This document describes GE Fanuc's Genius Modular Redundancy (GMR) system for safety critical applications. The GMR uses triple modular redundancy with up to three Series 90-70 PLCs for fail-safe and fault-tolerant operation. It provides voting of I/O and logic across the redundant controllers and is scalable from simplex to triplex configurations. The GMR system is TUV certified according to relevant functional safety standards.

Uploaded by

4122aca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views34 pages

GMR Training Overview

This document describes GE Fanuc's Genius Modular Redundancy (GMR) system for safety critical applications. The GMR uses triple modular redundancy with up to three Series 90-70 PLCs for fail-safe and fault-tolerant operation. It provides voting of I/O and logic across the redundant controllers and is scalable from simplex to triplex configurations. The GMR system is TUV certified according to relevant functional safety standards.

Uploaded by

4122aca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

Series 90 -70 GE Fanuc Automation

Genius
Modular

Redundancy

Page 1
Series 90 -70 GE Fanuc Automation

GMR

• GENIUS Modular Redundancy


• Scaleable, Exclusive Elements:
• CPU
• LAN
• Input Subsystem
• Output Subsystem

Page 2
Series 90 -70 GE Fanuc Automation

GMR

• GENIUS Modular Redundancy


• GMR is GE Fanuc’s Scaleable, Modular Application of
Standard Products in Simplex, Duplex and Triplicated
(TMR) Configurations
• Safety Critical Applications
• System De-energised - F&G
• System Energised - ESD

• TUV Approved

Page 3
Series 90 -70 GE Fanuc Automation

GMR System
PLC A PLC B PLC C

Field
Device
Genius

Genius Genius

LOAD C
Genius

Genius Genius

D
Genius

Page 4
Series 90 -70 GE Fanuc Automation

GMR

• GENIUS I/O Diagnostics


• Market Requirements call for a Packaged,
PLC-Based ESD System that is Easy to
Apply
• Customers Demand Scaleable Costs for
Small or non-Critical Applications
• TUV Approved - Class 6

Page 5
Series 90 -70 GE Fanuc Automation

Certified

• Triplicated (2oo3) Fault Tolerant and Fail


Safe Controller System Certified
• TUV Approved - Class 6
• DIN V 19250 / DIN V VDE 0801 Standards
• Issued March 1995

Page 6
Series 90 -70 GE Fanuc Automation
Genius Field Bus I/O

P C G P C G
S P B S P B
U U C U U C

Genius

Inputs are Broadcast to all Devices


Page 7
Series 90 -70 GE Fanuc Automation
Genius Field Bus I/O

P C G
S P B
U U C

Genius
Genius

Outputs are Targeted to a Device


Page 8
Series 90 -70 GE Fanuc Automation
Genius Field Bus I/O

P C G P C G P C G
S P B S P B S P B
U U C U U C U U C

31 30 29

Genius

GMR Mode
Page 9
Series 90 -70 GE Fanuc Automation
Genius Field Bus I/O

P C G P C G P C G
S P B S P B S P B
U U C U U C U U C

31 30 29

Genius

GMR Mode
Page 10
Series 90 -70 GE Fanuc Automation
Genius Field Bus I/O

P C G P C G P C G
S P B S P B S P B
U U C U U C U U C

31 30 29

Genius

GMR Mode
Page 11
Series 90 -70 GE Fanuc Automation
Voting with 3 PLC’s Online

PLC A PLC B PLC C Duplex Output


Output Output Output Default State
0 0 0 X 0
0 0 1 X 0
0 1 0 X 0
0 1 1 X 1
1 0 0 X 0
1 0 1 X 1
1 1 0 X 1
1 1 1 X 1

Page 12
Series 90 -70 GE Fanuc Automation
Voting with 2 PLC’s Online

PLC A PLC B PLC C Duplex Output


Output Output Output Default State
0 0 1 0
0 0 1 0
0 1 1 1
0 1 1 1
1 0 1 1
1 0 1 1
1 1 1 1
1 1 1 1

Page 13
Series 90 -70 GE Fanuc Automation
Voting with 2 PLC’s Online

PLC A PLC B PLC C Duplex Output


Output Output Output Default State
0 0 0 0
0 0 0 0
0 1 0 0
0 1 0 0
1 0 0 0
1 0 0 0
1 1 0 1
1 1 0 1

Page 14
Series 90 -70 GE Fanuc Automation
Voting with 1 PLC Online

PLC A PLC B PLC C Duplex Output


Output Output Output Default State
0 X 0
0 X 0
0 X 0
0 X 0
1 X 1
1 X 1
1 X 1
1 X 1

Page 15
Series 90 -70 GE Fanuc Automation

Duplex System - 1oo2 to trip 1oo1d

PLC A PLC B

Field
Device
Genius Genius Genius

A LOAD B
Genius

SIL 2
TUV 6
Fail Safe

Page 16
Series 90 -70 GE Fanuc Automation

Duplex System - 2oo2 to trip

PLC A PLC B

Field
Device
Genius Genius

-ve Common

A LOAD
Pending
B
Genius

SIL 2
TUV 4
Genius

16 Point Fault Tolerant

Page 17
Series 90 -70 GE Fanuc Automation

Duplex System - 1oo2 / 2oo2 to trip 1oo2d


Quad Block Output
PLC A PLC B

Field
Device
Genius Genius Genius

SIL 3
TUV 6
LOAD C Fail Safe
Genius
Genius Genius

SIL 2
TUV 4
B D Fault Tolerant

Page 18
Series 90 -70 GE Fanuc Automation
GMR Dual Operation

• No Single Point of Failure


• Input Voting Options in each PLC
• Logic is performed Independently by each PLC
• Outputs Voted at O/P Blocks
• GENIUS I/O Embedded Diagnostics
• Scaleable System
• Fail Safe OR Fault Tolerant

Page 19
Series 90 -70 GE Fanuc Automation
Triplicated System 2oo3 to trip 1oo2d
PLC A PLC B PLC C

Field
Device
Genius

Genius Genius

LOAD C
Genius

Genius Genius

SIL 3
TUV 6
D
Genius

Fail Safe & Fault Tolerant

Page 20
Series 90 -70 GE Fanuc Automation

GMR - 2oo3 Load Operation

• Attributes of GMR 1oo2 / 2oo2


• Increased Integrity & Availability
• Capability for Entire System to be
Triplicated
• Fail Safe AND Fault Tolerant

Page 21
Series 90 -70 GE Fanuc Automation

GMR - Features

• Scaleable Redundancy Architecture


• Mechanical Isolation of System Components
• Input, Processor, Output
• Field Proven Series 90-70 PLC, Genius I/O
• Centralised
• Distributed
• High Levels of Integrity and Availability
• High Degree of Self Test and Monitoring
Page 22
Series 90 -70 GE Fanuc Automation
GMR Input Sub-system
PLC A PLC B PLC C

Field
Devices • Three Separate Input Blocks
Genius
• Separate Genius LAN for Each Block
Genius Genius

• All PLC’s Receive All Three Inputs


Genius
• Input Autotest
LOAD Function
• Initiated By Any PLC
Genius Genius

• Performed By Each Input Block


Genius

Page 23
Series 90 -70 GE Fanuc Automation

GMR Discrete Input Diagnostics


• Input Autotest
- Input to Input Short
Field
Devices - Stuck On Input
Genius
• Supervised Inputs
- Input Shorted High - Tri-State
• Input Discrepancy Checking
Genius

• Input Vote Adaptation


• Loss of Block
Genius

• Fault Table Entries


• App. Program Fault Contacts
Page 24
Series 90 -70 GE Fanuc Automation
GMR Analogue Input Diagnostics
• High and Low Alarm
• Underrange and Overrange
Field
Devices • Input Open Wire
-
V
+ Genius
• Input Shorted (RTD)
• Wiring Error (RTD)
• Internal Fault
- +
Genius

V
• Input Discrepancy Checking
• Input Vote Adaptation
Genius
• Loss of Block
-
V
+
• Fault Table Entries
• App. Program Fault Contacts
Page 25
Series 90 -70 GE Fanuc Automation

GMR System Overview


PLC A PLC B PLC C

• Three Separate PLC CPU’s


• Separate Genius
LOAD Bus LAN’s
Genius

• All PLC’s Receive And Transmit


Genius Genius

on all Three LAN’s


• Application Data Initialisation
Genius

(Auto Start-Up)
Page 26
Series 90 -70 GE Fanuc Automation
GMR PLC Sub-system Diagnostics
PLC A PLC B PLC C

• Embedded Power Up and Runtime Module Tests


• Extensive Comprehensive Memory testing
• Automatic Data Fault and System Fault Detection
• Shared / Distributed Autotest Responsibilities
• Automatic PLC and I/O Fault Tables
• Utilises Inter - PLC Communication Busses
Page 27
Series 90 -70 GE Fanuc Automation

GMR Logical Voting


OUTPUT ADDRESS
INPUT ADDRESS %Q
%I
SIMPLEX
VOTED INPUTS USER PHYSICAL
Single APPLICATION OUTPUTS
Inputs PLC TEST SIMPLEX
SINGLE INPUTS LOGIC TEST LOGIC 2oo3 VOTED
LOGIC
OUTPUT
SIMPLEX, DUAL
A or TRIPLE INPUTS “H” PATTERN
LOGICAL
SIMPLEX, DUAL OUTPUTS
B or TRIPLE INPUTS
“H” PATTERN
SIMPLEX, DUAL
Simplex, C or TRIPLE INPUTS
PHYSICAL
Dual or OUTPUTS
Triplicated
Inputs FAULT-
TOLERANT
INPUT VOTING 2oo3 VOTED
LOGIC OUTPUTS

Page 28
Series 90 -70 GE Fanuc Automation
GMR Output Sub-system
PLC A PLC B PLC C

• Standard ‘H’ Pattern


Genius

• Sink and Source Blocks Geniu


s
Geniu
s

• Each Block Receives Command from


LOAD
All Three PLC’s Genius

Geniu Geniu
s s

• 2oo3 Vote in the Output


Subsystem
• Discrepancies are Reported to Each
CPU
Page 29
Series 90 -70 GE Fanuc Automation
GMR Output Diagnostics
• Output Autotest
- Open Circuit Load - Load Shorted Low
- Open Circuit Output - Load Shorted High
- Stuck On Output - Output to Output Short
- Stuck Off Output

• Output Overload Genius Genius

• Output Overtemp C
A LOAD

• Output Discrepancy Checking Genius Genius

• Loss of Block
B D
• Fault Table Entries
• App. Program Fault Contacts
Page 30
Series 90 -70 GE Fanuc Automation

GMR - Input / Output Testing


• Automatic, Periodic
• Complete Continuity Checks - Sensor to Load
• Complete Output Fault Coverage and Isolation
• Bad Block
• Shorted or Open Load
• Wiring Faults
• Diagnostics Reported to Operator Interface
• Genius Hand Held Monitor
• Programming Terminal
• CIMPLICITY HMI
• DCS
Page 31
Series 90 -70 GE Fanuc Automation

GMR - The Solution

• Each Point Configurable - 1oo1, 1oo2, 2oo2, 2oo3


• All Voting and Diagnostics Transparent to User
• Inputs Broadcast and Voted at PLC, Outputs
Voted at Load
• Program Design as per Single PLC System
• Series 90-70 GMR CPU’s Provide Continuous
Internal Error Checking and External Discrepancy
Checking
• PLC Program Equivalence Checks

Page 32
Series 90 -70 GE Fanuc Automation

GMR - The Solution

• On-line Diagnostics Expose System Failures in I/O


and each PLC
• Diagnostics Automatically Reported Through
Built-in “Fault Table”
• On-Line Repair, Modular Replacement Philosophy
• Configurable Fault Degradation Path:
• 3 to 2 to SHUTDOWN (TUV)
• 3 to 2 to 1 to SHUTDOWN

Page 33
Series 90 -70 GE Fanuc Automation

GMR - Competitive Strengths

• Flexible
• Independent Manufacturer
• Scalability - Configurable Redundancy
• Fully Isolated CPU’s
• Distributed Intelligent I/O
• No Fuses
• Hand Held Monitor Reduces Installation and
Maintenance Periods

Page 34