U-STO Parametre Kılavuzu V1.00 TR
U-STO Parametre Kılavuzu V1.00 TR
U-STO Parametre Kılavuzu V1.00 TR
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
U-STO
No Contactor Required
Integrated Elevator Control Unit
Parameter Guide
www.mik-el.com 1/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
Contents
1. Menus and Usage................................................. .................................................................. .......................... 4 1.1.
LCD Display and Keypad .................................................. .................................................................. ............ 4 1.2.
Entering the Menu and Setting Parameters ............................................. .............................................. 6 1.3.
Parameters................................................. .................................................................. ......................... 7
2. Errors and Explanations................. .................................................................. .................................................................. ...27
3. Drive Solid Fault and Descriptions ............................. .................................................................. ..............35
www.mik-el.com 2/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
• This manual has been prepared to instruct the user on the correct use of the U-STO Integrated Elevator
Control Unit with other necessary components in a control cabinet and a revision box to control an
elevator.
• Mik-el Elektronik San. ve Tic. Ltd. Sti. does not guarantee the conformity of the system with EN-81 and
assumes no responsibility in case of non-compliance with the points specified in this document and
other documents of the U-STO Integrated Elevator Control Unit.
• Mik-el Elektronik San. ve Tic. Ltd. Sti. shows the necessary attention and care to ensure that there are no
errors or omissions in all technical documents. However, despite all efforts, users should be careful
against errors and deficiencies that may occur in the documents and apply the information in the
documents by filtering them in line with their professional knowledge and experience, as well as all
relevant norms, regulations and directives. Mik-el will be grateful if such errors and omissions are
reported and will take steps to correct them.
• All property rights of the content of this document belong to Mik-el Elektronik San. ve Tic. Ltd. ÿti.
Reproduction and distribution, in whole or in part, is subject to the written permission of Mik-el.
www.mik-el.com 3/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
1. Menus and Usage
1.1.LCD Screen and Keypad
Home Screen and Keypad
[NORMAL] [11:30] ÿ
[ = 00 ÿ ] [0.000] ESC ENT
CAGRI IS WAITING
ÿ
The functions of the buttons on the CPU board are listed below.
Button Mission
Splash Screen; After the card is energized, it is the start screen of the card software.
vx.yy.zz
FLASH CRC OK
EEPROM CRC OK
CAN-BUS SYNC OK
- Mission
*1 : If there is an error in the software installed on the card or an error occurred during the installation, the warning “FLASH
CRC ERROR” appears on the screen. Software must be installed on the card via the bootloader, if the software installation fails,
the card must be sent to the company for repair.
*2 : “EEPROM CRC ERROR” message appears on the screen if there is an error or an error has occurred in the parameters
found and set on the card . When this message is seen , the factory values of the parameters are tried to be reloaded by
pressing the “ENT” button. As a result of this process, the parameters of the card will be reset to their factory values, so the
elevator parameters must be rechecked and adjusted. If this error cannot be corrected despite pressing the “ENT” button, the
card must be sent to the company for repair. The details of the EEPROM CRC checks and the parameters affected by the error
are given below.
In addition , EEPROM CRC check is done at every movement start and in call standby mode. If an error has occurred, the
message “EEPROM CRC ERROR” appears on the screen.
Error seen;
Error Explanation
MAIN CRC ERROR The menu parameters have been reset, they need to be reset.
FLOOR CRC ERROR Well, gauges and door parameters have been reset, need to be reset.
EEPROM CRC ERROR All parameter values have been reset, must be reset.
www.mik-el.com 4/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
Software Version Screen; The software of all serial communication cards in the system
versions are displayed on this screen. To access this screen, the “ESC” key must be pressed on the main screen.
U-STO Vx.yy.zz
AAA Vx.yy
BBB Vx.yy
- Mission
AAA Vx.yy Shows the software version of the revision box board.
BBB Qx.yy Displays the firmware version of the cabinet cassette (COP) card.
Quick Menu
The list of operations that are displayed in the quick menu and that can be done quickly are given below.
To access the main screen, “UP / UP” or “DOWN / DOWN” keys must be pressed.
• Q1 Quick internal call screen.
• Easy monitoring of cabin and cabin top, pit and panel signals connected to the system.
• Q6 Communication status of floor cards with serial communication.
• Q7 Cab speed, distance from its position in cm and m/s.
• Auxiliary parameters in testing and commissioning.
ÿ Q10 Canceling external calls . (Outside calls cannot be given from floors.)
ÿ Q11 Canceling door opening. (Door opening process is cancelled.)
ÿ Q12 Car cassette communication cancel . (Car cassette communication control is cancelled.)
ÿ Q13 Test travel with mixed internal calling. (The system automatically generates the call and
serves calls.)
• Q14 UCM test start.
• Voltage control of Q24 CPU card 3V battery (Real time clock), CPU 24V supply, Cabin board 24V supply and
emergency lighting battery.
• Q31 Clearing the saved UCM error.
• Q32 Automatic addressing of floor cards with serial communication.
• Q33 Exit/reset operation of the well dibivision.
• Q34 Starting well learning mode.
• Q37 Motor current, motor voltage, DC bus voltage.
• Q38 Speed, rpm, frequency, slip frequency.
• Q39 Coolant temperature information.
• Q40 Run times.
• Q41 Measurement travel. (It is used to find the pole position angle in gearless motors.)
• Values of the Q44 Maneuver counter.
If there is a "ÿ" sign next to the signal on the signal monitoring screen in the quick
>KRU ÿ INV
menu, it means that the signal is active.
>KRL EFK PTC
For example, it is understood that the “KRU ÿ” KRU signal is read by the card.
>KRO ÿ FR1 ÿ PI1
Using this screen in case of error and detection will save you time and benefit.
>DSI FR2 ÿ PI2
www.mik-el.com 5/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
Floor Card Monitoring Screen with Serial Communication
On the Q6 screen, the communication of the floor cards with serial communication connected
Q6 to the system can be monitored.
01234567891012345 - : The floor card is not connected or there is no communication.
678920123456789301
S : Indicates that the floor card is Simplex selected and is communicating.
23456789401234567 A : Indicates that the floor card is selected in the “A” group and is communicating.
B : Indicates that the floor card is selected in the “B” group and is communicating.
In order to enter the menu, press and hold the “ENT” button while on the Main Screen.
Note: to access the menu, the elevator can be used for error, undo, revision or stationary (All calls
completed, call waiting) status.
[NORMAL] [11:30] ÿ
[ = 00 ÿ ] [0.000] ESC ENT
CAGRI IS WAITING
ÿ
If there is no password protection in the menu, you will enter the menu. If there is password protection in the menu, the
password screen will appear. Enter the password with the “Up” and “Down” arrows and press the “ENT” button.
If the password you entered is correct, you will enter the menu. If the password is incorrect, the "PASSWORD WORTH" warning message is displayed.
and you will not be able to enter the menu.
Parameter Setting
The menus are grouped for more efficient use of the parameters and easy use according to the relevant task.
Button Mission
www.mik-el.com 6/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
1.3.Parameters
• W Menu Quick Setup Settings
In the U-STO Integrated Elevator Control Unit, the parameters that the user needs to set for basic operation are gathered under a
single menu. Thus, the basic parameter in commissioning
system is activated quickly. After the commissioning process is completed, other settings related to the elevator can be made under the relevant
menus. The parameter list under the quick setup menu is given below.
CAN GET
PARAMETER EXPLANATION
VALUES
A35 Turkish
Menu language is set from this parameter
menu language English
A30 -
The time and date settings of the system are made from this parameter.
Date and Time Settings
A03 EN81-20 The standard to which the control card will work is selected from this
Standard Compliance EN81-1/2 +A3 2-48 parameter.
A06 The number of stops that the elevator will serve is determined.
Number of Stops (24) *HSM module over 24 stops is required.
COLLECT AS/LOAD - KS
The logic of the system to serve the calls is determined.
BATON. COLLECTION - KSA S24T (With internal calls, without external calls aggregate)
A10 KS (Double Button, Bidirectional Addition)
Control Type KARIS. SUM-KSL KSA (One Button, Downward Gathering)
KSL (One button, Stupid Collection)
IC COLLECTION – S24T
SINGLE ELEVATOR In group operation, the identity selection of the elevator is adjusted from this
A15 parameter. If group work is not used, it should be set as “Single elevator”. * HSM
Working Mode module is required for 3 or 4 group work.
GROUP A/B/C/D
NONE Applies to controller type KSA only. The number of stops under the ground is entered
A20
from this parameter. The elevator collects the external calls of these floors upwards.
Number of Underground Stops 1 -5
GEAR ENCODER
GEARLESS ENDAT
C10.7 LEFT
Motor rotation direction is adjusted from this parameter.
Motor rotation direction RIGHT
C10.9 0-9000
Engine Rated Speed Engine speed is entered in this parameter.
C09 (1460rpm)
Driver
Fast
C10.15 2-98
Number of In gearless motors, the number of poles of the motor is entered in this parameter.
Settings (2)
Motor Poles
C10.17 0-42 A
The nominal current value written on the motor nameplate must be entered in
Motor Rated
(18A) this parameter.
Current
C10.19 0.65-0.95
Cosÿ value written on the gear motor label must be entered into this parameter.
CosinePhi
(0.84)
Value
C10.21 230-450
The nominal voltage value written on the motor nameplate is entered in this
Motor rated
(400V) parameter.
voltage
www.mik-el.com 7/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C10.23 0.1-200
Gear transmission ratio of the motor is entered in this parameter. gearless
engine transmission
(35) 1 must be entered for motors.
rate
C10.25 0-5000
motor pulley The diameter of the carrier pulley of the motor is entered.
(440mm)
diameter of
C15.13 0.1-3000rpm
The nominal travel speed of the elevator is adjusted from this parameter. It gives
High Speed V3 the value of the speed in m/s according to the entered value and the value of the
deceleration path that will be needed in mm. 817/818 mandatory retarder switches
(1400rpm)
should be placed according to this distance.
C09
Driver The value of the second intermediate speed to be used in the elevator is
Fast C15.11 adjusted from this parameter. It gives the value of the speed in m/sec according
0-1399.9rpm
Settings Intermediate speed V2
to the entered value and the value in mm of the deceleration path that will be
needed. The distance of the 820 switch must be adjusted according to the
(0rpm)
deceleration distance of the lowest speed entered in the parameters C15.11 and
C15.9.
The value of the 1st intermediate speed to be used in the elevator is adjusted
C15.9 from this parameter. It gives the value of the speed in m/sec according to the
0-1399.9rpm
Intermediate speed V1
entered value and the value of the required deceleration path in mm. The
distance of the 820 switch must be adjusted according to the deceleration
(0rpm)
distance of the lowest speed entered in the parameters C15.11 and C15.9.
C15.7
0-500rpm
Berthing speed Vo The berthing speed is adjusted from this parameter. Its default value
(100rpm)
corresponds to 0.05 m/s.
C15.1
Leveling Vn 0-500rpm The speed value to be used during level renewal is entered from this
(10rpm) parameter. Its default value corresponds to 0.02 m/s. It should be below 0.3
m/s.
C15.5
0-401.2rpm
Undo speed Vr The value of the speed to be used during the Undo operation is set
(100rpm)
from this parameter. It should be below 0.3 m/s.
C15.3
0-842.6rpm
Revision rate Vi The speed value to be used during the revision work is adjusted from this
(250rpm)
parameter. It should be below 0.63 m/s.
ART ENCODR+MP/A3
D05 COUNTER+LOVE LIGHT
How to read the information about the cabin position is determined.
Well Copy Type INCREMENTAL ENCODER
COUNTER
AUTOMATIC
The type of landing door is set.
F05 MANUAL
AUTO+MANUAL : If only one floor (F15) door is automatic and the other floors
Landing Door Type AUTO + MANUAL
are swing doors, this value is selected.
NO DOOR
LIMIT
The opening time of the elevator door is set.
It changes by 1 second increasing-decreasing. When “Limit” is selected, the door
F20
continues to open until the door is fully open signal to the K16x input during door
Door Opening Time
opening.
1 – 30 s
(3s)
www.mik-el.com 8/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
When the door open signal (photocell or DTO) comes, how long the door will open is
LIMIT
set. (It changes by increasing and decreasing by 1 second) When “Limit” is selected,
F25
the door opens until the limit signal is received at the K16x input.
Door Back Open Time 1 – 30 s
(1 second)
NONE The device to be used to prevent the unintentional movement of the cabinet (UCM)
is selected from this parameter.
G01 SPEED REGULATOR When “Speed Governor” is selected, the status of the speed governor is monitored
from the “KRO” input.
UCM Source
When “Engine Brake” is selected, the state of the engine brake is monitored from
ENGINE BRAKE the FR1 and FR2 inputs. Monitoring is done before and during movement.
PASSIVE
Phase control is done with the 3 phase reading circuit on the card.
SINGLE PHASE
I01 PASSIVE: Phase control is not performed.
Phase Protection Mode SINGLE PHASE: The phase connected between TN is controlled.
WITHOUT PHASE SEQUENCE
PHASE ORDERED: Phase control is done out of order.
PHASE SEQUENCE: Phase control is done sequentially.
PHASE SEQUENCE
THERE IS
I05 If the mains voltage is cut off, whether the UPS will be brought to the floor
Is There Recovery? or not is determined by this parameter.
NONE
YEAH
F60 Whether early door opening will be made or not is set from this parameter.
Early Door Opening NO
H05 PASSIVE
Level Correction It is set whether the lift will make level correction or not.
Function? ACTIVE
7 SEGMENTS The Gray/Binary code output type of the revision card is determined.
K05 GRAY Cards with 7-segment outputs can be output continuously.
Cab Indicator Type BINARY
GRAY
K10 Gray/binary code output type of GBx outputs to which floor indicators are connected
Floor Display Type is determined.
BINARY
-9..-1
0-47
A
B
C
D
TO
F
G
K15 H It defines the floor characters to be displayed on the floor and car displays.
7 Segment Sorting L
n
HE
P
R
T
U
P0-P9
B0-B9
www.mik-el.com 9/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
• A Menu General Settings
CAN GET
PARAMETER EXPLANATION
VALUES
EN81-20
The operating functions of the control card are adjusted according
A03 Standard Compliance EN81 -1/2 + A3 to the relevant standard operation.
2-48
The number of stops that the elevator will serve is determined.
A06Number of Stops
(24) *HSM module over 24 stops is required.
COLLECT AS/LOAD - KS
The logic of the system to serve the calls is determined.
BATON. COLLECTION - KSA S24T (With internal calls, without external calls aggregate)
SINGLE ELEVATOR In group operation, the identity selection of the elevator is adjusted from
this parameter. If group work is not used, it should be set as “Single lift”.
A15 Working Mode
DUBLEX A/B/C/D
*HSM module is required for 3 or 4 group operation.
NONE Applies to controller type KSA only. The number of stops under the ground
A20 Underground Station
is entered from this parameter. The elevator collects the external calls of
Number 1-5 these floors upwards.
NONE
In group work, the difference between elevator A and other elevators is
A21 Bottom Stop Difference
12 selected from the bottom.
NONE
In group work, the difference between lift A and other lifts is selected from
A22 Top Stop Difference
12 the top.
-
A30 Date and Time Settings System clock settings are made from this parameter.
TURKISH
A35 Menu Language The language option of the menu parameters can be adjusted.
ENGLISH
CAN GET
PARAMETER EXPLANATION
VALUES
GEAR ENCODER
GEARLESS ENDAT
512-8192
C10.3
The pulse number of the encoder used is entered.
Number of encoder pulses (1024)
BA It is the parameter that determines which of the A and B channels comes
C10.5
first. If wrong direction error is given, this parameter value is changed.
Encoder Direction A -B
0-9000
C10.9
Engine speed is entered in this parameter.
Engine Rated Speed (1460rpm)
www.mik-el.com 10/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
0-350Hz
C10.11
The frequency value written on the motor nameplate is entered into this parameter.
Rated Motor Frequency (50Hz)
It is the value of the angle between the encoder and the motor poles in
gearless motors. It can be determined automatically by performing
0-360°
C10.13 “Q41:Measurement Travel”. The process should be repeated more than
Pole position angle once to ensure that the values close to each other are found. For the most
(240°)
accurate result, it is recommended to select the "Without Rope" option on the idle
motor.
2-98
C10.15 In gearless motors, the number of poles of the motor is entered in this parameter.
Number of motor poles (2)
0-42 A
C10.17 The nominal current value written on the motor nameplate must be entered in
Motor Rated Current this parameter.
(18A)
0.65-0.95 Cosÿ value written on the gear motor label must be entered into this parameter.
C.10.19
CosinePhi Value (0.84)
230-450
C10.21 The nominal voltage value written on the motor nameplate is entered in this
Motor rated voltage (400V) parameter.
0.1-200
C10.23 Gear transmission ratio of the motor is entered in this parameter. 1 must be
engine transmission ratio (35) entered for gearless motors.
0-5000
C10.25
The diameter of the carrier pulley of the motor is entered.
Motor pulley diameter (500mm)
1/1-1/4
C10.27
The hanger ratio of the cabinet is entered.
Rope suspension ratio (1/1)
0-5
C10.31 The motor output current limit is set to the value resulting from the product of the
Motor Output current limit (2) rated current with this parameter.
66-75°C
C10.37 The maximum temperature value allowed to operate the IGBT module is set.
IGBT temperature threshold (66°C)
C10.38 ABSOLUTE
In gearless motors, the encoder channels to be used in calculating the rotor
rotor position
INCREMENTAL position are selected from this parameter.
calculator
PASSIVE
C10.39 If the value of this parameter is "ACTIVE", it is checked whether the motor is
Motor phase loss control ACTIVE connected or not.
www.mik-el.com 11/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C15- Drive speed selection menu
CAN GET
PARAMETER EXPLANATION
VALUES
C15.13 The nominal travel speed of the elevator is adjusted from this parameter.
High Speed V3 0.1-3000rpm It gives the value of the speed in m/s according to the entered value and
(1400rpm) the value of the deceleration path that will be needed in mm. 817/818
mandatory retarder switches should be placed according to this distance.
C15.1 0-500rpm The speed value to be used during level renewal is entered from
Leveling Vn (30rpm) this parameter. Its default value corresponds to 0.02 m/s. It should be
below 0.3 m/s.
C15.5 0-401.2rpm
Undo speed Vr The value of the speed to be used during the Undo operation is set
(380rpm)
from this parameter. It should be below 0.3 m/s.
C15.3 0-842.6rpm
Revision rate Vi The speed value to be used during the revision work is adjusted from
(760rpm)
this parameter. It should be below 0.63 m/s.
C15.15 90-200% If the difference between the measured speed value and the desired
Overspeed error limit (150%) value exceeds the value set here, the device goes into error.
AVAILABLE
PARAMETER EXPLANATION
VALUES 0.01-3
C20.3 m/s^2 Adjusts the steepness or tilt of the acceleration curve, it should be selected
Acceleration Slope (0.50 m/s^2) lower than 0.40 on old and heavy drive roller machines.
C20.5 0.01-3 m/s^3 Adjusts the smoothness of the transition to high speed at the end of the
Acceleration Transition Slope (0.50 m/s^3) acceleration curve, it should be chosen lower than 0.30 on old and heavy
drive pulley machines.
C20.7 0.01-3 m/s^2 Adjusts the steepness or tilt of the deceleration curve, it should be selected
Deceleration Slope (0.80 m/s^2) lower than 0.40 on old and heavy drive roller machines.
C20.9 0.01-3 m/s^3 Adjusts the smoothness of the transition to slow speed at the end of the
Deceleration Transition Slope (0.80 m/s^3) deceleration curve, it should be selected lower than 0.30 on old and heavy
drive roller machines.
www.mik-el.com 12/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C25-Drive Control Settings Menu
CAN GET
PARAMETER EXPLANATION
VALUES 0-100
C25.1 % (0%) It suppresses the speed control PID values at take off. If there is
Gain Attenuation at Start C25.3 0-100 % vibration in the engine, it is increased, if the driving target is exceeded, it is decreased.
Gain Attenuation at acceleration (0%)
C25.5 Gain Attenuation at high Suppresses speed control PID values on acceleration.
speed C25.7 Gain Attenuation at
deceleration C25.9 Gain Attenuation
0-100 %
at coasting C25.11 Speed control It suppresses speed control PID values at high speed.
(0%)
P coefficient C25.13 Speed control
I coefficient C25.15 Speed control
0-100 %
D coefficient C25.17 Speed control Suppresses speed control PID values at deceleration.
(0%)
time constant C25.19 Speed
control dynamic C25.21 Speed
0-100 %
control PT1 Filter C25.23 Current It suppresses the docking speed control PID values.
(0%)
control P factor C25.25 Current
control I coefficient C25.27 Current 0-32000 Motor speed control error rate coefficient
control D coefficient C25.29 (20000)
Current control dynamic C25 .31 0-32000 Motor speed control error sum coefficient
Current control PT1 filter C25.33 (2000)
Current control ID PT1 filter C25.35 0-32000 Motor speed control error correction coefficient
Current control IQ PT1 Filter (0) 10
C25.43 Alt. Current Control Trigger -500ms (90 The motor speed control cycle time is set.
Threshold C25.37 Alt. Current ms) 0-90
Control P Coefficient C25.39 Alt. % (50%) The motor speed control suppresses the PID values.
Current Control I Coefficient 0-9999ms
C25.41 Alt. Current Control D (0 ms) Filters motor speed control feedback.
Coefficient 0-32000
(5000) Motor current control error rate coefficient
0-32000
( 500) Motor current control error sum coefficient
0-32000
(0) 0-90% Motor current control error correction coefficient
(0 %)
0-999ms Motor current control suppresses PID values.
(0 ms)
0-128 ms (0 Filters motor current control feedback.
ms) 0-128
ms (0 ms) Filters motor current control ID feedback.
PASSIVE The following PID values are used at speeds above the speed specified with
this parameter. Alternative PID values can be used when the motor vibrates
0.1-1500rpm at low speeds.
0-32000 Alternating current control error rate coefficient
(5000)
0-32000 Alternating current control error sum coefficient
(500)
0-32000 Alternating current control error correction coefficient
(0)
www.mik-el.com 13/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C30-Drive Control/Stance
CAN GET
PARAMETER EXPLANATION
VALUES
It determines the start delay of the movement after the brake is opened.
0-3000ms It prevents the start of movement when the brake is still closed. A value
C30.1
Brake open delay (350ms) depending on the opening delay of the mechanical brake is selected.
C30.3 AUTOMATIC It indicates how many mm to stop after the floor switch.
braking distance When “AUTO” is selected, it is automatically determined to incline 0.5
0.1-99.9mm
m/s2 according to the approach speed.
C30.7 0-500%
Backflow prevention DC (0%) It is used in geared motors to prevent run-back at start-up.
component
C30.9 0-500%
Anti-backflow PI values (0%) It is used to prevent run-back on takeoff.
C30.11 0-80% In open loop starting, it increases the current of the motor as a
Open loop take-off support percentage of the entered value. If the motor cannot rotate despite the
(40%)
motion command, this value should be increased.
C30.12 0-80%
During docking in open loop, it increases the motor current as a
Support in open loop berthing percentage of the entered value. If the elevator cannot move at the
(40%)
approaching speed, this value should be increased.
C30.13 0-100% It is used to compensate for variations in rotational speed caused
Slip in open loop speed (10%) by load variation in open loop.
Whether to hold at take off or position at take off is set with this parameter.
C30.15 NONE It is used to prevent backtracking. If the rope is connected in synchronous
hold on takeoff motors, this parameter is set. If the rope is not connected in asynchronous
THERE IS motor and synchronous motor, this parameter is set to none.
www.mik-el.com 14/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C35- Function Settings
AVAILABLE
PARAMETER EXPLANATION
VALUES 0.01-4.0
C35.1 m/s Sets the speed limit threshold of the unlock zone. If the speed is below the
V03 Relay threshold (0.30 m/s) specified threshold, the relay is activated and its contact is closed.
• Safety Circuit Monitoring
• Inverter Error Output
• Brake Control
C35.3
• Phase Loss
PRG1 Relay output safety circuit ÿ Normally Open
monitoring
ÿ Normally Closed
• Posture Zone
• Deceleration Zone
• Main Contactor Output
C35.5
• Rescue Change Direction
PRG2 Relay output safety circuit
• Pre-Filling
monitoring
• Short Circuit Contactor
• External Fan
• Overload
• Engine Hot
• Drive Hot
• V<Vx Threshold
C35.15 48-400V If UPS is 325V is selected.
Recovery unit output voltage (325V) If it is battery, the battery voltage is selected.
C35.17 -80% to 100% range Intensity of dc injection at the start of the rescue movement
Recovery exit support -20%
C35.19 TEST
Recovery easy wayfinding NONE Easy navigation mode is selected here during recovery.
FINAL LOAD MEASUREMENT
ENCODER MONITORING
C35.25 90-500% During the rescue, the lift can go as high as the rate in the parameter
Speed limit in rescue 300% from the maximum rescue speed.
C35.29 TEMPORARY Whether the errors are permanent or not is set with this parameter. If the errors are
Overcurrent fault mode PERMANENT selected as temporary, the commands are dropped and the error is exited.
This parameter determines where the backup power input used in the recovery
will be made.
UPS IN L1-N
If recovery will be made with UPS, the "L1-N" option should be selected.
In this case, the UPS connection must be made from the UPS input
C35.31
terminals.
Backup power input
“L11-L31” value should be selected if recovery will be made with battery.
L11-L31 PHASE In this case, by using mains and backup power contactors of suitable amperage,
it should be ensured that the mains are disconnected from the device in case of
a power outage and the batteries are fed to the L11-L31 inputs.
C35.32 ACTIVE This parameter is used to determine whether or not to check for the not allowed error.
No permission error PASSIVE controlled with.
www.mik-el.com 15/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C40-Drive Communication settings menu
VALUES THAT
PARAMETER EXPLANATION
CAN BE TAKEN
C40.5 Version:7.25 Displays device version and amperage.
Driver definition version Device Length: 18A
C40.9 19:02094
Device serial number
Serial number
www.mik-el.com 16/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
C50.19 It is used to filter the undervoltage fault that occurs during the
revision delay 0-5000ms frequent hard stop during revision work. If the dc bus voltage is below the
1000ms required value at the end of the set time, the low intermediate voltage error
is recorded.
C50.21 500-5000ms In order to find the easy direction in recovery, the test time is determined by
Recovery test time 1000ms this parameter.
C50.23 0-20000ms How long after a transaction ends, a new transaction can start is set
motion delay 1000ms in this parameter.
• D-Well Settings
CAN GET
PARAMETER EXPLANATION
VALUES
COUNTER
INCREMENTAL ENCODER
D05 COUNTER + LEVEL
How to read the information about the cabin position is determined.
Well Copy Type CORRECTION
INCREMENTAL
ENCODER+MP/A3
After the motion starts, it is checked whether the encoder receives pulses
D08 0-7 sec after the time entered in this parameter and whether the encoder rotates in
Encoder Tracking Delay (3.5 sec) the correct direction. If there is no pulse or the encoder rotation direction is
reversed, a position error is given.
If the value of this parameter is different from “0”, direct docking is cancelled.
D09 0-5 sec
During the time entered before the stop, the elevator moves at the
Additional Berthing Distance (0 sec)
approaching speed.
1. Magnet
D10 In order for the elevator to stop at the target floor, which magnet of that floor
Deceleration Magnet Selection 2.Magnet should slow down is set.
D15 If D05 Counter or Counter + Level Correction is selected, the lift switches to
None(X) … 48 slow speed at the 2nd magnet between the stops specified in this parameter.
Long Floor Range
D16 If D05 Counter or Counter + Level Correction is selected, the lift switches to
None(X) … 48 slow speed at the 1st magnet between the stops specified in this parameter.
Short Floor Spacing
The distance that the elevator will slow down when it is at V3 high speed is
D17High Speed KV3 adjusted from this parameter.
10-500cm
Deceleration Distance *HSM module is required if the deceleration distance is greater than 500cm.
D18 Intermediate Speed-2 KV2 The distance that the elevator will slow down when it is at intermediate speed
0-(< D17)cm
Deceleration Distance V2 is adjusted from this parameter.
D19 Intermediate Speed-1 KV1 The distance that the elevator will slow down when it is at intermediate speed
0-(< D17)cm
Deceleration Distance V1 is adjusted from this parameter.
D20 - In well copying with encoder, floor alignments are adjusted from this
Floor Alignment Settings parameter.
D21 This parameter is set to delay the upward stop after the floor signal is
Floor Alignment on Exit 0 – 2.5 s detected.
delay (changes by 0.1 second increment-decreasing)
This parameter is set to delay the downward stop after the floor signal is
D22 Floor Alignment on Landing
0 – 2.5 s detected.
delay
(changes by 0.1 second increment-decreasing)
D23 5 – 120 s If the location information does not change within the set time, the system
Floor to Floor Time Limit (20sec) records "Timeout Error" and goes out of service.
www.mik-el.com 17/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
D24 1.50 – 2.50 See section “3.12 Determining the Travel Speed of the Elevator”.
Speed Usage Multiplier (2)
NONE It is set how long after the elevator goes into standby mode, the cabin lamp
E05
will turn off.
Cabin Lamp Extinguish 1-15 sec
(It changes by increasing-decreasing for 1 second. “X” option should be
Time
(9 sec) selected for cabin lamp to stay on continuously.)
NONE The maximum number of calls that the elevator can receive from the internal
E10 control in normal operating mode is set.
Internal Call Limit The parameter value is shown as "X" instead of "N/
1-9
A".
E15 10 – 300 sec How long the cabin fan will run after the fan button is pressed is set in this
Cabin Fan Working Time parameter. If the Fan button is pressed again while the fan is running, the
(50 sec) Fan will stop.
NO DOOR
F10
The type of cabinet door is set
Cabin Door Type AUTOMATIC
YEAH
F12
Whether there is a second door in the cabin is adjusted from this parameter.
Is There a Backdoor? NO
A
F13 B Which door will work on which floor is determined by this parameter.
Front/Back Door Selection
A&B
F15 0 – 47 When landing door type (F05) "AUTO + MANUAL" is selected, Automatic
Automatic Door Floor door floor is adjusted from this parameter.
LIMIT The opening time of the elevator door is set.
It changes by 1 second increasing-decreasing. When “Limit” is selected, the
F20 door continues to open until the door is fully open signal to the K16x input
1 – 30 sec during door opening.
Door Opening Time
(3 sec)
www.mik-el.com 18/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
LIMIT When the door open signal (photocell or DTO) comes, how long the door will
F25 open is set. It changes by increasing and decreasing by 1 second. When
1 – 30 sec
Door Back Open Time “Limit” is selected, the door opens until a limit signal is received at the K16x
(1 sec) input.
F30 0 – 30 sec After the elevator door is opened, it stays open for the value set in this
Door Close Delay (1 sec) parameter and starts to close.
F31 In elevators without a manual landing door and without a car door, how long
1 – 30 sec
Waiting Time on the Floor the elevator will wait on the floor before going to the next call is set with this
parameter.
The time that the elevator will wait for the door to be closed and locked before
starting the movement is adjusted from this parameter.
F32 0 – 30 sec
If the door is not closed and locked within this period, it is tried to be closed
Lock Waiting Time (10 sec) and locked by opening and closing the door again. “Door Not Closed” if the
door does not close after 3 attempts, “Door Klt. error” is given.
If the front and back doors are opened together (A&B) on the floor, before the
bridges in the A door can be detected, the safety circuit is checked for the
F33 0 – 30 s time set in this parameter by opening the A door. If door A is not unlocked or
Door Lock Monitoring Time (2 sec) unplugged after this period, it means that there is a bridge in the plug or lock
of door A.
The system switches to the Safety Circuit fault.
The operating mode of the door limits is selected from this parameter.
Normally Open
Normally Closed: the corresponding limit signal is cut off when the door is
F34
opened or closed.
Door Limits Contact Type
Normally Closed Normally Open: The corresponding limit signal comes when the door is
opened or closed.
F35 How long after the landing door is closed before starting the movement, the
0 – 3 sec
lirpompun will be energized and the landing door will be locked from this
Lyre Withdrawal Delay
parameter.
The operation mode of the photocell input is adjusted from this parameter.
Normally Open
F36 Normally Open: When the photocell detects an object, a signal should be sent to
the K30 input.
Photocell Input Contact Type
Normally Closed Normally Closed: When the photocell detects an object, the signal at the K30
input should be cut off.
NONE If this parameter is not selected, the function is passive. If the photocell signal
F36.1 is detected during the entered time, the low-power door closing command is
Photocell Timeout 10-60 sec given by ignoring the photocell signal at the end of the time. (with K1x relay).
F40 In elevators with manual landing doors, how long after the interior door starts
0 - 20 sec to open, the unlocking of the landing door is set from this parameter.
LIR Release Delay
F50 10 sec – 60 sec When the door of the elevator is kept open, the time after which it will go out
Door Left Open Out of Service of service is set from this parameter (changes by increasing-decreasing for 5
(60 sec) seconds).
Pass Time
YEAH When the elevator receives a floor call from the floor it is on while closing the
F55
door before starting the movement, whether the door will be opened back or
Door Back Open on Outside Call NO
not is adjusted from this parameter.
YEAH
F60 Whether early door opening will be made or not is set from this parameter.
Early Door Opening NO
0-30cm In systems with encoder duplication, the number of cm before the floor level
F63
to start the early door opening process is set from this parameter.
Early Door Opening Distance (10cm)
www.mik-el.com 19/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
F65 Early door opening is started after the time set in this parameter after MLA and
0–1s
Early Door Opening Delay MLB region are detected.
NONE The device to be used to prevent the unintentional movement of the cabinet
(UCM) is selected from this parameter.
SPEED REGULATOR
G01 When “Speed Governor” is selected, the status of the speed governor is
UCM Source monitored from the “KRO” input.
When “Engine Brake” is selected, the state of the engine brake is monitored
ENGINE BRAKE
from the FR1 and FR2 inputs. Monitoring is done before and during movement.
G05 ACTIVE
When this parameter is selected as “Active”, internal calls from inside the car
Internal Call Delete Function PASSIVE are deleted when the button is pressed again.
G10 0 – 3 sec After the landing and car doors are closed, how long the elevator will wait before
Departure Delay (0.1 sec) starting the movement is set.
G11 PASSIVE If the elevator is to be used as a Fireman's elevator, this parameter should be
Firefighter Mode ACTIVE selected as “Active”.
G12 PASSIVE If the fireman key will be used in the cabin, this parameter should be selected
Fireman in Cabin as active. In this case, the firefighter key in the cabin must be connected to the
Switch>USTO IN6 ACTIVE
IN6 input of the USTO.
G13 A
In two-door elevators, which door will work in Firefighter mode is determined by
Firefighter Mode Door Selection B this parameter.
G14.1 NORMALLY OPEN When the G12 parameter is active, the contact type of the fireman switch
813C (USTO > IN6) Contact Type (connected to the U-STO IN6) input used in the cabin is determined by this
NORMALLY CLOSED
parameter.
G16 How long after the elevator goes to the waiting state, it will go to the parking
Immediately – 5 min.
Parking Delay floor is selected from this parameter.
G17 Open
Whether the door is closed or open on the parking floor can be adjusted from
Door Status in the Park Closed this parameter.
G20 0 – 47
Fire evacuation stop is selected from this parameter. A value between 0 and the
Fire Evacuation Floor (0) maximum number of stops (A06) can be selected.
G22 ACTIVE
When the system is in fire evacuation mode, it is selected whether it can be
Vatman Mode on Fire PASSIVE used with the "Vatman" key.
G23 ACTIVE
If the fire evacuation function in accordance with EN81-73 standard will be used,
Fire Evacuation Mode PASSIVE this parameter is selected as “Active”.
www.mik-el.com 20/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
How to terminate the fire evacuation mode is determined by this parameter.
SIGNAL
G23.1 When "Signal" is selected, the elevator returns to its normal operation when the
Fire Evacuation Mode Output signal connected to the 816 input returns to normal.
Type
SIGNAL & RESET>Q42 When “Signal &Reset>Q42” is selected, after the signal connected to the 816
input returns to normal, the lift must be reset from the Q42 menu so that it can
return to normal operation.
When the value of this parameter is selected as “Close”, the door on the fire
G24 OPEN
evacuation floor is closed after keeping it open for 20 seconds. The door can
Fire Evacuation Door be opened again for 20 seconds by pressing the floor call button on the DTO or
Status CLOSED fire evacuation floor. When “Open” is selected, the door is kept open until the
fire alarm signal is cut off at the fire evacuation floor.
G25.1 When "With 806 Signal" is selected, the elevator returns to its normal operation
when the signal connected to the 806 input returns to normal.
Earthquake Mode Output Type
806 AND RESET>Q43 When “806 &Reset>Q43” is selected, after the signal connected to the 806
input returns to normal, the lift must be reset from the Q43 menu so that it can
return to normal operation.
When the earthquake signal is detected and the elevator stops at the nearest
OPEN
floor, if the value of this parameter is "Open", the door is kept open until the
G26 earthquake signal is cut off. When “Close” is selected, the door is closed again
Door Status in Earthquake
CLOSED after opening. DTO button is active, the door can be opened again by pressing
this button.
The SSR card is used to detect the entrance of unauthorized persons to the
PASSIVE elevator shaft from the landing doors and to stop the operation of the elevator.
In order for the SSR card to be used, the SSR card must be connected and the
G35 value of this parameter must be selected as “Active”. Opening any of the landing
SSR Board Well Protection
doors outside the control of the control card causes the "SSR Well Protection"
function
error to occur. In this case, the system is blocked.
ACTIVE
From this parameter, the closing time of the car door is entered to be used in
LIMIT
the well protection function. When “Limit” is selected, it is detected that the car
G36
door is closed from the door closed limit signal connected to the K19 input.
SSR Card Door Closing
Time Otherwise, it is detected that the car door is closed at the end of the entered
1-30 sec time or when the safety circuit is completed (whichever comes first).
If a card access system is used at the floors, after the signal is detected at the
G40 NONE (X)
IN2 input of the U-STO, calls are received from the floors for the set time. Calls
Card Entry on the Floor
Reading Time 1 – 10 s from floors are not accepted when the time expires or the signal at IN2 is cut off.
If a card access system is used in the car, after the signal is detected at the IN2
G41 NONE (X)
input of the car cassette card (SC24,PCR,MVCDD..), a call is received from the car
Cabin Card Entry for the set time. At the end of the time or when the signal in IN2 is cut off,
Reading Time 1 – 10 s incoming calls from the car are not accepted.
www.mik-el.com 21/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
TEMPORARY ERROR The operating mode selection is made after the system records the 120 error.
G45 Depending on the value of this parameter, after 120 signal is received, it can
Error 120 exit the error or remain on the error.
PERMANENT ERROR
TEMPORARY ERROR The operating mode selection is made after the system registers error
G46 130. According to the value of this parameter, after 130 signal is
Error 130
PERMANENT ERROR received, it can exit from the error or remain in the error.
TEMPORARY ERROR
The operating mode selection is made after the system records 140 errors.
G47 After the 140 signal is received, it can exit the error or remain in the error
Error 140 depending on the value of this parameter.
PERMANENT ERROR
When the value of this parameter is selected other than “0”, when the
control card detects a KRU error, it repeats the KRU control by giving a
motion command for the time entered in this parameter and interrupting it.
The purpose here is to ensure that the closed contacts are seated by
G48 0 – 1 sec pulling and releasing the contactors without moving the elevator. If KRU
Command Controlled by KRU
(0 sec) error is detected in three consecutive attempts, KRU error is passed and
The time
the system is blocked.
The time set from this parameter should be enough to not allow the speed
controller to pull the brake contactors.
This ensures that the cabinet will not move.
No
G49 When “Save From MD” is selected, the driver settings are backed up.
Inverter Settings Save From MD Selecting “Restore to MD” restores previously backed up driver settings.
Save / Restore
Restore to MD
NO
This parameter is used to reset parameter values to factory settings. Control
SXU PARAMETERS
G50 card Parameters, well/indicator and MD parameters can be reset
settings
to factory
without
Return to Initial Settings SXU WELL/INDICATOR affecting each other.
MD PARAMETERS
PASSIVE When the value of this parameter is "Active", open source remote monitoring
G55 data is sent over the internal CAN-Bus (CAN-INT) line.
Remote Monitoring Data ACTIVE
In some elevators, special ropes are used. The service life of these
ropes is determined by the manufacturer.
When these ropes expire, the ropes must be replaced before continuing
PASSIVE to use the elevator.
MBM card and special hand terminal are required to use this function.
When “activated”, the maneuvers of the elevator are counted and stored
G65 on the MBM card. When the number of maneuvers of the elevator
Rope Maneuver Counter
reaches the value set in the G66 parameter, the elevator is blocked. In
order for the elevator to return to normal operation, a new MBM card
must be installed after the ropes are replaced. Since the MBM card
ACTIVE matches the U-STO in which it is installed, it cannot be inserted into any
other U-STO for any purpose. The MBM card, whose maneuver counter
is full, cannot be used again.
www.mik-el.com 22/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
The number of maneuvers allowed by the manufacturer of the rope used
must be entered in this parameter. !!! The allowed number of maneuvers
G66 0-9999999
may vary from lift to lift, depending on the rope suspension ratio. Consult
Number of Rope Maneuvers (1000000)
your rope manufacturer for the correct value.
G68 - If rope control is not performed, the date on which the system will be blocked is
Rope Inspection Date entered from this parameter.
CAN GET
PARAMETER EXPLANATION
VALUES
H05 PASSIVE
Whether the lift will make level correction or not is adjusted from this parameter.
Level Correction ACTIVE
Function?
H15 0 – 2.5 sec Level correction starts after the time set in this parameter after the car slips
Leveling Up Start
(1 sec) from the floor level.
delay
While the elevator is leveling up in the upward direction, it is set how long it will
H20 0 – 2.5 sec
take to finish leveling after it reaches the full floor.
Up Level Correction
(0.1 sec)
Stop Delay
(changes by 0.1 second increment-decreasing)
While the elevator is leveling in the down direction, it is set how long it will take
H25 0 – 2.5 s to complete the level correction after it reaches the full floor.
In Down Level Correction
(0.1 sec)
Stop Delay
(changes by 0.1 second increment-decreasing)
PASSIVE Phase control is done with the 3 phase reading circuit on the card.
www.mik-el.com 23/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
I06 0 – 15 sec It is set how long the elevator will switch to recovery mode after the power is
cut off.
Recovery Start Delay (8 sec) (changes by 1 second increasing-decreasing)
I07 How long after the lift goes into recovery mode, it will start to move is
0 – 15 sec
Recovery Movement Start adjusted from this parameter. (changes by 1 second increasing-decreasing)
delay (8 sec)
In rescue mode, how long the movement will continue to bring the car to the
I08 30 – 210 sec
floor is set from this parameter. If the car cannot reach the floor level within
Recovery Time Limit (60 sec) this period, the movement is terminated.
I09 0 – 10 sec How long after the mains voltage is restored, the elevator will return
to the normal operating mode is set.
Recovery End Delay (3 sec)
www.mik-el.com 24/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
• K Menu Display Settings
CAN GET
PARAMETER EXPLANATION
VALUES
K05 The 7-segment display outputs on the PCR card are always active
BINARY
regardless of this parameter. The type of GBx outputs on the cabinet
Cab Indicator Type
cards is selected from this parameter.
GRAY
K10 GRAY
Gray/binary code output type of SLFCP and STPXX card is determined.
Floor Display Type BINARY
K12 0–8
The first initial value of Gray or Binary code is set from this parameter.
Gray/Binary Initial Value (0)
-9
-8
-7
-6
…
0
one
47
A
K15 D
It defines the floor characters to be displayed on the floor and car
7 Segment Sorting TO
displays.
G
H
L
HE
P
R
P0-P9
B0-B9
www.mik-el.com 25/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
The direction it is going: the direction of movement of the car and the direction it will go
THE DIRECTION IT'S GOING
K25 when it reaches the floor are shown on the display.
Direction Arrow Type The direction it will go: the direction of the car is not shown, only the direction
DIRECTION TO GO it will go when it reaches the floor is shown on the display.
ACTIVE When the call given on the floor cassettes with serial communication is
K30 recorded by the system, the warning sound can be activated with this
PASSIVE
Call Received Voice Alert parameter.
• M-REGISTERED ERRORS
PARAMETER VALUES AVAILABLE EXPLANATION
M05
-
Control System Registered Indicates faults in the control system.
Show Errors
M06
-
Driver Saved Errors Shows errors recorded in the drive bay
Show
M10 YEAH
When "Yes" is selected, recorded errors in the control system are deleted.
Control System Registered
Delete Errors NO
M11 YEAH
When “Yes” is selected, recorded errors in the driver are deleted.
Delete Driver Saved Errors NO
Errors that occur in the system are recorded by the control card with date and time, up to 48 errors. 48 errors
When a new error occurs on the record, the oldest error record is deleted and the new error is recorded.
Logged Errors
M05
CONTROL SYSTEM By pressing the “ENT” button, the recorded errors are displayed.
STORED ERROR Saved errors are displayed with Up and Down arrows.
SHOW ERRORS
M10
CONTROL SYSTEM By pressing the “ENT” button, it is seen that the “M10” parameter is flashing.
DELETE ERRORS The "YES" option is reached with the Up and Down arrows.
NO “ENT” button is pressed and recorded errors are deleted.
www.mik-el.com 26/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
fault is corrected.
www.mik-el.com 27/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
o Take the elevator to the lowest floor and move it upwards.
ÿ In counter systems, MB contact must be closed first. The switch may be faulty.
ÿ
In the well copying system with encoder, it is observed that the position information has changed on the
Q7 screen. If the position information does not change, the encoder operation and connection is checked.
Sometimes run-backs that occur during take-off can be detected. In this case, the value of
the “Encoder monitoring delay” parameter should be increased.
2.6.MLA/MLB ERROR
• Cause of error:
o MLA-MLB signals are not interrupted even though the lift is outside the unlock zone.
• Working mode of the elevator when the error occurs:
o The elevator goes to slow speed, stops at the floor and gets blocked.
o Lift early door opening and door open level correction without MLA-MLB error
do not do.
• Troubleshooting:
o MLA/MLB unlock zone magnets should be placed 15 cm before floor level. Check that the magnets
are in the correct position. These magnets should not be located between the floor position
information magnets (between the floors) in the counter system.
o Check the strength of the MLA/MLB switches.
o Make sure that the MLA/MLB inputs are not bridged over 100.
www.mik-el.com 28/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
2.10. ERROR 817, 818
• Reasons for the error:
o One or both signals 817 or 818 have a bridge or fault. signals
it keeps coming.
o One or both signals 817 or 818 have a fault. Signals are not coming at all.
• Working mode of the elevator when the error occurs:
o The lift is blocked when this error occurs
• Troubleshooting:
o Connections of 817 and 818 switches are checked.
o The operation of 817 and 818 switches is checked, if there is a fault, they are replaced with a new one.
www.mik-el.com 29/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
2.13. SSR WELL PROTECTION ERROR
• Cause of error:
o Opening any of the landing doors beyond the control of the control card
It causes the "SSR Well Protection" error to occur.
• Working mode of the elevator when the error occurs:
o When this error occurs, the lift is blocked.
• Troubleshooting:
o Make sure that no landing doors are open.
o Check SSR board connections.
o Check the second contact of the landing doors and the resistors connected to these contacts.
• Cause of error:
o Elevator started to move, contactors were energized, contactor/contactors
and were not energized. but
The KRU circuit is not interrupted.
• Working mode of the elevator when the error occurs:
o The lift tries to start 3 times to energize the contactor(s) that are not energized. If the problem still persists,
the system switches to an error and deletes all recorded errors, if it is on the floor, it opens the doors and
allows the passengers to be evacuated. It returns to normal operation after 10 seconds.
• Troubleshooting:
o Check the NC contact of the contactors on the control panel where the KRU signal circulates. Replace the
defective contactors with new ones.
o When the contactors pull, the contactors pull out due to the contact failures in the safety circuits.
may have quit. Check all safety contacts.
• Cause of error:
o The control system waits for the doors to be locked before starting the movement. If the doors are not locked
within the time set in the F32 “LOCK WAIT TIME” parameter, the door is opened and closed 3 times to
ensure that the doors are locked, and if the door is not locked in the third attempt, the door lock line is
given.
• Working mode of the elevator when the error occurs:
o When this error occurs, the lift deletes all recorded calls and returns to normal operation after 5 seconds. In
the next operation, every time the door cannot be locked, it switches to the door lock error without trying 3
times.
• Troubleshooting:
o Check the lock and lock contact. You can observe it from the 140 leds on the PT1 board.
o Check whether the lock contacts are conducting properly.
o Check the wiring of terminal 140 on the control panel.
o The value of the F32 parameter must be more than the closing time of the door.
www.mik-el.com 30/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
2.17. MOTION DOOR ERROR
• Cause of error:
o The door circuit of the elevator was opened while the elevator was in motion.
• Working mode of the elevator when the error occurs:
o When this error occurs, the elevator makes an emergency stop and the elevator is blocked until the door
circuit is closed.
• Troubleshooting:
o Check all door safety circuits. You can observe it from the 130 led on the PT1 board.
www.mik-el.com 31/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
2.22. ROPE CONTROL ERROR
• Cause of error:
o Elevator ropes were not checked until the entered date.
• Working mode of the elevator when the error occurs:
o The elevator is blocked.
• Troubleshooting:
o Check the ropes for wear. If it needs to be changed, replace it. If the wear on the ropes is within tolerance,
enter the next rope inspection date in the "Rope Inspection Date" parameter.
• Troubleshooting:
o Make sure that 3-phase power is supplied to the L1, L2, L3 terminals. o If a
UPS is used, make sure that the UPS is connected correctly and is working.
o By removing all the cards (SCR, PCR, SC24, ) in the internal CAN-Bushat one by one, the error can be detected.
check if it is fixed.
o Sometimes encoder corruption or connection errors can cause this error to be triggered. Check if the
error is corrected by removing the encoder terminal.
2.25. INVERTER ERROR
• Cause of error:
o An error occurred on the driver floor. The error is shown on the bottom line of the screen. See the driver
errors section for a description and troubleshooting of these errors.
www.mik-el.com 32/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
2.27. WELL LEARN ERROR • Reason for the
o The control panel is taken to the REVERSE position with the BACK-UP
switch. o Quick menu is entered and the system is recovered from UCM error by selecting Q31 parameter
“YES”. o Entering the revision mode and returning to the normal mode or powering off the panel does not allow
the system to recover from the UCM error.
o If the error cannot be resolved, the CPU board should be sent to the company for repair.
www.mik-el.com 33/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
2.32. PHASE SEQUENCE
• Reasons for the error:
o Phases connected to 3 phase monitoring inputs are not in correct order
• Working mode of the elevator when the error occurs:
o The elevator is blocked until the phases are connected in the correct order.
• Troubleshooting:
o 3 phase supply line connections are controlled according to phase order.
o The two phases at the panel entrance should be replaced with each other. After this operation, the engine
Mechanical rotation direction must be checked.
www.mik-el.com 34/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
3. Driver Solid Error and Descriptions
3.1.ERROR-01 overcurrent HW
• Transistor module and heatsink temperature should not exceed 150 degrees. Drive temperature should be checked.
• It may be drawing excessive current. The empty car should be moved downwards from the top floor and the currents
drawn should be followed on the monitoring screen.
• If there is abnormality in current values, MACHINE-MOTOR parameters should be checked.
should be done.
• It must be ensured that the device current is equal to or higher than the motor current.
• Values of attenuation parameters in CONTROL PARAMETERS menu
should be increased.
• If it is an induction motor, make sure that the problem is not caused by the encoder.
should be tested in open loop.
www.mik-el.com 35/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
3.6.ERROR-07 internal pre-fill
• Within 5 seconds after the device is energized, the DC power voltage returns to its normal level.
he can't get out.
• The voltage value on the device label and the mains voltage should be compared and compatible.
must be sure.
• There may be a short circuit to ground in the braking resistor and its cables.
www.mik-el.com 36/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
• Ensure that the encoder is intact. • Make sure that the encoder
cables are connected and the encoder is coupled to the motor. • Check the encoder supply voltage. • Make
sure that the exposed encoder cables do not touch other cables.
• It must be ensured that the device current is equal to or higher than the motor current. • Values of
attenuation parameters in CONTROL PARAMETERS menu
should be
increased. • It should be checked whether there is a short circuit at the motor
output. • If there is a star-delta connection, it should be checked.
www.mik-el.com 37/38
Machine Translated by Google
U-STO “SafeTorqueOff“
Integrated Elevator Control Unit No Contactor Required
Document Version: V1.00 -En / 07-10-2019
3.21. ERROR-50 current control
• Although the motor is activated, it does not draw current.
• Motor connections should be checked.
ÿ END OF DOCUMENT ÿ
www.mik-el.com 38/38