NCD (Nox Control Diagnostic System) Inducement Fault Group Summary & Repeat Offense
NCD (Nox Control Diagnostic System) Inducement Fault Group Summary & Repeat Offense
Revision v.1.68
PAGE 27 / 934
8. NCD (NOx Control Diagnostic system) inducement fault group summary &
Repeat offense
The NCD(NOx Control Diagnostic system) inducement fault group is below one. Fault codes can be
added or deleted depending on the fault strategy during development.
"EGR Block" group 24 faults were added (with EGR system only), Not used for No EGR system
DEF
EGR Dosing DEF
Engine consumption Tampering
Emission block interrupt quality
system (Group3 (Group5)
(Group1) (Group2) (Group4)
- Not Used)
1 2 4 5
No. EGR block Dosing interrupt DEF quality Tampering
SPN FMI P-code SPN FMI P-code SPN FMI P-code SPN FMI P-code
1 27 0 P042E 3031 14 P205E 3516 0 P106D 1761 19 P1230
2 27 1 P042F 3216 4 P2397 3516 1 P106C 3216 18 P225D
3 27 3 P0406 3226 4 P2398 3219 7 U030D
4 27 4 P0407 3360 14 P263D 3224 5 P2203
5 27 20 P0C17 3361 3 P2047 3224 6 P2202
6 27 22 P0C18 3361 4 P2048 3229 7 U030E
7 27 23 P0C19 3361 13 P202E 3234 5 P2216
8 102 3 P0108 3361 22 P2050 3234 6 P2215
9 102 4 P0107 3361 23 P2051 3242 3 P2033
10 105 3 P00AD 3363 3 P20B4 3242 4 P2032
11 105 4 P00AC 3363 4 P20B3 3242 11 P2034
12 110 3 P0118 3363 7 P30B1 3251 3 P2455
13 110 4 P0117 4335 7 P202D 3251 4 P2454
14 132 3 P0103 4374 3 P208D 3251 18 P1454
15 132 4 P0102 4374 4 P208C 3361 5 P2049
16 132 19 P0100 4374 7 P208B 3361 14 P2C11
17 132 21 P00BE 4374 8 P108A 3361 27 P208E
18 2789 3 P0546 4374 9 P108B 3363 5 P20B1
19 2789 4 P0545 4374 12 P108C 3520 3 U1028
20 2791 3 P2145 5491 3 P20C0 3520 4 U1030
The repeat offense of NCD(NOx Control Diagnostic system) inducement is different dependent on
Emission regulation. Refer to the below example case for better understanding.
* EU Stage5
If DEF quality or Dosing Interrupt faults are confirmed up to warning/Level1, and faults are occurred
again within 40 hours, the fault counter is setting to last value when repeat offense is enabled.
Graph 8-1. EU Stage5 DEF quality or Dosing interrupt Repeat offense at Warning/Level
If DEF quality or Dosing Interrupt faults are confirmed up to Severe level, and faults are occurred
again within 40 hours, the fault counter is changed before 90%(18hrs) of counter value of Severe
level. It means that the fault level is changed to Level1 and Severe level will be reached within 2hrs.
Graph 8-2. EU Stage5 DEF quality or Dosing interrupt Repeat offense at Severe Level
The repeat offense of Impeded EGR or Tampering faults are only differed the NCD inducement
counter(time), and the operation is same to DEF quality or Dosing interrupt fault
If Impeded EGR or Tampering faults are confirmed up to warning/Level1, and faults are occurred
again within 40 hours, the fault counter is setting to last value when repeat offense is enabled.
If Impeded EGR or Tampering faults are confirmed up to Severe level, and faults are occurred again
within 40 hours, the fault counter is changed before 95%(95hrs) of counter value of Severe level. It
means that the fault level is changed to Level1 and Severe level will be reached within 5hrs.
Graph 8-4. EU Stage5 Impeded EGR or Tampering Repeat offense at Severe level
* US Tier4Final
If any NCD inducement faults are confirmed and occurred again within 40 hours, fault level is
changed to Level2 and Final inducement level will be reached within 25min.