Rectifier Module User Manual (UM1R481000), Revision K
Rectifier Module User Manual (UM1R481000), Revision K
Rectifier Module User Manual (UM1R481000), Revision K
DANGER! Warns of a hazard the reader will be exposed to that will likely result
in death or serious injury if not avoided. (ANSI, OSHA)
WARNING! Warns of a potential hazard the reader may be exposed to that could result in
death or serious injury if not avoided. This admonition is not used for situations that pose a
risk only to equipment, software, data, or service. (ANSI)
CAUTION! Warns of a potential hazard the reader may be exposed to that could
result in minor or moderate injury if not avoided. (ANSI, OSHA) This admonition is not
used for situations that pose a risk only to equipment, data, or service, even if such use
appears to be permitted in some of the applicable standards. (OSHA)
ALERT! Alerts the reader to an action that must be avoided in order to protect
equipment, software, data, or service. (ISO)
ALERT! Alerts the reader to an action that must be performed in order to prevent
equipment damage, software corruption, data loss, or service interruption. (ISO)
FIRE SAFETY! Informs the reader of fire safety information, reminders, precautions,
or policies, or of the locations of fire-fighting and fire-safety equipment. (ISO)
Voltages
AC Input Voltages
DANGER! This system operates from AC input voltage capable of producing fatal electrical shock.
Hazardous Voltage
DANGER! HAZARD OF ELECTRICAL SHOCK.
More than one disconnect may be required to de-energize the system before servicing.
Specifications
DC Output Ratings
• Voltage: Nominal -48.0 VDC, Positive Ground.
a) Adjustment Range: The output voltage can be set within the range of -42V to -58V, adjustable via
the controller.
• Output Power and Current:
a) R48-500 (1R48500): 500W (10.5A) @ -48 VDC. See Figure 1.
b) R48-1000 (1R481000): 1000W (20.9A) @ -48 VDC. See Figure 2.
• Power Derating Based on Input Voltage:
a) R48-500 (1R48500): The rectifier can provide maximum rated power (500W) as long as the input
voltage is within the range of 90 to 300 VAC. The relationship between the output power and input
voltage is illustrated in Figure 3.
b) R48-1000 (1R481000): The rectifier can provide maximum rated power (1000W) as long as the
input voltage is within the range of 176 to 300 VAC. From 176 VAC to 90 VAC, the rectifier will
continue to operate, but maximum power is reduced. The relationship between the output power
and input voltage is illustrated in Figure 4.
50
Output Voltage (V)
40
30
20
10
0
0 2 4 6 8 10 12
For R48-500 Output Current (A)
60
50
Output Voltage (V)
40
30
20
10
0
0 5 10 15 20 25
For R48-1000 Output Current (A)
120
100
% of output power
80
60
40
20
0
50 100 150 200 250 300 350
100
% of output power
80
60
40
20
0
0 50 100 150 200 250 300 350
For R48-1000 Input Voltage (Vac)
120
100
% of output power
80
60
40
20
0
-40 -20 0 20 40 60 80 100
100
% of output power
80
60
40
20
0
-40 -20 0 20 40 60 80 100
For R48-1000 Temperature (℃)
• Regulation:
a) Static: Steady state regulation is ±0.5% as controlled within the rectifier for any and all combinations
of load from no load to full load, input voltage, and input frequency at a constant ambient
temperature. The associated system controller may provide increased regulation.
b) Dynamic: For any step load change within the range of 10% to 90% of full load within 50
microseconds, per Telcordia GR-947-CORE, the maximum voltage transient will not exceed 5% of
the initial steady state voltage within 50±10 microseconds. Recovery to within 1% of the initial
steady state voltage does not exceed 4 milliseconds.
• Filtering:
a) Voice Band Noise: Complies with Telcordia GR-947-CORE.
1. Output noise according to Telcordia GR-947-CORE is <32 dBrnC at normal input and full load.
2. Psophometric noise is ≤1 mV at 5% to 100% of rated load.
b) Wide Band Noise: Complies with Telcordia GR-947-CORE.
1. Wideband noise emission is <250 mV peak to peak between 0 Hz – 30 MHz,
and <100 mV rms in any 3 kHz band 10 – 20 MHz.
AC Input Ratings
• Voltage: Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an operating range of 100
to 250 volts. Acceptable input frequency range is 45 to 65 Hz.
a) Permitted Variation: 85 to 300 VAC.
• Harmonic Content (THD): ≤5% from 50% to 100% of rated load. Meets EN61000-3-2.
• Inrush Current: Peak does not exceed 1.5 times of the peak value of the maximum steady-state input
current at full load, nominal input voltage, and for any duration of AC input interrupts. Under the above
conditions, standard AC distribution circuit breakers will not trip.
b) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the
shelf output terminals.
OPERATION
AC Input Protection Device Requirements/Recommendations
Refer to the system documentation supplied with the system the rectifier is installed in.
Local Indicators
Location and Identification: Refer to Figure 7.
Description: There are three (3) indicators located on the rectifier’s front panel. The functions of these
indicators are as shown in Table 2.
Power Indicator
(Green)
Protection Indicator
(Yellow)
Alarm Indicator
(Red)
Installing Rectifiers
The rectifier is hot swappable. It can be installed with the system operating.
WARNING! To prevent damage to the latching mechanism, ensure the handle is in the open position
when installing or removing a module. NEVER hold the handle in the closed position when installing a
module into a shelf.
Procedure
1. Place the rectifier into an unoccupied mounting slot without sliding it in completely.
2. Loosen the captive fastener securing the top of the latch mechanism to the front of the rectifier. Pull
the top of the latch mechanism away from the rectifier (this will retract the latch mechanism located on
the underside of the rectifier). Refer to Figure 8 for latch mechanism illustration.
3. Push the rectifier completely into the shelf.
4. Push the top of the latch mechanism into the front panel of the rectifier, and secure by tightening the
captive fastener. This locks the rectifier securely to the shelf.
Captive Fastener
Latch Mechanism
Fan Connector
Rectifier Module
Front Cover