DS - Automatic Cable Test Van - Titron - BAUR

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

titron® ▪

Optimum ergonomics and


flexibility
BAUR automatic cable test van ▪ High vehicle load capacity with
full system configuration

High voltage and functions

▪  Available test voltages:


–  VLF truesinus®
–  DC voltage
–  Surge voltage
▪  Cable and cable sheath testing
▪  Cable fault location
The figure is illustrative. ▪  Tracing
▪  Cable diagnostics

The intelligent system for cable fault location, Higher efficiency through
testing, and diagnostics innovative technology

↗  Simple, convenient, and fast operation ▪  Time savings thanks to parallel dissipation
factor and partial discharge measurement
↗  High-performance technology and the highest safety standard
▪  Interface to GIS systems
↗  Customised, process-oriented, and adaptable ▪  Central data management

↗  Complete 3-phase cable fault location and diagnostics ▪  Surge energy up to 3000 J, complete surge
energy on all voltage levels
system in a vehicle up to 3.5 t
▪  Precise fault location methods for every
type of fault and various cables, e.g.
titron® is a fully automatic, centrally controlled, and intelligent system for cable fault –  SIM/MIM – the most effective method
location, cable testing, and diagnostics. for cable fault location
–  Conditioning-SIM/MIM – helpful in
Thanks to the innovative operational concept and high-performance technology, locating wet faults that are difficult to
the titron® system is able to carry out measurements faster, more easily, and with detect
greater precision. All of the test van's functions are controlled centrally via the BAUR –  DC-SIM/MIM – for breakdown faults and
software. The intuitive user interface of the BAUR software provides optimal support intermittent faults
to both asset managers and measurement engineers in their workflows. –  Differential methods for the fault loca-
tion in branched networks
Fault location. Recommendations for the cable fault location process are generated ▪  BAUR Fault Location App3) for remote con-
based on a multitude of factors that link the system, in an intelligent manner, to an trol of the cable fault pin-pointing process
algorithm specifically designed for this purpose. Nevertheless, the user is still, at any ▪  Maximum safety for the operator and the
time, able to override the given specifications of the system and to carry out the system
measurement process based on his own experience and knowledge. For cable fault
location, the BAUR software includes a multitude of precise fault location methods
for every type of fault and various cables.1)

Testing and diagnostics. With the diagnostics methods based on dissipation factor F urther information can be found in the
and partial discharge measurement, proven methods are available for comprehensive following data sheets:
1)
IRG 4000 time domain reflectometer and
cable analysis. This not only enables the early detection and location of PD-related
BAUR software for cable fault location
weak points in medium-voltage cables and cable accessories, but also the assessment 2)
BAUR software for cable testing and
diagnostics
of dielectric ageing based on the dissipation factor values.2) 3)
BAUR Fault Location App

Note: The availability of individual methods, functions, and voltage levels depends on the system configuration.

BAUR GmbH · Raiffeisenstraße 8, 6832 Sulz, Austria · T +43 (0)5522 4941-0 · F +43 (0)5522 4941-3 · [email protected] · www.baur.eu
titron®
The state-of-the-art in cable fault location

Central automatic control with complete system monitoring

↗  Central system control via the BAUR software and high-performance industrial PC
↗  Highest level of efficiency and measurement precision through the optimally
adjusted measurement path, combined with modern digital signal processing
↗  Extremely high reliability by monitoring and recording all system events
↗  Quick start: ready for operation in just a few seconds

The innovative operational concept

↗  Intuitive modern user interface in multiple languages – no


long introduction or familiarisation period is required
↗  Process-oriented support for both asset managers and
measurement engineers for the efficient planning and
performance of measurements, as well as the precise
monitoring of the condition of cable networks
↗  Mapping:
–  Unique combination of road maps, including the cable
route
–  GPS-based system location determination
–  Cable routes and cable faults displayed on the map
↗  Optimal operator support during cable fault location provided by the Smart Cable Fault Location Guide
↗  Cable Mapping Technology CMT: Overview of cable accessories and faults in relation to the cable length
↗  All data on the cable route, such as the geographic position, voltage level, joints, all measured values, etc. is automatically
saved and can be accessed at any time.
↗  Quick and easy compilation of clear and precise measurement records – with freely selectable company logo, comments and
figures of the traces.
↗  Fast and precise location of the cable fault in combination with the BAUR Fault Location App
Comprehensive safety concept in accordance with the latest standards

↗  Safety concept in compliance with EN 61010-1 and EN 50191


↗  Monitoring of all safety-relevant parameters (protective and auxiliary
earthing, rear door and HV connection sockets)
↗  Separation into the operating area and HV area
↗  Red and green signal lamps to indicate the operating state
↗  Emergency off button in the operating area and optional external emergency
stop feature
↗  Key-operated switch to prevent unauthorised operation

↗  All operation-related error messages are displayed clearly on the screen and Figures and screenshots are illustrative
are immediately visible to the user.

Page 2/8 Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications
titron®
Find your cable fault with just a few clicks!
Smart Cable Fault Location Guide

↗  The intelligent Smart Cable Fault Location Guide leads the operator step-by-step – quickly and efficiently
– to the cable fault.
↗  A special algorithm continuously analyses the current measurement results, which it uses to generate
optimum recommendations for the operator regarding the further procedure required to reliably locate
the cable fault.
↗  Automatic fault analysis with clear graphical presentation giving a better overview.
↗  Test voltage wizard:
–  The system recommends voltage values according to the cable data and the fault type.
–  The test voltages can be defined according to the user.
↗  Automatic cursor positioning at the cable end and at the fault location
↗  Automatic adjustment of method-related parameters for quick and efficient fault location.
↗  Clear graphical presentation of the measurement results with helpful functions for evaluation
↗  Envelope curve display for intermittent faults – even small changes in impedance are made visible and
saved.
All this with full flexibility for experienced operators! Experienced measurement engineers can use
their know-how directly at any point during the measurement process and select a user-specific procedure.

Fault analysis Pre-location Pin-pointing Report

Cable route MPS 135 Cable length 999 m Voltage level 12/20 kV Phases 3 Cable data

Start 999 m End


Phase
L1
L1
Cable
L2 806 m
N presentation
L3 !
L3 L2
N !

SIM/MIM High-resistance fault at L3N. Next step: Pin-pointing

Phase selection Recommendation of the Cable fault mapping: Fault


Smart Cable Fault Location Guide location with distance indicator

Screenshot is illustrative
Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications Page 3/8
titron®
A sophisticated workstation – ergonomic, practical, and comfortable
Better ergonomics in the workplace Easy and convenient to operate

↗  Large monitors for greater productivity and a better


overview during evaluation
The following are available:
–  1 x 24" monitor
–  1 x 19" monitor
–  2 x 19" monitors
↗  Standard, convenient operation by means of a mouse and
keyboard
↗  Proven Windows operating system
↗  GIS interface enables the exchange of cable data between
your GIS system and the BAUR software.
↗  Optimum ergonomics in the workplace for greater efficiency ↗  Time savings thanks to interactive user support
↗  Large work surface and lots of storage space (up to 32 RU) ↗  Online support via the Internet
↗  Easily accessible data interfaces for the simple connection –  With your permission, BAUR's customer service
department can access the computer of your cable test
of additional equipment, e.g. printer, laptop, etc.
van, identify your problem, and quickly find a solution.
–  4 x USB 3.0
–  During the fault location, your engineers can share the
–  1 x Ethernet desktop with the test engineer on site and support him in
↗  Sockets directly on the workstation the analysis of the measurement results (where applicable,
a licence for a desktop-sharing program may be required).
↗  Charging options for portable devices, e.g. the protrac®
portable pin-pointing system, even while on the move
↗  LV connector panel directly on the workstation for connecting
external devices, e.g. the TG 20/50 audio frequency
transmitter or an external ohmmeter
↗  Movable seat console with lots of storage space and optional
backrest

Inverter with integrated battery charging function

↗  Industrial PC can be supplied with power via the vehicle


battery for several hours
↗  Automatic switchover to supply via vehicle battery in the
event of mains failure
↗  System sockets can be supplied with power via the vehicle
battery while on the move (up to max. 800 W)
↗  Automatic switch off of the inverter if critical battery voltage
is not reached
↗  Vehicle battery is charged as soon as the system is connected
to the mains voltage

Figures are illustrative


Page 4/8 Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications
Technical data
titron® titron® titron®
3-phase 1-phase compact

I. High voltage
Surge voltage
Surge voltage ranges 0 – 8 kV, 0 – 16 kV, 0 – 32 kV
Surge energy 3000 J @ 8, 16, and 32 kV Surge energy Surge energy Surge energy
2050 J @ 8, 16, and 32 kV of choice of choice of choice
1540 J @ 8, 16, and 32 kV
Surge capacitor extension SZ 1550: SZ 2650: Option Option Option
For surge energy class 3000 J: 1820 J @ 4 kV 2890 J @ 4 kV
For surge energy class 2050 J: 1580 J @ 4 kV 2660 J @ 4 kV
For surge energy class 1540 J: 1460 J @ 4 kV 2530 J @ 4 kV
Surge sequence 5 – 20 pulses/min, single surge
Capacitor charge time Max. surge voltage 32 kV in 3 s
Voltage sources
SSG 40 surge voltage generator
DC voltage 0 – 40 kV, Imax = 50 mA
viola VLF HV generator Option Option Option
DC voltage 0 to ±60 kV
VLF voltage truesinus® 0 – 44 kVrms Square wave 0 – 60 kV
Frequency range 0.01 – 0.1 Hz
Max. capacitive load Up to 10 µF; 0.85 µF @ 0.1 Hz at 44 kVrms
2.7 µF @ 0.03 Hz at 44 kVrms; 7.7 µF @ 0.01 Hz at 44 kVrms
PHG 70 VLF HV generator Option Option Option
DC voltage 0 to ±70 kV; Imax = 10 mA @ 70 kV; 90 mA @ 20 kV
VLF voltage truesinus® 0 – 38 kVrms Square wave 0 – 57 kV
Frequency range 0.01 – 1 Hz
Max. capacitive load Up to 20 µF; 3 µF @ 0.1 Hz at 38 kVrms
PHG 80 VLF HV generator Option Option Option
DC voltage 0 to ±80 kV; Imax = 1.8 mA @ 80 kV; 90 mA @ 20 kV
VLF voltage truesinus® 0 – 57 kVrms Square wave 0 – 80 kV
Frequency range 0.01 – 1 Hz
Max. capacitive load Up to 20 µF; 1.2 µF @ 0.1 Hz at 57 kVrms
3 µF @ 0.1 Hz at 38 kVrms

= included in standard delivery / Option = available as an optional extra / – = not available

Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications Page 5/8
Technical data
titron® titron® titron®
3-phase 1-phase compact

I. High voltage (continued)


Voltage sources (continued)
PGK HB AC/DC HV test set Option Option Option
DC voltage
PGK 70 HB: 0 to ±70 kV, Imax = ±3 mA / ±12 mA1), 1.2 kVA
PGK 70/2,5 HB: 0 to ±70 kV, Imax = ±20 mA / ±84 mA1), 6.5 kVA
PGK 110 HB: 0 to ±110 kV, Imax = ±5 mA / ±17 mA1), 2.65 kVA
PGK 110/5 HB: 0 to ±110 kV, Imax = ±22 mA / ±104 mA1), 11.7 kVA
PGK 150 HB: 0 to ±150 kV, Imax = ±4 mA / ±20 mA1), 2.65 kVA
PGK 150/5 HB: 0 to ±150 kV, Imax = ±18 mA / ±77 mA1), 11.7 kVA
AC voltage
PGK 70 HB: 0 – 55 kVrms, Imax = 7 mArms / 20 mArms1), 1.2 kVA
PGK 70/2,5 HB: 0 – 55 kVrms, Imax = 50 mArms / 117 mArms1), 6.5 kVA
PGK 110 HB: 0 – 80 kVrms, Imax = 14 mArms / 30 mArms1), 2.65 kVA
PGK 110/5 HB: 0 – 110 kVrms, Imax = 66 mArms / 137 mArms1), 11.7 kVA
PGK 150 HB: 0 – 150 kVrms, Imax = 9 mArms / 23 mArms1), 2.65 kVA
PGK 150/5 HB: 0 – 110 kVrms, Imax = 50 mArms / 108 mArms1), 11.7 kVA
PGK E DC HV tester Option Option Option
DC voltage
PGK 50 E: 0 – 50 kV, Imax = -2 mA / -25 mA1), 1.6 kVA
PGK 80 E: 0 – 80 kV, Imax = -1.5 mA / -20 mA1), 1.4 kVA

II. Cable fault location


Insulation resistance measurement
Voltage up to 1,000 V Measurement range: 0 ohm – 5 GOhm
3-phase measurement L-N, L-L via HV connection – –
3-phase measurement L-N, L-L via LV connection with TDR connection cable, 50 m Option Option
Pulse reflectometry
The technical data of the time domain reflectometry are provided in the data sheet for the IRG 4000 time domain reflectometer and BAUR Software 4 for
cable fault location.
Fault conditioning through burning
ATG 2 burn down transformer 0 – 10 kV, up to 32 A; 2.3 kVA Option Option Option
ATG 6000 burn down transformer 0 – 15 kV, up to 90 A; 5.75 kVA Option Option Option

= included in standard delivery / Option = available as an optional extra / – = not available


1)
In short-circuit

Page 6/8 Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications
Technical data
titron® titron® titron®
3-phase 1-phase compact

II. Cable fault location (continued)


Pre-location methods
TDR Time Domain Reflectometry
3-phase measurement L-N, L-L via HV connection – –
3-phase measurement L-N, L-L via LV connection with TDR connection cable, 50 m Option Option
SIM/MIM secondary/multiple impulse method up to 32 kV
DC-SIM/MIM secondary/multiple impulse method used in DC mode up to 32 kV, Imax = 120 mA
Conditioning-SIM/MIM fault conditioning with subsequent SIM/MIM measurement
ICM impulse current method up to 32 kV
DC-ICM impulse current method used in DC mode up to 32 kV, Imax = 120 mA
Decay method up to 40 kV1)
Breakdown voltage detection up to 40 kV1)
Differential methods Option – –
For cable fault pre-location in branched low-voltage and medium-voltage networks:
ICM differential method, decay differential method, DC-ICM differential method
Measuring bridge measurement for the pre-location of cable and cable sheath faults Option Option Option
(shirla sheath test and fault location device)
Pin-pointing methods
Acoustic pin-pointing: Voltage ranges: 0 – 8 kV, 0 – 16 kV, 0 – 32 kV2)
Step voltage method up to 40 kV, Imax = 50 mA
Tracing, audio frequency methods (twisted field and minimum distortion methods)
– TG 600 integrated audio frequency transmitter, 600 VA Option Option –
– TG 20/50 mobile audio frequency transmitter, 20 VA/50 VA Option Option Option
All pin-pointing methods: protrac® pin-pointing system Option Option Option
III. Safety devices and protective features
Safety standard According to EN 50191 and EN 61010-1
Electrical safety Overvoltage category IV/300
Safety monitoring Protective earthing, operational earthing, auxiliary earthing, potential
monitoring, HV connections, rear doors, emergency off button
Monitoring of the supply Overvoltage protection, undervoltage protection
voltage
Isolation transformer 5 kVA or 7 kVA with switch current limiter Option Option Option
External emergency off unit with signal lamps, incl. connection cable, 50 m Option Option Option
IV. System data
Connection cable
3 x 1-phase HV connection cable, 50 m – –
3 x 1-phase HV connection cable, 80 m Option – –
1 x 3-phase HV connection cable, 50 m Option – –
1 x 1-phase HV connection cable, 50 m –
1 x 1-phase HV connection cable, 80 m – Option Option
TDR connection cable, 3-phase, 25 or 50 m, on hand cable drum, measurement category CAT IV/600 V Option Option
Phase and device selection
Automatic phase and device selection (Device –
selection)
= included in standard delivery / Option = available as an optional extra / – = not available
1)
 ptional up to 150 kV (depending on the size of the vehicle), see the optional voltage sources listed in section „I. High voltage“ of the
O
technical data
2)
For data on surge voltage and available options, see section „I. High voltage“ of the technical data
Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications Page 7/8
Technical data
titron® titron® titron®
3-phase 1-phase compact

IV. System data (continued)


Cable drum rack
KTG M cable drum rack
KTG M cable drum rack with motor drive Option Option Option
KTG NE cable drum rack with motor drive Option – –
Operating system and display
Operating system Windows 10
Memory 8 GB RAM
Hard disk SSD industry standard
Display 1 x 24" monitor (resolution 1920 x 1080)
Instead of 24" monitor – 1 x 19" monitor (resolution 1280 x 1024) or Option Option Option
– 2 x 19" monitors
Optional software functions
GIS interface
Mapping (available countries on request) Option Option Option
BAUR software 4 for office PC (office installation)
Remote control of the system
BAUR Fault Location App For remote control of the surge voltage generator Option Option Option
Control via laptop Option Option Option
Systems supply and operating conditions
Input voltage 190 – 264 V, 47 – 63 Hz
Max. power consumption 7.5 kVA
Inverter with battery 230 V ±2%, 50 Hz ±0.1%, 700 W / 800 VA
charging function
Charger DC 13.2 – 14.4 V, 35 A
Ambient conditions
Ambient temperature HV area: -20°C to +50°C Operating area: 0°C to +50°C
Storage temperature -20°C to +60°C
Mobile power supply
Synchronous generator 7 kVA, 230 V Option Option Option
Electronic generator 5 kVA, 230 V Option Option Option
Battery-Power system For battery mode; battery capacity 5.5 kWh, 230 V Option Option Option
Climate control units
Fan heater 230 V, 2000 W Option Option Option
Air conditioner 230 V Option Option Option
Weight
Standard version From 800 kg From 800 kg From 450 kg

Contact:
BAUR GmbH (Headoffice Österreich) BAUR France 奥地利保尔公司上海代表处
T +43 (0)5522 4941-0 T +33 (04) 69 98 27 27 电话 +86 (0)21 6133 1877
[email protected] [email protected] [email protected]

BAUR Prüf- und Messtechnik GmbH Baur do Brasil Ltda. BAUR Representative Office Hong Kong
T +49 (0)2181 2979 0 T +55 11 297 25 272 T +852 2780 9029
[email protected] [email protected] [email protected]

BAUR GmbH (Branch UAE) BAUR Test Equipment Ltd. (UK) BAUR representatives:
T +971 50 4440270 T +44 (0)20 8661 0957 www.baur.eu > BAUR worldwide
[email protected] [email protected]

Page 8/8 Data sheet: BAUR GmbH · 826-132-2 · 07.2021 · Subject to modifications

You might also like