G-030 - GSD 8 Trio

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

BITZER Scroll - VFD

General Guidelines VFD w/Original piping (GSD8)


/ All compressor must operate at the same speed
/ Inverter sized to control all compressors
 1.1*(MOA Comp1 + MOA Comp2)

/ Operating limits must be maintained


/ “Last on, first off” restriction
/ If inverter is sized for one compressor:
 VFD compressor speed can only vary with compressor #2 off

 Both compressor on, they must operate at 60Hz