
5
18 17
11
STRAINER
Y15S
5 2
CONDENSER
R5T 14
CHECK VALVE FLARE CONN. SCREW CONN. FLANGE CONN. PINCHED PIPE SPINNED PIPE
Functional diagram
EUWA(*)80-120KX
The figure below displays the functional diagram of the refrigeration circuit of the chiller types
EUWA(*)80-120KX: 1
WATER OUT
8
Y11S Y21S
EVAPORATOR
16 R4T 4
10 Y12S Y22S 10
7 Y13S Y23S 7
12 12
S1HP S14HP
12 S15HP S2HP
B1P R3T B4P
B2P B5P
WATER IN
3
M1C M2C
13 1 1 13
SUCTION SUCTION
1" STOPVALVE 1"
STOPVALVE
(OPTIONAL) (OPTIONAL)
SAFETY VALVES SAFETY VALVES
AT 19 BAR AT 19 BAR
6 15 6
.
S3T
9
5 5
9
S4T
4
17 17
Y14S Y24S 18
11 11
STRAINER STRAINER
Y15S Y25S
CONDENSER CONDENSER
R5T 14
CHECK VALVE FLARE CONN. SCREW CONN. FLANGE CONN. PINCHED PIPE SPINNED PIPE
2 Air-heat exchanger - The air-heat exchanger is of the cross fin coil type with
(condenser) Hi-X-tubes and chromate coated waffle louvre fins. The
air-cooling discharge is upward.
3 Fan M11F- All fan motors are directly driven single or two speed
3 M14F,
M21F-
motors.
M24F
6 Dryer with charge - The replaceable filter dryer will keep the refrigerant
5 valve system dry. It is equipped with a charge valve.
7 High pressure S1PH, The refrigerant circuit(s) contains 2(4) high pressure
switch S14HP, switches in order to act as a safety for the compressor to
S2HP, switch off.
S15HP
8 Water in- and out- - The water connections exist out of flexible joints or gas
let connections pipe connections straight to the evaporator.
9 Liquid injection Y14S, The liquid injection valve maintains the discharge
solenoid valve Y24S temperature of the compressor by cooling with liquid
from the condenser. It opens on compressor start and
closes on compressor stop.
11 Liquid line solenoid Y15S, This valve shuts off the refrigerant flow when the com-
valve Y25S pressor stops or in case of a power failure. It is used to
prevent liquid backflow from the condenser to the
evaporator in order to avoid wet start and liquid pumping.
12 Low and high B1P, The low and high pressure transmitters (or sensors) are
pressure transmit- B4P, used to gain information in order to perform some con-
ter B2P,B5P trols and also act as safety.
13 Head pressure - This stop valve is used during pump down and service
stop valve work in combination with the liquid line stop valve.
15 Sight glass with - The sight glass with moisture indicator is used to check
moisture indicator the refrigerant shortage and/or moisture level in the
system.
16 Water R3T,R4T The water temperature sensors are used to control the
temperature thermostat function in the outlet or inlet water control.
sensor They can also act as safety.
17 Liquid stop valve - The liquid stop valve shuts off the liquid line in case of
pump down and in case of the procedure to replace the
drier filter. Refer to 4.6 – Filter Procedure on page 3-29.
3
18 Discharge S3T, The discharge temperature protector uses bimetals to
temperature S4T control the discharge temperature.
protector
5
condensers
compressors
1 low pressure
unloader
high pressure
discharge
shut off
transmitter transmitter
valves valve
Compressor
F-Type
5 liquid line
solenoid valve evaporator
liquid stop low pressure
valve service port
inlet water
temperature sensor inlet water sight glass + filter drier charge valve
expansion
moisture indicator 3/8”
valve
12%
40%
70%
ambient thermistor
outlet water
connection
outlet water
temperature
sensor
Part 1
1
3 Wiring Layout
Introduction The purpose of this chapter is to guide you through the switch box and the wiring diagrams. Therefore,
we have used schematic drawings, which indicate and locate the necessary information on both the
switch box and the wiring diagram. 3
Overview This chapter covers the following topics:
page 1-34
4
3.4 – Wiring Diagrams page 1-40
Photo switch box The following picture shows a the main components of the switch box of EUWA(*)80-120K(X):
Switch box
EUWA(*)40-60K(X)
The following figure shows the layout of the switch box for the EUWA(*)40-60K(X) types:
1
TR2
A1
TR1 PE L1 L2 L3
PCB TR3
B3A B7V
reverse phase
Switch box The following figure shows the layout of the switch box for the EUWA(*)80-120K(X):
EUWA(*)80-120K(X) 5
options
TR1 F10S F11S
L3 L2 L1 PE
transformators
power wiring
main contactors
rev. phase
PCB K6M
F12B F13B F8B F9B R1P R2P K1M K2M K3M K4M K5M
fuses
K17S K18S
A1 A2
K1A
K2A
K3A
K4A
K5A
K6A
G 1
J17
G0
3 J9 J8
B8
J1
J11
+24Vcc
1 B7
J19
4 3
2
3
2
B6
AVSS
B5
1 J15 J14 1 B4
J2
AVSS
VG0 1 B3
J20
VG1 B2
Y1 AVSS
Y0 1 B1
5 ID11R
ID11
1 IDCM2
ID10
ID9
J3
J21
ID12R ID8
ID7
ID12 1 ID6
IDCM1
NO11 1
ID5
C11 ID4
J4
NC11 ID3
ID2
NO10 1
J22
ID1
C10
NC10 C1
NO1
J5
NO9
C9 C2
NC9 1 NO2
1
NO8 C3
C8 NO3
NO7 C4
C7 NO4
J24
J6
NO6 C5
C6 NO5
NO13 C12
C13 NO12
1
4898
Description PCB
EUWA(*)40-60K(X)
The following table explains the different components of the EUWA(*)40-60K(X) PCB:
1
Wiring diagram
Block Connection Description
symbol
ID6
ID7
K2A
S8L/S9L
auxiliary relay compressor thermal protector
Wiring diagram
1 Block Connection
symbol
Description
Description PCB’s The following table explains the different blocks of the EUWA(*)80-120K(X) PCB A and B:
EUWA(*)80-120K(X)
Wiring diagram
Block Connection Description
symbol
Wiring diagram
Block Connection
symbol
Description
1
B1 R5T ambient temperature sensor
B1 — —
4
B2 — —
B3 — —
B6 — —
ID9 — —
ID10 — —
Wiring diagram
1 Block Connection
symbol
Description
4 J5A
C1-NO1 K3M star contactor circuit 1
5 C3-NO3
C4-NO4
K1M
C4-NO4 — —
J6B
C5-NO5 — —
C12-NO12 — —
ID11-ID11R — —
J21B
ID12-ID12R — —
Wiring diagram
Block Connection
symbol
Description
1
C9-NO9-NC9 K7F fan step 1 contactor circuit 1
5
User Terminal
DIPSWITCH Address = 3
C A
ON t-device
OFF
SW 1 2 3 4 5 6
A B
Address = 1 Address = 2
DIPSWITCH DIPSWITCH
ON ON
OFF OFF
SW 1 2 3 4 5 6 SW 1 2 3 4 5 6
Part 1
Wiring diagram
EUWA(*)40-60K(X)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A1
1
22 23 24
10
2
75 76
80 73 71
2
3
98
L1
L2
L3
85
3 1
68
66
K17S 97
70
V1 F6B 77 78 79
25
75
74
72
71
C4 C5
R1P OP57 83
2
1
1
L1 S5E K1M J6
p>
86
583
4 2 S1PH 84
2
L2 1 (1A) 4 2
22
J3 ID7 J4 ID4 J3 ID9 J3 ID10
3
L3 NO4 NO5
73
20
1
J4 ID1 p> S14PH
69
yellow
84
white
4 2
83
67
65
A1 +15 0 -15 230 400 0 230 27 81 74 72
84
26
OP57 TR1 TR2
250VA 24V 30VA 15
E2 J4 ID2
21
R1P
20
S1
E1 230V S2
orange
blue
¬ 16 18
81
82
88
2
4
7
J4 ID3
F8B
1 3 5 1 3 5 1 3 5 1 K2A
K1M K2M K3M F9B 2 3
79
80
red
red
2 4 6 2 4 6 2 4 6
4 J2 J1
1 3 5
24V B7 +24V B8
1 B1 AVSS B2 B3 AVSS B4 B5 AVSS B6
¬ J3 ID6
K3A
F12B G0 G TR3
6
24V 10VA
77
J17 2 2 3
78
¬
8 black
9 black
22
0...20mA
0...20mA
4 5
96
W
U
POWER
4...20mA
4...20mA
U V W 2 4 6 2 SUPPLY K17S
1 3 5 J4 ID5 95 R5T R3T R4T
S5E CONTROLLER
BRN
BRN
8+
8+
10 -
10 -
BLU
K17S
t˚ t˚ t˚
76
0...500V
1 (10A)
2 4 6
1
3
1
3
-1...34bar
-1...12bar
A1 K1A
3
J4 IDCM1 J3 IDCM2
1
2
1
2
0...5A
M 11
M1C A1 B3A V1 B7V
3
A2 OP57 OP57
13 23 33 13 23 33 28 B2P B1P
K8F K7F
Y
X Z Y 14 24 34 14 24 34
12
22
Z
89
X
22
22
13
FIELD SUPPLY
U1 V1 W1 U1 V1 W1
53
89
1 : ST NOT POSS. AS OPTION POSS. AS OPTION
K1M C3 OBLIGATORY # ##
54
L1 L2 L3 NOT OBLIGATORY * **
J6
90
L1 L2 L3 N03
M14F M11F
3 3
91
1 : OP52 C9 C10 C11 C6 C8 C13
4
K1A Y15S LIQUIDLINE SOLENOID VALVE
J22 J24 3
1 3 5
Y14S LIQUID INJECTION VALVE OF THE COMPRESSOR
S13S Y13S 70% CAPACITY STEP FOR COMPRESSOR
37
NC9 NC10 NC11 NO6 NO8 NO13 ID11
2 4 6 Y12S 40% CAPACITY STEP FOR COMPRESSOR
74/64 74 17 Y11S 12% CAPACITY STEP FOR COMPRESSOR
L1 L2 L3 13 23 33
25
27
29
TR3 TRANSFO DIGITAL INPUTS
52 54 57 K3M K1M 18
K9F 21 73/63 73 TR2 TRANSFO SUPPLY CONTROLLER
14 24 34
34
31
33
TR1 TRANSFO CONTROL CIRCUIT
38
K1M
22 S14HP HIGH PRESSURE SWITCH
Q11F Q14F Q13F
201
41
R5T SENSOR FOR AMBIENT TEMPERATURE
39
M12F M13F 51 53 55 22 22 83/13 13 R4T SENSOR FOR EVAPORATOR OUTLET WATER TEMPERATURE
200
202
26
28
30
Q1M THERMAL PROTECTOR COMPRESSOR MOTOR
14 Q11F-Q14F THERMAL PROTECTORS FAN MOTORS
Y12S
PE MAIN EARTH TERMINAL
40
42
43
40% K2M
13 53 53 M1C COMPRESSORMOTOR
F1U F2U F3U F4U F5U 21
10
35
36
K2M K3M M11F-M14F FAN MOTORS
54 54
L1,L2,L3 MAIN SUPPLY TERMINALS
K3A AUXILIARY RELAY FOR DISCHARGE THERMAL PROTECTOR
A1 K7F A1 K8F A1 K9F Y11S Y13S A1 K3M A1 K2M A1 K1M Y15S Y14S
E1HC
44
A1 K2A L A1 K3A K2A AUXILIARY RELAY COMPRESSOR THERMAL PROTECTOR
ID11R 12% 70%
Power Supply : Power Supply : A2 A2 A2 A2 A2 A2
29 K1A AUXILIARY RELAY FOR SAFETIES
9 K17S OVERCURRENT RELAY
3~50Hz 400V 1~50Hz 230V A2 A2
K9F FANCONTACTOR
20
20
20
7 8
K8F FANCONTACTOR
K7F FANCONTACTOR
K3M STARCONTACTOR
NOTES TO GO THROUGH BEFORE STARTING THE UNIT: 40HP K2M DELTACONTACTOR
K1M K2M K3M K1A
K1M LINECONTACTOR
(6) output terminals for fieldwiring (7) 1 14 4 3
(1) L1,L2,L3 : main terminals (5) input terminals for fieldwiring (9) 1 1 1 2 1 2 1 2 1 3 1 2 J17 CONTROLLER PCB POWER SUPPLY
Connections inside the
1 .. 29 : terminals on main rail EXAMPLE 1 3 4 2 3 4
compressorswitchbox 1: 1 1 1 3 3 4 1 . 7 6 J1,2 CONTROLLER PCB ANALOG INPUTS
51 .. 57 : terminals for fans OBLIGATORY EXAMPLE 71 80 73 FUSES +
71 .. 81 : terminals on field rail OVERCURRENT 40Y1 50Y1 60Y1 WIRENUMBER IN 1 1 5 6 1 2 5 6 1 3 5 6 J5,6,22,24 CONTROLLER PCB RELAY OUTPUTS
TERMINAL IN CABLE BETWEEN
U .. Z : main terminals in compressor switchbox 75 76 76
F1U, F2U, F3U 3x125A 3x160A 3x160A COMPRESSOR- COMPRESSORSWITCHBOX 1 1 14 13 14 1 . 13
13 14 1 13 21 22
K2A J3,4,21 CONTROLLER PCB DIGITAL INPUTS
COMPONENT SWITCHBOX 1 AND MAIN SWITCHBOX
A .. N : other terminals in compressor switchbox 1 6 21 22 1 12 21 22 1 16 53 54 1 11 H3P * INDICATION LAMP OPERATION COMPRESSOR
remote start/stop
F4U, F5U 2A 2A 2A
6 53 54 16 53 54 3 4
H2P H3P H1P 1 1 1 1 . 61 62 H2P * INDICATION LAMP ALARM
dual setpoint
*
.
S6S Y11S
F8B AUTOFUSE FOR SECONDARY OF TR1
K17S 50 64 77 E 4 3
F6B AUTOFUSE FOR PRIMARY OF TR1
.
C
1
18
Y13S 1 3 5 6 E1HC CRANKCASE HEATER COMPRESSOR
PROJECT
G 6 16..
77 79 78 1 14 13 14 B7V (V1) ** TRANSMITTER (VOLTAGE)
(8) OPTIONAL : OP10 = evaporator heatertape
A 1 13 21 22
K17S B3A ** TRANSMITTER (CURRENT)
72 81 74 OP52 = main isolator switch
OP57 = A-meter,V-meter Y14S
7 1 16 53 54
1 12 98 97 B2P TRANSMITTER (HIGH PRESSURE)
H
1 13 63 64
11 95 96 B1P TRANSMITTER (LOW PRESSURE)
*TW5****
8 1
I A1 ** CURRENT TRANSFO
Top view of unit S3T
D PROCESS : . 4
J 9 NIT
DIGITAL INPUTS DIGITAL OUTPUTS (RELAYS) ANALOG INPUTS K7F K8F K9F S3T COPY CODE TOLER. .
DIR.
10 KOK 3
J4 (ID1-IDCM1): low pressure switch J3 (ID6-IDCM2): compr. motor th. prot. J5 (C1-NO1): compressor star J24 (C6-NO6): 12% J2(B1-AVSS): ambient t˚ measurement
K
1 4 13 14 1 3 13 14 1 4 13 14 1 16 . ENG. CHANGE No. DATE
E1HC VEK WAP 2
J24 (C7-NO7): 25% REVIS. CLASS BR97W123AE 98-06-04
J4 (ID2-IDCM1): high pressure switch J3 (ID7-IDCM2): flowswitch J5 (C2-NO2): compressor delta J2(B2-AVSS): evaporator inlet t˚ measurement L 11 1 4 23 24 1 3 23 24 1 4 23 24
M11F M12F M13F M14F
DOC.Nr. FM.45.029-3
Wiring diagram
EUWA(*)80-120K(X)
A0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
J2A
10
10
10
22
23 24 25 44 45
B1 AVSS B2 B3 AVSS B4 B5 AVSS B6
20
75 76 84
yellow
white
2
3
L1
L2
L3
85
55
0 230 98 98
0...20mA
0...20mA
3 1 K17S K18S (dual remote enable/disable enable/disable
97 97 setpoint) start/stop circuit 1 circuit 2
F6B TR2 77 78 79 85 86
V1 R5T R3T R4T
26 46
8+
8+
10 -
10 -
24V 50VA
2 t˚ t˚ t˚
0...500V
OP57
S5E
74
57
72
71
58
59
75
1 3 5
1
3
1
3
orange
blue
(1A) 1 1
1
553
S2PH
583
86
p>
56
F10S 4 2 S1PH p>
4 2 42 A1 B3A V1 B7V
2 4 6 OP57
J3A ID7 J4A ID4 J4B ID4 J3A ID9 J3A ID10 J3B ID7 J3B ID8 OP57
7
4
73
1 1
J4A ID1 p> J4B ID1 p> S15PH
S14PH
83
53
54
84
42 42
+15 0 -15 230 400 28 48
84
54
G0 G 27 47
TR1 J17A J2B
2
400VA 15 15
E2 J4A ID2 J4B ID2 B1 AVSS B2 B3 AVSS B4 B5 AVSS B6
R1P R2P
S1 POWER
3
E1 230V S2 SUPPLY
¬ CONTROLLER 16 18 16 18
82
52
51
R1P
81
0...20mA
88
21
2
1
L1 4 4
20
J4A ID3 J4B ID3
8+
L2
10 -
F8B
G0 G 1 K2A K5A
3
L3
J17B F9B 2 3 2 3
1
3
80
50
79
red
red
49
4 4
POWER 24V A2 B6A
1
1 3 5 1 3 5 1 3 5 SUPPLY ¬ J3A ID6
K3A
J3B ID6
K6A OP57
7 CONTROLLER TR3
K1M K2M K3M 24V 30VA 2 2 3 2 3
78
48
2 4 6 2 4 6 2 4 6
77
¬
47
8 black
9 black
1 3 5 4 5 6
96 96
22
22
K17S K18S J1A
F12B 2 J4A ID5 J4B ID5 95
A1 S5E 95
B7 +24V B8
76
46
1 (10A)
OP57
A1 K1A A1 K4A
W
J4A IDCM1 J3A IDCM2 J4B IDCM1 J3B IDCM2
V
U V W 2 4 6 12
1 3 5 A2
K17S A2
4...20mA
4...20mA
8
8
8
2 4 6 29 49
BRN
BRN
BLU
M
22
22
M1C
3 13
-1...34bar
-1...12bar
3
3
1
2
1
2
0...5A
89
13 23 33 13 23 33 13 23 33
14
89
89
89
K8F K7F K9F 53
Y
X Z Y 14 24 34 14 24 34 14 24 34 B2P B1P
Z
K1M C3
54
23
X
J6A
90
90
N03
J1B
B7 +24V B8
U1 V1 W1 U1 V1 W1 U1 V1 W1 U1 V1 W1
91
C9 C10 C11 C6 C8 C13 4
K1A
J22A J24A 3
4...20mA
4...20mA
J21A
37
M14F M11F M12F M13F NC9 NC10 NC11 NO6 NO8 NO13 ID11
BRN
BRN
3 3 3 3
BLU
74/64 74 18
-1...34bar
-1...12bar
3
3
52 54 57 K3M K1M 19
1
2
1
2
0...5A
21 21 73/63 73
25
27
29
31
33
34
38
K4M K1M
22 22 Q11F Q14F Q13F
89
B5P B4P
15 16 17
56 C1 C2
L1
L2
L3
J5A 80 82 73 71
70
61
68
66
Q12F Q1M
NO1 NO2
21
20
41
S3T C4 C5
35
39
1 3 5 83 63
51 53 55 22 22 83/13 13
F11S
K3M K1M K4M J6A
2 4 6 K2M K1M 84 64
21 21 84/14 14
62
24
26
28
30
NO4 NO5
14
Y12S
40
42
43
1
K2M
69
60
67
65
40% 13 53 53
22 81 83 74 72
31 11 K2M K3M
43
2
54 54
44
3 A1 K7F A1 K8F A1 K9F Y11S Y13S A1 K3M A1 K2M A1 K1M Y15S Y14S 30
E2HC E1HC
12% 70% A1 K2A L A1 K3A
R2P J21A ID11R
A2 A2 A2
20
20
32 10 A2 A2 A2
A2 A2
1
L1
20
20
20
20
20
20
20
20
20
2
L2 8 9
L1 L2 L3 PE
3
L3 FIELD SUPPLY
NOT POSS. AS OPTION POSS. AS OPTION
OBLIGATORY # ##
22
22
NOT OBLIGATORY * **
201
1 3 5 1 3 5 1 3 5
89
3 K4M K5M K6M
2 4 6 2 4 6 2 4 6 35
1 3 5
89
89
1 3 5 53
S13S C12
E3H
2 4 6 OP10 F13B K4M C3
OP52 J6A A2 54
Y15S,Y25S liquid line solenoid valve circuit 1, circuit 2
N012 J6B
OP57 Y14S,Y24S liquid injection valve of the compressor circuit 1, circuit 2
101
101
N03 Y13S,Y23S 70% capacity step for compressor circuit 1, circuit 2
W
U
202
123
Y11S,Y21S 12% capacity step for compressor circuit 1, circuit 2
K18S
C9 C10 C11 C6 C8 C13 4 TR3 transfo digital inputs
1 2 2 4 6 TR2 transfo supply controller
K4A
M J22B J24B 3 TR1 transfo control circuit
M2C S14PH,S15PH high pressure switch circuit 1, circuit 2
3
114
F1U F2U F3U NC9 NC10 NC11 NO6 NO8 NO13 S13S ## main isolator switch
F4U F5U
13 23 33 13 23 33 13 23 33 S11S,S12S * switch that disables circuit 1, circuit 2 when closed
74/64 74 39 S10S * dual setpoint selection switch
K11F K10F K12F
Y
S8L # flowswitch
112
109
111
102
104
106
115
Power Supply : S6S * remote start/stop switch
X
Power Supply :
Q21F Q24F Q23F S5E emergency stop push button
89
3~50Hz 400V 1~50Hz 230V 36 37 38 S3T,S4T discharge thermal protector circuit 1,circuit 2
S1PH,S2PH high pressure switch circuit 1, circuit 2
C1 C2 R5T sensor for ambient temperature
U1 V1 W1 U1 V1 W1 U1 V1 W1 U1 V1 W1 63
107
J5B R4T sensor for evaporator outlet water temperature
Q2M R3T sensor for evaporator inlet water temperature
Q22F NO1 NO2
R1P,R2P reverse phase protector circuit 1, circuit 2
42 Q1M,Q2M thermal protector compressor motor circuit 1, circuit 2
M24F M21F M22F M23F 41 Q21F-Q24F thermal protectors fan motors circuit 2
118
113
116
3 3 3 3 S4T Q11F-Q14F thermal protectors fan motors circuit 1
58 60 62 22 22 83/13 13 PE main earth terminal
K5M K6M K4M M1C,M2C compressor motors circuit 1, circuit 2
21 21 84/14 14 M21F-M24F fan motors circuit 2
103
105
107
M11F-M14F fan motors circuit 1
14
L1,L2,L3 main supply terminals
120
117
119
Y22S K3A,K6A auxiliary relay for discharge thermal protector circuit 1, circuit 2
K5M
40% 13 53 53
43 K2A,K5A auxiliary relay compressor thermal protector circuit 1, ciruit 2
K5M K6M K1A,K4A auxiliary relay for safeties circuit 1, circuit 2
54
54
NOTES TO GO THROUGH BEFORE STARTING THE UNIT: K17S,K18S overcurrent relay for circuit 1, circuit 2
122
(7) A1 K10F A1 K11F A1 K12F Y21S Y23S Y25S Y24S 50
A1 K6M A1 K5M A1 K4M K9F,K12F fancontactor for cir cuit 1, circuit 2
12% 70% A1 K5A L A1 K6A
K8F,K11F fancontactor for cir cuit 1, circuit 2
(1) L1,L2,L3 : main terminals (5) input terminals for fieldwiring (6) output terminals for fieldwiring FUSES +
OVERCURRENT 80Y1 100Y1 120Y1 A2 A2 A2 A2 A2 A2 K7F,K10F fancontactor for circuit 1, circuit 2
1 .. 50 : terminals on main rail EXAMPLE
A2 A2
51 .. 64 : terminals for fans OBLIGATORY EXAMPLE 71 80 82 73 F1U, F2U, F3U 3x200aM 3x250aM 3x315aM K3M,K6M starcontactor for circuit 1, circuit 2
20
20
20
20
20
20
20
20
71 .. 86 : terminals on field rail F4U, F5U 2A 2A 2A 33 34 K2M,K5M deltacontactor for circuit 1, circuit 2
U .. Z : main terminals in compressor switchbox 75 76 76 84 84
F6B 2x6A 2x6A 2x6A K1M,K4M linecontactor for cir cuit 1, circuit 2
A .. N : other terminals in compressor switchbox
F8B 2A 2A 2A J17A,J17B controller pcb power supply pcb A, pcb B
H2P H3P H4P H1P J1A,J2A;J1B,J2B controller pcb analog inputs pcb A, pcb B
contactor- F9B 2A 2A 2A
(2) = earth wiring flowswitch
enable/disable C1
enable/disable C2
coil ev. F10S, F11S 3x100aM 3x125aM 3x160aM J22B,J24B controller pcb relay outputs pcb B
remote start/stop
< S8L
dual setpoint
waterpump F12B,F13 3x16A 3x16A 3x16A J22A,J24A controller pcb relay outputs pcb A
13
* (10) connections between PCB's 40HP 40HP J5B,J6B controller pcb relay outputs pcb B
K17S,K18S 50 64 77
general operation
S6S position of jumpers and dipswitches K1M K2M K3M K4M K5M K6M K1A K4A
Connections inside the Connections inside the J5A,J6A controller pcb relay outputs pcb A
- recommended fuses aM, gG compressorswitchbox 1: compressorswitchbox 2: 1 22 4 3 1 22 4 3
max. 4A/output 1 4 1 2 1 5 1 2 1 6 1 2 1 4 1 2 1 5 1 2 1 6 1 2
operation c1
operation c2
pumpcontact according to IEC standard 269-2 J3B,J4B,J21B controller pcb digital inputs pcb B
WIRENUMBER IN WIRENUMBER IN
(4)
13
= terminal number 13 (F1U,F2U,F3U = aM ; F4U,F5U = gG) TERMINAL IN CABLE BETWEEN TERMINAL IN CABLE BETWEEN USERTERMINAL 1 4 3 4 1 5 3 4 1 7 3 4 1 4 3 4 1 5 3 4 1 7 3 4 1 . 7 6 1 . 7 6
J3A,J4A,J21A controller pcb digital inputs pcb A
< S9L ADDRESS = 3
COMPRESSOR- COMPRESSORSWITCHBOX 1 COMPRESSOR- COMPRESSORSWITCHBOX 2 1 5 5 6 1 6 5 6 7 5 6 1 4 5 6 1 6 5 6 7 5 6 *
alarm
J14-J15 ON 2-3 1 17 4 1 20 4
3 3 3 3 F8B autofuse for secondary of TR1
B B B
F6B autofuse for primary of TR1
.
M11F M12F M13F M14F K3M K6M F4U,F5U fuses for evaporator heater
T-DEVICE
C C 1 6 1 2 1 6 1 2 F1U,F2U,F3U # main fuses
K17S K18S
Y13S Y23S
7 3 4 7 3 4 E3H ** evaporator heater
.
6 6 1 1
G G 1 21 98 97 1 22 98 97
1 7 5 6 1 7 5 6 E1HC,E2HC crankcase heater compressor circuit 1, circuit 2
17 95 96 20 95 96
PROJECT
E1HC E2HC K7F K8F K9F K10F K11F K12F COPY CODE TOLER. . 3
J3A (ID7-IDCM2): flowswitch J3B (ID7-IDCM2): enable/disable C1 J24A (C6-NO6): 12% C1 J24B (C6-NO6): 12% C2 J1A (B8)-J1(+24V): low pressure 1 J1A (B8)-J1(+24V): low pressure 2 11 11 KOK
J3A (ID8-IDCM2): controller bypass J3B (ID8-IDCM2): enable/disable C2 J24A (C7-NO7): 25% C1 J24B (C7-NO7): 25% C2
L L
1 7 13 14 1 6 13 14 1 9 13 14 1 7 13 14 1 6 13 14 1 9 13 14 . ENG. CHANGE No. DATE
DIPSWITCH DIPSWITCH VEK VE5 WAP 2
12 12 REVIS. CLASS BR97W123AE 98-06-04
J3A (ID9-IDCM2): dual setpoint J3B (ID9-IDCM2): - J24A (C8-NO8): 40% C1 J24B (C8-NO8): 40% C2 M M 1 7 23 24 1 6 23 24 1 9 23 24 1 7 23 24 1 6 23 24 1 9 23 24
DOC.Nr. FM.45.030-3A
. . 1
J3A (ID10-IDCM1): remote start/stop J3B (ID10-IDCM1): - J24A (C13-NO13): 70% C1 J24B (C13-NO13): 70% C2
13 13
ON ON 1 8 33 34 1 6 33 34 1 10 33 34 1 8 33 34 1 6 33 34 1 10 33 34 UNIT
EENHEID
mm EUWAB80-120K/KX
J21A (ID11-ID11R): emergency stop J21B (ID11-ID11R): - J22A (C9-NO9-NC9): fan 11 J22B (C9-NO9-NC9): fan 21 N N DESCRIPTION - OMSCHRIJVING
OFF OFF . 43 44 . 43 44 . 43 44 . 43 44 . 43 44 . 43 44
J21A (ID12-ID12R): - J21B (ID12-ID12R): - J22A (C10-NO10-NC10): fan 14 J22B (C10-NO10-NC10): fan 24
. . . . . . PAGE . WIRING DIAGRAM
M1C M2C SW 1 2 3 4 5 6 SW 1 2 3 4 5 6 BLAD
J22A (C11-NO11-NC11): fan 12 + 13 J22B (C11-NO11-NC11): fan 22 + 23 PART CODE
DAIKIN EUROPE NV
OOSTENDE - BELGIE 943500 0TW51166-1 B
Part 1
3.5 Field Wiring
1
Schematic The schematic drawings on the following pages will help you to locate the field wiring connections on
drawings the wiring diagrams and the switch boxes.
Field wiring The tables on the following pages give an overview of all possible field wiring connections for each
components unit. The item numbers will be repeated throughout the explanation to show the position on both wiring
overview diagram and switch box layout.
Options for The following devices are optionally available for EUWA(*)40-120K:
EUWA(*)40-120K
Code Description
OP10
OP12
evaporator heatertape
suction stopvalve
3
OP52 main isolator switch
OP57 A-meter, V-meter
EKEM emergency operation
ZH
ZL
glycol applications (leaving water evaporator=-5 °C)
glycol applications (leaving water evaporator=-10 °C)
4
Options for The following devices are optionally available for EUWA(*)40-120KX:
EUWA(*)40-120KX
Code Description
Field wiring view The following photo gives a visual view of field wiring terminals:
1 EUWA(*)40-60K(X)
location location in switchbox location in wiring diagram
PE L1 L2 L3 5 3 4 9 11 8
field wiring
1
12
field wiring
EUWA(*)40-60K(X) examples
EUWA(*)40-60K(X)
EUWA(*)40-60K(X)
3 terminal
connections Item Code Description Terminals Remarks
Remarks:
1:
These require programming; see page 2-27.
2: The inputs and outputs can also be consulted in the ‘Input/Output Menu’ on page 2-37.
3: Available as an option.
Example
main rail terminals on field rail
1 2 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86
ON ON
8 11 9
FL
The numbers refer to
3 4
the items in the
OFF OFF terminal connections.
5
12
ON = operation
~230 V ~24 V
OFF = no operation
FL = flow switch
P = pump contact
EUWA(*)80-120K(X)
location location in switchbox location in wiring diagram
1
L3 L2 L1 PE 5 3 4 6 7
field wiring
9 10 11 8
2
1
12
field wiring
EUWA(*)80-120K(X) examples
EUWA(*)80-120K(X)
EUWA(*)80-120K(X)
terminal
connections Item Code Description Terminals Remarks 3
1 L1/L2/L3/PE power supply to unit L1/L2/L3/PE
Remarks:
1:
These require programming, see page 2-27.
2: The inputs and outputs can also be consulted in the ‘Input/Output Menu’ on page 2-37.
3: Available as an option.
1 Example
main rail terminals on field rail
1 2 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86
S2 ON ON ON
8 11 9 10
3 4 6 7
FL S1 OFF OFF OFF
5
12 P
3
The numbers refer to ON = operation
~230 V ~24 V the items in the
terminal connections.
OFF = no operation
FL = flow switch
P = pump contact
4
Part 2
Functional Description
2
Introduction This part gives more detailed information on the functions and controls in the unit. This information is
used as background information for troubleshooting. An extensive overview of the functioning of the
3
controller is also given in this part. Knowledge of the controller is indispensable to gain valuable
information prior to servicing and troubleshooting.
Part 2
1
1 Functional Control
2
1.1 What Is in This Chapter
Introduction This chapter will give more detailed information on the functions used to control the system.
Understanding these functions is vital when diagnosing a malfunction, which is related to the functional
control. 3
Overview This chapter covers the following topics:
1.4 – Fan Speed Control after Start-up (Head Pressure Control) page 2-7
page 2-12
5
1.8 – Discharge Temperature Protector page 2-14
2 50
ambient temperature (o CDB )
43
40
39
36
30
3
20
CONTINUOUS OPERATION PULL-DOWN
10 AREA AREA
-10
-15
4 -20
ZL
Glycol
(optional)
ZH
Water
(standard) leaving evaporator
water temperature (o C)
-30
-5 4 16 26
-20 -10 -0 10 20 30
Protect the water circuit against freezing ambient conditions:
- or heater tape (optional for EUWAB, M, S, K, standard for EUWAT)
- or filling up the system with a glycol concentration related to your lowest expected ambient condition.
5
Operation range The following figure shows the operation range of EUWA(*)40-120K:
EUWA(*)40-120KX
EUWA(*) 40 - 50 - 60 - 80 - 100 - 120KX
43
40
39
33
30
20
CONTINUOUS OPERATION PULL-DOWN
AREA AREA
10
-10
-15
Glycol Water
-20 (optional) (standard) leaving evaporator
ZL ZH water temperature (o C)
-30
-5 4 16 26
-20 -10 -0 10 20 30
Protect the watercircuit against freezing ambient conditions:
- or heater tape (optional)
- or filling up the system with a glycol concentration related to your lowest expected ambient condition.
automatic control
no thermostat control.
Thermostat steps The following table shows the maximum number of thermostat steps for each chiller type:
Chiller type
EUWA(*)40-60K(X)
Maximum number of thermostat steps
3
4
EUWA(*)80-120K(X) 7 (when equal start-up or no equal start-up)
For more information about equal start-up, refer to ‘Lead-lag Control (only for EUWA(*)80-120K(X))’
on page 2-12.
5
Display controller Screen 3 of the user settings menu provides the ability to modify the thermostat parameters. Refer to
the user settings menu on page 2-27.
Lower Upper
Line n° Display Description Step Default
limit limit
3 STEPDIFFERENCE (°C) step difference (b) 0.2 0.8 0.1 0.5 (inlet)
0,2 (outlet)
1 Inlet water
temperature control
The figure below clarifies the inlet water temperature control:
step number
2 0
1
12.0 13.5
14.0
12.0 14.5
2
12.5 15.0
3
13.0 15.5
4
13.5 16.0
5
14.0 16.5
6
14.5
7
3 15.0
Outlet water The figure below clarifies the outlet water temperature control (in equal start-up):
4 temperature control
setpoint
In the following table you will find the limit and default values of a1, a2, b1 and b2:
1:
Parameter a1 is the set-up as parameter a in the software.
2:
Parameters b1 and b2 are always equal and are set up as parameter b in the software.
Overview fan steps The following table clarifies the different fan steps:
Fan sequence In the tables below you will find an overview of the 4 steps of relay and fan:
Ry1=ON, Ry2=OFF, Ry3=OFF M11F M12F M13F M14F M21F M22F M23F M24F
EUWA(*)40-60K(X) OFF ON ON ON — — — —
Ry1=ON, Ry2=ON, Ry3=OFF M11F M12F M13F M14F M21F M22F M23F M24F
STEP 3 means no speed Ry1=ON, Ry2=ON and Ry3=ON all fans are off
1 Fan control
procedure
The following procedure explains head pressure control in case of inlet water control:
start
(all fans are off)
■ Ta means ambient temperature.
■ Hp means high pressure.
2 M11F (M21F) starts
(Ry1 = off)
3
head pressure control
time up = 180 s
4 time down = 20 s
NO time up = time up - 1
time up = 0 s time down = time down - 1
5
YES
o
Ta > 17 C NO NO
or time down = 0 s time down = time down - 1
Hp > X* bar
YES YES
o
Ta < 15 C
NO
and
Hp < Y** bar
YES
Fans location The following illustration shows the position of the fans according to the compressor.
2
M11F M12F M13F M14F
3
compressor switchbox
Start-up of the The following diagram explains the start-up procedure of the compressor and fans in a time frame. 4
compressor The total start-up period is 140 s in case of manual mode or 200 s in case of automatic mode.
fan M12F+M13F(*)
5
fan M14F
fan M11F
100%
70%
40%
12%
12%
time
5s 15s fixed time (120s) or thermostat load-up time (180s)
Phase Description
Initial Initially, the compressor starts up in star wiring and only fan M11F operates.
Phase At the beginning of phase 1, the compressor start-up turns from star to delta. The
1 capacity remains 12%. This action also starts fan M14F.
Phase From phase 2, you can put the fans on and off according to the settings in manual mode
2 or according to the head pressure control in automatic mode. Refer to ‘Fan Speed Con-
trol after Start-up (Head Pressure Control)’ on page 2-7. The compressor remains at
40%.
Phase From phase 3, the compressor turns in the desired capacity steps according to the
3 settings in manual mode or according to the thermostat in automatic mode.
Refer to ‘Thermostat Control’ on page 2-5.
2 Freeze-up Freeze-up prevention will be activated before the actual freeze-up protection in an attempt to prevent
prevention the actual protection by loading down the thermostat step.
Freeze-up In the following table you will find all the characteristics of the freeze-up prevention:
prevention
activation outlet water temperature < M.O.W. -1K (3°C for standard unit)
4 result
reset
loaddown of 1 thermostat step
Freeze-up Freeze-up protection is a protection against ice formation in the water circuit at the evaporator outlet.
5 protection It is controlled by the software using the outlet water temperature sensor.
Freeze-up In the following table you will find all the characteristics of the freeze-up protection:
protection overview
Characteristics Freeze-up protection
(1):
Alarm is on hold and reset goes automatically.
General overview The following table shows a general view of freeze-up temperatures in case of protection and
prevention: 1
Minimum outlet water (M.O.W.) Freeze-up protection Freeze-up prevention
Standard 4 °C 2.5 °C 3 °C
2 °C 0.5 °C 1 °C
0 °C -1.5 °C -1 °C 2
ZH -5 °C -6.5 °C -6 °C
-7 °C -8.5 °C -8 °C
Available modes The lead-lag control is available in 3 modes as explained in the table below:
2 Mode Description
manual C1 > C2 Circuit 1 starts up before circuit 2. If circuit 1 is de-activated due to a fail-
ure, circuit 2 will start up instead.
3 manual C1 < C2 Circuit 2 starts up before circuit 1. If circuit 2 is de-activated due to a fail-
ure, circuit 1 will start up instead.
Lead-lag hours in When the lead-lag control is done automatically, the software calculates the difference in operation
automatic mode time between the circuits. When this time is higher than the preset lead-lag hour value, the start
sequence of both circuits is swapped. The compressor that started first will then start as second.
4 The limit values of the lead-lag hours are the following:
■ lower limit: 100 hours
■ upper limit: 1000 hours
■ default value: 1000 hours
5 This value is important for maintenance purposes. It should be set high enough so that both circuits
do not require maintenance at the same time and that at least one circuit can remain constantly
active.
Equal start-up The following table gives an explanation of the possible settings:
N (no) The leading circuit will try to go to full capacity before the lagging circuit can
start up.
To program the settings of the lead-lag control, consult screen 6 of the user settings menu on
page 2-27.
Lead-lag working The following table shows the different compressor steps in case of an equal start-up or no equal
start-up: 1
If equal start-up, then If no equal start-up, then
Steps (lead) Steps (lag) Capacity % Steps (lead) Steps (lag) Capacity %
compressor 1 compressor 2 compressor 1 compressor 2
0 0 0 0 0 0
2
40 0 25 40 0 25
70 0 38 70 0 38
40 40 50 100 0 50
70
70
40
70
63
76
70
100
40
40
63
76
3
100 70 88 100 70 88
3 Illustration The following photo shows the position of the sensor S3T:
4
S3T (bimetal)
During the winter, never switch off the field supply of the heatertape if you want to activate it.
total cap = 0 %
or
Tamb M.O.W. + 3K
YES
Heatertape OFF
4
NO
General overview The following table shows a general view of freeze-up temperatures in case of protection and
prevention:
5
Minimum
outlet water FP Set (Freeze-up protection) FP Solution Glycol weight
(M.O.W)
Standard 4 °C 2.5 °C 0 °C 0%
ZH -5 °C -6.5 °C -16 °C 30 %
HP (R-134a) >15.5 bar (59°C) compressor step=100% compressor step becomes 70%.
2 HP (R-22) >23.5 bar (59°C) compressor step=100% compressor step becomes 70%.
Reset Once activated, the head pressure setback will stop after 3 minutes.
Part 2
1
2 The Digital Controller
2
2.1 What Is in This Chapter
Introduction In this chapter you will learn to work with the controller for the chiller types EUWA(*)40-120K(X).
5
Overview This chapter covers the following topics:
2.6 – How to Read or Adjust Parameter Settings: the Programming Procedure page 2-23
Front panel The illustration below shows the front panel of the controller (with open cover).
a read-out
3 V
—
z set points
e user settings
r timers
t history
y information
u input/output
q password
4 d not used
f start/stop
g alarm
h scroll through screens/change value
j enter key
5
How to go from one Each menu contains a number of screens. You can go from one screen to another using the h key.
screen to another In the upper-left corner of the screen you will find a screen indicator, indicating whether there is a
previous or next screen. An overview is given below:
Screen detail Each screen contains 4 lines which give information about a setting (a description and an entry field).
The entry fields can be adjusted using the h key. The cursor is marked by the sign _. You can move
the cursor between the screen indicator and the entry fields using the j key.
You can move the cursor directly to the screen indicator by pressing the active menu key.
screen v
—
indicator
cursor
Make sure that the cursor is at the screen indicator position when scrolling through the screens.
To avoid damage to the LCD display of the digital controller, never switch off the power supply during
winter.
Remote start/stop The procedure to start or stop the unit depends on the setting of the remote start/stop.
Emergency stop In case of emergency, switch off the unit by pushing the emergency stop button.
5
Temperature To adjust the inlet or outlet water temperature, use the set points menu (z key), refer to page 2-26.
setting
3 Action to
take
Press g to acknowledge the alarm. Press gto acknowledge the alarm.
4 example
FLOW SWITCH (1) HIGH PRESSURE SWITCH (1)
INL. OUTL. INL. OUTL.
AMB. AMB.
(1)
The safeties that may occur are listed in the table below:
Screen 2
Screen 3
To consult information about the status of the circuits.
page 2-24
2
Screen 4 To consult information about the pressures of circuit 22. page 2-25
Screen 5 To consult the voltage and compressor current (optional). page 2-25
Screen 6 To consult the ambient temperature and the total running page 2-25
hours of the compressors. 3
z Set points direct or Screen 1 To enter a password1. page 2-26
password1
Screen 2 To consult and adjust the inlet and outlet water temperature page 2-26
set points.
Screen 2
To enter the password.
page 2-27
4
Screen 3 To adjust and activate manual control mode. page 2-27
r Timers direct Screen 1 To read the actual value of the general timers. page 2-30
Screen 2 To read the actual value of the compressor timers. page 2-30
Screen 3 To read the actual value of the compressor start-up timers. page 2-30
t History direct Screen 1 To read the unit safety information after a shutdown. page 2-33
Subscreen To read the high and low pressure of the refrigerant circuit 1.
1-1
Subscreen To read the high and low pressure of the refrigerant circuit 2.
1-2
Subscreen To read the total running hours of the compressors and the
1-4 capacity steps.
Screen 2 To read the safety information of circuit 1 after a shutdown. page 2-34
Screen 3 To read the safety information of circuit 2 2 after a shutdown. page 2-35
Screen 2 To read the status of the low and high pressure switch and page 2-37
of the reverse phase protector of circuit 1.
Screen 3 To read the status of the low and high pressure switch and page 2-37
2 of the reverse phase protector of circuit 22.
Screen 4 To read the status of the overcurrent relay, the discharge page 2-38
thermal protector and the compressor thermal protector of
circuit 1.
Screen 5 To read the status of the overcurrent relay, the discharge page 2-38
3 thermal protector and the compressor thermal protector of
circuit 22.
Screen 6 To read the status of the remote dual set point switch and page 2-38
the remote start/stop.
Screen 7 To read the status of the remote ‘compressor disable’ page 2-38
switches.
4 Screen 8 To read the status of the power relays of circuit 1. page 2-39
Screen 9 To read the status of the power relays of circuit 22. page 2-39
Screen 13 To read the status of the fan speed relays of circuit 22. page 2-40
Screen 14 To read the status of the pump, the alarm and the page 2-40
evaporator heater contacts.
1:
You can assign a password protection to the set point menu (refer to page 2-29).
2:
Only for EUWA(*)80-120K(X).
BEGIN1
2
Press the desired menu-key.
NO
Does the controller prompt you to give the password?
YES
3
Enter the password using the h key.
4
Select the desired screen using the h key.
NO
Do you want to adjust a parameter setting?2
YES 5
Select the parameter using the j key.
NO
Do you want to save the modifications?
YES
Press j.
YES
Do you want to adjust another parameter in the same screen?
NO
YES
Do you want to adjust a parameter in another screen?
NO
1:
The display shows a screen of the last menu used.
2: Only for the menus z, e and q.
Screen 1 This screen shows information about the operation mode, the set points and the temperatures:
2 Line n° Display Description
4 Screen 2 This screen shows information about the status of the circuits:
BYPASS MODE the internal controller is being bypassed and the unit is controlled
by an external controller
TIMERS BUSY one of the software timers is counting (refer to page 2-30)
CAN START UP the circuit is ready to start up when extra cooling load is requested
4 UNIT CAPACITY the percentage refers to the actual cooling capacity of the unit
When a circuit is in a high pressure setback, the indication 70% will be flashing. A high pressure
setback is a loaddown from 100% to 70% caused by a too high pressure.
2 HP1 high pressure refrigerant circuit 1 (in bar and equivalent in °C)
3 LP1 low pressure refrigerant circuit 1 (in bar and equivalent in °C)
Screen 4 This screen shows information about the pressures of circuit 2 (only for EUWA(*)80-120K(X)):
1
Line n° Display Description
2 HP2 high pressure refrigerant circuit 2 (in bar and equivalent in °C)
3 LP2 low pressure refrigerant circuit 2 (in bar and equivalent in °C)
2
Screen 5 This screen shows information about the voltage and compressor current.
This screen is available if optional voltage and current transmitters are installed.
2 VOLTAGE voltage
3 Screen 2:
two temperature set
This menu provides the ability to set the inlet and outlet water temperature. You can adjust two sets of
temperature set points. Each set contains an inlet and an outlet water temperature set point. These
points set points will only be active in automatic control mode.
Step
Line n° Display Description Default value Limit value*
value
■ The actual active setpoint can be consulted in the read-out menu (refer to page 2-24).
■ To change the settings, refer to ‘Entering the factory menu’ on page 3-26.
* For glycol units the lower limit of the cooling temperature set point can be adapted in the factory
menu. The following values apply:
■ inlet: 5°C, 3°C, -2°C, -7°C, -12°C
■ outlet: 2°C, 0°C, -5°C, -10°C, -15°C.
For more information about these temperatures, refer to ‘General overview’ on page 2-11.
Selection between You can select set point 1 or 2 by the remote dual set point switch (if installed), refer to ‘Field Wiring’
set point 1 and 2 on page 1-43.
Selection between The selection is done in screen 3 of the user settings menu on page 2-27. Use the programming
inlet and outlet procedure on page 2-23.
control
Menu description This menu allows a full customizing of the units and provides the following 6 screens:
2
Screen n° Display Description See page
3 CONTROL SETTINGS To adjust and activate manual control mode. page 2-27 3
4 THERMOST. SETTINGS To adjust the thermostat settings. page 2-28
6 LEAD-LAG SETTINGS To define the lead-lag mode of both circuits page 2-29
(only for EUWA(*)80-120K(X))
Screen 1 You need to enter the correct password before you can consult the screens in this menu:
The procedure to start or stop the unit is given in ‘Start/Stop and Temperature Setting’ on page
page 2-19.
Screen 3 This screen provides the ability to modify the control settings:
3 F1* / F2* fan speed circuit 1/2 (manual mode) OFF/ LOW/ MEDIUM/ HIGH
4 CIR1 / CIR2 capacity step circuit 1/2 (manual 0%, 40%, 70%, 100%
mode)
1 Screen 4 This screen provides the ability to modify the thermostat parameters:
Lower Upper
Line n° Display Description Step Default
limit limit
2 STPLENGTH (°C) step length (a) 0.4 2.0 0.1 1.5 (inlet)
2 0,6 (outlet)
3 STEPDIFFERENCE (°C) step difference (b) 0.2 0.8 0.1 0.5 (inlet)
0,2 (outlet)
Inlet water The figure below shows the inlet water thermostat control:
thermostat control step number
set point: 12.0 °C
4 a: step length
b: step difference
a b
12.0 13.5
0
14.0
1
12.0 14.5
2
12.5 15.0
3
13.0 15.5
4
5 5
6
7
13.5
14.0
14.5
16.0
16.5
15.0
For more information on thermostat control, refer to ‘Thermostat Control’ on page 2-5.
Screen 5 (optional) You can install an optional PCB to control the unit from a PC (this feature is under development). The
BMS (Building Management System) parameters provide communication between the unit and the 1
PC. This screen provides the ability to activate the PC control mode and to modify the BMS settings:
Possible
Line n° Display Description
settings
BMS SETTINGS
1
This screen will only be displayed if the optional BMS-PCB is installed (under development).
3
Screen 6 This screen provides the ability to adjust the lead-lag settings.
3 LEAD-LAG HOURS The maximum difference between the lower limit: 100 h
running hours of both circuits upper limit: 1000 h
(in automatic mode). default value: 1000 h
For a functional description of the lead-lag control, refer to ‘Lead-lag Control (only for
EUWA(*)80-120K(X))’ on page 2-12.
Screen 7 This screen provides the ability to assign password protection to the set point menu:
Screen 1 This screen shows the actual value of the general timers:
2 LOADUP delay timer for loading up; during countdown, the unit is unable
to enter a higher thermostat step (default: 180 s)
DWN delay timer for loaddown; during countdown, the unit is unable
3 to enter a lower thermostat step (default: 20 s)
FLOWSTOP delay timer that starts counting when the water flow through the
evaporator stops during normal operation; if the water flow has
not restarted during the countdown, the unit will shut down
4 (default: 5 s)
4 COMPR. STARTED delay timer to start the next compressor; used in manual mode
or when only one thermostat step is set up (default: 10 s)
Screen 2 This screen shows the actual value of the compressor timers:
5 Line n° Display Description
2 GRD 1 AREC 1 guard timer: delay timer to prevent the compressor from
restarting after a shutdown (default: 60 s)
3 GRD 2 AREC 2
antirecycling: delay timer to prevent the compressor from
restarting after the compressor has started; used to limit the
number of restarts (default: 600 s)
Screen 3 This screen shows the actual value of the compressor start-up timers:
Overview timers An overview of the software timers is shown in the example on the next page.
compr. started 10 s 10 s
start-up timer 1 20 s 120 s 20 s 120 s
start-up timer 2 140 s
(without lead-lag)
step 7
100 - 70
step 6
100 - 40 100 - 40
The following view shows an example of the working of the timers:
step 5
70 - 40 70 - 40
step 4
step 3 100 - 0
70 - 0 70 - 0
step 2
40 - 0 40 - 0
step 1
initial 12 - 0 12 - 0
2–31
The Digital Controller
5
4
3
2
1
The Digital Controller ESIE98–03
2 Overview screens The table below gives an overview of the screens and sub-screens in this menu:
and subscreens
Activated safety Unit safety Circuit 1 safety Circuit 2 safety
4
INL.
AMB.
OUTL. inlet/outlet water temperature
ambient temperature
2
Subscreen 1-1 This screen shows information about the pressures of circuit 1:
2 HP1 high pressure refrigerant circuit 1 (in bar and equivalent in °C)
3 LP1 low pressure refrigerant circuit 1 (in bar and equivalent in °C)
Subscreen 1-2 This screen shows information about the pressures of circuit 2:
4
Line n° Display Description
HP2
2
3 LP2
high pressure refrigerant circuit 2 (in bar and equivalent in °C)
This screen is available if optional voltage and current transmitters are installed.
2 VOLTAGE voltage
Subscreen 1-4 This screen shows information about the total running hours of the compressors and the capacity
steps:
Subscreen 2-1 This screen shows information about the pressures of circuit 1:
2 HP1 high pressure refrigerant circuit 1 (in bar and equivalent in °C)
3 LP1 low pressure refrigerant circuit 1 (in bar and equivalent in °C)
4 Subscreen 2-2 This screen shows information about the pressures of circuit 2:
5 2
3
HP2
LP2
high pressure refrigerant circuit 2 (in bar and equivalent in °C)
Subscreen 2-3 This screen shows information about the voltage and compressor current.
This screen is available if optional voltage and current transmitters are installed.
2 VOLTAGE voltage
Subscreen 2-4 This screen shows information about the total running hours of the compressors and the capacity
steps:
Subscreen 3-1 This screen shows information about the pressures of circuit 1:
2 HP1 high pressure refrigerant circuit 1 (in bar and equivalent in °C)
3 LP1 low pressure refrigerant circuit 1 (in bar and equivalent in °C)
Subscreen 3-2 This screen shows information about the pressures of circuit 2:
4
Line n° Display Description
3
HP2
LP2
high pressure refrigerant circuit 2 (in bar and equivalent in °C)
Subscreen 3-3 This screen shows information about the voltage and compressor current.
This screen is available if optional voltage and current transmitters are installed.
2 VOLTAGE voltage
Subscreen 3-4 This screen shows information about the total running hours of the compressors and the capacity
steps:
3 not used
4 not used
5
Screen 1 This screen shows the status of the emergency stop, the flow switch and the bypass mode:
2
Line n° Display Description Possible settings
Screen 2 This screen shows the status of the low and high pressure switch and of the reverse phase protector
of circuit 1: 4
Line n° Display Description Possible settings
You can find more information in ‘Switch box EUWA(*)40-60K(X)’ on page 1-33 and in ‘Main board
EUWA(*)40-120K(X)’ on page 1-34.
Screen 3 This screen shows the status of the low and high pressure switch and of the reverse phase protector
of circuit 2:
You can find more information in ‘Switch box EUWA(*)80-120K(X)’ on page 1-33 and in ‘Main board
EUWA(*)40-120K(X)’ on page 1-34.
1 Screen 4 This screen shows the status of the overcurrent relay, the discharge thermal protector and the
compressor thermal protector of circuit 1:
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)40-60K(X)’ on page 3-4.
3 Screen 5 This screen shows the status of the overcurrent relay, the discharge thermal protector and the
compressor thermal protector of circuit 2:
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)80-120K(X)’ on
5 page 3-5.
Screen 6 This screen shows the status of the remote dual set point switch and the remote start/stop:
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)40-60K(X)’ on page 3-4
and in ‘Overview of Inputs and Outputs of EUWA(*)80-120K(X)’ on page 3-5.
Screen 7 This screen shows the status of the remote ‘compressor disable’ switches.
The ‘compressor disable’ switches are only available on chiller types EUWA(*)80-120K(X):
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)80-120K(X)’ on
page 3-5.
Screen 8 This screen shows the status of the power relays of circuit 1:
1
Line n° Display Description Possible settings
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)40-60K(X)’ on page 3-4.
Screen 9 This screen shows the status of the power relays of circuit 2:
3
Line n° Display Description Possible settings
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)80-120K(X)’ on
page 3-5.
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)40-60K(X)’ on page 3-4.
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)80-120K(X)’ on
page 3-5.
1 Screen 12 This screen shows the status of the fan speed relays of circuit 1:
2 You can find more information in ‘Fan Speed Control after Start-up (Head Pressure Control)’ on
page 2-7.
Screen 13 This screen shows the status of the fan speed relays of circuit 2:
You can find more information in ‘Fan Speed Control after Start-up (Head Pressure Control)’ on
page 2-7.
4
Screen 14 This screen shows the status of the pump, the alarm and the evaporator heater contacts:
You can find more information in ‘Overview of Inputs and Outputs of EUWA(*)40-60K(X)’ on page 3-4
and in ‘Overview of Inputs and Outputs of EUWA(*)80-120K(X)’ on page 3-5.
3 CONFIRM the controller requests the new password a second time (for
safety reasons) 4
How to change the To change the password, proceed as follows:
password
Step Action
4
Part 3
Troubleshooting
Introduction The large chillers (EUWA(*)40-120K(X)) are equipped with electronic PCBs. These PCBs use the
information gained from the input signals to control the output signals. If the unit is not performing
3
properly, first check the input devices, then the PCBs and finally the output devices. The chapters in
this part are arranged according to this sequence.
Part 3
1
1 Overview of Inputs and Outputs
Introduction The first step in a troubleshooting sequence is to check the inputs and outputs. In this chapter an
overview is given.
3
Overview This chapter covers the following topics:
3 transmitter B3A
B7V
J2/B5
J2/B6
current transmitter (optional)
K17S
J4/ID3
J4/ID4
reverse phase protector
overcurrent relay
The following table describes the relation between the wiring diagram symbols and the wiring
1
connections of chiller types EUWA(*)80-120K(X). We refer to the wiring diagram and the PCB layout
to find the exact location on both wiring diagram and switch box.
digital input transducer R1P J4A/ID3 reverse phase protector for circuit 1
4 Y13S
K7F
J24A/C13
J22A/C9
70 % capacity step compressor for circuit 1
Part 3
1
2 Overview of Fault Indications and Safeties
Introduction In the first stage of the troubleshooting sequence it is important to interpret the fault indication on the
controller display. This will help you to find the cause of the problem.
3
Overview This chapter covers the following topics:
3 Action to
take
Press g to acknowledge the alarm. Press gto acknowledge the alarm.
4 AMB. AMB.
For more information about the safety devices, refer to ‘What Happens in Case of an Alarm’ on
page 2-20.
3 Press g to reset the ■ The g LED goes out and the alarm screen is
alarm. deactivated.
■ The first screen of the readout menu is displayed
automatically.
Unit safety screens If a unit safety occurs, the following screen is displayed:
1
Line n° Display Description
By pressing the j key, you can consult the subscreens. After 20 seconds, these screens
Subscreens
automatically disappear. 3
Subscreen 1 This screen shows information about the pressures of circuit 1:
3 LP1 low pressure refrigerant circuit 1 (in bar and equivalent in °C)
2 HP2 high pressure refrigerant circuit 2 (in bar and equivalent in °C)
3 LP2 low pressure refrigerant circuit 2 (in bar and equivalent in °C)
Subscreen 3 This screen shows information about the voltage and compressor current.
This screen is available if the optional voltage and current transmitters are installed.
2 VOLTAGE voltage
1 Subscreen 4 This screen shows information about the compressors total running hours and the capacity steps:
*: Other circuit safeties are overcurrent relay, discharge thermal protector, compressor motor thermal
protector and reverse phase protector.
Subscreens By pressing the j key, you can consult the subscreens. After 20 seconds, these screens
5 automatically disappear.
2 HP1 high pressure refrigerant circuit 1 (in bar and equivalent in °C)
3 LP1 low pressure refrigerant circuit 1 (in bar and equivalent in °C)
2 HP2 high pressure refrigerant circuit 2 (in bar and equivalent in °C)
3 LP2 low pressure refrigerant circuit 2 (in bar and equivalent in °C)
Subscreen 3 This screen shows information about the voltage and compressor current.
1
This screen is available if optional voltage and current transmitters are installed.
2 VOLTAGE voltage
Subscreen 4 This screen shows information about the total running hours of the compressors and the capacity
steps:
3
Line n° Display Description
Wiring
Alarm description Alarm indication Activation Reset Device
code
emergency stop EMERGENCY STOP push the emergency unlock the button and S5E contact
button start the unit
flow switch or pump FLOWSWITCH no flow for 5 seconds manual software reset S8L contact
contact ACTIVATED OR NOT closed on
flow
freeze-up FREEZE-UP outlet water temperature manual software reset R4T NTC sensor
protection < 2,5 °C
3 (refer to page 2-10)
Circuit safeties
Wiring
Alarm description Alarm indication1 Activation Reset
code
Device
4 high pressure HIGH PRESSURE discharge pressure > ■ manual software S1PH, switch on/off
switch SWITCH 1/2 17 bar (R-134a) reset S2PH, contact
S14PH,
discharge pressure > ■ reset on the switch
S15PH
25 bar (R-22)
low pressure LOW PRESSURE 1/2 < 0.5 bar manual software reset B1P low pres-
transmitter sure
5 transmitter
discharge thermal DISCHARGE discharge temperature > manual software reset S3T, bimetal
protector THERMAL 135 °C when discharge S4T on/off
PROTECTION 1/2 temperature < 115 °C
overcurrent relay OVERCURRENT 1/2 overcurrent 2 ■ manual hardware K17S, bimetal
reset K18S on/off
■ manual software
reset
compressor motor COMPRESSOR compressor motor automatic reset at Q1M, bimetal
thermal protector THERMAL PROTEC- windings temperature > 93 °C Q2M on/off
TOR 1/2 115 °C
reverse phase REVERSE PHASE ■ single phasing correct phase R1P contact
protector PROTECTION 1/2 sequence, switch
■ imbalance of more
power back on
than 20 % between
the phases
■ reversed phases
■ no power
fan motor thermal - fan motor windings automatic reset at Q11F- bimetal
protector temperature > 160 °C ± 130 °C ± 15 K Q14F, on/off
10 K Q21F-
Q24F
1:
The circuit 1 or 2 is not indicated on the single circuit units EUWA(*)40-60K(X).
2:An overview of the fuses and overcurrent relays is given in ‘Checking the Power Supply and Fuses’
on page 3-19.
Safety devices The following pictures give a visual view of some of the safety devices:
1
high pressure
service port
high pressure
switch 2
3
high pressure
switch 1
discharge safety
4
valve
5
emergency stop
power supply
covers
overcurrent + reset
Part 3
1
3 Checking the Inputs and Outputs
Introduction In this chapter you will find information on how to measure and check the most important inputs.
page 3-19
4
For more information about these sensors, refer to ‘Main board EUWA(*)40-120K(X)’ on page 1-34.
3 Step Action
3 Check if the measured values correspond with the values in the appropriate table.
Table 1 In the following table you will find the temperature-resistance values of the controller sensors R3T,
R4T and R5T. 1
Tempera- Tempera- Tempera-
Resistor value Resistor value Resistor value
ture ture ture
°C kΩ kΩ kΩ °C kΩ kΩ kΩ °C kΩ kΩ kΩ
-50 344.40 329.20 314.70 1 26.64 26.13 25.62 56 3.49 3.42 3.35
-49 324.70 310.70 297.20 2 25.51 25.03 24.55 57 3.39 3.31 3.24
-48 306.40 293.30 280.70 3 24.24 23.99 23.54 58 3.28 3.21 3.14
-47 289.20 277.00 265.30 4 23.42 22.99 22.57 59 3.18 3.11 3.04
-46 273.20 261.80 250.60 5 22.45 22.05 21.66 60 3.09 3.02 2.95
-45 258.10 247.50 237.20 6 21.52 21.15 20.78 61 2.99 2.92 2.86
-44 244.00 234.10 224.60 7 20.64 20.29 19.95 62 2.90 2.83 2.77
-43
-42
-41
230.80
218.50
206.80
221.60
209.80
198.70
212.70
201.50
191.00
8
9
10
19.80
19.00
18.24
19.40
18.70
17.96
19.15
18.40
17.67
63
64
65
2.81
2.73
2.65
2.75
2.66
2.58
2.69
2.60
2.52
3
-40 195.90 188.40 181.10 11 17.51 17.24 16.97 66 2.57 2.51 2.45
-39 185.40 178.30 171.59 12 16.80 16.55 16.31 67 2.49 2.43 2.37
-38 175.5. 168.90 162.00 13 16.13 15.90 15.87 68 2.42 2.36 2.30
-37 166.20 160.10 154.10 14 15.50 15.28 15.06 69 2.35 2.29 2.24
-36 157.50 151.80 140.20 15 14.89 14.68 14.48 70 2.28 2.22 2.17
-35
-34
149.30
141.60
144.00
136.60
138.80
131.80
16
17
14.31
13.75
14.12
13.57
13.93
13.40
71
72
2.21
2.15
2.16
2.10
2.10
2.04
4
-33 134.40 129.70 125.20 18 13.22 13.06 12.89 73 2.09 2.04 1.98
-32 127.60 123.20 118.90 19 12.72 12.56 12.41 74 2.03 1.98 1.93
-31 121.20 117.10 113.10 20 12.23 12.09 11.95 75 1.97 1.92 1.87
-30 115.10 111.30 107.50 21 11.77 11.63 11.07 76 1.92 1.87 1.82
-29 109.30 105.70 102.20 22 11.32 11.20 11.07 77 1.86 1.81 1.78
-28
-27
103.80
98.63
100.40
95.47
97.16
92.41
23
24
10.90
10.49
10.78
10.38
10.60
10.27
78
79
1.81
1.76
1.76
1.71
1.71
1.68
5
-26 93.75 90.80 87.93 25 10.10 10.00 9.90 80 1.71 1.66 1.62
-25 89.15 86.39 83.70 26 9.73 9.63 9.52 81 1.66 1.62 1.57
-24 84.82 82.22 79.71 27 9.38 9.28 9.18 82 1.62 1.57 1.53
-23 80.72 78.29 75.93 28 9.04 8.94 8.84 83 1.57 1.53 1.49
-22 76.85 74.58 72.36 29 8.72 8.62 8.52 84 1.53 1.49 1.44
-21 73.20 71.07 68.99 30 8.41 8.31 8.21 85 1.49 1.45 1.40
-20 69.74 67.74 65.80 31 8.11 8.01 7.91 86 1.45 1.41 1.37
-19 66.42 64.54 62.72 32 7.82 7.72 7.62 87 1.41 1.37 1.33
-18 63.27 61.52 59.81 33 7.55 7.45 7.35 88 1.37 1.33 1.29
-17 60.30 58.66 57.05 34 7.28 7.19 7.09 89 1.34 1.30 1.26
-16 57.49 55.95 54.44 35 7.03 6.94 6.84 90 1.30 1.26 1.22
-15 54.83 53.39 51.97 36 6.79 6.69 6.60 91 1.27 1.23 1.19
-14 52.31 50.96 49.83 37 6.56 6.46 6.37 92 1.23 1.20 1.16
-13 49.93 48.66 47.12 38 6.33 6.24 6.15 93 1.20 1.16 1.13
-12 47.67 46.48 45.31 39 6.12 6.03 5.94 94 1.17 1.13 1.10
-11 45.53 44.41 43.32 40 5.92 5.82 5.73 95 1.14 1.10 1.07
-10 43.50 42.25 41.43 41 5.72 5.63 5.54 96 1.11 1.08 1.04
-9 41.54 40.56 39.59 42 5.53 5.43 5.35 97 1.08 1.05 1.01
-8 39.68 38.76 37.85 43 5.34 5.25 5.17 98 1.05 1.02 0.99
-7 37.91 37.05 36.20 44 5.16 5.08 4.99 99 1.03 0.99 0.96
-6 36.24 35.43 34.03 45 4.99 4.91 4.82 100 1.00 0.97 0.94
-5 34.65 33.89 33.14 46 4.83 4.74 4.66 101 0.98 0.94 0.91
-4 33.14 32.43 31.73 47 4.67 4.59 4.51 102 0.95 0.92 0.89
-3 31.71 31.04 30.39 48 4.52 4.44 4.36 103 0.93 0.90 0.87
-2 30.35 29.72 29.11 49 4.38 4.30 4.22 104 0.91 0.87 0.84
-1 20.00 28.47 27.89 50 4.24 4.16 4.08 105 0.88 0.85 0.82
0 27.83 27.28 26.74 51 4.10 4.02 3.95 106 0.86 0.83 0.80
52 3.97 3.90 3.82 107 0.84 0.81 0.78
53 3.84 3.77 3.69 108 0.82 0.79 0.76
54 3.72 3.65 3.57 109 0.80 0.77 0.74
55 3.61 3.53 3.46 110 0.78 0.75 0.73
Troubleshooting In most cases a malfunction occurs in the unit itself and not in the control circuit of the unit. If however
the latter is the case, then you should measure the relevant signals using the schematic input route
3 shown above.
Output route The output is generated from the PCB. If a device does not operate, you should find the relevant output
signal from the PCB in order to decide whether the PCB or the device needs replacement. The output
route is shown in the block diagram below:
voltage free
contact 230 V (supply) e.g. fan, valve
PCBs All PCBs are supplied with a 24 V AC voltage. The red led on the main board indicates that power is
supplied.
4
Overview fuses and The table below gives an overview of the fuses for each chiller type in the range EUWA(*)40-60K(X):
overcurrent
EUWA(*)40-60K(X) Fuses EUWA(*)40K(X) EUWA(*)50K(X) EUWA(*)60K(X)
F8B 1A 1A 1A
F9B 1A 1A 1A
F12B 3 x 16 A 3 x 16 A 3 x 16 A
K17S 50 A 64 A 77 A
Overview fuses and The table below gives an overview of the fuses for each chiller type in the range EUWA(*)80-120K(X):
overcurrent
EUWA(*)80-120K(X) Fuses EUWA(*)80JX EUWA(*)100JX EUWA(*)120JX
F8B 2A 2A 2A
F9B 2A 2A 2A
F12B, F13B 3 x 16 A 3 x 16 A 3 x 16 A
K17S, K18S 50 A 64 A 77 A
Part 3
1
4 Troubleshooting
Introduction When a problem occurs, you have to check all possible faults. This chapter gives a general idea of
where to look for defects. Further the general procedures for refrigeration circuit repairs and for
electrical circuit repairs are explained. 3
Not all repair procedures are described. Some procedures are considered common practice.
page 3-29
5
4.7 – Oil Changing Procedures page 3-30
No malfunction The unit does not start and there is no malfunction indication.
indication
Possible causes Items to be checked
3 ■ PCB supply
The unit is not switched on ■ Check the remote start/stop setup and correct if setup
incorrectly
■ Check the field wiring in case of remote control
One of the timers is still active Check the timers overview in this manual or in the controller
An overview of the fault indications and safeties is given in ‘Overview of Fault Indications and Safeties’
on page 3-7. 5
1 Recover the refrigerant from the unit or perform a pump down (depending on the part that
needs to be changed). Refer to ‘Pump Down’ on page 3-28.
3 There are no special procedures for the replacement of refrigeration parts. We refer
to the general DAIKIN air-conditioning service manual for more information on the stand-
ard practice of refrigeration works.
4 All refrigeration work must be carried out by a licensed refrigeration engineer, and it must comply with
all relevant European and national regulations.
Service tools or equipment coming in contact with R-22 or mineral oils should not be used on R-134a
units and vice versa. Therefore, we strongly advice to have a separate set of manifolds, charging units,
vacuum pump and oil recipients only to be used with R-134a and polyester oils.
5
Electrical circuit The general procedure for electrical circuit repairs is explained below:
repairs
Step Action
1 Perform the measurements needed to locate the defective parts of the system.
All electrical work must be carried out by a licensed electrical engineer, and it must comply with all
relevant European and national regulations.
Step Action
2 Remove the old PCB. For the chillers EUWA(*)80-120K(X), also remove the address
board.
3 Place the new PCB in the same way as the old PCB.
4 Reconnect the PCB. Put also the address board back for the chillers EUWA(*)80-120K(X).
Address board for The address boards on the PCBs indicate the addresses of the PCBs of 2 circuits. From factory, the
3
EUWA(*)80-120K(X) PCB on top refers to circuit 2 and the PCB beneath refers to circuit 1.
■ Make sure that the dip switches are correctly set. Refer to ‘T-device between PCB A and PCB B’
on page 1-39.
Always make sure that PCB 1 is completely configured before PCB 2. If this is not taken into
■
account, this can result in a communication problem between PCB 1 and PCB 2. 4
Configuration To start configuration, proceed as follows:
procedure for
EUWA(*)40-120K(X) Step Action Result
1 Put on the power supply. Nothing will appear on the screen, because no configuration
has been made.
5
2 Press a,zand e After a few seconds, the user terminal will enter a screen, in
simultaneously for 5 which:
seconds.
TERMINAL ADR: 3
I/O BOARD ADR: 1 (in case of PCB 1) or 2 (in case of PCB 2)
If the values on the screen are different from the values
above, you can change them using h.
4 Press j to continue.
For more information concerning the controller, refer to ‘The Digital Controller’ on page 2-17.
1 In case of PCB 1, use h to change the address for terminal 1 into 3. In TRM1: 03 or
case of PCB 2, use h to change the address for terminal 1 into none. TRM1: NONE
2 Press j.
4 Press j.
7 Press j.
10 Press j.
12 Press j to leave the configuration screen and to enter the read-out menu.
1 Put on the power supply. After a few seconds, the user terminal
will enter the read-out menu. Refer to
4 ‘a Read-out Menu’ on page 2-24.
2 Press aand esimultaneously for 5 seconds. The leds above aand e light up.
5 For more information concerning the controller, refer to ‘The Digital Controller’ on page 2-17.
Load defaults When you have entered the factory menu, proceed as follows:
5 Scroll upwards using h to go to the first screen. You can start initialization.
6 Press j.
Settings Follow the screens on the next page to insert the settings of the former PCB.
Screen 1 This screen shows the information about the unit type:
1
Line n° Display Description Default setting To change the setting:
1 UNIT TYPE chiller type EUWA*40j *(1 circuit) 1 Use h to select the correct type.
EUWA*80j* (2 circuits) 2 Press j.
2 MANUFACT. NR. manufacturing number 0000000 1 Use hand j to change the digits.
2 Press j.
3 REFRIGERANT refrigerant type R-134a 1 Use h to select the correct refrigerant.
2 Press j.
Screen 2 This screen shows the information about the protection settings: 3
Line n° Display Description Default setting To change the setting:
1 MIN. OUTL. WATER minimum outlet water temperature 4˚C 1 Use h to select the
correct temperature.
When you enter a lower temperature 2 Press j.
than 4 °C, make sure that you adapt the glycol
quantity in the water. 4
2 BMS CARD INSTALLED not available N Press j.
3 LOAD DEFAULTS to change the default settings N Press j.
5
Screen 3 This screen shows the running hours of the compressor:
1 RUNN. HOURS 1 running hours of compressor 1 00000H 1 Use hand j to change the digits.
2 Press j.
2 RUNN. HOURS 2 running hours of compressor 2 00000H 1 Use hand j to change the digits.
(only for EUWA(*)80-120K(X)) 2 Press j.
Changing of the running hours is very important when the parts are used as spare parts.
Bypass mode means the mode, in which the electronic device is bypassed by an other optional
electronic device. This can be in case of failure of the electronic device.
3 Step Action
3 Press q until you see the circuit chiller. It takes approximately 10 seconds. In case of a
double circuit, select the circuit that you want to pump down.
4 4 Close the liquid line stop valve.
5 Press j.
9 Use a recovery unit to compartiment the rest of the refrigerant on the low pressure side.
Compartimentation: Pumping of the refrigerant from the low to the high pressure side using a pump
out unit. A gas bottle is not needed to recuperate the refrigerant.
Picture The following picture gives a visual view of the high pressure service port:
schroeder
valve
2 Operate the compressor until the unit pumps down to ± 1.5 bar.
4 Remove the remaining pressure via the 3/8” charging valve on the filter body by
connecting the discharge of the pump out unit to the condenser side of the unit (High
pressure service point). This step is also named compartimentation.
Do not stop the liquid injection to the compressor during pump down. This will
3
cause overheating and compressor damage.
5 Warm up the filter body with a hand-hold heater before opening the filter dryer to avoid
moisture deposits within the filter body and liquid line.
6 Prepare the filter cover gasket before opening the new filter core container in order to
keep air exposure to a strict minimum. 4
The compressor suction stop valve (if installed) and discharge stop valve must be closed during
service or repair to avoid moisture.
Step Action
2 Using compartimation, lower the suction pressure to a slight positive pressure in order to
force the oil into a receptacle.
Oil filter cleaning The following procedure explains how to clean the oil filter:
4 Step Action
1 Follow the oil drain procedure to recover the refrigerant and to drain the oil.
5 4
5
Clean the oil separator with an ozone-friendly cleaning solvent.
Oil charging After used oil has been drained, a fresh oil charge is required. This is normally the same amount as
was removed and is visually less than the initial charge, because a small part of the oil still remains in
some of the parts.
The equipment to charge is a vacuum pump and a charging line fitted with a shut-off valve. A pressure
gauge can be useful. The purpose is to get clean oil into a contaminent-free system. Therefore,
proceed as follows:
Step Action
4 Connect the oil container via a charging hose to the oil charge valve.
5 Purge the oil charge hose and open the oil drain valve.
The oil container should only be opened before charging. Since ester oils are very hygrocopic, use
containers corresponding to the required oil charge quantity.
Illustration The following photos shows the content of the oil separator:
1
discharge from the
screw side
unloader mechanism
oil filter
5
discharge side of the
compressor
the unit is under the pressure limit 1 look for oily spots on fittings and flanges.
2 wipe clean.
3 verify at a later stage.
Liquid charging This method is customary for larger systems. Therefore, a 3/8” charging valve is provided on the filter
dryer body so that the refrigerant can be added while the system is operating.
3 Step Action
1 Connect the refrigerant to the 3/8” charging port. Use a short 3/8” charging line to
minimise contamination or via a dryer if indicated. The cylinder should be upside down
if it does not have a liquid/vapour valve.
6 Close the liquid line valve at the condenser outlet in order to prevent the condenser
5 pressure from forcing liquid into the cylinder.
7 Slowly open the 3/8” charging port valve while the compressor is running (40%) and
charge liquid at a fast rate to prevent the compressor from cutting out on low pressure
control. The refrigerant flow can also be controlled by the cylinder valve to avoid ending
up with a hose full of liquid refrigerant. The same result will be obtained by closing the
cylinder valve when the charging is finished. This will avoid a charging line full of liquid
refrigerant.
10 Check the operating unit. If the sight glass is clear and high pressure and low pressure
appear normal, then the unit is correctly charged.
Make sure that the compressor rotates at 100 % for at least 15 minutes. This is
to assure stabilization.
13 Replace the caps on the cylinder valve and the charging valve.
Vapour charging This method is mainly used for smaller systems. However, trim charging through the schroeder valve,
mounted on the suction line of the unit, is possible. Follow the following steps: 1
Step Action
1 Remove the cap from the schroeder valve mounted on the suction side.
3 Connect the centre line from the manifold to the refrigerant cylinder.
4 Air purge the charging lines or open the charging line stop valves.
6 Place the charging cylinder on a weighing scale to verify the charge quantity.
7 Open the cylinder valve fully and control the refrigerant flow from the manifold. 3
Head pressure and suction pressure should be stabilized before charging.
8 Close the cylinder valve from time to time and verify the sight glass and suction pres-
sure.
If the cylinder pressure drops too low, place the cylinder in a bucket of warm
4
water or use a hand-held heater to increase the pressure.
10 Close the charging lines stop valves when the pressure indicated on the manifold is
5
equal to the suction pressure.
11 Disconnect the charging line from the schroader valve and replace the cap.
4
Part 4
Commissioning and Test Run
Introduction Commissioning and test run are well-known practices in service engineering. This part offers a
systematic approach to test-run checks and test values, which will guarantee a high quality installation
3
and operation of the units. It is, therefore, recommended to read the chapters in this part with attention.
Part 4
1
1 Pre-Test Run Checks
Introduction As shown in the table below, we have grouped the pre-test run checks into three main groups to
facilitate the servicing.
3
Overview This chapter covers the following topics:
Check if …
3 6 it is necessary to place a heatertape inside the drain system to prevent ice accumulation and
possible drain blockage during winter time.
7 no metal dust or burrs remain after grinding or drilling in the metal construction parts during
the installation. This facilitates the rust process and thus shortens the unit’s lifetime.
10 the air volume over the coil is adequate; no blockage (from paper, plastic,...) or air short cir-
cuit due to wrong positioning.
11 all shut-off valves indicated by a red label “OPEN THIS VALVE BEFORE OPERATION” are
opened
5
EUWA(*)40-60K(X): 2 shut-off valves
EUWAS40-60K(X): 3 shut-off valves
EUWA(*)80-120K(X): 4 shut-off valves
EUWAS80-120K(X): 6 shut-off valves
(*)= B, M, T or D
In order to avoid compressor damage, it is necessary to switch on the crankcase heater for at least 8
hours before starting the compressor after a long period of standstill.
Check if …
3 the water quality meets the standards (see table on the next page).
5 measurement points for temperature and pressure are available on the water circuit.
8 drain taps are installed at the low points of the water piping to permit complete drainage
during maintenance or shut-down, and drain plugs to drain the evaporator.
10 vibration compensators are installed to avoid straining the piping and transmitting vibration
and noise.
5
Water volume, flow To assure proper operation of the unit, the water volume and flow must be within the operation range
and pressure as specified in the following table:
Chiller type Minimum water volume* Minimum water flow Maximum water flow
EUWA(*)40K 1700 l 185 l/min 737 l/min
EUWA(*)40KX 2400 l 150 l/min 600 l/min
EUWA(*)50K 1700 l 185 l/min 737 l/min
EUWA(*)50KX 2750 l 200 l/min 715 l/min
EUWA(*)60K 2100 l 230 l/min 920 l/min
EUWA(*)60KX 3600 l 235 l/min 950 l/min
EUWA(*)80K 2400 l 290 l/min 1080 l/min
EUWA(*)80KX - 300 l/min 1165 l/min
EUWA(*)100K 3000 l 370 l/min 1160 l/min
EUWA(*)100KX - 390 l/min 1565 l/min
EUWA(*)120K 3600 l 460 l/min 1660 l/min
EUWA(*)120KX - 450 l/min 1665 l/min
The water pressure should not exceed the maximum working pressure of 10 bar.
1 Calculation of the
minimum water
The following calculation method is based on the fact that the water volume in a chiller should be large
enough to prevent the compressor from excessive cycling. Sufficient water volume will give a certain
volume inertia to the system so that water (or glycol) temperature does not drop too fast when the unit turns
on and that the temperature does not rise too fast when the unit turns off.
0,5 x Q x t
V= [m³]
2 x ρ x d x Cw
with:
4 Water quality In the table below you will find the required water quality specifications:
Tendency if out
Evaporator water
of criteria
Items to be controlled
Items to be referred to
Check if …
1 main fuses, earth leak detector and main isolator are installed.
2 the main power supply voltage deviates less than 10% from the nominal value.
3 the flow switch and pump contact are properly wired up.
7 the flow switch and pump contact are connected in series, so that the unit can only come in
operation when the water pumps are running and the water flow is sufficient.
8 the heater tape for the drain system (field supply) is powered up via a separate power supply.
4
To prevent the evaporator from freezing and to avoid damage to the LCD displays of the digital
controller, never switch off the power supply during winter. 5
Part 4
1
2 Test Run & Operation Data
Introduction The following tables give an overview of the measurements that you can do. Use it as a guideline
during commissioning.
For the location of the measurement points we refer to the piping and wiring diagrams in Part 1.
3
Pressures
Measurement Value
The minimum values are not valid in case of head pressure control.
5
Temperatures
Measurement Value
Voltages
Measurement Value
1 Currents
EUWA(*)40K 71 A 97 A 3x125 aM
Compressor Connect your pressure gauges on the suction and the discharge side of the compressor. Start the
rotation compressor for about 5 seconds and check if there is a pressure build-up. If not, change two phases
of the power supply.
5
Part 4
3 Refrigerant R-134a
1
3.1 What Is in This Chapter?
Introduction As R-134a, used for EUWA(*)40-120KX, is not on the market for a very long time, we will describe its
components and characteristics in this chapter
Service tools or equipment in contact with R-22 or mineral oils should not be used on R-134a units and
3 vice versa. Use separate manifolds, charging units, vacuum pump and oil recipients for R-134a and
polyester oils.
Humidity control Ester oil is very hygroscopic. This strong affinity for water increases the water content by hundred PPM
in a few hours. While it is very difficult to remove this humidity by means of a vacuum pump, the
maximum humidity level is set at 75 PPM after 48 hours operation.
4
The new filter cores on base of ZEORUM are very sensitive to this humidity. Therefore, a
minimum air exposure before installation in the system is a must.
Mineral oil The maximum contamination of mineral oil in ester oil is 5000 PPM.
5 contamination
Handling R-134a For more information about the handling of R-134a, refer to ‘Precautions’ on page 5-4.
3.3 Characteristics
1
Characteristic table The following table shows the characteristics for R-134a:
Description
Critical temperature
bar
40.64
0.508
3
Critical density kg/l 1.26
mPa.s
1.7
0.205
5
Dynamic viscosity (25°C) saturated vapour mPa.s 0.012
Data R134a versus The following table compares the working values of R-134a with R-12.The used symbols are:
R12
■ compression ratio: pc/po
■ volumetric refrigerating effect: q0,th
■ compressor discharge: th
R-134a R-12
-25 9.51 748 59.1 2.8 -25 7.78 822 62.6 2.9
-20 7.63 942 57.7 3.2 -20 6.37 1012 60.8 3.3
-15 6.19 1176 56.5 3.7 -15 5.27 1235 59.3 3.8
-10 5.05 1455 55.4 4.2 -10 4.39 1495 57.9 4.3
t0 t0
Compression ratio Compressor discharge temperature
C C
3 qo.th kJ / m
3
t0, sh = 10 K 6
t0, sh = 10 K
2000 o
tc = 40 C
o tc = 40 C
1800
5
tc, sc = 5 K tc, sc = 5 K
1600
1400 4
1200
4 1000
800
R-12
R-134a
3 R-12
R-134 a
2
5 0 -5 -10 -15 -20 -25 -30 5 0 -5 -10 -15 -20 -25 -30
t0 OC
O
t0 C
Volumetric refrigerating effect Coefficient of performance (COP)
4
Part 5
Maintenance
Introduction Preventive maintenance should be set up for operation at maximum capacity or to avoid damage. The
following chapters explain how to or when to maintain the waterchillers.
3
What is in this part? This part contains the following chapters:
Part 5
1 Maintenance
5
1.1 What Is in This Chapter
Introduction As shown in the table below, we have grouped the maintenance in maintenance of the main parts
(condenser, compressor and evaporator) and periodical checks.
3 Compressor No maintenance is normally required. In case of vibration, check the mechanical operation.
maintenance To maintain the oil-level:
the oil-level in the sight glass is add oil via the stop valve on the bottom section of the oil
approximately 3/4 of the sight glass separator by reducing the air contact to minimum.
when the compressor is running.
Reduce the crankcase pressure to 0 before adding
oil or use a hand pump.
5 ■
■
compressor (types EUWA(*)40K and EUWA(*)80K) is SUNISO 4GSD (7.5 l)
compressor (types EUWA(*)50K, EUWA(*)60K, EUWA(*)100K and EUWA(*)120K) is SUNISO
4GSD (10 l)
■ compressor (types EUWA(*)40KX and EUWA(*)80KX) is IDEMITSU FVC68D (10 l)
■ compressor (types EUWA(*)50KX, EUWA(*)60KX, EUWA(*)100KX and EUWA(*)120KX) is
IDEMITSU FVC68D (13 l)
The compressor suction stop valve, if installed, and discharge stop valve must be closed during
service to avoid moisture level increase.
Condenser A fouled condenser indicating an abnormally high condensing pressure can result in an increasing
maintenance power consumption and trip-outs. Verify the saturated condenser pressure temperature difference to
the leaving air temperature. If the difference is more than 15°C, clean the outside surface of the
condenser by rinsing the coil surface with low pressure fresh water in order to remove possible salt
deposits.
Evaporator ■ Inspect the evaporator tubes after the first operating season. This condition indicates the required
maintenance frequency of cleaning and also whether water treatment is needed in the chilled water circuit.
■ Check the air plugs and drain plugs to prevent or detect water leakage.
Water checks
Check the water condition. Dirty water causes a cooling capacity drop
1. Drain the water from the air release plug. as well as corrosion of the water heat
2. If the water is dirty, replace all the water in the sys- exchanger and pipe.
tem.
3. Check the water connection.
Noise checks
4
Appendix A
Photo parts
Introduction In order to find a visual view of some of the components, the following list will give you the references
of the parts according to photos integrated in this manual.
3
Parts versus The following table shows the page of the photo on which the part is pointed:
photos
Call-outs See page...
page 1-32
A
4
controller page 1-32
A
3 sight glass page 1-28
4
Appendix B
Drawings
Introduction In order to find quickly the drawings inserted in this manual, appendix B offers a list with all the
drawings.
3
Drawings table The following table shows the page and description of all the drawings:
B
3
Index
1
General index
A
address board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-25
air-heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
alarm
circuit alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20, 3-8
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20
3
unit alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20, 3-8
ambient temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
analog input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
B
BMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-29
4
Building Management System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-29
C
calculation of the minimum water volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
change parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
change password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-41
5
changing
filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-29
oil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-32
charging
oil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
checking
digital inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-15
power supply and fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-19
temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
checks
electrical checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-7
general checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-4
water flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
water piping checks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
water pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
water quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
water volume. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
cleaning
filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
compressor
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
start-up sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-30
condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-44, 1-45
contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-5
control
inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
Index i
ESIE97–02
General index
1
controller
compressor timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-30
discharge temperature controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
front panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-18
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-32
info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-36
input/output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22, 2-37
password set points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-29
password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22, 2-41
read-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-24
remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-27
set points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-26
D
4 digital controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-17
digital input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-5
digital inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-18
digital output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-6
discharge temperature controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27, 2-14
draining
oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
5
E
electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-12, 1-13
emergency stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
equal start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-12
evaporator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
expansion valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
F
factory menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-26
fan
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
start-up sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
fan control procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
fans speed control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
fault indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-8
field wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-43
freeze-up
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-10
functional diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-22, 1-23, 1-24, 1-25
fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-19
H
head pressure control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-7
head pressure setback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-16
head pressure stop valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
high pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
ii
ESIE97–02
General index
1
high pressure transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
history menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-32
humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-12
I
info menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-36
inlet water temperature control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
input/output menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22, 2-37
inputs
analog inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4
digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-5
digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-6
inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-3, 3-4, 3-5
installation outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-19
3
L
lead-lag control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-12
k
liquid injection solenoid valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
liquid line solenoid valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
liquid stop valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
k
k
1-26
1-26
1-27
4
low pressure transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
M
main board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-34
main pcb layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-34
maintenance
5
compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-3
main parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
menu overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21
O
oil
concentration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-12
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-30
operation data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-9
operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-4
options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-43
outlet water temperature control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6
outlook. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-14, 1-15, 1-16, 1-17
overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-19
overview of inputs/outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-3
P
parameters
how to change. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
how to read . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
password
change password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-41
set points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-29
password menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-22, 2-41
PCB
changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-25
pcb. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-34
Index iii
ESIE97–02
General index
1
piping layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-21
power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-19
pre-test run checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-3
procedure
fan control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-8
programming procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-23
pump down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-28
R
read-out menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-24
3 refrigerant
characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-13
handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5-4
refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-32, 4-11
refrigeration circuit
ambient temperature sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
S
safety
circuit safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20, 3-12
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-12
unit safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-20, 3-12
sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-5
sensors
ambient temperature sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
controller sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-17
type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
water temperature sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
set points menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-26
sight glass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
software timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-30
start-up sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-9
switch box
layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-32
switch box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-33
iv
ESIE97–02
General index
1
T
T-device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-39
technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-4, 1-6, 1-8, 1-10
temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-16
temperature setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-19
temperature-resistance values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-17
terminal connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-44, 1-45
test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-3, 4-9
thermostat
automatic mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
load up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5, 2-28
loaddown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5, 2-28
manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5, 2-28
stepdifference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5, 2-28
3
steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
STPL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5, 2-28
thermostat control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-5
thermostat parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-6, 2-28
timers menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-30
transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-5
transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-4, 3-5 4
transmitters
high pressure transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
low pressure transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3-21
U
unloading solenoid valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
5
user settings menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2-21, 2-27
W
water
calculation of the minimum water volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
in- and outlet connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-6
temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-27
volume. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 4-5
water-heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-26
wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-41, 1-42
wiring layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1-31, 1-40
Index v