2022handout 1 - 1 Pilot Wire Circuits
2022handout 1 - 1 Pilot Wire Circuits
0.0 Introduction
To control something is to exercise directing influence over something.
To supervise something is to be in charge of something.
Supervisory Control is the general term used for control of many individual
controllers and control loops, whether by human or by an automatic control system
although almost every operating system is a combination of both.
A more specific use of the term is for SCADA systems which refers to the network of
computer processes that provide control and monitoring of a remote mechanical or
electrical operation like management of a power distribution grid or control of a
mechanical process in a manufacturing plant.
When a fault takes place it is detected by protective relays and the fault current
is interrupted by the circuit breaker.
The maintenance personnel must then rush to the fault location, rectify the fault,
and restore the supply. This applies to permanent faults.
However, there is statistical evidence that about 80% of faults are not permanent
but are transient.
AUTHOR: UCHIYABU 1
Fault Statistics
type of fault probability
Transient 80%
Semi-Permanent 10%
Permanent 10%
Thus, whenever a fault takes place, we can tentatively assume that a transient fault
has interrupted the supply. We then wait for a short while before switching on the
circuit breaker. This is known as re-closure.
If the fault was indeed a transient one and the interruption was of duration greater
than the de-ionisation time, then the re-closure would be successful, meaning that
there would be no recurrence of the fault.
If the fault is a permanent one, re-closure will be unsuccessful, meaning that the
protective relay would immediately cause the circuit breaker to trip.
Re-closure has different implications for low/medium voltage (LV/MV) and high or
extra high voltage (HVIEHV) systems.
AUTHOR: UCHIYABU 2
Only one re-closure is allowed in HV/EHV systems because re-closure imposes
arduous duty on the circuit breakers and other elements of the power system as the
fault MVA is very large.
In HV/EHV systems, re-closure, if done sufficiently fast, helps in improving the
stability of the system. This is so because as soon as there is an interruption in the
system, the rotor angles of various generators start drifting apart and if they drift
apart beyond a critical angle, the system loses stability. If, however, the supply is
restored before this critical time elapses, the system can pull together and remain
stable.
Since HV/EHV lines are generally tie lines, there is presence of source at both the
ends.
Thus, in order for the transient fault arc to be quickly quenched, the line must be
instantaneously and simultaneously tripped from both ends, before a re-closure can
be attempted.
The three-stepped distance protection for the entire line length does not
meet the requirement of instantaneous and simultaneous tripping from
both ends. Only about 60%of the length in the middle of the line gets high speed
protection from both ends.
For about 20% of line length, near each end of the line, i.e. a total of 40% of line
length, the protection is instantaneous from the local end but is delayed from the
remote end.
Only 60% of line length in the middle gets high speed protection from both ends
AUTHOR: UCHIYABU 3
0.2 Various Options for a Carrier
Protective relays process information contained in the voltage and current at the
local end. The relay, only indirectly infers about the conditions at the remote end
through these signals.
As the fault distance increases, there is always an ambiguity about the exact location
of a remote fault. It becomes impossible to distinguish between a fault just beyond
the remote bus and one just ahead of it.
However, there is no ambiguity about the same fault from the end nearest to the
fault because as the fault moves from just beyond the bus to just ahead of it, there
is an almost 1800 change in the phase of current at the nearest end.
Thus, the nearest end has the clear-cut information which is so difficult to extract
using power, frequency, current and voltage at the remote end.
If we could, somehow pass on this small amount of information from one end to the
other, it would enhance the quality of decision making at both the ends.
We, therefore, need some carrier to carry this information.
AUTHOR: UCHIYABU 4
0.4 Available Options for a Carrier Signal
possible carrier description
Leased telephone line from Running cost is very high. Maintenance is a problem and guarantee
the telephone line provider of quality of service may be difficult to obtain.
Terrestrial Microwave Frequency range is between 3 and 30 GHz. The range of
Communication channel communication is line of sight. A large number of antenna towers
(either owned by the utility are required. Therefore, initial investment and maintenance cost are
or leased) both very high. Provides very large bandwidth, which may be shared
with other data communication services.
Satellite Communication via Frequency range is between 3 and 30 GHz. Propagation delays
VSAT terminals using involved are of the order of [2*36000km] / [3*105km/s] =240ms i.e.
geostationary satellite at 12 cycles (50 Hz basis) and this is not permissible for real-time
36, 000 km power system protection. Large bandwidth is available.
Power Line Carrier Most economical, since power line conductor doubles as the physical
communication medium for carrying the carrier signal. The carrier signal is a signal
of much higher frequency, compared to power frequency, which is
coupled to the EHV line. Frequency band allocated to this service is
50-200 kHz. Thus, the carrier signal frequency is just above the
audible frequency range and just below the medium wave radio
broadcast band. Due to moderately low frequency of the carrier, a
small bandwidth is available. However, protective relaying does not
need a large bandwidth. What is important is the delay involved,
which is very small in case of power line carrier, for example, a
1000kmline will cause a delay of 0.33 milliseconds.
AUTHOR: UCHIYABU 5
0.6 Pilot Protection Systems
Concepts Basic to a Protective System: selectivity, reliability, security
1. Selectivity:
1.1 Requires that the protection system be dependable in identifying faults in its
zones of protection
1.2 This is achieved by the relay designer, who uses sound logic for fault
detection and line tripping.
2. Reliability
2.1 Requires that the protection system be operable, meaning that the overall
design will ensure appropriate protective action even if some portion of the
protective apparatus may have failed
2.2 This is achieved by:
1. using equipment of high quality
2. performing routine testing to ensure that the equipment remains operable
3. designing a protective system that has redundancy
3. System Security
3.1 Refers to the capability of the protection system to refrain from operating
when it should not operate
3.2 For the protection system, this means that the relaying system must be
selective and also that precautions are taken to ensure that no operation is
initiated, either by the relay logic or other means, that would cause the
tripping of important lines or other facilities when not absolutely necessary
Pilot Relaying Systems utilise a communications path for sending signals from the
relaying system at one end of the line to that at the other end.
AUTHOR: UCHIYABU 6
Notes
1. The relay systems at each end of the transmission line monitor the local currents
and voltages.
2. These signals, or a derived response, are sent to the local relay equipment only,
where trip signals may be generated and sent to the circuit breakers at the local
relay location (shown by dashed lines).
3. Additional equipment is provided that permits each relay to send signals to the
relay equipment at the remote end of the line.
This provides each relay location with new information regarding the need for
tripping, namely, the view of the disturbance seen from both ends of the line.
Both relays can now operate on the basis of the condition observed from both
relay locations.
There are different physical methods of signalling between the two ends of a
transmission line for protective relaying purposes. These signalling systems are
called pilot systems.
AUTHOR: UCHIYABU 7
Equipment used in Pilot Protection
1. The innermost link identifies the physical equipment used for signalling between
the line terminals.
The physical link can be any of the following: telephone line, microwave link,
radio link, or fibre-optic communications system.
For protective relaying the physical link will be a dedicated telecommunications
system, since it is not acceptable that the relay might receive a busy signal when
trying to communicate.
2. The tele-protection equipment level includes the physical link and its terminal
equipment, and also includes hardware, and associated software, at the terminals
that are required to take the relay output data and inject it into the
communications equipment.
This might include coupling equipment, modems, or other devices required to
make this translation from the protective equipment to the telecommunications
equipment.
3. The terminal equipment of the pilot protection system is the protective devices.
This includes transducers required to gather data from the power system, a logic
system to process that data, and determine if a certain signal should be
transmitted to the relay system at the opposite end.
AUTHOR: UCHIYABU 8
Pilot Wire System Classification
AUTHOR: UCHIYABU 9
2. Phase Comparison based on Relative Phase Angles of the Currents
Wave deflections based on wave deflection at the fault point is relatively a new
technique
3. Current-Based Systems
3.1 Current Differential
3.2 AC Pilot Wire
3.3 Digital Current Differential
3.4 Charge Comparison
Many pilot schemes are referred to as permissive schemes. This is a general term
which signifies that functional cooperation of two or more relays is required before
control action is taken.
Classification based on
the Consortium for Large Power Systems (CIGRE) Working Group:
pilot
protection systems
non-unit
unit schemes
schemes
phase directional
comparison comparison
AUTHOR: UCHIYABU 10
Signal Frequencies
The following signal frequencies have been used:
AUTHOR: UCHIYABU 11
The term pilot means that between the ends of the transmission line there is an
interconnecting channel of some sort over which information can be conveyed.
The foregoing classifications of transmission media separate the pilot systems into
significantly different physical systems. The methods of signal conditioning and
transmission may be any number of different types.
In power system protection communications, the signalling applications have
traditionally been analogue transmission in any of these media, although digital
systems may predominate in the future as digital systems become available at
reasonable costs.
It is not clear whether future protection signalling will ever be performed using the
integrated services digital networks (ISDN), which are planned
telecommunications systems that utilise digital transmission and switching
technologies to support voice, data, text, and image transmission.
AUTHOR: UCHIYABU 12
Such future systems may offer higher reliability for protection functions, because of
their inherent multiple redundancies, but at the expense of not having dedicated
facilities, which are defined as facilities for only a particular function. It would not be
satisfactory, for example, for a protective system to receive a busy signal indicating
that all available channels are in use.
The ISDN system may, however, offer a very reliable redundant channel for relaying
purposes.
Wire pilot relaying systems have been used for many years to protect transmission
lines, but these schemes are limited in their application.
1. this technique is limited to lines that are short enough to justify the cost of the
installation or leasing of separate pilot circuits for relaying.
A Wire Pilot is generally economical for distances of up to 15 or 20 km.
2. the pilot wires are themselves a transmission line, with the usual series resistance
and inductance and shunt capacitance per unit of length.
As the pilot transmission lines become long, the pilot line requires special tuning
to optimise signal transmission, and this is usually feasible only at the two
terminals rather than being distributed along the circuit.
This also limits the use of wire pilot to relatively short transmission lines.
The first type is called a circulating current scheme for pilot protection.
AUTHOR: UCHIYABU 13
schematic of a circulating-current wire pilot system
Note that a current balance relay is used at each end of the line. The currents shown
in the figure represent the normal condition, with current entering one end of the
line and leaving the other end. Under this condition, the CT secondary currents flow
in the restraint windings of each relay and no current flows through the operate
windings.
If a fault occurs on the line, the currents at the right-hand end of the line will
reverse, which will cause currents to flow in the operate windings of both relays.
Note that the pilot wires are an exact low-voltage replica of the transmission line.
In this system, the pilot wires are crossed and no current flows in the pilot wires
under the normal condition shown in the figure, which forces the currents to flow
through the restraint windings of each relay.
For both of the wire pilot schemes illustrated, only the currents of one phase are
shown in the diagrams to reduce on cost and complexity.
In practice, the three-phase currents are combined in various ways to provide
correct relay action for all types of faults.
One method of combining the phase currents into one signal is shown below, where
the transformer is a kind of summing system for the three-phase currents.
AUTHOR: UCHIYABU 14
sequence filter used for a pilot wire relay system
In many cases, the pilot channels are leased from a common carrier telephone
company, with restrictions on the voltages that can be tolerated on the telephone
circuits.
Even if the pilot system is owned by the electric utility, there may be problems with
induced voltage from a parallel power transmission line, especially under faulted
conditions. This requires care in the installation of the pilot circuit. The pilot wires
must also be protected from lightning, which may cause considerable damage to the
terminal equipment. Moreover, the metallic connection between remote high-voltage
stations may introduce problems due to the possibly large difference in ground
potential at the two ends of the line during fault conditions.
AUTHOR: UCHIYABU 15
A Carrier-Current System is economical for distances beyond 20 km.
In this type of pilot relaying, the coupling to the power line is by means of a line
tuner and a coupling capacitor voltage transformer (CVT), with impedance matching
performed by a hybrid (HYB), which is a transformer arrangement that permits the
transmitted and received signals to be separated and also directs the output of the
transmitter to the line rather than entering the receiver.
The relays at each end of the line are assumed to have distance measuring
capability. A close-in fault at either end would be positively detected by the relay at
that end, but the relay at the opposite end would have difficulty discriminating
between faults on the protected line and those beyond the protected line. However,
if the relay close to the fault sends confirmation that the fault is indeed on the
protected line, then the opposite-end relay may be permitted to trip without delay.
This is termed permissive tripping. It has the capability of preventing long delays
in tripping faults on the protected line that might otherwise be necessary.
A wave trap is used at both ends of the protected line to prevent the carrier
frequency signals from spreading to other circuits and possibly causing false tripping
of those circuits.
The signalling for system protection may also be provided using microwave
communications between the two ends of the transmission line, with equipment
arranged as shown above.
In this arrangement, audio tone signals pass through the microwave modulator -
demodulator equipment before being transmitted at microwave frequencies to the
other end of the line.
AUTHOR: UCHIYABU 16
Usually this arrangement is called a permissive scheme since the audio-tone
signals permit the line relays at the opposite end of the line to trip when a fault is
detected.
The microwave path between the two ends of the transmission line shown above
may be quite different from the physical path of the high-voltage circuit.
Microwave systems utilise repeater stations that are almost always located at points
of the highest terrain. This permits longer "hops" between repeaters, and lower
overall cost of installation. In many cases, the intermediate stations are located on
mountain tops, or even in high-rise buildings. This may mean that the route of the
microwave signal travels much farther than the route of the transmission line being
protected. This greater length of communications travel will usually cause no
difficulty in the relaying, as long as the time delay of the signal is known and is
constant.
Directional comparison schemes can be used in microwave pilot systems with little
concern for differences in propagation delay.
AUTHOR: UCHIYABU 17
4.0 Fibre-Optic Pilot Systems
Power-line Carrier-Current, Microwave, and Fibre Optics, all share the characteristic
of providing a communications path between the relay sets at the two ends of the
transmission line. The physical apparatus and signalling equipment vary according to
the communications technology used to transmit the information. Many relays are
not affected by the method of communications and can be connected to any of the
three types of systems. The choice of pilot system used will depend on several
factors, such as the availability of fibre-optic or microwave paths, cost, reliability,
and the type of relay scheme.
There are no rigid rules that dictate the choice of communications method for pilot
relaying.
Wire Pilot
Wire pilot systems are generally applicable under the following conditions:
1. A pair of metallic communication wires is available.
2. The wire pilot pair is less than 14.5 km long.
3. The protected line is two terminal and likely to remain so, or if three terminal
each leg is less than 3.7 km long and the total line length is less than 11.1 km.
AUTHOR: UCHIYABU 18
Power Line Carrier
Power line carrier is generally applicable under the following conditions:
1. The transmission line is too long to consider wire pilot.
2. Fibre-optic systems are unavailable or too expensive.
3. Data communication is not required.
Microwave
Microwave communication is used in the protection of long transmission lines where
power line carrier does not offer enough channel capacity, or as a second
communications path in addition to power line carrier.
Fibre Optics
Fibre-optic communication is used in the protection of short transmission lines
where PLC is not suitable, or as an alternate communications path in addition to
other communications.
Example:
For a three-phase line, six pilot conductors would be required, one for each phase
CT and one for the neutral connection and two for the trip circuit.
On this basis alone, Current-Differential Relaying with six pilot wires would be
limited to very short lines.
AUTHOR: UCHIYABU 19
4. The large voltage drops in the pilot wires requiring better insulation
5. The pilot currents and voltages would be excessive for pilot circuits rented from a
telephone Company.
The Pilot Wire is used for the transmission of pilot signals that are used to provide
the protective devices with information that can be used to determine the need for
tripping the line.
Example:
2. Assume that you were at station A, where very accurate meters were available for
reading voltage, current, and the phase angle between them for the line section
AB.
3. Knowing the impedance characteristics per unit length of the line, and the
distance from A to B, you could, like a distance relay, tell the difference between
a short circuit at C in the middle of the line and at D, the far end of the line.
But you could not possibly distinguish between a fault at D and a fault at E just
beyond the breaker of the adjoining line section, because the impedance between
D and E would be so small as to produce a negligible difference in the quantities
that you were measuring.
Even though you might detect a slight difference, you could not be sure how
much of it was owing to inaccuracies, though slight, in your meters or in the
current and voltage transformers supplying your meters. And certainly, you would
have difficulties if offset current waves were involved.
Under such circumstances, you would hardly wish to accept the responsibility of
tripping your circuit breaker for the fault at D and not tripping it for the fault at E.
AUTHOR: UCHIYABU 20
4. But, if you were at station B, in spite of errors in your meters or source of supply,
or whether there were offset waves, you could determine positively whether the
fault was at D or E.
There would be practically a complete reversal in the currents, or, in other words,
approximately 1800 phase-angle difference.
5. What is needed at station A is some sort of indication when the phase angle of
the current at station B (with respect to the current at A) is different by
approximately 1800 from its value for faults in the line section A B.
6. The same need exists at station B for faults on either side of station A.
This information can be provided either by providing each station with an
appropriate sample of the actual currents at the other station, or by a signal from
the other station with its current phase angle using pilot circuits.
DC Wire-Pilot Relaying
1. Tripping Pilot
If one end cannot trip without receiving a certain signal or current sample from
the other end, the pilot is said to be a tripping pilot.
DC Wire-Pilot has advantages where the distances are short and where a line may
be tapped to other stations at one or more points.
DC Wire-Pilot Relaying is now used in very special applications.
AUTHOR: UCHIYABU 21
Schematic illustration of a DC wire-pilot relaying equipment:
D = voltage-restrained directional (mho) relay
O = over-current relay
T = auxiliary tripping relay
S = auxiliary supervising relay
PW = pilot wire
1. Over-current Relay at the station nearest to the fault will pick up if a fault occurs
in the external line circuit, but the directional relay will not close its contact
because of the direction of current flow, and the circuit will be open at that point,
thereby preventing tripping at the other stations.
2. If an internal fault occurs for which there may be no short-circuit current flow at
one of the stations, the over-current relay at that station will not pick up.
However, pilot-wire current will flow through the supervising auxiliary relay
(whose resistance is equal to that of the tripping auxiliary relay), and tripping will
still occur at the other two stations.
(The supervising relays not only provide a path for current to flow so that tripping
will occur as just described but can also be used to actuate an alarm should the
pilot wires become open circuited or short circuited.)
3. This arrangement has the characteristics of a blocking pilot where the blocking
signal is an interruption of current flow in the pilot.
However, if the over-current and the supervising relays were removed from the
circuit, it would be a tripping pilot, because tripping could not occur at any station
unless all the directional relays operated to close their contacts, and tripping
would be impossible if there was no flow of short-circuit current into one end.
2. Blocking Pilot
If the relaying equipment at one end of the line must receive a certain signal or
current sample from the other end in order to prevent tripping at the one end, the
pilot is said to be a blocking pilot.
AUTHOR: UCHIYABU 22
Schematic illustration of a DC wire-pilot scheme where information is transmitted over
the pilot:
D = voltage-restrained directional (mho) relay
B = auxiliary blocking relay
O = over-current relay
TC = trip coil
PW = pilot wire
1. The Directional Relay at each station is arranged to close its contact when short-
circuit current flows out of the line as to an external fault.
For an external fault beyond any station, the closing of the directional-relay
contact at that station will cause a d-c voltage to be impressed on the pilot that
will pick up the blocking relay at each station.
The opening of the blocking relay B contact in series with the trip circuit will
prevent tripping at each station.
For an internal fault, no directional relay will operate, and hence, no blocking
relay will pick up, and tripping will occur at all stations where there is sufficient
short-circuit current flowing to pick up the over current relay.
The reason for this is to be certain that any time the tripping relay can pick up for
an external fault the blocking relay will be sure to pick up also, or else undesired
tripping will occur.
3. With this scheme, the over-current relay must be given sufficient time delay to
make this a safe race.
An ingenious scheme can be used to avoid the necessity for adding time delay.
AC Wire-Pilot Relaying
AC Wire-Pilot Relaying is very much similar to Current-Differential Relaying.
However, in modern ac wire-pilot relaying, the magnitude of the current that flows
in the pilot circuit is limited, and only a two-wire pilot is required.
These two features make ac wire-pilot relaying economically feasible over greater
distances than current-differential relaying.
AUTHOR: UCHIYABU 23
schematic illustration of the circulating-current principle of AC wire-Pilot Relaying
Opposed-Voltage means that current does not normally circulate through the
pilot.
2. The restraining coils serve to prevent relay operation owing to imbalance currents.
3. Should a short circuit occur on the protected line section, current will circulate in
the pilot and operate the relays at both ends.
Current will also flow through the restraining coils, but, this current will not be
sufficient to prevent relay operation
The impedance of the pilot circuit will be the governing factor in this respect.
AUTHOR: UCHIYABU 24
Short circuits or open circuits in the pilot wires have opposite effects on the two
types of relaying equipment.
The application of either principle may involve certain features that provide tripping
only at the end having short-circuit-current flow.
The feature that makes AC Wire-Pilot Relaying economically feasible, for the
distances over which it is applied, is that only two pilot wires are used.
In order to use only two wires, some means are required to derive a representative
single-phase sample from the three-phase and ground currents at the ends of a
transmission line.
AUTHOR: UCHIYABU 25
Supervision of Pilot-Wire Circuits
Pilot-Wire Requirements
Because Pilot-Wire circuits are often rented from the local telephone company, and
because the telephone company imposes certain restrictions on the current and
voltage applied to their circuits, these restrictions effectively govern wire-pilot-
relaying-equipment design.
The AC equipment that have been described are suitable for telephone circuits since
they impose no more than the permissible current and voltage on the pilot, and the
wave forms are acceptable to the telephone companies.
The equipment that have been described operate without special adjustment over
pilot wires having as much as approximately 2kΩ DC loop resistance and 1.5µF
distributed shunt capacitance.
However, one should determine these limitations in any application.
AUTHOR: UCHIYABU 26
Secondary Injection Tests
Secondary Injection Tests are conducted before the Primary Injection Tests.
It is essential that the pilot wires are connected correctly and the remote end relay is
de-energised, as would be the case with an isolated feeder.
If, during maintenance tests, it is impracticable to de-energise the line, Secondary
Injection Testing can only be carried out provided the secondaries of both groups of
line-end CTs are terminated, and the relay summation transformer input of the
remote-end relay left open-circuit.
The following tests assume initial commissioning tests are being carried out on a de-
energised feeder.
1000–pilotloopresistance
pilot padding resistance = ohms
2
AUTHOR: UCHIYABU 27
5. Insulation Resistance Tests
With the pilots isolated from the relay circuits at both ends of the feeder, measure
the insulation resistance between both pilot wires and between each pilot wire
and earth.
Measurements will depend on pilot length and type, but a figure in excess of 1MΩ
at 500V would normally be accepted as satisfactory.
Lower insulation results should be compared with insulation data for the type of
cable used.
Primary injection testing is, however, the only way to prove correct
installation and operation of the whole of a protection scheme.
Primary Injection Tests are always carried out after Secondary Injection
Tests, to ensure that problems are limited to the VTs and CTs involved, plus
associated wiring, all other equipment in the protection scheme having been
proven satisfactory from the Secondary Injection Tests.
Therefore, primary injection is usually carried out bt means of a Portable Injection
Transformer.
AUTHOR: UCHIYABU 28
These are connected in series or in parallel according to the current required and
the resistance of the primary circuit. Outputs of 10V and 100A can be obtained.
Alternatively, modern PC-controlled test sets have power amplifiers capable of
injecting currents up to about 200A for a single unit, with higher current ratings
being possible by using multiple units in parallel.
1. CT Ratio Check
Connect ammeters as shown below and apply a known level of current (say 50-
100% of CT rating) through the A phase CT.
Current is passed through the primary conductors and measured on the test set
ammeter, A1 in the figure below.
The secondary current is measured on the ammeter A 2 or relay display, and the
ratio of the value on A 1 to that on A2 should closely approximate to the ratio
marked on the current transformer nameplate.
AUTHOR: UCHIYABU 29
2. CT Polarity Check
If the equipment includes directional, differential or earth fault relays, the polarity
of the main current transformers must be checked.
It is not necessary to conduct the test if only overcurrent relays are used.
The circuit for checking the polarity with a single-phase test set is shown in figure
below.
A short-circuit is placed across the phases of the primary circuit on one side of the
current transformers while single-phase injection is carried out on the other side.
The ammeter connected in the residual circuit, o relay display, will give a reading
of a few milliamperes with rated current injected if the Current Transformers are of
correct polarity.
A reading proportional to twice the primary current will be obtained if they are of
wrong polarity.
Connect the primary injection test set across the A phase CT primary.
Monitor the CT secondary current into relay terminal.
Increase the injected current until the local relay operates
AUTHOR: UCHIYABU 30
Record both primary and secondary pick up levels.
With the DC trip circuit links/fuses replaced, the circuit breaker should be tripped by
actuating the relay.
This can be done by carefully actuating the output relay.
AUTHOR: UCHIYABU 31