CT1 CORE-3
CT DATA FOR MFAC14- 87REF
DESCRIPTION
3000-2500-2000-1500-1250-1000-750/1A
CLASS:TPS, Rct<=6.7Ω, VK>=5500V, Im<=50mA
BY
DATE
NO.
REVISIONS
DRAWN
BY:-
DATE:-
CHECKED
BY:-
DATE:-
OPRG. DEPT
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
AS BUILT BY DATE 12/30/99
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
RIYADH SAUDI ARABIA JOB ORDER NO. DWG. CONT. SHT.
CERT'D
APPR'D National Grid Saudi Arabia
1 SYSTEM PARAMETERS
CHK'D
Nominal Voltage : 110 kV
Max. SC current capacity : 40 kA
System frequency : 60 Hz
Resistivity of the Copper
ρ75 = ρ20 [(1 + α (θ - 20)]
DESCRIPTION
where:
ρ20 Resistivity of the copper at 20 deg c = 0.01786 Ωmm2/m
α Cofficient of resistance = 0.00393
ρ75 Resistivity of the copper at 75 deg c = 0.021720439 Ωmm2/m
BY
DATE
NO.
REVISIONS
DRAWN
BY:-
DATE:-
CHECKED
BY:-
DATE:-
OPRG. DEPT
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
AS BUILT BY DATE 12/30/99
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
RIYADH SAUDI ARABIA JOB ORDER NO. DWG. CONT. SHT.
CERT'D
APPR'D National Grid Saudi Arabia
1.1 CT Designation : 87REF
CHK'D
Application : Restricted Earth Fault
Relays : MFAC14
System Data
System Voltage 110 kV
System Frequency 60 Hz
System fault level 40 kA
Time constant 80 ms
CT Data
DESCRIPTION
CT Ratio 3000-2500-2000-1500-1250-1000-750/1 A
CT used tap 3000 A
Class TPS
CT resistance (Rct) 6.7 Ω
CT secondary 1 A
CT knee voltage 5550 V
CT mag current 50 mA
Cable data
Cable Length (lwire1) 240 m
Cross Section (awire1) 4 mm2
Resistivity at 75 deg C (ρ75) 0.021720439 Ωmm2/m
Eff. Wire length p.u. (k) 2
BY
RLEAD1 = (k*lwire1*pcu)/awire1
DATE
= 2.607 Ω
Relay Data
NO.
Relay Description Relay Type Relay Burden Make
REVISIONS
Restricted Earth Fault (REF) MFAC14 0.00 VA Alstom
DRAWN
BY:-
DATE:- Other Burden 0.00 VA
CHECKED
BY:-
DATE:-
OPRG. DEPT Power Transformer Data:
BY SMVA = 502 MVA
DATE:- %IMPED = 19.50%
ENG'G. DEPT. IFL = 2634.82 A
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
AS BUILT BY DATE 12/30/99
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
RIYADH SAUDI ARABIA JOB ORDER NO. DWG. CONT. SHT.
CERT'D
APPR'D National Grid Saudi Arabia
CT requirement for MFAC14
Requirement No.-1
CHK'D
To prevent maloperation of the relay during saturation of the CT on external fault, the relay setting Vs
must be greater than the voltage produced by the maximum secondary flowing through the cable resistance.
Vs > Ithrough * ( 1∕ T ) * ( RLEAD + Ri )
Requirement No.-2
For appropriate application of the relay, the min. primary fault current required to operate
through fault current the relay should be greaer than 10% of the nominal primary full load current.
Iop ≥ 0.1 * IFL
Requirement No.-3
The Knee point voltage must be greater than twice the voltage setting of the relay.
DESCRIPTION
Vkp ≥ 2 * VS
Where,
Iop = Minimum relay primary operating current
Vkp = Knee point voltage of the CT
IFL = Nominal primary full load current
Vs = Relay voltage setting
Ithrough = Maximum through fault current
T = Turns ratio of CT
RLEAD = Connecting cable resistance
Ri = Internal resistance of the CT
IMAG. = CT mag. Current at Vs.
CT Adequacy Check
BY
Requirement No.-1
DATE
Vs > Ithrough * ( 1∕ T ) * ( RLEAD + Ri )
> 40000 * ( 1∕ 3000 ) * ( 2.607 + 6.7 )
> 124.09333 V
NO.
Thus,
REVISIONS Vs = 124 V
DRAWN Requirement No.-2
BY:- Iop ≥ 0.1 * IFL
DATE:- ≥ 263.482 A
CHECKED
BY:- Requirement No.-3
DATE:-
OPRG. DEPT Vkp ≥ 2 * VS
BY
DATE:- Vkp ≥ 248 V
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
AS BUILT BY DATE 12/30/99
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
RIYADH SAUDI ARABIA JOB ORDER NO. DWG. CONT. SHT.
CERT'D
APPR'D National Grid Saudi Arabia
Now , actual operating current of the relay shall be:
IOP1 = T * ( IR + n * IMAG1 )
Where IR = The relay operating current = 0.02 A
CHK'D
(At setting voltage as relay catalouge)
n = No. of current transformer in parallel with relay = 10
Since the magnetizing curve shall be linear in the region upto knee-point voltage , therefore the magnetizing current
at setting voltage can be calculated as under:
IMAG at Vkp is = 0.05 A
IMAG at setting volts is = ( Vs * IMAG ) ∕ Vkp
IMAG1 at setting volts is = 0.00111711712 A
IOP1 = 93.52 A < 263.482 A
DESCRIPTION
SHUNT RESISTOR CALCULATIONS:
As the relay will operate at a current much less than the actual fault current , therefore ,
it may be increased by the addition of a resistor RST to give a current IST to achieve the necessary primary current.
IST1 = (IOP/Tp)-(IR+n*IMAG1)
IST1 = 0.05665616216 A
The value of resistor is:
RST1 = Vs/IST1
RST1 = 2188.641
BY
= 3282.962 Ohms (50% more than the calculated value)
METROSIL CALCULATIONS:
DATE
VP1 = 2√(2*Vkp(Vf1-Vkp)
If:
NO.
VP1 > 2 kV
REVISIONS Then metrosil are required
DRAWN VP1 = Peak voltage across relay under maximum internal fault condition
BY:- Vkp = Knee point voltage of C.T
DATE:- Vf1 = (ISCC/Tp)*(RLEAD+Ri+RRELAY)
CHECKED
BY:- RRELAY = VSETTING ∕ IRELAY
DATE:- = 124 ∕ 0.02
OPRG. DEPT RRELAY = 6200 Ohm
BY For a fault of 40kA on primary side, we will check the requirement of metrosils
DATE:- Vf1 = (ISCC/Tp)*(RLEAD+Ri+RRELAY)
ENG'G. DEPT. Vf1 = 82790.76 V
BY:-
DATE:- Therefore
CERTIFIED. VP1 = 58561.8454627 Vp-p
BY:- METROSIL IS REQUIRED
DATE:-
AS BUILT BY DATE 12/30/99
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
RIYADH SAUDI ARABIA JOB ORDER NO. DWG. CONT. SHT.