Laser Power Supply Family LPS 2000 Plus Operating Manual: English Edition
Laser Power Supply Family LPS 2000 Plus Operating Manual: English Edition
Operating Manual
m c English Edition
m c Laser Power Supply Family LPS 2000 plus
Characteristics ............................................................................... 5
Type summary ............................................................................... 6
Available power .............................................................................. 6
Description ..................................................................................... 6-7
Control options ............................................................................... 8-9
Signals and data at the interfaces .................................................. 10 - 14
Timing diagrams ............................................................................ 15 - 16
Interface description
Applications
Specifications
Dimensions .................................................................................... 58 - 61
Address .......................................................................................... 63
Please read this instruction carefully and pay particular attention to the use as agreed and
the safety labelings.
You will lose any warranty claim for damages caused by nonobservance of the
instructions.
We don’t undertake liability for resultant damages.
Use as agreed
The device serves for constant current operation of pump lamps for lasers.
The device is suitable for the constant current operation of ohmic, capacitive and inductive loads.
The maximum permitted output power of 6000 W or a maximum input power of 7000 W may not
be exceeded.
Safety labelings
The safety rules of the federation of professional trade associations for electrical plants in
commercial facilities have to be followed.
The device isn’t allowed for the use on people and animals.
The supply lines to the pump lamp must be designed for the intended lamp current.
Dimensioning: recommended cross-section 4 sqmm.
At the LPS 2000 plus use wire end sleeves for the corresponding cross-section.
Use only the allowed and prescribed manufacturer squeezing tool for squeezing the
wire end sleeves.
Incorrect squeezing connections can show an inadmissibly high transfer resistance. This may lead
to increased power dissipation at the squeezing point and can cause a cable fire.
Pay attention to a firm screw connection of the supply lines.
Never disconnect the lines from the LPS 2000 to the laser lamps during operation.
It could cause a dangerous arc because of the current source characteristics of the device which
leads to skin burnings, to injury of the eyes or to a fire.
Never put the LPS 2000 plus into operation when it was just taken from a cold to a warm room.
The condensed water arising in this process can influence the function of the device or even
destroy it.
Let the LPS 2000 plus assimilate to room temperature before use.
If the LPS 2000 plus is used in electrically conductive dust in commercial or industrial
surroundings, then the intaken air must absolutely be filtered.
The fan may not be put out of operation when an alternative water cooling is used.
If a safe mode of the LPS 2000 plus cannot be guaranteed, set it out of operation and secure it
against unintentional use.
In every case the LPS 2000 plus has to be put out of operation if
Characteristics
The LPS 2000 plus family consists of altogether 4 devices of equal dimensions.
The difference is the number and precision of the interfaces and the extent of supply.
Type summary
LPS 2000 plus type Output Power Lamp Current Lamp Voltage
max. max.
10100200 6000 W 0 - 30 A 350 V
10100201 6000 W 0 - 30 A 350 V
10100202 6000 W 0 - 30 A 350 V
10100220 6000 W 0 - 25.5 A 350 V
Output power
Within the input voltage range from 342 V up to 506 V (3-phase mains) the maximum output
power of 6000 W is independent of the input voltage.
Description
The devices of the LPS 2000 plus family are based on the new developed MAPS technology and
are distinguished by its excellent electrical and mechanical characteristics as well as maximum
electromagnetic compatibility (EMC) and leakage current.
The running costs are considerably reduced through the Power Factor Correction and the high
power factor of 0.95.
Cost-intensive external filters at the input or output, shielded or twisted supply lines to the lamp
and shielded interface cables are not required.
Because of the low leakage current a mains plug connector is allowed and there are no problems
with differential-current switches.
A Serial Interface and an Analog Interface with input and output are available. The devices are
optionally deliverable with a Parallel Interface.
The LPS 2000 plus is short circuit proof between the output lines and between the output lines to
PE.
The LPS 2000 plus is immediately ready after turning on the mains voltage. No initial period has to
be waited for.
The high speed boost generator charges within 3 seconds onto 1000 V. 1800 V are reached within
10 seconds.
The integrated power and interface connections allow a space-saving mounting and wiring. The
fan is integrated too. It is temperature regulated for increasing lifetime.
Mounting is both horizontally and vertically possible. For control cubicle installation horizontal and
vertical mounting plates are deliverable.
All rules and guidelines are met. The device has CE sign. The device is manufactured in a
documented production flow.
TM
Parallel Windows is a re-
gi- (optional) stered trademark of
the Microsoft Corpora-
tio n USA.
RS 232 C
Analog In
Analog Out
DIP Switch
Control options
The output current of the LPS 2000 can be controlled by the Analog Port. The output current can
be monitored at the Analog Output Port (current monitor).
The boost voltage can be adjusted between 300 volts and 1800 volts by setting the DIP-switches
1 to 4.
In the Auto Start mode the LPS 2000 plus only needs a current set point at the Analog Port for
operating.
The RS 232 Port allows operation and supervision of the LPS 2000 plus with access to all
implemented functions and measurements.
The LPS can be controlled by a PC and important device parameters and limiting values can be
permanently programmed with the control- and configuration software.
The LPS 2000 sends constantly the current measurements and settings at the RS 232 Port,
independently of the selected or active interface.
At the Parallel Port the LPS 2000 plus can be controlled digitally with wide performance range.
The interfaces can also be used at the same time without any problems.
For example is it possible to control the LPS 2000 plus digitally at the Parallel Port and add or
subtract (modulation) an additional current by feeding in a current set point at the Analog Port.
Simultaneously is it possible to read out all current values, measurements and settings at the
RS 232 Port.
It is not possible using the RS 232 Port and the Parallel Port both at the same time to control the
LPS 2000 plus.
Bit
a
it
ort
a
l8B
Dat
Por
l 10
Dat
P
n
232
ctio
trol
log
alle
alle
tus
e
er
Nam
Con
Ana
Fun
Oth
Par
Par
Sta
RS
CA Current Set Point Analog CSPA ·
SA Output Current Analog COUTA ·
CD Current Set Point 10 Bit CSPD10 · ·
CD Current Set Point 8 Bit CSPD8 · ·
CD Power Supply On ON · · ·
CD Boost On BON · · ·
CD Standby Current Activated SBA · ·
CD Interlock Input ILIN · ·
CD Reset Fault RESF · ·
CD Autostart AUTO ·
SD Power Supply Ready PSR · · ·
SD Boost Voltage Ready BVR · ·
SD Output Current Ok COUTR · · ·
SD Current Fault CF · · ·
SD Lamp Break LB ·
SD Summation Fault SF · ·
SD Interlock Output ILOUT · ·
SD Heat Sink Temperature 8 Bit T ·
Bit
a
it
t
a
t
Por
l8B
Dat
Por
l 10
Dat
232
ctio
trol
log
alle
alle
tus
e
er
Nam
Con
Ana
Fun
Oth
Par
Par
Sta
RS
SD Output Current 8 Bit COUT ·
SD Mains Voltage 8 Bit (Peak Value) MV ·
SD Boost Voltage 8 Bit BV ·
SD Output Voltage 8 Bit VOUT ·
Temperature Limit Reached
SD TLCR ·
3 Bit Counter
SD Temperature Limit Reached TLR ·
Temperature Warning Limit
SD TWLCR ·
Reached - 3 Bit Counter
Temperature Warning Limit
SD TWLR · · ·
Reached
Output Current Time Out
SD COUTTC ·
4 Bit Counter
SD Output Current Time Out COUTT ·
SD Current Limit Reached CLR ·
SD Pump Lamp Defect PLD ·
SD Current Fault CF ·
Output Voltage Exceeded
SD VOUTCE ·
3 Bit Counter
SD Output Voltage Exceeded VOUTE ·
Boost Voltage Exceeded
SD BVCE ·
3 Bit Counter
SD Boost Voltage Exceeded BVE ·
Bit
a
it
t
a
t
Por
l8B
Dat
Por
l 10
Dat
232
ctio
trol
log
alle
alle
tus
e
er
Nam
Con
Ana
Fun
Oth
Par
Par
Sta
RS
SD System Fault SF ·
SD RS 232 Frame Fault SIFF ·
SD RS 232 Time Out SITO ·
SD RS 232 Illegal Character SIIC ·
SD Voltage Summation Fault VSF ·
SD Current Summation Fault CSF ·
SD Temperature Summation Fault TSF ·
SD IGBT Fault IGBTF ·
SD Parallel Active PA ·
SD Serial Active SA ·
SD Overcurrent OC ·
SD DIP Switch Boost Voltage 4 Bit BVDIP ·
DIP Switch
SD BVPDIP ·
Boost Programming Mode 4 Bit
SD DIP Switch Autostart ASDIP ·
DIP Switch
SD CPDIP ·
Current Programming Mode
DIP Switch
SD ISDIP ·
Interface Selection
SD Boost Voltage Internal 4 Bit BVI ·
SD PWM Power Module Locked PPML ·
SD PWM Boostgenerator gesperrt PBGL ·
Bit
a
it
t
a
t
Por
l8B
Dat
Por
l 10
Dat
232
ctio
trol
log
alle
alle
tus
e
er
Nam
Con
Ana
Fun
Oth
Par
Par
Sta
RS
SD Power Module Reset PMR ·
SD Power Module Fault Reset PMFR ·
SD Hardware Fault HF ·
SD Current Set Point 10 Bit CSPD10 ·
SD Current Set Point 8 Bit CSPD8 ·
SD LED 1 - Input Voltage Ok LED1 ·
SD LED 2 - Output Voltage Ok LED2 ·
SD LED 3 - Waiting for UOut Ok LED3 ·
SD LED 4 - Current Flows, Lamp Ok LED4 ·
SD LED 5 - Boost Voltage Ok LED5 ·
SD LED 6 - Fan Control Ok LED6 ·
SD LED 7 - Fault LED7 ·
SD Temperature Limit 8 Bit TL ·
SD Maximum Output Current 8 Bit COUTMA ·
SD Minimum Mains Voltage 8 Bit MVMI ·
SD Temperature Warning Limit 8 Bit TW ·
SD Operating Hours 32 Bit WH ·
SD Minimum Output Current 8 Bit COUTMI ·
SD Maximum Boost Voltage 8 Bit BVMA ·
SD Boost Release Value 8 Bit BVR ·
Bit
a
it
t
a
t
Por
l8B
Dat
Por
l 10
Dat
232
ctio
trol
log
alle
alle
tus
e
er
Nam
Con
Ana
Fun
Oth
Par
Par
Sta
RS
SD Maximum Output Voltage 8 Bit VOUTMA ·
SD Baud Rate BR ·
SD Auxiliary Voltage +15 V AUX+15 · ·
SD Auxiliary Voltage -15 V AUX-15 ·
SD Auxiliary Voltage + 5 V AUX+5 ·
Timing diagrams
Temperature Transgression
Excess Temperature
500 ms ± 100 ms
Mains Voltage
Unit Ready
2400 ms ± 1000 ms
Unit On
Unit Ready
80 ms ± 20 ms
Interlock Characteristic
Interlock Input
Interlock Output
Fault
Unit Ready
1600 ms ± 400 ms
Characteristic at Unit On
Unit On
Output Current Ok
3800 ms ± 600 ms
Fault
Fault Reset
4800 ms ± 400 ms
5100 ms ± 400 ms
Analog Port
Signals and data at the interfaces (continuation)
The Output Current of the LPS 2000 plus can be controlled at the Analog Port with minimal effort.
If the LPS 2000 plus shall be controlled only via the Analog Port the operating mode Autostart has
to be selcted at the DIP-switches. This is not necessary in operation together with the Parallel Port
or the RS 232 Port.
The Output Current is controlled by a voltage in the range from 0 to 10 V at the input Analog In.
1 volt corresponds to 3 A.
0 volt corresponds to 0 A. 10 volts correspond to 30 A Output Current.
The voltage at the output Analog Out is an image of the Output Current.
1 volt corresponds to 3 A Output Current.
0 volt corresponds to 0 A. 10 volts correspond to 30 A Output Current.
Parallel Port
Interface description - Parallel Port 10 bit
Inputs
Pin Function
Outputs
Pin Function
25 + 15 V *
13 GND
* Internal supply voltage of the LPS 2000 plus to supply peripheral equipment with a maximum
current of 50 mA.
Connection: 25-pole pin plug connector according to DIN 41652 and MIL-C-24308,
internal thread UNC 4-40.
Parallel Port
Interface description - Parallel Port 8 bit
Inputs
Pin Function
Outputs
Pin Function
Connection: 25-pole pin plug connector according to DIN 41652 and MIL-C-24308,
internal thread UNC 4-40.
Parallel Port
Input levels
All inputs are active-high.
Levels between 0 V and 0.8 V are Low,
levels between 2 V and < 30 V are High.
Levels between 0.8 and 2 V can cause nonreproducible states.
Minimum required rise and fall time is 3 µs. The signals must be applied for a minimum time of
128 µs.
Output levels
All outputs are active-low (NPN open collector).
The inputs of the connected circuitry must have pull up resistors to its relevant supply voltage to
ensure a correct function.
The maximum permitted voltage is 30 V. The maximum permitted current is 20 mA (sink mode).
Levels between 0 V and 0.4 V are Low, all other levels are High.
Minimum Low and High time: 128 µs ... 130 µs.
In the Analog mode (DIP-switch 7 = Off) the Output Current is controlled by a voltage feed in at
the Analog Input (Scaling: 0.3 V / A).
In the mode Digital Plus Analog (DIP-switch 7 = On) the output current is digitally controlled by a
10 bit data word (1023 digits) with data bits 0 to 9.
1 digit corresponds to 29.3 mA. Full scale (data bits 0 to 9 = High) corresponds to 30.0 A.
A current set point feed in at the analog input is added to the digital current set point.
The analog current set point may also be negative and acts subtracting.
Modes of operation
The LPS 2000 plus can be operated in two ways.
The operation mode Autostart Activated (DIP-switch 6 = On) allows an automatic startup.
After turning on the mains voltage the power module is activated automatically and the boost
generator starts. The boost generator is switched off automatically after igniting the pump lamp.
The operation mode Autostart Deactivated (DIP-switch 6 = Off) allows the fully controlled
operation of the functions Power Supply On, Boost On, Standby Current Activated, Interlock
Input, Reset Fault, and Current Set Point by the Parallel or the Serial Port.
Parallel Port
Functions
The control bit Power Supply On activates the power module of the
LPS 2000 plus. An Output Voltage of 350 V is applied to the output.
The control bit Boost On activates the boost generator. The programmed boost voltage is applied
to the output.
The control bit Standby Current Activated changes the output current to a value of 7 A.
The value can be changed with the configuration software in the range from 0 to 30.0 A.
If a signal is missing, the LPS 2000 plus switches off and signals a summation and interlock fault.
If the LPS 2000 plus has switched off because of frequently faults, it can be activated again by the
control bit Reset Fault or by disconnecting the mains voltage.
Outputs
The status Power Supply Ready will be signalled, if the LPS 2000 plus is connected to the
correct supply voltage and there are no faults.
The status Boost Voltage Ready will be signalled if the boost voltage has reached the
programmed value.
The status Output Current OK will be signalled if the output current corresponds to the program-
med value and flows for one second.
The status Current Fault will be signalled if the output current differs from the programmed value
for one second.
The signal will be reset if the output current corresponds to the programmed value again.
If the maximum permissible current is exceeded the LPS 2000 plus limits to 30 A.
The status Lamp Break will be signalled if there is no Current Fault, the output voltage is lower
than the programmed value of 50 V and the output current is higher than the programmed value of
3 A.
The values can be changed in the range of 0 ... 300 V and 0 ... 30.0 A with the configuration
software.
The status Temperature Warning Limit Reached will be signalled if the LPS 2000 plus has
reached a temperature of + 75 °C at the heat sink. The LPS 2000 Plus switches off at + 80 °C.
The Temperature Warning Limit Reached value can be changed in the range of 0 ... + 80 °C with
the configuration software.
The signal Interlock Output is generated from the control bit Interlock Input.
RS 232 Port
Interface description - RS 232 Port
Pin Function
1 NC *
2 TX
3 RX
4 NC
5 GND
6 NC
7 CTS
8 RTS
9 NC
* The internal supply voltage of the LPS 2000 plus (± 15 V and + 5 V) can be applied by internal
jumpers to the following pins for supplying peripheral equipment with a maximum current of 50
mA.
+ 15 V pin 6
- 15 V pin 1
+5V pin 9
The logic states of the interface correspond to the CCITT recommendation V.28.
Connection: 9-pole pin plug connector according to DIN 41652 and MIL-C-24308, internal thread
UNC 4-40.
The LPS 2000 plus can communicate with a PC via a 9-pole D sub line (socket-socket, one-to-one
wiring). The fully performance range is available.
The LPS 2000 plus receives control data and sends status and diagnosis data. Status and
diagnosis data are always sent even if the LPS 2000 plus is controlled by the Parallel Port or by
the Analog Port.
The limiting values of the LPS 2000 plus can be programmed by the configuration software.
RS 232 Port
Software protocol
The baud rate is variable and can be set factory-aligned to the following rates:
2400, 4800, 9600 or 18382 (customer-specific) bauds.
The data format is 8 data bits, no parity, one stop bit.
No software handshake (XON, XOFF) is used.
00 °C 54
10 °C 58
25 °C 67
40 °C 87
45 °C 94
50 °C 106
55 °C 116
60 °C 128
65 °C 144
70 °C 175
75 °C 195
80 °C 249
RS 232 Port
Data Byte 6 Boost Voltage SD-BV
8 bit value, binary output, linear.
2235 V correspond to 255 digits.
1 digit corresponds to 8.765 V.
If the temperature limit value (data byte 25) is exceeded the device will be switched off with the
message 'Temperature Limit Exceeded' after a duration of approximately 0.5 seconds.
Bit 0 to 2 3 bit counter for the maximum permitted heat sink temperature
Bit 3 Excess temperature bit, the device is switched off.
If the value of the temperature warning byte (data byte 28) is exceeded
the temperature warning bit will be set after 0.5 s. This allows to activate an
additional cooling.
Bit 4 to 6 3 bit counter for temperature warning
Bit 7 Temperature warning bit, shows that the warning temperature is reached.
The device is not switched off.
RS 232 Port
Bit 5 Shows a current fault.
Bit 5 is set if the output current differs from the current set point
for at least one second. If the maximum Output Current of 30 A
is not exceeded then the device isn't switched off. If the output
current matches the current set point again Bit 5 is reset.
Bit 7 Shows that the output current was not reached within one minute.
The device switches off immediately.
RS 232 Port
Data Byte 13 Data Inputs Parallel Operation
Shows the values (inputs) if the Parallel Port is activated.
Binary output.
Bit 0 Current Set Point data bit 8 (not applicable at the 8 bit interface)
Bit 1 Current Set Point data bit 9 (MSB 10 bit interface, not applicable at the
8 bit interface)
Bit 2 Control bit Power Supply On
Bit 3 Control bit Boost On
Bit 4 Control bit Stand-by Current Activated
Bit 5 Control bit Interlock Input
Bit 6 Control bit Reset Fault, occured faults are reset
Bit 7 Control bit Auto Start. Allows an automatic startup. The power module is
automatically activated and the boost generator switches on immediately
after switching on the mains. The boost generator switches off automatically
after igniting the pump lamp.
RS 232 Port
Bit 2 = 1 Signals that the Output Current corresponds to the
programmed current since approximately one second.
Bit 3 = 1 Unit Ready is signalled if the correct mains voltage is
applied to the device and there is no fault.
Bit 4 = 1 Shows a current fault.
Bit 5 is set if the output current differs from the current set point for at least one
second. If the output current matches the current set point again Bit 5 is reset.
Bit 5 = 1 If the boost voltage has reached the programmed value, Boost Voltage Ready is
signalled.
Bit 6 = 1 If the device has reached a temperature of + 80 °C at the heat sink Excess
Temperature is signalled. At + 85 °C switches the device off. The excess
temperature value can be changed in the range of 0 ... + 80 °C with the
configuration software.
Bit 7 = 1 Shows the transgression of the maximum permitted current. If the permitted current
is no longer exceeded then Bit 7 is reset.
Bit 0 Boost Voltage data bit 0 LSB (for the internal D/A converter)
Bit 1 Boost Voltage data bit 1 (for the internal D/A converter)
Bit 2 Boost Voltage data bit 2 (for the internal D/A converter)
Bit 3 Boost Voltage data bit 3 MSB (for the internal D/A converter)
Bit 4 not used
Bit 5 Locks the PWM of the power module
Bit 6 Locks the PWM of the boost generator
Bit 7 Resets faults of the power module
RS 232 Port
Data Byte 20 and 21 Current Set Point 10 Bit SD-CSPD10
16 bit value (resolution 10 bit), right justified in the 16 bit word, binary output.
Byte 21 is the Low byte (bit 0 is LSB) and byte 20 is the High byte
(bit 7 is MSB).
25.575 A correspond to 1023 Digits.
1 Digit corresponds to 0.025 A.
Data Byte 25 Limit Value Maximum Permitted Heat Sink Temperature SD-TL
8 bit value, binary output, nonlinear.
00 °C 54
10 °C 58
25 °C 67
40 °C 87
45 °C 94
50 °C 106
55 °C 116
60 °C 128
65 °C 144
70 °C 175
75 °C 195
80 °C 249
RS 232 Port
Data Byte 27 Limit Value Minimum Mains Voltage SD-MVMI
The value sets the lower limit for the mains voltage (peak value).
8 bit value, binary output, linear.
775 V correspond to 255 digits.
1 digit corresponds to 3.04 V.
00 °C 54
10 °C 58
25 °C 67
40 °C 87
45 °C 94
50 °C 106
55 °C 116
60 °C 128
65 °C 144
70 °C 175
75 °C 195
80 °C 249
RS 232 Port
Data Byte 37 Default Configuration Register
Binary output.
Data Byte 39
Has no meaning. The value is 0.
RS 232 Port
Received data and their meaning:
In the operation mode 'Serial Port activated' (DIP-switch 8 = On) the device
can be controlled by the Serial Port.
If the device is controlled in the operation mode Serial Port Activated (DIP-switch 8 = On) a series
of 8 bytes is cyclically expected. If the sequence stops for longer than one minute the device
switches off and signals a Timeout Fault.
The baud rate for receiving data and sending data is identical.
RS 232 Port
Data Byte 6 Control Register
Binary output.
The Laser Power Supply Control Software 'LPSCS' allows (if the LPS 2000 plus is controlled via
the parallel interface) a monitoring of the operating states of the LPS 2000 plus or the operation
via the RS 232 interface.
The baud rate of the software must be adapted to the settings of the device in the window ‘RDT
Settings’ (callable about ‘Com’ in the menu bar). These settings are permanently stored.
Use a 9-pole D sub line (socket-socket, one-to-one wiring) to connect the PC and the LPS 2000
plus.
To control the LPS 2000 plus via the Parallel Interface, the DIP switch 8 must be 'Off'.
The software allows a monitoring and shows the current data and settings of the LPS 2000 plus.
The current measurements are displayed in the frame ‘Current’ and the limit values in the frame
‘Limits’.
The settings of the LPS 2000 plus DIP switches are displayed in the frame 'Setting'.
The status and error messages are displayed in the frame 'Data Out ‘.
The frame 'Data In Parallel' shows the values applied at the Parallel Interface. The status is
displayed in the frame 'Actual Configuration'.
For the different LPS 2000 plus types the corresponding model number must be selected in the
field ‘Type’.
Display mask for monitoring at the PC at control via the Parallel Interface
To control the LPS 2000 plus via the Serial Interface, the DIP switch 8 must be 'On'.
To operate the LPS 2000 plus use the frame 'Control Panel'.
For the different LPS 2000 plus types the corresponding model number must be selected in the
field ‘Type’.
After leaving the field all permitted values appear in the field ‘Current Set Point’.
The desired value can be selected with the scroll bar or the nearest possible value by entering the
desired value.
Further settings can be selcted by click on the check boxes below. The values are transmitted to
the device by pressing the 'Confirm' button.
A 'Summation Fault' is shown in the frame 'Data Out' if the device is in a error condition, for exam-
ple due to a communication interruption. It will be reset by pressing the key 'Reset Fault'. Then the
key 'Confirm' has to be selected to send the data again to the device.
Status indication
By selecting the menu item ‘Status’ the window ‘Status Indication’ opens. It shows the state of the
LPS 2000.
Status window
Alternating current
The frame ‘Timer for Alternating Current’ opens by selecting the menu item 'Timer'. By entering
two current values and a hold time an alternating current, for example for test purposes, can be
generated.
The alternating output can be started with the button 'Activate'. It can be stopped again with the
button 'Deactivate' which replaces the button 'Activate' after switching on. The set value for the
'Current Set Point' in the frame 'Control Panel' isn't used by alternating operation.
If the alternating is stopped again, one of the two Current Set Point values for the alternating
current remain at the output. The LPS 2000 plus returns to the Current Set Point settings of the
field 'Control Panel' not until the button 'Confirm' is selected.
Display mask for control via the RS 232 interface with frame 'Alternating Current'
Application 1
Operation at the Analog Port
With the DIP-switches a maximum boost voltage is set and the Auto Start mode for the LPS 2000
plus is activated.
The LPS 2000 plus starts automatically and delivers the desired output current after applying the
mains voltage.
Parallel
Port
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
Application 2
Operation at the Analog Port. Monitoring at the Parallel Port
With the DIP-switches a maximum boost voltage is set and the Auto Start mode for the LPS 2000
plus is activated.
The LPS 2000 plus starts automatically and delivers the desired output current after applying the
mains voltage.
The state of the LPS 2000 plus is transmitted via the Parallel Port to the laser control. The laser
control signals the state.
Unit Ready
Boost Voltage Ready
Output Current Ok
Current Fault
Parallel GND
Port Lamp Break
Excess Temperature
Fault
Interlock
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
Application 3
Operation at the Analog Port. Monitoring at the RS 232 Port.
With the DIP-switches a maximum boost voltage is set and the Auto Start mode for the LPS 2000
plus is activated.
The LPS 2000 plus starts automatically and delivers the desired output current after applying the
mains voltage.
The feedback digital and analog signals are passed on by the RS 232 Port and processed by the
microcontroller of the laser control.
RX
LPS 2000 RS 232 GND Laser Control
plus Port TX and
Supply
Coaxial
Port
Parallel
Port
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
Application 4
Operation at the Parallel Port.
With the DIP-switches a maximum boost voltage for the LPS 2000 plus is set.
The microcontroller delivers a 10 or 8 bit wide digital signal for the Current Set Point and
4 additional digital signals of different meaning to switch on the LPS 2000 plus.
The feedback digital and analog signals are processed by the microcontroller.
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
Application 5
Operation at the Parallel Port. Monitoring at the RS 232 Port.
With the DIP-switches a maximum boost voltage for the LPS 2000 plus is set.
The microcontroller delivers a 10 or 8 bit wide digital signal for the Current Set Point and
4 additional digital signals of different meaning to switch the LPS 2000 plus on.
The digital and analog signals, feedback via the RS 232 Port, are processed by the
microcontroller.
RX
LPS 2000 RS 232 GND Laser Control
plus Port TX with
Micro Controller
Coaxial In and
Port Out Supply
Unit Ready
Boost Voltage Ready
Output Current Ok
Current Fault
Lamp Break
Excess Temperature
Fault
Parallel Interlock Output
Port GND
Current Set Point 10 bit / 8 bit
Unit On
Boost Generator On
Standby
Reset Fault
Interlock Input
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
Application 6
Operation at the RS 232 Port
With the DIP-switches a maximum boost voltage for the LPS 2000 plus is set. It can be done by
the RS 232 Port too.
The microcontroller delivers via the RS 232 Port a digital signal for the Current Set Point and
additional digital signals of different meaning to switch on and control the LPS 2000 plus.
The digital signals, feedback via the RS 232 Port, are processed by the microcontroller.
RX
LPS 2000 RS 232 GND Laser Control
plus Port TX with
Micro Controller
Coaxial and
Port Supply
Parallel
Port
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
Application 7
Operation at the RS 232 Port. Monitoring at the Parallel Port.
With the DIP-switches a maximum boost voltage for the LPS 2000 plus is set. It can be done via
the RS 232 Port too.
The microcontroller delivers via the RS 232 Port a digital signal for the Current Set Point and
additional digital signals of different meaning to switch on and control the LPS 2000 plus.
The digital signals, feedback via the RS 232 Port, are processed by the microcontroller.
RX
LPS 2000 RS 232 GND Laser Control
plus Port TX with
Micro Controller
Coaxial and
Port Supply
Unit Ready
Boost Voltage Ready
Output Current Ok
Current Fault
Lamp Break
Excess Temperature
Fault
Parallel Interlock Output
Port GND
Current Set Point 10 Bit / 8 Bit
Unit On
Boost Generator On
Standby
Reset Fault
Interlock Input
L3
L2
Line AC L1
PE
Current - Cout -
Cout +
Output +
DIP-switch functions
Boost Boost 1 2 3 4
Voltage Charge
Operation modes
DIP-switches 5 - 8
Nr Funktion On Off
Boost Voltage
5 Internal External
Programming Mode
6 Auto Start Activated Analog
Current Programming
7 Digital plus Analog Analog
Mode
Boost
Voltage 300 V ... 1800 V (via 66 W)
Charge 5 J ... 190 J
Resolution 4 bit 100 V / digit
Current static 10 mA
Charging time up to 1000 V 3s
Charging time up to 1800 V 10 s
Interfaces
Dielectric strength to PE 63 V DC
Serial interface RS 232 C DEE CCITT V.28 9-pole pin plug connector
Baud rate 2400 ... 18382 bauds according to DIN 41652
No hardware hand shake and MIL-C-24308
RTS/CTS looped-through Internal thread
by a jumper
RTS configurable by a jumper Logical 0 or 1 UNC 4-40
Level logical 0 >+ 3 V
Level logical 1 <-3V
Continuation
Serial Interface RS 232 C
Overvoltage protection
Human body model ± 15 kV
Contact discharge ± 8 kV IEC 1000-4-2
Air gap discharge ± 15 kV IEC 1000-4-2
Analog Interface
Input (output current) Chinch jack
Scaling 0.3 V / A output current
Input resistance 10 kW
Output (current monitor) Chinch jack
Scaling 0.3 V / A output current
Output resistance 470 W
Temperature range
Ambient 0 ... + 45 °C
Storage - 20 ... + 80 °C
Weight 10 kg
Conformity
Security VDE 0100
VDE 0160
EN 50178
Surge voltage check IEC 50178
Partial discharge test IEC 664-1
Boost
Voltage 300 V ... 1800 V (via 66 W)
Charge 5 J ... 190 J
Resolution 4 bit 100 V / digit
Current static 10 mA
Charging time up to 1000 V 3s
Charging time up to 1800 V 10 s
Interfaces
Dielectric strength to PE 63 V DC
Serial Interface RS 232 C DEE CCITT V.28 9-pole pin plug connector
Baud rate 2400 ... 18382 baud according to DIN 41652
No hardware hand shake and MIL-C-24308
RTS/CTS looped through Internal thread
by a jumper
RTS configurable by a jumper Logical 0 or 1 UNC 4-40
Level logical 0 >+ 3 V
Level logical 1 <- 3 V
Continuation
Serial Interface RS 232 C
Overvoltage protection
Human body model ± 15 kV
Contact discharge ± 8 kV IEC 1000-4-2
Air gap discharge ± 15 kV IEC 1000-4-2
Analog Interface
Input (output current) Chinch jack
Scaling 0.3 V / A output current
Input resistance 10 kW
Output (current monitor) Chinch jack
Scaling 0.3 V / A output current
Output resistance 470 W
Temperature range
Ambient 0 ... + 45 °C
Storage - 20 ... + 80 °C
Weight 10 kg
Conformity
Security VDE 0100
VDE 0160
EN 50178
Surge voltage check IEC 50178
Partial discharge check IEC 664-1
Boost
Voltage 300 V ... 1800 V (via 66 W)
Charge 5 J ... 190 J
Resolution 4 bit 100 V / digit
Current static 10 mA
Charging time up to 1000 V 3s
Charging time up to 1800 V 10 s
Interfaces
Dielectric strength to PE 63 V DC
Serial Interface RS 232 C DEE CCITT V.28 9-pole pin plug connector
Baud rate 2400 ... 18382 bauds according to DIN 41652
No hardware hand shake and MIL-C-24308
RTS/CTS looped through Internal thread
by a jumper
RTS configurable by a jumper Logical 0 or 1 UNC 4-40
Level logical 0 >+ 3 V
Level logical 1 <-3V
Continuation
Serial Interface RS 232 C
Overvoltage protection
Human body model ± 15 kV
Contact discharge ± 8 kV IEC 1000-4-2
Air gap discharge ± 15 kV IEC 1000-4-2
Temperature range
Ambient 0 ... + 45 °C
Storage - 20 ... + 80 °C
Weight 10 kg
Conformity
Security VDE 0100
VDE 0160
EN 50178
Surge voltage check IEC 50178
Partial discharge check IEC 664-1
Boost
Voltage 300 V ... 1800 V (via 66 W)
Charge 5 J ... 190 J
Resolution 4 bit 100 V / digit
Current static 10 mA
Charging time up to 1000 V 3s
Charging time up to 1800 V 10 s
Interfaces
Dielectric strength to PE 63 V DC
Serial Interface RS 232 C DEE CCITT V.28 9-pole pin plug connector
Baud rate 2400 ... 18382 bauds according to DIN 41652
No hardware hand shake and MIL-C-24308
RTS/CTS looped through Internal thread
by a jumper
RTS configurable by a jumper Logical 0 or 1 UNC 4-40
Level logical 0 >+ 3 V
Level logical 1 <-3V
Continuation
Serial Interface RS 232 C
Overvoltage protection
Human body model ± 15 kV
Contact Discharge ± 8 kV IEC 1000-4-2
Air Gap Discharge ± 15 kV IEC 1000-4-2
Analog Interface
Input (output current) Chinch jack
Scaling 0.3 V / A output current
Input resistance 10 kW
Output (current monitor) Chinch jack
Scaling 0.3 V / A output current
Output resistance 470 W
Temperature range
Ambient 0 ... + 45 °C
Storage - 20 ... + 80 °C
Weight 10 kg
Conformity
Security VDE 0100
VDE 0160
EN 50178
Surge voltage check IEC 50178
Partial discharge check IEC 664-1
Connection elements
Parallel
(optional)
RS 232 C
Analog In
Analog Out
Current Output
Mains Connection
PE L1 L2 L3 - +
Coaxial Port
2-pole SMB coaxial female connector.
Parallel Port
25-pole pin plug connector according to DIN 41652 and MIL-C-24308, internal thread UNC 4-40.
RS 232 Port
9-pole pin plug connector according to DIN 41652 and MIL-C-24308, internal thread UNC 4-40.
Dimensions
Parallel (optional)
120
RS 232 C In Out
Analog
DIP switch
Cooling Surface
312
247
Dimensions
Analog
Out In RS 232 C
Parallel (optional)
227 112
20 6
20
20
M5 (4x) M5 (4x)
292
292
+ - L3 L2 L1 PE
Dimensions
Parallel
120
RS 232 C In Out
Analog
DIP switch
Cooling Surface
312
247
Dimensions
Analog
Out In RS 232 C
Parallel
227 112
20 6
20
20
M5 (4x) M5 (4x)
292
292
+ - L3 L2 L1 PE
Printed circuit board with LCD display for displaying the output current 10360245
Our address
Messtec Power Converter GmbH
Grube 41
D-82377 Penzberg
Telephone +49 (0) 8856/803060-0
Telefax +49 (0) 8856/9998
[email protected]
www.powerconverter.de