EM24
Energy analyzer for three-phase systems

Benefits
• Time saving set-up, by frontal joystick and selector.
• Error-proof installation, by self-power supply and
phase sequence detection.
• Easy variable scrolling, by means of the front joystick.
• Wide interfacing capability, choosing among 2 pulse
outputs, the RS485, the M-Bus, Dupline or the Ethernet
communication port.
• Extended energy measurements, using total/partial or
total/multi-tariff metering.
• Flexible installation, by means of the direct connection
up to 65 A or the connection of 5 A current transformers.
• Extended alarm control on any available variable by
means of up to two digital outputs.
• Legal metrology, guaranteed by the MID approval

Description

Three-phase energy analyzer for DIN-rail mounting


with configuration joystick, frontal selector and
LCD display. Direct connection up to 65A or
via current and voltage transformers. It can be
equipped with 2 digital outputs (pulse transmission
or alarm function). In alternative the Modbus RTU
or Dupline communication port and 3 digital inputs,
the M-Bus communication, or the Modbus TCP/IP
Ethernet ports are available.

Applications

EM24 is perfect solution in any application, specially in building and industrial automation, for cost allocation,
and for energy efficiency monitoring, legal submetering in commercial and residential installations, and
wherever energy and main electrical variables monitoring is required.
EM24 is particularly suited for:
• energy efficiency monitoring
• cost allocation
• fiscal/legal sub-billing

Main functions

• Measurement of energy consumption and main electrical variables of single-phase, two-phase or three-phase loads.
• Display of single phase measurements and total measurements.
• Transmission of data via serial communication (Modbus RTU, M-Bus or Dupline) or Ethernet (Modbus TCP/IP).
• Transmission of power consumption via pulse output (optional).
• Easy connection function

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 1


EM24


Main features

• Energy measurements: total and partial kWh and kvarh or based on 4 different tariffs; single phase measurements
• Gas, cold water, hot water, kWh remote heating measurements
• TRMS measurements of distorted sine waves (voltages/currents)

Structure

Fig. 1 Direct connection Fig. 2 CT connection

Area Description
A LCD display
B Voltage/current connections
C Joystick
D Selector with pin for MID seal (programming block)
E Inputs/outputs or communication port
F Pins for MID seal (protection covers included)

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 2


EM24


Features

General

Protection degree Front: IP50. Terminals: IP20


Screw terminals
Terminals AV2, AV9: Max.: 16 mm2, min.: 2.5 mm2 (by cable lug)
AV5, AV6: Max.: 1.5 mm2
Overvoltage category Cat. III
Pollution degree 2
Noise rejection (CMRR) 100 dB, from 42 to 62 Hz
Mounting DIN rail
Weight 400 g (packaging included)

Environmental specifications

Operating temperature From -25 to +55 °C/from -13 to +131 °F


Storage temperature From -30 to +70 °C/from -22 to +158 °F

NOTE: R.H. < 90 % non-condensing @ 40 °C / 104 °F.

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 3


EM24


Input and output insulation

Communi-
Open Auxil-
Measuring Relay cation port Ethernet Self power
Type collector Dupline iary power
inputs outputs and digital port supply
outputs supply
inputs
Measuring
- 4 kV 4 kV 4 kV 4 kV 4 kV 0 kV 4 kV
inputs
Relay out-
4 kV - - - - - 4 kV 4 kV
puts
Open
collector 4 kV - - - - - 4 kV 4 kV
outputs
Communi-
cation port
4 kV - - - - - 4 kV 4 kV
and digital
inputs
Dupline 4 kV - - - - - 4 kV 4 kV
Ethernet
4 kV - - - - - 4 kV -
port
Self power
0 kV 4 kV 4 kV 4 kV 4 kV 4 kV - -
supply
Auxiliary
power sup- 4 kV 4 kV 4 kV 4 kV 4 kV - - -
ply

Compatibility and conformity

Directives 2011/65/EU (RoHs)


Electromagnetic compatibility (EMC) - emissions and immunity: EN 62052-11
Electrical safety: EN 61010-1, EN 50470-1 (MID)
Standards
Accuracy: EN 62053-21, EN 62053-23, EN 50470-3 (MID)
Pulse outputs: IEC 62053-31, DIN 43864

Approvals

(AV5, AV6 only, except M2)

MID (PF only)

Electrical specifications

Voltage - MID models


Voltage inputs AV2 AV9 AV5 AV6
Voltage connection Direct
Rated voltage L-N (from Un min to Un max) 133 to 230 V 230 V 230 V 57.7 to 120 V
Rated voltage L-L (from Un min to Un max) 230 to 400 V 400 V 400 V 100 to 208 V
Voltage tolerance (*) -20%, +15%
Overload (**) Continuous: 1.15 Un max
Input impedance Refer to “Power supply”
Frequency 50 Hz

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 4


EM24


Voltage - Non MID models (according to IEC 62052-11)
Voltage inputs AV2 AV9 AV5 AV6
Voltage connection Direct Direct or via VT
Rated voltage L-N (from Un All models except E1: 133 to 230 V 230 V 230 V 57.7 to 120V
min to Un max) E1 model: 120 to 277 V / 120 to 277 V /
Rated voltage L-L (from Un All models except E1: 230 to 400 V 400 V 400 V 100 to 208 V
min to Un max) E1 model: 208 to 480 V / 208 to 480 V /
Voltage tolerance (*) -20%, +15%
Continuous: 1.15 (Un
Overload (**) Continuous: 1.2 (Un max)
max)
Input impedance Refer to “Power supply” >1600 kΩ
Frequency 50/60 Hz

Voltage - Non MID models (according to UL 508)


Voltage inputs AV2 AV9 AV5 AV6
Voltage connection Direct Direct or via VT
Rated voltage L-N (from Un min to Un max)
/ / 230 to 346 V 57.7 to 144 V
All models except E1, M2
Rated voltage L-L (from Un min to Un max)
/ / 400 to 600 V 100 to 250 V
All models except E1, M2
Voltage tolerance (*) -20%, +15%
Overload (**) Continuous: 1.15 (Un max)
Input impedance Refer to “Power supply” >1600 kΩ
Frequency 50/60 Hz

(*) reference range for stated accuracy


(**) max reference for no instrument damage
Current
Current inputs AV2 AV9 AV5 AV6
Current connection Direct Via CT
Rated current (In) - 5A
Base current (lb) 10 A -
Minimum current (lmin) 0.5 A 0.05 A
Maximum current (lmax) 65 A 10 A
Start-up current (lst) 0.04 A 0.01 A
Continuous: 65 A @50 Hz Continuous: 10 A @50 Hz
Overload
For 10 ms: 1950 A @ 50 Hz For 500 ms: 200 A @ 50 Hz
Input impedance < 1.7 VA < 0.7 VA
4 3
Crest factor
(Imax peak 92 A) (Imax peak 15 A)

Maximum CTxVT ratio


Current inputs AV2 AV9 AV5 AV6
Non-MID models except E1 - - 4629 14529
Non-MID E1 model - - 6975 -
MID models - - 3150 -

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 5


EM24


Power supply

Non MID models


AV2 AV9 AV5 AV6
D: 115/230 V ac, +/-15%, 50/60Hz
L: 24 to 48 V ac/dc; ac: +/-15%,
Type Self power supply
50/60Hz, dc: +/-20%
X (E1 only): Self power supply
IS and DP: < 12VA/2W
D: < 2.5VA/1.5W
Consumption E1: 4.7VA/< 2.9W
L: < 2.5VA/1W
Others: < 20VA/1W

MID models
AV2 AV9 AV5 AV6
Type Self power supply
IS and DP: < 12VA/2W
<4.5VA/2.9W
Consumption E1: < 4.7VA/2.9 W
E1: < 4.7VA/2.9 W
Others: < 20VA/1W

Measurements

Method TRMS measurements of distorted waveforms


1600 samples/s @50 Hz
Sampling
1900 samples/s @60 Hz

Available measurements

Active energy Unit System Phase Note


Imported (+) Total kWh+ ● ●
Imported (+) partial kWh+ ● -
Exported (-) Total kWh- ● -
Imported (+) by tariff kWh+ ● - T1, T2, T3, T4

Reactive energy Unit System Phase


Imported (+) Total kvarh+ ● -
Imported (+) partial kvarh+ ● -
Exported (-) Total kvarh- ● -
Imported (+) by tariff kvarh+ ● -

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 6


EM24


Electrical variable Unit System Phase
Voltage L-N V ● ●
Voltage L-L V ● ●
Current A - ●
DMD MAX A ● -
Active power kW ● ●
DMD kW ● -
DMD MAX kW ● -
Apparent power kVA ● ●
DMD kVA ● -
DMD MAX kVA ● -
Reactive power kvar ● ●
Power factor PF ● ●
Frequency Hz ● -
Run hour meter h ● -

Measurement accuracy

Current AV2 AV9 AV5 AV6


From 0.5 A to 2 A ±(0.5% rdg + 3dgt) - -
From 2 A to 65 A ±(0.5% rdg + 1dgt) - -
From 0.05 A to 1 A - - ±(0.5% rdg + 3dgt)
From 1 A to 10 A - - ±(0.5% rdg + 1dgt)

Phase-phase voltage AV2 AV9 AV5 AV6


In the range Un ±(1% rdg +1dgt)

Phase-neutral voltage AV2 AV9 AV5 AV6


In the range Un ±(0.5% rdg +1dgt)

Active and apparent power AV2 AV9 AV5 AV6


From 1.0 A to 65.0 A (PF=0.5L,
±(1% rdg +1dgt) -
1, 0.8C)
From 0.5 A to 1.0 A (PF=1) ±(1.5% rdg +1dgt) -
From 0.25 A to 10 A (PF=0.5L,
- ±(1% rdg +1dgt)
1, 0.8C)
From 0.05 A to 0.25 A (PF=1) - ±(1.5% rdg +1dgt)

Reactive power AV2 AV9 AV5 AV6


From 1.0 A to 2.0 A (sinϕ=0.5L,
0.5C) ±(2.5% rdg + 1 dgt) -
From 0.5 A to 1.0 A (sinϕ=1)
From 2.0 A to 65.0 A
(sinϕ=0.5L, 0.5C) ±(2% rdg + 1 dgt) -
From 1.0 A to 65.0 A (sinϕ=1)
From 0.25 A to 0.5 A
(sinϕ=0.5L, 0.5C) - ±(2.5% rdg + 1 dgt)
From 0.1 A to 0.25 A (sinϕ=1)
From 0.5 A to 10 A (sinϕ=0.5L,
0.5C) - ±(2% rdg + 1 dgt)
From 0.25 A to 10 A (sinϕ=1)
Class 1 (EN62053-21)
Active energy
Class B (EN50470-3) (MID)
Reactive energy Class 2 (EN62053-23)

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 7


EM24


Frequency
From 45 to 65 Hz ±0.1 Hz

Display

Type LCD
Refresh time < 750 ms
3 rows:
1st: 8 digits (7 mm)
Description
2nd: 4 digits (7 mm)
3rd: 4 digits (7 mm)
Instantaneous: 4 digits, min: 0.000, max: 9999
Variable readout
Energy: 8 digits (imported), 7 digits (exported), min: 0.00, max: 99 999 999

LED

Model CT*VT Weight (kWh per pulse)


≤7 0.001
> 7 ≤ 70.0 0.01
AV5/AV6
> 70 ≤ 700.0 0.1
> 700 1
AV2/AV9 N/A 0.001

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 8


EM24


Digital outputs/inputs

Digital outputs: static output (O2)

Connection type Screw terminals


Maximum number of outputs 2
Type Open collector
Function Pulse output or alarm output
VON 1.2 V dc, max. 100 mA
Features
VOFF 30 V dc max
Output function (pulse/alarm)
Output normal status
Pulse weight (0.001 to 10 kWh/pulse or kvarh/pulse)
Configuration parameters
Pulse duration (30 or 100 ms)
Linked variable
Alarm delay
Configuration mode Via keypad

Digital outputs: relay output (R2)

Connection type Screw terminals


Maximum number of outputs 2
Type relay (SPST)
Function Pulse output or alarm output
AC-1: 5 A@250 V ac
DC-12: 5 A@24 V dc
Features
AC-15: 1.5 A @ 250 V ac
DC-13: 1.5 A @ 24 V dc
Output function (pulse/alarm)
Output normal status
Pulse weight (0.001 to 10 kWh/pulse or kvarh/pulse)
Configuration parameters
Pulse duration (30 or 100 ms)
Linked variable
Alarm delay
Configuration mode Via keypad

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 9


EM24


Digital inputs (IS, DP)

Number of inputs 3
Remote status
DMD synchronization
Functions
Pulse counting
Tariff management
Frequency 20Hz max, duty cycle 50%
Pulse weight From 0.001 to 999.9 m3 or kWh per pulse
Contact measuring voltage 5 V dc +/- 5%
Contact measuring current 10 mA max
Input impedance 680Ω
Open contact resistance ≥500 kΩ
Closed contact voltage ≤100 Ω
Input function
Configuration parameters
Pulse weight
Configuration mode Via joystick or UCS software (IS)

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 10


EM24


Communication ports

RS485 port (IS)

Protocol Modbus RTU


Devices on the same bus Max 160 (1/5 unit load)
Communication type Multidrop, bidirectional
Connection type 2 wires
Modbus address (from 1 to 247)
Configuration parameters Baud rate (4.6/9.6 kbps)
1 stop bit, no parity
Refresh time < 750 ms
Configuration mode Via keypad or UCS software

M-Bus (M1, M2)

M1: M-Bus according to EN13757-3:2005


Protocol
M2: M-Bus according to EN13757-3:2013
Driver input capability 1 unit load
Communication type One-drop, directional
Connection type 2 wires
Primary address (1 to 247)
Configuration parameters
Baud rate (0.3/ 2.4 / 9.6 kbps)
Configuration mode Via keypad

Ethernet port (E1)

Protocols Modbus TCP/IP


Client connections Maximum 5 simultaneously
Connection type RJ45 connector (10 Base-T, 100 Base-TX), maximum distance 100 m
IP address
Subnet mask
Configuration parameters Gateway
TCP/IP port
DHCP enabling
Configuration mode Via keypad or UCS software

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 11


EM24


Dupline port (DP)

Protocol Dupline
Connection type 2 wires
Dupline data format 3 1/2 dgt BCD
Full scale value selectable from 1.999 to 1999 M
Used channels depending on the number of variables
A1 to A4
G1 to H8 (1st group of 16 variables)
I1 to J8 (2nd group of 16 variables)
Multiplexer
K1 to L8 (3th group of 16 variables)
M1 to N8 (4th group of 16 variables)
O1 to P8 (5th group of 16 variables)
Available variables all, except for the “max” variables
Dupline inputs
Dupline counters
Configuration parameters
Dupline analogue variables
Dupline output
Configuration mode Via keypad

Counters
Function Multiplexer for counter values
Number of counters 6 per instrument, 128 per network
Counter range 0... 99 999 999
Used channels B to F
Multiplexer B2 to B8
Reset B1
Value C1 to F8
Counter reset enable/disable function for all the counters
kWh tot, -kWh tot,
kvarh tot, -kvarh tot,
kWh t1, kWh t2,
kWh L1, kWh L2, kWh L3,
Available counters
counter dig. in. 1,
counter dig. in. 2,
counter dig. in. 3,
Run hour meter

Input (synchro/tariff)
Function Monostable (push-button), realtime
Used channels A5
selectable:
• none
Working mode
• Wdmd synchronization
• total and partial energy meter (kWh, kvarh) managed by time periods (t1-t2).

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 12


EM24


Outputs (alarms)
Function monostable (push-button)
selectable (A1 to P8). No control that the selected channels are not used for counters
Used channells
or analog variables
Number of alarms 2 per instrument
Alarm modes up alarm, down alarm
Set-point adjustment from 0 to 100% of the display scale
Hysteresis from 0 to full scale
On-time delay 0 to 255 s
Output status normally energised
Available variables all, except for the “max” variables

Analogue variables
Function Multiplexer for analogue values
Number of variables 8 per instrument, 80 per network

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 13


EM24


Connection Diagrams

Three-phase with neutral (4-wire)

Fig. 3 AV2, AV9 Fig. 4 AV5, AV6 Fig. 5 AV6

Fig. 6 AV5, AV6 balanced load

Three-phase without neutral (3-wire)

Fig. 7 AV2, AV9 (except IS, R2) Fig. 8 AV5, AV6 Fig. 9 AV5, AV6

Fig. 10 AV6 Fig. 11 AV6 Fig. 12 AV5, AV6 balanced load

Fig. 13 AV6 balanced load

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 14


EM24

Two-phase system with neutral (3-wire)

Fig. 14 AV2, AV9 Fig. 15 AV5, AV6 Fig. 16 AV6

Single-phase (2-wire)

Fig. 17 AV2, AV9 (except IS, R2) Fig. 18 AV2, AV9 (IS, R2) Fig. 19 AV5, AV6

Fig. 20 AV6

Power supply

Fig. 21 D option. F = 250 V, 50 mA Fig. 22 D option. F = 250 V, 100 Fig. 23 L option. F = 250 V, 200
mA mA

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 15


EM24

Static outputs and relay outputs

Fig. 24 Static outputs, GND refer- Fig. 25 Static outputs, VDC refer- Fig. 26 Relay outputs
ence ence

Digital inputs, RS485 and Dupline ports

Fig. 27 Digital inputs Fig. 28 RS485 port Fig. 29 Dupline port

M-Bus

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 16


EM24


MID connection diagrams

Three-phase with neutral (4-wire)

Fig. 30 AV2, AV9 Fig. 31 AV5, AV6

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 17


EM24


References

Order code

Non MID models


Component name/part number I/O communication Voltage inputs Current inputs Power supply
230V L-N
EM24DIN AV5 3D XX X none 5(10) A via CT 115/230 V ac
400V L-L
230V L-N Self power sup-
EM24DIN AV9 3X XX X none 10 (65) A
400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
230V L-N
EM24DIN AV5 3D R2 X 2 relay outputs 5(10) A via CT 115/230 V ac
400V L-L
230V L-N Self power sup-
EM24DIN AV9 3X R2 X 2 relay outputs 10 (65) A
400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
230V L-N
EM24DIN AV5 3D O2 X 2 static outputs 5(10) A via CT 115/230 V ac
400V L-L
230V L-N From 24 to 48 V
EM24DIN AV5 3L O2 X 2 static outputs 10 (65) A
400V L-L ac/dc
From 57.7 to 120
V L-N
EM24DIN AV6 3D O2 X 2 static outputs 5(10) A via CT 115/230 V ac
From 100 to 208
V L-L
From 57.7 to 120
V L-N From 24 to 48 V
EM24DIN AV6 3L O2 X 2 static outputs 5(10) A via CT
From 100 to 208 ac/dc
V L-L
From 133 to 230
V L-N Self power sup-
EM24DIN AV2 3X O2 X 2 static outputs 10 (65) A
From 230 to 400 ply
V L-L
230V L-N Self power sup-
EM24DIN AV9 3X O2 X 2 static outputs 10 (65) A
400V L-L ply

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 18


EM24


Component name/part number I/O communication Voltage inputs Current inputs Power supply
230V L-N
EM24DIN AV5 3D DP X 3 digital inputs + Dupline 5(10) A via CT 115/230 V ac
400V L-L
230V L-N From 24 to 48 V
EM24DIN AV5 3L DP X 3 digital inputs + Dupline 5(10) A via CT
400V L-L ac/dc
From 57.7 to 120
V L-N
EM24DIN AV6 3D DP X 3 digital inputs + Dupline 5(10) A via CT 115/230 V ac
From 100 to 208
V L-L
From 57.7 to 120
V L-N From 24 to 48 V
EM24DIN AV6 3L DP X 3 digital inputs + Dupline 5(10) A via CT
From 100 to 208 ac/dc
V L-L
From 133 to 230
V L-N Self power sup-
EM24DIN AV2 3X DP X 3 digital inputs + Dupline 10 (65) A
From 230 to 400 ply
V L-L
230V L-N Self power sup-
EM24DIN AV9 3X DP X 3 digital inputs + Dupline 10 (65) A
400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
3 digital inputs + RS485 230V L-N
EM24DIN AV5 3D IS X 5(10) A via CT 115/230 V ac
Modbus RTU 400V L-L
3 digital inputs + RS485 230V L-N From 24 to 48 V
EM24DIN AV5 3L IS X 5(10) A via CT
Modbus RTU 400V L-L ac/dc
From 57.7 to 120
3 digital inputs + RS485 V L-N
EM24DIN AV6 3D IS X 5(10) A via CT 115/230 V ac
Modbus RTU From 100 to 208
V L-L
From 57.7 to 120
3 digital inputs + RS485 V L-N From 24 to 48 V
EM24DIN AV6 3L IS X 5(10) A via CT
Modbus RTU From 100 to 208 ac/dc
V L-L
From 133 to 230
3 digital inputs + RS485 V L-N Self power sup-
EM24DIN AV2 3X IS X 10 (65) A
Modbus RTU From 230 to 400 ply
V L-L
3 digital inputs + RS485 230V L-N Self power sup-
EM24DIN AV9 3X IS X 10 (65) A
Modbus RTU 400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
From 120 to 277
V L-N Self power sup-
EM24DIN AV5 3X E1 X Ethernet Modbus TCP/IP 5(10) A via CT
From 208 to 480 ply
V L-L
From 120 to 277
V L-N Self power sup-
EM24DIN AV2 3X E1 X Ethernet Modbus TCP/IP 10 (65) A
From 208 to 480 ply
V L-L

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 19


EM24


Component name/part number I/O communication Voltage inputs Current inputs Power supply
M-Bus according to EN 230V L-N
EM24DIN AV5 3D M1 X 5(10) A via CT 115/230 V ac
13757-3 (2005) 400V L-L
M-Bus according to EN 230V L-N From 24 to 48 V
EM24DIN AV5 3L M1 X 5(10) A via CT
13757-3 (2005) 400V L-L ac/dc
From 57.7 to 120
M-Bus according to EN V L-N
EM24DIN AV6 3D M1 X 5(10) A via CT 115/230 V ac
13757-3 (2005) From 100 to 208
V L-L
From 57.7 to 120
M-Bus according to EN V L-N From 24 to 48 V
EM24DIN AV6 3L M1 X 5(10) A via CT
13757-3 (2005) From 100 to 208 ac/dc
V L-L
From 133 to 230
M-Bus according to EN V L-N Self power sup-
EM24DIN AV2 3X M1 X 10 (65) A
13757-3 (2005) From 230 to 400 ply
V L-L
M-Bus according to EN 230V L-N Self power sup-
EM24DIN AV9 3X M1 X 10 (65) A
13757-3 (2005) 400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
M-Bus according to EN 230V L-N
EM24DIN AV5 3D M2 X 5(10) A via CT 115/230 V ac
13757-3 (2013) 400V L-L
M-Bus according to EN 230V L-N From 24 to 48 V
EM24DIN AV5 3L M2 X 5(10) A via CT
13757-3 (2013) 400V L-L ac/dc
From 57.7 to 120
M-Bus according to EN V L-N
EM24DIN AV6 3D M2 X 5(10) A via CT 115/230 V ac
13757-3 (2013) From 100 to 208
V L-L
From 57.7 to 120
M-Bus according to EN V L-N From 24 to 48 V
EM24DIN AV6 3L M2 X 5(10) A via CT
13757-3 (2013) From 100 to 208 ac/dc
V L-L
From 133 to 230
M-Bus according to EN V L-N Self power sup-
EM24DIN AV2 3X M2 X 10 (65) A
13757-3 (2013) From 230 to 400 ply
V L-L
M-Bus according to EN 230V L-N Self power sup-
EM24DIN AV2 3X M2 X 10 (65) A
13757-3 (2013) 400V L-L ply

MID models
Component name/part number I/O communication Voltage inputs Current inputs Power supply
EM24DIN AV5 3X XX PFA 230V L-N Self power sup-
none 5(10) A via CT
EM24DIN AV5 3X XX PFB 400V L-L ply
EM24DIN AV2 3X XX PFA 230V L-N Self power sup-
none 10 (65) A
EM24DIN AV2 3X XX PFB 400V L-L ply
EM24DIN AV9 3X XX PFA 230V L-N Self power sup-
none 10 (65) A
EM24DIN AV9 3X XX PFB 400V L-L ply

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 20


EM24


Component name/part number I/O communication Voltage inputs Current inputs Power supply
EM24DIN AV5 3X O2 PFA 230V L-N Self power sup-
2 static outputs 5(10) A via CT
EM24DIN AV5 3X O2 PFB 400V L-L ply
EM24DIN AV2 3X O2 PFA 230V L-N Self power sup-
2 static outputs 10 (65) A
EM24DIN AV2 3X O2 PFB 400V L-L ply
EM24DIN AV9 3X O2 PFA 230V L-N Self power sup-
2 static outputs 10 (65) A
EM24DIN AV9 3X O2 PFB 400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
EM24DIN AV5 3X DP PFA 230V L-N Self power sup-
3 digital inputs + Dupline 5(10) A via CT
EM24DIN AV5 3X DP PFB 400V L-L ply
EM24DIN AV2 3X DP PFA 230V L-N Self power sup-
3 digital inputs + Dupline 10 (65) A
EM24DIN AV2 3X DP PFB 400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
EM24DIN AV5 3X IS PFA 3 digital inputs + RS485 230V L-N Self power sup-
5(10) A via CT
EM24DIN AV5 3X IS PFB Modbus RTU 400V L-L ply
EM24DIN AV2 3X IS PFA 3 digital inputs + RS485 230V L-N Self power sup-
10 (65) A
EM24DIN AV2 3X IS PFB Modbus RTU 400V L-L ply
EM24DIN AV9 3X IS PFA 3 digital inputs + RS485 230V L-N Self power sup-
10 (65) A
EM24DIN AV9 3X IS PFB Modbus RTU 400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
EM24DIN AV5 3X E1 PFA 230V L-N Self power sup-
Ethernet Modbus TCP/IP 5(10) A via CT
EM24DIN AV5 3X E1 PFB 400V L-L ply
EM24DIN AV2 3X E1 PFA 230V L-N Self power sup-
Ethernet Modbus TCP/IP 10(65) A
EM24DIN AV2 3X E1 PFB 400V L-L ply

Component name/part number I/O communication Voltage inputs Current inputs Power supply
EM24DIN AV5 3X M1 PFA M-Bus according to EN 230V L-N Self power sup-
5(10) A via CT
EM24DIN AV5 3X M1 PFB 13757-3 (2005) 400V L-L ply
EM24DIN AV2 3X M1 PFA M-Bus according to EN 230V L-N Self power sup-
10(65) A
EM24DIN AV2 3X M1 PFB 13757-3 (2005) 400V L-L ply

14/09/2018 EM24 DS ENG Carlo Gavazzi Controls S.p.A. 21


EM24


Further reading

Information Where to find it


User manual - E1 www.productselection.net/MANUALS/UK/em24_E1_im_use.pdf
Installation instruction - E1 www.productselection.net/MANUALS/UK/em24_E1_im_inst.pdf
Instruction manual - M2 www.productselection.net/MANUALS/UK/em24M2_im.pdf
Instruction manual - other versions www.productselection.net/MANUALS/UK/em24_im.pdf
Instruction manual - other versions MID www.productselection.net/MANUALS/UK/em24_mid_im.pdf

CARLO GAVAZZI compatible components

Purpose Component name/part number Notes


Monitor data from several analyzers VMU-C See relevant datasheet

COPYRIGHT ©2018
Content subject to change. Download the PDF: www.productselection.net