SG350HX: Multi-MPPT String Inverter For System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SG350HX

Multi-MPPT String Inverter for 1500 Vdc System


Preliminary

HIGH YIELD Low Cost


Up to 16 MPPTs with max. efficiency 99% Q at night function, save investment
20A per string, compatible with 500Wp+ module Power line communication (PLC)
Data exchange with tracker system, improving yield Smart IV Curve diagnosis*, active O&M

Grid Support PROVEN SAFETY


SCR≥1.16 stable operation in extremely weak grid 2 strings per MPPT, no fear of string reverse connection
Reactive power response time <30ms Integrated DC switch, automatically cut off the fault
Compliant with global grid code 24h real-time AC and DC insulation monitoring

CIRCUIT DIAGRAM EFFICIENCY CURVE

100%

DC1 MPPT 98%


(1) L1
96%
Efficiency

DC AC AC AC
Filter Relay EMI L2
EMI
94% Vdc=860V
MPPT L3
DC12 (12) Vdc=1160V
92% Vdc=1300V
Current DC DC SPD DC Bus Inverter AC SPD PE 90%
Monitoring switch circuit 5% 20% 30% 50% 100%
Normalized Output Power

EUROPE © 2021 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 1.1.1
Type designation SG350HX
Input (DC)
Max. PV input voltage 1500 V
Min. PV input voltage / Startup input voltage 500 V / 550 V
Nominal PV input voltage 1080 V
MPP voltage range 500 V – 1500 V
MPP voltage range for nominal power 860 V – 1300 V
No. of independent MPP inputs 12 (Optional: 14 / 16)
Max. number of input connector per MPPT 2
Max. PV input current 12 * 40 A (Optional: 14 * 30 A / 16 * 30 A)
Max. DC short-circuit current per MPPT 60 A
Output (AC)
AC output power 352 kVA @ 30 ℃ / 320 kVA @40 ℃ / 295 kVA @50 ℃
Max. AC output current 254 A
Nominal AC voltage 3 / PE, 800 V
AC voltage range 640 – 920 V
Nominal grid frequency / Grid f requency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Ajustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases 3/3
Efficiency
Max. efficiency / European efficiency / CEC 99.01 % / 98.8 % / 98.5 %
Protection
DC reverse connection protection Yes
AC short circuit protection Yes
Leakage current protection Yes
Grid monitoring Yes
Ground fault monitoring Yes
DC switch/ AC switch Yes / No
PV String current monitoring Yes
Q at night function Yes
Anti-PID and PID recovery function Optional
Overvoltage protection DC Type II / AC Type II
General Data
Dimensions (W*H*D) 1136*870*361 mm (44.7'' * 34.3'' * 14.2'')
Weight ≤110 kg (≤242.5 lbs)
Isolation method Transformerless
Ingress protection rating IP66 (NEMA 4X)
Night power consumption <6W
Operating ambient temperature range -30 to 60 ℃ (-22 to 140 ℉)
Allowable relative humidity range (non-condensing) 0 – 100 %
Cooling method Smart forced air cooling
Max. operating altitude 4000 m (> 3000 m derating) / 13123 ft (> 9843 ft derating)
Display LED, Bluetooth+APP
Communication RS485 / PLC
DC connection type MC4-Evo2 (Max. 6 mm², optional 10mm² / Max. 10AWG, optional 8AWG )
AC connection type Support OT/DT terminal (Max. 400 mm² / 789 Kcmil)
IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018,
Compliance VDE-AR-N 4120:2018, EN 50549-1/2, UNE 206007-1:2013, P.O.12.3, UTE C15-
712-1:2013, UL1741, UL1741SA, IEEE1547, IEEE1547.1, CSA C22.2 107.1-01-2001,
California Rule 21, UL1699B
Grid support Q at night function, LVRT, HVRT, active & reactive power control and power
ramp rate control, Q-U control, P-f control

*: Only compatible with Sungrow logger and iSolarCloud

© 2021 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 1.1.1 EUROPE