VRF 2020

Mitsubishi Heavy Industries Thermal Systems VRF inverter multi-system Air-Conditioners provide high performance heating and cooling for human use. The document outlines several precautions for installation and use, including ensuring proper installation to prevent leaks and fires. It also notes that performance may be reduced in very cold temperatures or if the unit is not properly maintained over time. Servicing by a specialist is recommended to maintain optimal operation.

Uploaded by

Dang Vu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
242 views116 pages

VRF 2020

Mitsubishi Heavy Industries Thermal Systems VRF inverter multi-system Air-Conditioners provide high performance heating and cooling for human use. The document outlines several precautions for installation and use, including ensuring proper installation to prevent leaks and fires. It also notes that performance may be reduced in very cold temperatures or if the unit is not properly maintained over time. Servicing by a specialist is recommended to maintain optimal operation.

Uploaded by

Dang Vu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 116

Mitsubishi Heavy Industries Thermal Systems VRF inverter multi-system Air-Conditioners

Before starting use


Heating performance Refrigerant leakage

VRF inverter multi-system


The heating performance values (kW) described in the catalogue are the The refrigerant (R410A) used for Air conditioner is non-toxic and in its
values obtained by operating at an outdoor temperature of 7 C and indoor original state.
temperature of 20 C as set forth in the ISO Standards. As the heating However, in consideration of a state where the refrigerant leaks into the
performance decreases the outdoor temperature drops, if the outdoor room, measures against refrigerant leaks must be taken in small rooms
temperature is too low and the heating performance is insufficient, use where the tolerable level could be exceeded. Take measures by installing

Air-Conditioners
other heating appliances as well. ventilation devices, etc.

Indication of sound values Use in snowy areas


The sound values are the values (A scale) measured in a chamber such as Take the following measures when installing the outdoor unit in snowy
an anechoic chamber following the ISO Standards. In the actual installation areas.
state, the value is normally larger than the values given in the catalogue
due to the effect of surrounding noise and echo. Take this into ·Snow prevention
consideration when installing. Install a snow-prevention hood so that the snow does not obstruct the air
intake port or enter and freeze in the outdoor unit.
Use in oil atmosphere
Avoid installing this unit in an atmosphere where oil scatters or builds up, ·Snow piling
such as in a kitchen or machine factory. In areas with heavy snow fall, the piled snow could block the air intake
If the oil adheres to the heat exchanger, the heat exchanging performance port. In this case, a frame that is 50cm or higher than the estimated
will drop, mist may be generated, and the synthetic resin parts may deform snow fall must be installed underneath the outdoor unit.
and break.
Automatic defrosting device
Use in acidic or alkaline atmosphere
High Performance
If the temperature is low, and the humidity is high, frost will stick to the
If this unit is used in acidic atmosphere such as hot spring areas having heat exchanger of the outdoor unit. If use is continued, the heating
high level of sulfuric gases or in alkaline atmosphere including ammonia or performance will drop.
calcium chloride, places where the exhaust of the heat exchanger is sucked The "Automatic defrosting device" will function to remove this frost.
in, or at coastal areas where the unit is subject to salt breezes, the outer
plate or heat exchanger, etc., will corrode. Please ask a dealer or specialist
when you use an air conditioner in places differing from a general
After heating for approx, three to ten minutes, it will stop, and the frost
will be removed. After defrosting, hot air will be blown again. Air-Conditioning

2020
atmosphere. Servicing the air-conditioner
After the air-conditioner is used for several seasons, dirt will build up in
Use in places with high ceilings the air-conditioner causing the performance to drop. In addition to
If the ceiling is high, install a circulator to improve the heat and air flow regular servicing, a maintenance contract by a specialist is
distribution when heating. recommended.

Safety Precautions
Air-conditioner usage target Installation
The air-conditioner described in this catalogue is a dedicated cooling/ Always commission the installation to a dealer or specialist. Improper
heating device for human use. installation will lead to water leakage, electric shocks and fires.
Do not use it for special applications such as the storage of food items, Make sure that the outdoor unit is stable in installation. Fix the unit to
animals or plants, precision devices or valuable art, etc. stable base.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current Usage place
leaks could occur. Do not install in places where combustible gas could leak or where there
are sparks.
Before use Installation in a place where combustible gas could be generated, flow or
Always read the "User’s Manual" thoroughly before starting use. accumulate, or places containing carbon fibers could lead to fires.

Mitsubishi Heavy Industries Thermal Systems, Ltd. 2-3 Marunouchi 3-chome, Chiyoda-ku, Tokyo 100-8332, Japan
( Wholly-owned subsidiary of MITSUBISHI HEAVY INDUSTRIES, LTD.) https://www.mhi-mth.co.jp/en/

Our factories are ISO9001 and ISO14001 certified.


Certified ISO 9001 Certified ISO 14001

ISO 9001 ISO 14001


Certificate:44 100 980813 Certificate:04 104 980813

Certificate Number : JQA-0709 Certificate Number : 4333-2007-AQ-RGC-RvA Certificate Number : YKA4005636 Certificate number : 02117E10160R0M

20KX02E December 2019 F Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. 50Hz
Edited in Japan 20KX02E
ASIA
High Performance
Air-Conditioning
2020

The Mitsubishi Heavy Industries Thermal Systems


KXZ VRF series delivers high performance in cooling and
heating for all commercial applications.
It offers the highest level of design flexibility, improved
efficiency as well as enhanced operational functions.

2
Line Up R410A

model KXZ Lite

RC-EX3A
Simple use with advanced setting Remote control

Contents
Introduction 4~29
Outdoor units 30~65
Micro model 30~33
KXZ Lite 34 . 35

KXZ Standard series 36~43

KXZ Hi-COP series 44~47

Corrosion Protection Treatment series 48~53

Water cooled series 54 . 55

High head series 56~59

Refresh series 60 . 61

Indoor units 66~105

EEV-KIT 1 06 . 107

Control systems 1 08~117

3
R410A

KXZ system is the best air conditioning solution for


"Sophisticated" buildings
KX VRF series delivers high cooling/heating performance for all commercial applications.

・High energy efficiency with advanced technology


High Efficiency & ・Energy saving control by VTCC (Variable Temperature &
Comfort Capacity Control)
・Individual, centralized and customized comfort control

・Long piping length and wide limitation of piping


Design Flexibility ・Various indoor units to each application
・Easy selection and design software

・Individual advanced control by wired and


Easy & wireless remote controller
Customized Control ・Various options for BMS & Centralized controller

・Easy access for maintenance


Good Serviceability ・Engineering and monitoring tool available

"Micro series" for small offices,


shops and residential applications
Industry leading compact design, energy efficiency, and high reliability from our high technology

4
Specific cases of VRF system installation from
Mitsubishi Heavy Industries Thermal Systems

Case study: Hotel and Leisure


VRF heat recovery systems
from Mitsubishi Heavy
Industries Thermal Systems
KX range are part of the
exacting specification for
luxury hotels and airport-style
bus station. Mitsubishi Heavy
Industries Thermal Systems
VRF systems feature
advanced inverter technology
which adjusts compressor
output to match the cooling or
heating demands of the indoor
units to save energy and
eliminate temperature
fluctuations. Simultaneous
heating or cooling can be
provided in different areas as
required, with heat gain in
sunnier, south facing rooms
providing useful energy for
rooms on the cooler, shadier
side of the buildings.

Case study: Education


A VRF system with inverter control from Mitsubishi Heavy
Industries Thermal Systems is helping to make Crossways
Academy in Lewisham a cool place to learn for 500 students.
Comfortable temperatures need to be maintained as
economically as possible in rooms where large numbers of
students will enter or leave at the same time. IT equipment
being switched on and off and the use of electric blinds to
control glare will all contribute to substantial fluctuations in
heat load. A VRF KX system from Mitsubishi Heavy Industries
Thermal Systems provides an ideal solution. Much of the
building was designed to rely on natural ventilation, with
windows operated electronically. The air conditioning system is
linked to this control system to close down when windows are
opened. Mitsubishi Heavy Industries Thermal Systems KX is
particularly appropriate for many such retrofit applications.

5
R410A

The KXZ product lineup has been extended to offer solutions delivering up to 60 horsepower (60HP) when using a combination
of 3 outdoor units. Furthermore with the addition of the Hi-COP series, installation options have been greatly increased.

Previous Model KXZE1

Up to 48HP Up to 60HP

KXZXE1 (Hi-COP)

8-36HP

By combining 3 outdoor units 60HP can be achieved

Heat pump systems


The heat pump systems operate with 2 inter-connecting pipes,
thus commonly referred to as a '2-pipe system'.

These systems provide either a heating or cooling operation to


all indoor units and are suitable for a wide range of applications
from an individual apartment to an entire multi storey building,
especially where there are significant open plan areas to be
controlled.
The range starts with a 11.2kW cooling capacity, up to 20HP
with 56.0kW cooling capacity. Outdoor units can also be
“twinned” or “tripled” providing up to 60HP/168.0kW on a
single system.

The range has a total piping length of 1000m (KXZ)


and the furthest indoor unit can be connected up to
160m (KXZ) from the outdoor unit.

Capacity Range
Capacity 4HP 5HP 6HP 8HP 10HP 12HP 14HP 16HP 17HP 18HP 20HP
Model Code : kW 11.2 14 15.5 22.4 28 33.5 40.0 45.0 47.5 50.0 56.0
BTU / h 38,200 47,800 52,900 76,400 95,500 114,300 136,500 153,500 162,100 170,600 191,100
Capacity 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
Model Code : kW 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0
BTU / h 209,800 228,600 250,800 273,000 290,000 307,100 324,100 341,200 361,700 382,100
Capacity 42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
Model Code : kW 120.0 125.0 130.0 135.0 142.5 145.0 150.0 156.0 162.0 168.0
BTU / h 409,400 426,500 443,600 460,600 486,200 494,700 511,800 532,200 552,700 573,200

6
Product Line Up
<Outdoor units>
model
11.2kW 14.0kW 15.5kW
4HP 5HP 6HP
FDC112KXEN6 FDC140KXEN6 FDC155KXEN6
FDC112KXES6 FDC140KXES6 FDC155KXES6

KXZ Lite
22.4kW 28.0kW 33.5kW 22.4kW 28.0kW
8HP 10HP 12HP 8HP 10HP
FDC224KXE6G FDC280KXE6G FDC335KXE6G FDC224KXZPE1 FDC280KXZPE1

Standard model KXZE1


28.0kW 33.5kW 40.0kW 45.0kW 47.5kW 50.0kW 56.0kW
10HP 12HP 14HP 16HP 17HP 18HP 20HP
FDC280KXZE1 FDC335KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1

FDC280,335 FDC400~560

61.5kW 67.0kW 73.5kW 80.0kW 85.0kW 90.0kW 95.0kW 100.0kW 106.0kW 112.0kW
22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
FDC615KXZE1 FDC670KXZE1 FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1
FDC280KXZE1 FDC335KXZE1 FDC335KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1
FDC615,670 FDC335KXZE1 FDC335KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1

FDC735 FDC800~1120

120.0kW 125.0kW 130.5kW 135.0kW 142.5kW 145.0kW 150.0kW 156.0kW 162.0kW 168.0kW
42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1
FDC400KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1
FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1
FDC1200~1680 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1 FDC560KXZE1

Hi-COP model KXZXE1


22.4kW 28.0kW 33.5kW
8HP 10HP 12HP
FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1

FDC224 FDC280,335 45.0kW 50.0kW 56.0kW 61.5kW 67.0kW


16HP 18HP 20HP 22HP 24HP
FDC450KXZXE1 FDC500KXZXE1 FDC560KXZXE1 FDC615KXZXE1 FDC670KXZXE1
FDC224KXZXE1 FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1
FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1

FDC450 FDC500 FDC560~670 73.5kW 80.0kW 85.0kW 90.0kW 95.0kW 100.0kW


26HP 28HP 30HP 32HP 34HP 36HP
FDC735KXZXE1 FDC800KXZXE1 FDC850KXZXE1 FDC900KXZXE1 FDC950KXZXE1 FDC1000KXZXE1
FDC224KXZXE1 FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1
FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1
FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1 FDC335KXZXE1
FDC735 FDC800 FDC850~1000

7
R410A

<Indoor units> A range of 17 types of exposed or concealed indoor units available in a wide range of capacities (total 93 indoor models).
The best solution of indoor units for all applications is available from our full lineup.
1.5kW 2.2kW 2.8kW 3.6kW
<0.5HP> <0.8HP> <1HP> <1.25HP>
model (4~6HP)

model (8~12HP)

KXZ Lite
Standard model KXZE1

Hi-COP model KXZXE1

4way FDT FDT28KXZE1 FDT36KXZE1

4way FDTC FDTC15KXZE1 FDTC22KXZE1 FDTC28KXZE1 FDTC36KXZE1


Compact NEW

Ceiling
2way FDTW FDTW28KXE6F
Cassette
1way FDTS

1way Compact FDTQ FDTQ22KXE6F FDTQ28KXE6F FDTQ36KXE6F

High FDU
Static Pressure
Low/Middle FDUM FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F
Duct Static Pressure
Connected Low Static
Pressure(thin) FDUT FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E

Compact & FDUH FDUH22KXE6F FDUH28KXE6F FDUH36KXE6F


Flexible
Wall Mounted FDK FDK15KXZE1 FDK22KXZE1 FDK28KXZE1 FDK36KXZE1

Ceiling Suspended FDE FDE36KXZE1

2way FDFW FDFW28KXE6F

Floor
With Casing FDFL
Standing
Without Casing FDFU FDFU28KXE6F

OA Processing unit FDU-F • FDU-F series are not connectable to Micro model (4~6HP), KXZ

Air flow m3/h 150 250 350 500


Fresh Air Ventilation and SAF SAF150E7 SAF250E7 SAF350E7 SAF500E7
Heat Exchange unit
Fresh Air Assembly SAF-DX SAF-DX250E6 SAF-DX350E6 SAF-DX500E6

8
4.5kW 5.6kW 7.1kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW
<1.6HP> <2HP> <2.5HP> <3.2HP> <4HP> <5HP> <6HP> <8HP> <10HP>

FDT45KXZE1 FDT56KXZE1 FDT71KXZE1 FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1

FDTC45KXZE1 FDTC56KXZE1

FDTW45KXE6F FDTW56KXE6F FDTW71KXE6F FDTW90KXE6F FDTW112KXE6F FDTW140KXE6F

FDTS45KXE6F FDTS71KXE6F

FDU45KXE6F FDU56KXE6F FDU71KXE6F FDU90KXE6F FDU112KXE6F FDU140KXE6F FDU160KXE6F FDU224KXZE1 FDU280KXZE1

FDUM45KXE6F FDUM56KXE6F FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6F

FDUT45KXE6F-E FDUT56KXE6F-E FDUT71KXE6F-E

FDK45KXZE1 FDK56KXZE1 FDK71KXZE1 FDK90KXZE1

FDE45KXZE1 FDE56KXZE1 FDE71KXZE1 FDE112KXZE1 FDE140KXZE1

FDFW45KXE6F FDFW56KXE6F

FDFL71KXE6F

FDFU45KXE6F FDFU56KXE6F FDFU71KXE6F

Lite. FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1

800 1000

SAF800E7 SAF1000E7

SAF-DX800E6 SAF-DX1000E6

9
R410A

1. High Efficiency & Comfort


Improved Efficiency
The below graphs highlight the improved efficiencies between the previous
models compared to the KXZ standard and Hi-COP models.
Previous model
KXZ Standard
Comparison of EER in Cooling Mode Hi-COP
EER
4.70
4.50
4.30
4.10
3.90
3.70
3.50
3.30
3.10
2.90
2.70
2.50
224 280 335 400 450 475 500 560 615 670 735 800 850 900 950 1000 1060 1120 1200 1250 1300 1350 1425 1450 1500 1560 1620 1680

MODEL

Comparison of COP in Heating Mode


COP
4.70

4.50

4.30

4.10

3.90

3.70

3.50
224 280 335 400 450 475 500 560 615 670 735 800 850 900 950 1000 1060 1120 1200 1250 1300 1350 1425 1450 1500 1560 1620 1680

MODEL

High efficiency and compact design are achieved by


applying advanced components

10~60HP

DC Fan Motor

Tetrahedral structure of Efficient Heat Exchanger


Heat Exchanger

Double tube

New Inverter Control Improved Scroll Compressor

10
Variable Temperature and Capacity Control

• The VTCC is a newly developed energy saving function

34%
designed by Mitsubishi Heavy Industries Thermal Systems.
• A new feature to all our KXZ ranges which provides
up to 34%* energy savings in both cooling and
heating mode.
• VTCC is a function specifically designed to maximise ENERGY SAVINGS*
energy savings in partial load conditions throughout
all seasons.

*34% energy savings are based on comparison with a KXZ standard model with
VTCC vs. a KXZ standard model both under partial load condition.

Normal operation (in the cooling mode) Energy saving operation (in the cooling mode)
Room temperature Room temperature
Check temp erature difference

Set temperature Set temperature

Compressor
Compressor

Off Off Off Target low pressure


Target low pressure
Constant level

VTCC adjusts the target pressure of the refrigerant cycle in the For example, in partial load conditions where you have low cooling
outdoor unit automatically according to the demand of the indoor and heating requirements, VTCC reduces the compressor frequency
units in partial load conditions. and controls the actuators in the outdoor unit.
These smooth adjustments ensure an optimal capacity usage of the Overall with the VTCC functionality you will always have an
indoor units as well as maximised energy savings. Ultimately this additional energy saving of up to 34% (depending on configuration
also increases comfort for the user. and usage of system) in low cooling and heating load requirements.

Multiport compressor that achieves high efficiency


The new multiport discharge area in the compressor has optimized pressure control with better balancing.
The performance improvement at medium Hz has resulted in higher annual efficiencies.

Multi-discharge port

By optimizing pressure
adjustment in decompression,
the compressor realizes higher
efficiency.

Discharge port

11
R410A

Concentrated winding motor achieves "High Output" and


"Total Efficiency Improvement" Total Efficiency
New Concentrated *

Output
The newly designed high performance CPU
Winding Motor
enables high precision optimization for
compressor speed, which leads to concentrated
winding motor use.
Our product achieves high output and better
energy saving effects and Conventional Distributed
in particular improves seasonal efficiency rating. Winding Motor

Improved Seasonal
Efficiency rating
Compressor Speed
* Applied for KXZE1:10/12/17/18/20HP, KXZXE1:8HP & KXZ Lite:8/10HP

Improved Heat-exchanger [Previous] [KXZ]


With piping layout rearranged from header to
heat exchanger, refrigerant distribution flow
has improved and maximum energy efficiency
has been achieved. Heat exchanger has Heat- Heat-
improved refrigerant distribution and Exchanger Exchanger
increased effectiveness.
Furthermore due to expansion of effective
heat transfer area in heat exchanger, energy
Header Distributor
efficiency has increased.

Strengthened resistance against frost


Resistance against frost has been strengthened by achieving improved heat-exchanger.

Vector control Vector Control


New applied Vector control has a high efficiency and many new
Power current

advanced features.
• Smooth operation from low speed to high speed
• Smooth Sine Voltage Wave form are attained
• Energy efficiency is further improved in low speed range

Operation period

DC Fan Motor
Long-chorded 3 propeller fan with serration Adoption of DC fan motor has enabled to realize an excellent
Fan blade design adapted from Mitsubishi Heavy Industries efficiency of approximate 60% higher than previous models.
aerospace division - with serrated edges that deliver increased
air volume with less power input. Rotor(Squirrel Cage made of conductor)
Stator (coil) Rotor(made of permanent magnet)

Serration Stator (coil)

12
Oil level control capability
Our proprietary technology of odjusts the oil level when combining
two or three outdoor units achieving level operation rate, keeping
performance of the units and ensuring long life of the system.

Oil-equalizing pipe

Capacity control (KXZ)


Capacity control can be set by peak cut function with RC-EX3A for better energy saving.
Five-step capacity control is available. (100-80-60-40-0%)

(kW)
PEAK CUT

AM PM
8 9 10 11 12 13 14 15 16 17 18 19

4~6HP (Micro)
Compact High Efficient Compact high efficiency Heat
Inverter Control
Heat Exchanger
Vector Inverter Control system Exchanger
• Optimizing relationship of the air flow velocity &
Twin Rotary fin pattern
Compressor • Improvement of air distribution Maximizing
efficiency of heat exchanger

Heat Exchanger

DC Fan Motor
Compact & High efficiency

Optimum Refrigerant System Control


Previous Micro

8~12HP (Micro)

DC Fan motor
Compact & High efficiency

Inverter Control
Compact & Vector Inverter Control system

Downsized accumulator

Receiver in fan section

3D-Scroll Compressor(12HP)

Previous Micro

13
R410A

2. Design Flexibility
Indoor unit capacity connection HP Capacity connection

Micro model 4~12 150%


KXZ Lite 8 . 10 120%

Standard KXZ 10~60 130%

KXZ

130% capacity connection


Connectable indoor units
HP 4 5 6 8 10 12 HP 8 10
Micro model KXZ Lite
Numbers 6 8 8 22 24 24 Numbers 8 8

HP 10 12 14 16 17 18 20 22 24 26 28 30 32 34
Numbers 24 29 34 39 41 43 48 53 58 63 69 73 78 80
Standard KXZ
HP 36 38 40 42 44 46 48 50 52 54 56 58 60
Numbers 80 80 80 80 80 80 80 80 80 80 80 80 80

Wide Range of Operation (KXZ, KXZ Lite)


KXZ series permits an extensible
Heating
system design considering a heating
-20ºC KXZ, KXZ Lite +15.5ºC
range operation down to -20˚C and a
cooling range operation up to 46˚C
(previous model : 43˚C) Cooling
Furthermore KXZ Lite extends a cooling -15ºC KXZ +46ºC
range operation up to 50˚C.
-15ºC KXZ Lite +50ºC

-20 -10 0 10 20 30 40 50

Control Systems
All series offer wide choice of control system and provide the best solution.

[Control system units with SUPERLINK- ]


Classification Type Model Connectable Indoor units Electric power
(Maximum) calculation
RC-E5 16
Individual controller Wired RC-EX3A 16
Wireless RCN-T-5AW-E2 etc. 16
SC-SL1N-E 16
Push buttons SC-SL2NA-E 64
SC-SL4-AE 128
Touch screen
Center Console SC-SL4-BE 128
Web gateway SC-WBGW256
BMS interface & BACnet 256(128x2)
units Lonworks SC-LGWNB 96(48x2)

14
Long Pipe Length 10~60HP(KXZ)
Piping length has extended max height difference between indoor units up to 18m and enables us to put indoor units on extra three floors.
The furthest indoor unit: 160m or total length: 1000m contributes to system design flexibility.

Max: 10m (oil equalizing pipe)

Total length: Outdoor unit Max: 0.4m


1000m
Height difference *2
Max: 5m 50m(outdoor unit above) 70m
To the
Indoor unit 40m(outdoor unit below)
first branch:
max 130m
Max height
Indoor unit difference
between
indoor units:
18m
*1 The difference between the longest and the
Indoor unit shortest indoor unit piping from the first
From the first branch
branch must be within 40m. (MAX85m)
to the furthest
indoor unit: 90m *
1
Furthest
indoor unit: *2 In case of height difference up to 70m, please
contact your dealer.
160m Height difference up to 100m is possible with
High Head series. Please refer to page 56.

Easy Transportation & Installation


Due to realization of significant reduction in size and foot print which is one of
the smallest in the industry, transportation in an elevator made for six persons
(Width:1400mm, Depth:850, Open area:800mm) is possible, eliminating cost
of a crane and reducing labor.

1,400

Transportation in an
8~12HP (Micro) elevator made for six
persons
H1,675 x W1,080 x D480
850

Easy
transportation

800

KXZ is portable and the uniform reduced footprint allows neat,


continuous installation.

1350mm
1350mm
1350mm

Blue Fin
Due to application of blue coated fins for the heat
exchanger of new outdoor unit, corrosion resistance
Blue
Fin
has been improved compared to previous models.

15
R410A

Automatic Select functions for capacity control (KXZ Lite)


The following 3 items are available for capacity control function. User can select one item individually or select 2or3 items at the same time.
In case of selecting 2or3 items, the unit will operate with the most effective function automatically.

• Compressor speed control


User can set compressor speed at 100%-80%-60%-40% before starting operation
with PWB in the outdoor unit or with a demand controller (procured locally).

• Capacity control timer


User can set capacity control with RC-EX3A up to 4 times per day maximum.
The timer setting can be changed using 5 minute intervals. Please refer to page 13.
• Silent mode
Considering noise regulations or surrounding circumstances, you can now select 4 levels of silent mode.
Setting the combination of silent mode is available by using timer function of RC-EX3A.

Priority operation mode rule


User can select the following priority operation mode. (for whole system)
1. First unit’s operation mode (by default setting) 3. Majority operation mode (see below)
2. Last unit’s operation mode 4. Master operation mode (see below)

<Majority operation mode> <Master operation mode>


The system is operated according to the mode selected by the The system is operated according to master operation mode.
majority of units in operation (whichever greater capacity When master operation mode is set at cooling mode, units
between the sums of cooling mode and heating mode). selected as heating mode is set to fan mode automatically.
The operation mode in minority is set to fan mode automatically.
Operation mode : Master setting :
Cooling Operation mode :
Cooling
Heating
45
Operation mode :
Heating 56 45

56 56
71 56
71

28
28

Operation mode Operation mode


cooling capacity heating capacity
45 + 45 + 56 + 56 + 56 + 56 71 + 71 + 28 + 28
Total Operation mode :
Total 198
314 Cooling Master setting :
Cooling

Operation mode : Operation mode :


FAN FAN

Fixed Cooling mode/fixed heating mode (summer/winter switch)


It is possible to fix the operational mode of the system (either cooling or heating) using a switch (SW3-7) on the outdoor unit PC board - this enables
the building user to decide the operation of the system (e.g. cooling only in summer/heating only in winter), to avoid unnecessary energy wastage.
It is also possible to wire the control switch to a remote location (inside the building) to a control room, or even linked to an ambient thermostat.

16
3. Serviceability
Easy Service Check Operation (10~60HP)
Quick and easy access to service parts by separation of Closing of Service valve, crossing connection of refrigerant
compartments. piping and electrical wiring, proper operation of EEV (Electrical
Expansion Valve) can be checked automatically in cooling
operation. This check operation can be done at 0~43ºC outdoor
temperature and 10~32ºC indoor temperature by use of
outdoor unit dip switch. The check should be done in one
refrigerant system. It takes 15~30 minutes and avoids frequent
failure by preventing careless mistakes during installation.
Blower dip switch
compartment

Mechanical
compartment

Monitoring Function
All series include features to assist with servicing and troubleshooting.
Various data can be monitored through 3-digit or 6-digit display on the outdoor unit PCB.

Detailed fault diagnosis and operation history memory via Equipped with RS232C
7-segment display. for connection directly to
your PC monitoring and
service tasks made
simple with our service
software (“Mente PC”).
All series

4~6HP 8~60HP
8 . 10HP(KXZ Lite)
Automatically produced test-run report Operation data storage during servicing
6

Operation data storage when a fault occurs

SL Checker 3 Layer Construction


Remote Control can be operated function from setting Superlink Thanks to control box structure with 3 layer/2 layer construction
checker. using hinge connection, service and maintenance has been made
much easier for inverter
components.

Indoor unit

Outdoor unit

USB
Superlink Line SL checker KXZ (3 layer) KXZ Lite (2 layer)
monitor interface SL checker

17
R410A

Back-up Operation
In the event that one unit has a failure, the system will keep operating In the event that one compressor has a failure, the unit will keep
with the other good units. operating with the other good compressor.
Combination of two or three outdoor units KXZ : 18 & 20HP

Keeping Compressor
operation failed

Inverter

Unit failed This operation is an emergency measure for a limited time and
a necessary repair should be done as soon as possible.

Improved features (KXZ Lite)

Improved freedom of piping layout Wire insertion holes for fall prevention External static pressure

Front 4 Rear
1 2 Right

3
Down
current
KXZ Lite External static pressure is
available up to 35 Pa.
135mm

90mm

50mm 90mm

Hole size becomes 120% bigger.

Four handles A transparent rain cover Fixing screws to service panel

2
4 1
2 1
3
5
2

Located at the same level for easy Attached as a standard for easy Decreasing number of screws from 5 to 2,
transport and transfer. maintenance. installation & service speed is improved.

18
Easy Selection Tool e-solution

e-solution is a design software tool which includes specification details of the latest KXZ VRF systems. By using e-solution this
simplifies the process and enables engineers to select the suitable indoor units, outdoor units, pipework, controls & calculate
the additional refrigerant required.
Engineers must register and download the e-solution software and ensure to download the latest updates when available and
this can be done by simply visiting
https://mhiae.com/e-solution/

Furthermore it was also developed to cater for the design of two and three pipe systems and specifies appropriate models and
sizes. It also generates wiring diagrams and engineering drawings which can be exported to AutoCAD or saved in PDF format.
This flexibility enables engineers to print select design
information and technical data for presentations to
clients. Engineers can also incorporate design
information into their own formats and documents for
personalised proposals.

19
R410A

New Generation FDTC


European design
& Flat panel

Ceiling cassette
Compact

FDTC
- More comfort and
Higher energy savings
- New European Design A' Design Award and Competition is the World’s largest, most
prestigious and influential design accolade, the highest achievement
- Lower noise in design. A' Design Award Winner Logo, symbolizes exceptional
design excellence in your products, projects and services.

Thin Panel Motion Sensor (Option)

FDTC thin panel fit within 10mm from the ceiling. Please refer to page 22,25

Unique Grille Design


Honeycomb grille Big Louver
Improved distribution
Draft Prevension Panel (Option)
Please refer to next page It is available to set draft prevention panel and motion sensor as well as FDT.

Compact Design Integrated


ceiling system
□700 mm → □620 mm
design 600x600.
It's only 14kg
Height of thin panel and main body is
only 248 mm allowing a very easy
installation.

Quieter operation
Current New Cooling New Heating
dB(A) dB(A) dB(A)
30 35 35
3 dB 5dB 7dB 34
3~5dB 3~8dB
Adopting new turbo fan and Down Down Down Down
Down 32
improving new heat exchanger 30 30 31 31 31
25 30
enable to reduce noise. 25 25 28 28
(Sound pressure level in the 25 25
26 26
Lo mode.) 22 25 25
20
20 20
Heating

Heating

Heating

Heating

Heating

Heating

Heating

Heating
Cooling

Cooling

Cooling

Cooling

Cooling

Cooling

Cooling

Cooling

FDTC15 FDTC22/28 FDTC36/45/56

20
Draft Prevention Panel
Keep maximum comfort with minimal draft : New FDT & FDTC control flaps with more flexibility.
(Option)

Flap

Draft Prevention
Panel Wing Draft Prevention Panel
Operating Image

When the unit is turned off,


the additional flaps close in.
- Brand new function in the market
- Flexible flap control for draft prevention
Each of the 4 flaps can be controlled individually at each operation mode. They change air flow direction and
prevent draft feeling. This new function also achieve more flexible control for air flow direction.
User can position Draft Prevention Panel panels by using the remote controller only (RC-EX3A,RCN-T-5AW-E2).

• It can also prevent user from being directly blown by hot drafts in heating mode.

Draft Prevention Panel Draft Prevention Panel


off Working

Draft Prevention Panel off Draft Prevention Panel working

Draft Prevention Panel provides a comfortable airflow without any draft feeling. Whether cooling or heating a room, the remote control can be used to instantly
suppress any warm or cool drafts. This accurately assists how air flow is directed out of the indoor unit.
Image is for illustration purposes

Ceiling cassette

FDT
The Good Design Award is Japan's only comprehensive design
evaluation and recommendation initiative, originating with the
"Good Design Products Selection System" founded in 1957.
It is now a global design award with participation from numerous
Japanese and international companies and organizations. The "G
Mark", the symbol of the Good Design Award, is known widely as
a symbol of excellent design. (FDT)

21
R410A

Motion sensor (Option)


Energy saving operation by
detecting human movement

Applied models

FDT FDTC FDTW FDTS FDU FDUM FDUT(71only) FDE FDK FDU-F

22
3 Step Control
1 Power Control 2 Stand by 3 Auto Off
New motion sensor (option) detects Unit will go on stand-by mode Unit will go off automatically
human activity. Energy saving control when no activity is detected. When when no activity is detected for
is achieved by shift set temperature the motion sensor detects activity 12 hours.
according to detected amount of again, the unit it will automatically
activity. re-start operation.

Low human activity (in cooling) High human activity (in cooling) Absence for 1 hour More 12 hours absence

Power Control Power Control Stand by Auto off


Increased Increased Operation stops Operation stops
energy savings comfort temporarily completely

Power Control Auto Off


in cooling
Activity:Low Activity:High Activity:Low None Stand by / Auto off
33℃
Set 29℃
temperature
eco

26
New
26℃ Function
ON
℃ comfort
23℃
(hour) 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Power Control Auto Off


in heating
Activity:High Activity:Low Activity:High None Stand by / Auto off
Set 25℃
temperature ON
comfort

22
New
22℃ Function

℃ eco
19℃ 15℃
(hour) 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Operation mode and Control of Motion sensor


Operation mode
eco operation comfort operation
Auto Cool Heat Dry Fan

+3℃
Low
Cooling
+3℃ +3℃ - -
Human Heating
+3℃
activity
Power -3℃
High
Cooling

Control -3℃ -3℃ - -


※1 Heating
-3℃
+3℃
None
Cooling
+3℃ -3℃ - -
Heating
-3℃
Auto Off ※2

※1 Set temperature is revised maximum +


- 3℃ at Cooling/Heating mode by detecting heat volume movement.
※2 Absence for 1 hour Operation stops (“Stand-by”) More 12 hours absence Operation stops completely

23
R410A

Builder Maintenance

Serviceability & workability


Easy and quick installation and maintenance Quick positioning !
Indoor unit is easily positioned and installed
Adjustable easier positioning of unit by new New slit in panel allows easier installation
1 slits
FDT
2 on site.
FDT
FDTC

New shape of slit is suitable to install the unit with more Flexible positioning is available, which helps adjusting the
flexibility, according to many kinds of suspending bolt direction of panel according to lines or pattern on the
pitch on site. ceiling.
Any rectangular or
Compatible with both square
squared pitch of or rectangular bolt pitch
suspending bolts are
available with this slit.

4 long slits are available.

Quick installation and maintenance


Easy access to component part for easy FDT FDT
1 maintenance. 2 New shape of path of wiring

1 The control box and bell mouth 2 Easy access to impeller New shape of path gives easy wiring work for installation.
can be removed together. and fan motor.

Control box

Bell mouth

No need to remove screws to open the FDT FDT


3 controller cover. 4 More safe installation by stopper of washer
FDTC

It is possible to loose and slide open the cover without When unit is installed
removing of the screws. with hook between
This prevents the cover from falling and damaging to washers, this stopper
stuffs on site. helps to install the unit
safely, without adjusting
washer.
Separate the provisional Washer on
washer securing material. the upper side

e sd own
Slid hang
ver
The co

Loosen Loosen

Slide

24
Builder Maintenance

For smooth
and easy
working

Easy installation and maintenance


Easy and flexible hook to FDT FDT
1 remove the filter FDTC
2 Securely fix the corner lid by strap

Hook of soft material helps to The direction of the strap hook part has
remove the filter without dust been changed from longitudinal to lateral.
spreading. Furthermore, a barb has been added to
the hook pin to prevent the strap from
coming off.

Easy to hook
but
not easy to loose

Before After
Press the filter tab to the outside
and remove the filter.

FDT FDT
3 Drain-up-lift increases up to 850 mm
FDTC 4 New port to check drain water flow

The drain can be lifted up to 850 mm from the ceiling surface. A water supply port has been provided in
the piping lid for easier testing of the drain
water flow.
(The port is usually sealed with a rubber cap.)
Previous New
FDT 700 850
FDTC 600 850
Up to
850
Flexible mm
hose

FDT FDT
5 Re-use of packages during construction work
FDTC
6 More flexible outlet for ducting
FDTC

Package material (carton) help to protect the unit from Both φ125 and φ200 (oval shaped) are available.
unexpected welding spatter or coming dust to the new
unit.

φ125 φ125

φ200
φ200

25
R410A

Simple use with advanced settings REMOTE CONTROL


Intuitive touch controller with Liquid Crystal Display

Add new function

RC-EX3A

26
Functions
Function Switch
The function switch allows you to select and set two functions of your choice
among the six available functions shown.

These functions can be used by simply pressing the button after they
are set, allowing you to use your preferable functions immediately.
Function switch Function switch
15
min 1 High Power Mode (F1) (F2)

High Power Mode achieve excessive cooling / heating


capacity for 15 minutes to quickly adjust the room
temperature to a comfortable level.
5 Favourite Mode
2 Energy Saving Mode Operation mode, set temperature, fan speed and air flow
Temperature is set to optimized to save energy direction are automatically adjusted to the programmed
without losing comfort. favourite setting.

3 Quiet Mode Now


6 Filter Sign
Outdoor unit starts to operate quietly by activating this Announces the due time for cleaning the air filter.
mode. The time of this mode can be set in conjunction NEW
with Indoor Silent Timer.

4 Home Leave Mode 7 Anti draft ON/OFF


Auti draft can be turned ON/OFF with a single tap of the
Home leave mode maintains the room temperature
button.
at a moderate level.

Favourite Mode Adjusting Brightness of the


Operation mode, set temperature, fan speed and air flow direction are Operation lamp
memorized and allocated to two buttons that can be operated by one touch.
The brightness of the operation lamp
behind Run/Stop switch can be adjusted
by 10 stages.

【e.g.】 【e.g.】
【operation mode】
Operation mode Operation mode

Cooling

Dry
Direction Fan speed Direction Fan speed

F1 Auto F2

Fan

Heating
Set temp Set temp

Draft prevention setting(only FDT/FDTC series) Easy adjustment of the Air Flow
User can enable/disable the motion of panel with anti draft User can visually confirm and set the direction of louvres
for each blow outlet for each operation mode. using the visual display on the remote controller.
This function can be set while operating. NEW

No.3?

This is No.3!

27
R410A

Motion sensor control


Presence of humans and activity are detected by a motion sensor to perform various controls.
1 Select Enable / Disable 2 Select Enable / Disable per control
Motion sensor control ・Power control
・Auto-off

1
2

Select Enable / Disable for the


motion sensor of the indoor unit 3
connected to the R/C.
Enable/Disable Enable/Disable

i
H!
Backup Control
Control restricted to two indoor units (two groups)

Fault backup control Capacity backup control Rotational operation control NEW

Reassurance C Comfort C Comfort


Energy
saving
Longer
unit life
Longer
unit life
Energy
saving

Keep back up all the time! Maintains users' comfort! Energy saving and longer life!
If one of the two indoor units malfunctions When the control system detects either of By operating two indoor units alternately,
and stops its operation, the other starts two units is operating with overload, the their chronological changes are equalized.
backup operation so that users' comfort other unit cover the capacity. (The alternate operation cycle can be
will not be compromised. specified in a range from 1 to 999 hours in
1 1
increments of 1 hours.)

1
Remote control Remote control

Remote control
2 2

3 3

Additional functions of External Input / Output HOTEL

The external input/output of indoor unit by remote


HOTEL

controller can set input/output based on user’s demand.

Remote surveillance system Card key on-off

CNT (New)
External Input External Output 2 Output - Operation
- Heating
CNT (1-6) - Compressor ON (thermo-ON)
CNTA (1-2) 3 Output - Inspection
Input On/Off - Cooling (defrosting)
- Fan operation
Permission/Prohibition
Cooling/Heating 4 Output - Fan operation with Phi or Hi
- Fan operation with Me or Lo
Emergency Stop - Defrosting (oil return in heating operation)
Set temp. shift - Ventilation
Forced thermo-off 5 Output - Heater ON
Newly added IU operation stop - Free cooling
Silent mode
Newly added - IU overload alarm

28
Silent mode control Indoor unit capacity display
The Outdoor unit is controlled prioritising quiet operation. Silent Capacities of Indoor units connected to the
mode control must be set to the F1 or F2 switch. User can RC-EX3A are displayed.
start/stop the silent mode control with a single tap of a button.

Timer START

No.000 Indoor unit


No. Capacity

Language Switching NEW


80
000 80
001 112
User can select from the following languages
002 140
and also switch them on the top display. No.001

112
English German French Spanish

No.002

Russian Polish Italian Dutch


140

Turkish Portuguese Chinese Japanese

Contact company & Error display


If any error occurs on the air conditioner, the “Unit protection stop” is indicated on the message display.

“Error”

Wireless Kit & Wireless Remote Controller


Line-up The functions and the operations will be improved.
Model Wireless kit
FDT RCN-T-5AW-E2
FDTC RCN-TC-5AW-E2
FDTW RCN-TW-E2 Display
FDTS RCN-TS-E2
FDK RCN-K-E2, RCN-K71-E2
FDE RCN-E-E3
FDFW RCN-FW-E2
FDTQ, FDU,FDUM, FDUT,
RCN-KlT4-E2
FDUH, FDFL, FDFU, FDU-F

Function added
1) High power
2) Energy-saving
3) ON/OFF Timer by clock
4) Child lock
5) Silent mode control for Outdoor unit
6) Home leave mode

29
R410A

Outdoor units
Heat pump systems model
4, 5, 6HP (11.2kW~15.5kW)
Model No. Nominal Cooling Capacity
FDC112KXEN6 11.2kW (220V)
Blue
Fin
FDC140KXEN6 14.0kW (220V)
FDC155KXEN6 15.5kW (220V)
FDC112KXES6 11.2kW (380V)
FDC140KXES6 14.0kW (380V)
FDC155KXES6 15.5kW (380V)

• Connect up to 8 indoor units/up to 150% capacity.


• High efficiency with COP (in cooling) up to 4.0.
• KX6 employs DC inverter compressors ONLY.
• Industry leading total piping length up to 100m and a maximum pipe Note: FDUT15KXE6F-E, FDTC15KXZE1 and FDK15KXZE1
can not be connected to the above systems.
run of 70m.

Total length: 100m Range of operation


Outdoor unit 50
+43ºC
Height difference 40
30m(outdoor unit above)
15m(outdoor unit below)
30
Indoor unit Cooling
20
Max height +15.5ºC
difference between 10
indoor units: 15m
Indoor unit
0
Heating
-10
-15ºC
Furthest -20
indoor unit: 70m -20ºC

* The total length of ø9.52mm(3/8") liquid piping must be 50m or less

Specifications
Item Model FDC112KXEN6 FDC140KXEN6 FDC155KXEN6 FDC112KXES6 FDC140KXES6 FDC155KXES6
Nominal horse power 4HP 5HP 6HP 4HP 5HP 6HP
Power source 1 Phase 220-240V, 50Hz 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 23 23.3 13.5
Cooling 11.2 14.0 15.5 11.2 14.0 15.5
Nominal capacity kW
Heating 12.5 16.0 16.3 12.5 16.0 16.3
Power Cooling 2.80 4.17 4.71 2.80 4.17 4.71
Electrical characteristics kW
consumption Heating 2.89 4.31 4.38 2.89 4.31 4.38
Exterior dimensions HxWxD mm 845x970x370
Net weight kg 85 87
Sound pressure level Cooling/Heating dB(A) 52/54 53/57 53/57 52/54 53/57 53/57
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 5.0 / 10.44
Liquid line ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line ø15.88(5/8")
Capacity connection % 80~150
Number of connectable indoor units 6 8 8 6 8 8
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.

30
Refrigerant piping
Outdoor unit (HP) 4 5 6 Branch pipes Header pipe

Gas pipe Furthest indoor unit ø15.88


Liquid pipe =<70m ø9.52

DIS-22-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G

Dimensions
All measurements in mm.

I II III
L1 Open Open 500

L2 300 5 Open

L3 150 300 150

L4 5 5 5

Mark Content Notes:


A Service valve connection (gas side) ø15.88 (5/8") (Flare) (1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm.
B Service valve connection (liquid side) ø9.52 (3/8") (Flare)
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces
C Pipe/cable draw-out hole perpendicularly to the dominant wind direction.
D Drain discharge hole ø20 x 3 places (4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
E Anchor bolt hole M10 x 4 places (6) The model name label is attached on the lower right corner of the front panel.
F Cable draw-out hole ø30 x 3 places

31
R410A

Heat pump systems model


8, 10, 12HP (22.4kW~33.5kW) Blue
Fin
Model No. Nominal Cooling Capacity
FDC224KXE6G 22.4kW
FDC280KXE6G 28.0kW
FDC335KXE6G 33.5kW

• Connect up to 24 indoor units/up to 150% capacity.


• High efficiency with COP (in cooling) up to 4.0.
• These units employ DC inverter compressors ONLY.
• Industry leading total piping length up to 510m and a maximum pipe
run of 160m.

Total length: 510m Outdoor unit Range of operation


50
To the Height difference +43ºC
first branch: 50m(outdoor unit above) 40
max 130m 40m(outdoor unit below)
Indoor unit
30

Max height Cooling


20
Indoor unit difference +15.5ºC

between 10
indoor units:
From the first Indoor unit 18m 0

branch to the Heating


furthest indoor -10

unit: 90m* Furthest -15ºC


-20
indoor unit: 160m -20ºC

* The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.

Specifications
Item Model FDC224KXE6G FDC280KXE6G FDC335KXE6G
Nominal horse power 8HP 10HP 12HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 20 23
Cooling 22.4 28.0 33.5
Nominal capacity kW
Heating 25.0 31.5 37.5
Power Cooling 5.60 8.09 9.82
Electrical characteristics kW
consumption Heating 6.03 8.21 10.12
Exterior dimensions HxWxD mm 1675x1080x480
Net weight kg 221 224
Sound pressure level Cooling/Heating dB(A) 58/58 59/60 61/61
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø9.52(3/8") ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8") ø25.4(1") [ø22.22(7/8")]
Capacity connection % 50~150
Number of connectable indoor units 22 24 24
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

32
Refrigerant piping
Outdoor unit (HP) 8 10 12 Branch pipes Header pipe

Gas pipe Furthest indoor unit ø19.05 ø22.22 ø25.4(ø22.22)


Liquid pipe =<90m ø9.52 ø12.7
Gas pipe 90m ø22.22 ø25.4(ø22.22)
Liquid pipe =<Furthest indoor unit ø12.7 DIS-22-1G DIS-371-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G
HEAD8-371-2

Dimensions
All measurements in mm.

B L3 I II II
L2 Intake
A L4 L1 Open Open 1500
G Intake L2 300 5 Open
69

L1
Service Outlet L3 300 300 300
space
43
L4
69
51

5 5 5
60
120 Minimum installation space

Terminal block
1675

B
A

C
640(8.10HP)
634(12HP)

F
G
35

553

35
20

174
84

84
194
159

159
84

F C 54 67 F
C 54
55

55

55

51 14 42 50
1080 14 51

195 690 195 E 989


E C 701
50 30 461
421
39
19

30

141
241
321
361
105
520
480

80
D
19
39

Mark Content 224 280 335 Notes:


(1) It must not be surrounded by walls on the four sides.
A Service valve connection of the (2) The unit must be fixed with anchor bolts. An anchor bolt
ø19.05 (3/4") (Flare) ø19.05 (3/4") (Flare) ø19.05 (3/4") (Flare)
attached connecting pipe (gas side) must not protrude more than 15mm.
B Service valve connection (liquid side) ø9.52 (3/8") (Flare) ø9.52 (3/8") (Flare) ø12.7 (1/2") (Flare) (3) Where the unit is subject to strong winds, the blower
outlet shoud face perpendicularly to the dominant wind
C Pipe/cable draw-out hole 4places 4places 4places direction.
D Drain discharge hole ø20 x 4places ø20 x 4places ø20 x 4places (4) Leave a 1m or more space above the unit.
E Anchor bolt hole M10 x 4places M10 x 4places M10 x 4places (5) A wall in front of the blower outlet must not exceed the
units height.
ø30 x 2places (front) ø30 x 2places (front) ø30 x 2places (front)
(6) The model name label is attached on the lower right
F Cable draw-out hole ø45 (side) ø45 (side) ø45 (side) corner of the front.
ø30 x 2places (back) ø30 x 2places (back) ø30 x 2places (back) (7) Connect the Service valve with local pipe by using the
Connecting position of the local pipe. pipe of the attachment.(Gas side only)
G ø19.05 (3/4")(Brazing) ø22.22 (7/8")(Brazing) ø25.4 (1")(Brazing) (8) Mark shows the connecting position of the local
(gas side)
pipe.(Gas side only)

33
R410A

KXZ Lite Heat pump systems


8, 10HP (22.4kW · 28.0kW)
Model No. Nominal Cooling Capacity
Blue
FDC224KXZPE1 22.4kW Fin
FDC280KXZPE1 28.0kW

• Connect up to 8 indoor units/up to 120% capacity.


• High efficiency with COP (in cooling) up to 4.0.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• KXZ Lite extends a cooling range operation up to 50˚C.
• External static pressure is available up to 35 Pa.
• Tropical usage mode.

Total length: 150m Range of operation


Outdoor unit +50ºC
50

To the Height difference 40


first branch: 30m(outdoor unit above)
max 90m 30m(outdoor unit below)
Indoor unit 30

Cooling
20
Max height +15.5ºC
Indoor unit difference 10
between
indoor units: 0
From the first Indoor unit 18m Heating
branch to the -10

furthest indoor -15ºC


unit: 40m Furthest -20
-20ºC
indoor unit: 120m

Specifications
Item Model FDC224KXZPE1 FDC280KXZPE1
Nominal horse power 8HP 10HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 21 22
Cooling 22.4 28.0
Nominal capacity kW
Heating 22.4 28.0
Power Cooling 5.6 7.87
Electrical characteristics kW
consumption Heating 4.8 6.47
Exterior dimensions HxWxD mm 1505x970x370
Net weight kg 165
Sound pressure level Cooling/Heating dB(A) 59/60 60/63
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 8.9 / 18.583
Liquid line ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8")
Capacity connection % 50~120
Number of connectable indoor units 8 8
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.

34
Refrigerant piping
Outdoor unit (HP) 8 10 Branch pipes Header pipe

Gas pipe Furthest indoor unit ø19.05 ø22.22


Liquid pipe =<90m ø9.52
Gas pipe 90m ø22.22 ø25.4/ø28.58
Liquid pipe =<Furthest indoor unit ø9.52 DIS-22-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G

Dimensions
All measurements in mm.

Notes:
I II III
*1 At the time of the installation at ( )
L1 Open Open 500 dimension,
L2 300 5 Open Secure space of 250mm in lateral
(L4) by unit movement at the time
L3 150 300 150 of the exchange work of the
L4 250 (5)*1 250 (5)*1 250 (5)*1 compressor.

Mark Content Notes:


(1) It must not be surrounded by walls on the four sides.
A Service valve connection of the (2) The unit must be fixed with anchor bolts.
ø19.05 (3/4") (Flare)
attached connecting pipe (gas side) An anchor bolt must not protrude more than 15mm.
B Service valve connection (liquid side) ø9.52 (3/8") (Flare) (3) Where the unit is subject to strong winds, lay it in such a direction that the
blower outlet faces perpendicularly to the dominant wind direction.
C Cable draw-out hole (front · side) ø30 x 2places (4) Leave 1m or more space above the unit.
D Cable draw-out hole (front · side) ø45 x 2places (5) A wall in front of the blower outlet must not exceed the units height.
E Cable draw-out hole (back) ø50 (6) The model name label is attached on the lower right corner of the front panel.
(7) Connect the Service valve with local pipe by using the pipe of the attachment.
F Pipe/cable draw-out hole 4places
(Gas side only) (Accessory pipe is used only by FDC280KXZPE1)
G Drain discharge hole ø20 x 3places (8) Regarding attaching the pipe of accessories, refer to an attached installation
H Anchor bolt hole M10 x 4places manual.

35
R410A

Heat pump systems


10, 12HP (28.0kW, 33.5kW)
Model No. Nominal Cooling Capacity
FDC280KXZE1 28.0kW Blue
FDC335KXZE1 33.5kW Fin

• Connect up to 29 indoor units/up to 130% capacity.


• High efficiency with COP (in cooling) up to 3.9.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• Industry leading total piping length up to 1000m and a maximum
pipe run of 160m. Uniform footprint of models (10,12HP)
allows continuous side-by-side installation

Total length: Outdoor unit


1000m
Range of operation
Height difference *2
50
50m(outdoor unit above) 70m +46ºC
To the
Indoor unit 40m(outdoor unit below)
first branch: 40
max 130m
Max height
30
Indoor unit difference
between Cooling
indoor units: 20
+15.5ºC
Indoor unit 18m
From the first branch 10
to the furthest
indoor unit: 90m*
1
Furthest 0
indoor unit: Heating
160m -10

*1 The difference between the longest and the shortest indoor unit piping
-15ºC
-20
from the first branch must be within 40m. (MAX85m)
*2 In case of height difference up to 70m, please contact your dealer.
-20ºC

Height difference up to 90m is possible with High Head series.


Please refer to page 56.

Specifications
Item Model FDC280KXZE1 FDC335KXZE1
Nominal horse power 10HP 12HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 21.2
Cooling 28.0 33.5
Nominal capacity kW
Heating 31.5 37.5
Power Cooling 7.24 8.96
Electrical characteristics kW
consumption Heating 7.28 9.04
Exterior dimensions HxWxD mm 1690x1350x720
Net weight kg 272
Sound pressure level Cooling/Heating dB(A) 55/57 61/58
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.0 / 22.968
Liquid line ø9.52(3/8") ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø22.22(7/8") ø25.4(1") [ø22.22(7/8")]
Capacity connection % 50~130
Number of connectable indoor units 24 29
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

36
Dimensions
All measurements in mm.

Mark Content 280 335 Installation example


A Refrigerant gas piping connection pipe ø22.22(Brazing) ø25.4(Brazing) Dimensions 1 2

B Refrigerant liquid piping connection pipe ø9.52(Flare) ø12.7(Flare) L1 500 Open

C Refrigerant piping exit hole ø88(or ø100) L2 10(30) 10(30)

D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (bottom) L3 100 100

F Anchor bolt hole M10 x 4 places L4 10(30) Open

G Drain waste water hose hole ø45 x 3 places H1 1500 Open

H Drain hole ø20 x 10 places H2 No limit No limit

K Refrigerant oil equalization piping connection pipe ø9.52(Flare) H3 1000 No limit

L Carrying in or hole for hanging 230 x 60 H4 No limit Open


() :In case it is the promised installation location
that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

Installation example
When more than one unit is installed Dimensions 1 2

Wall height
H3
L1 500 Open

L3 L2 10(30) 200

L3 100 300
Wall height

Wall height

L2 L5 L6 L4
H2

H4

L4 10(30) Open
L1 (Unit front side) L5 10(30) 400
Wall height
H1
L6 10(30) 400

H1 1500 Open

H2 No limit No limit

H3 1000 No limit

H4 No limit Open

() :In case it is the promised installation location


that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

37
R410A

Heat pump systems


14, 16, 17, 18, 20HP (40.0kW~56.0kW)
Model No. Nominal Cooling Capacity
FDC400KXZE1 40.0kW
FDC450KXZE1 45.0kW
Blue
Fin
FDC475KXZE1 47.5kW
FDC500KXZE1 50.0kW
FDC560KXZE1 56.0kW

• Connect up to 48 indoor units/up to 130% capacity.


• High efficiency with COP (in cooling) up to 3.6.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.

Uniform footprint of all models (from


14HP~20HP) allows continuous side-
by-side installation
Total length: Outdoor unit
1000m
Range of operation
Height difference *2
50
50m(outdoor unit above) 70m +46ºC
To the
Indoor unit 40m(outdoor unit below)
first branch: 40
max 130m
Max height
30
Indoor unit difference
between Cooling
20
indoor units: +15.5ºC
Indoor unit 18m
From the first branch 10
to the furthest
indoor unit: 90m*
1
Furthest 0
indoor unit: Heating
160m -10

*1 The difference between the longest and the shortest indoor unit piping -20
-15ºC
from the first branch must be within 40m. (MAX85m)
*2 In case of height difference up to 70m, please contact your dealer.
-20ºC

Height difference up to 90m is possible with High Head series.


Please refer to page 56.

Specifications
Item Model FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1
Nominal horse power 14HP 16HP 17HP 18HP 20HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5 8
Max current A 32 42.4
Cooling 40.0 45.0 47.5 50.0 56.0
Nominal capacity kW
Heating 45.0 50.0 53.0 56.0 63.0
Power Cooling 10.96 13.98 13.98 13.97 16.62
Electrical characteristics kW
consumption Heating 10.69 12.50 13.00 13.49 15.95
Exterior dimensions HxWxD mm 2048x1350x720
Net weight kg 317 370
Sound pressure level Cooling/Heating dB(A) 60/62 61/62 61/61 61/62 64/66
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø25.4(1") [ø28.58(1 1/8")] ø28.58(1 1/8")
Capacity connection % 50~130
Number of connectable indoor units 34 39 41 43 48
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

38
Dimensions
All measurements in mm.

Mark Content 400 450, 475, 500, 560 Installation example


A Refrigerant gas piping connection pipe ø25.4(Brazing) ø28.58(Brazing) Dimensions 1 2

B Refrigerant liquid piping connection pipe ø12.7(Flare) L1 500 Open

C Refrigerant piping exit hole ø88(or ø100) L2 10(30) 10(30)

D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (bottom) L3 100 100

F Anchor bolt hole M10 x 4 places L4 10(30) Open

G Drain waste water hose hole ø45 x 3 places H1 1500 Open

H Drain hole ø20 x 10 places H2 No limit No limit

K Refrigerant oil equalization piping connection pipe ø9.52(Flare) H3 1000 No limit

L Carrying in or hole for hanging 230 x 60 H4 No limit Open


() :In case it is the promised installation location
that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

Installation example
When more than one unit is installed Dimensions 1 2

Wall height
H3
L1 500 Open

L3 L2 10(30) 200

L3 100 300
Wall height

Wall height

L2 L5 L6 L4
H2

H4

L4 10(30) Open
L1 (Unit front side) L5 10(30) 400
Wall height
H1
L6 10(30) 400

H1 1500 Open

H2 No limit No limit

H3 1000 No limit

H4 No limit Open

() :In case it is the promised installation location


that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.
39
R410A

Heat pump combination systems


Blue
22, 24HP (61.5kW, 67.0kW) Fin

Model No. Nominal Cooling Capacity


FDC615KXZE1 (FDC280+FDC335) 61.5kW
FDC670KXZE1 (FDC335+FDC335) 67.0kW

• Connect up to 58 indoor units/up to 130% capacity.


• High efficiency with COP (in cooling) up to 3.8.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.
Uniform footprint of all
models (from 22HP, 24HP)
Max: 10m (oil equalizing pipe) allows continuous side-by-
side installation
Total length: Outdoor unit Max: 0.4m
1000m
Height difference *2 Range of operation
Max: 5m 50m(outdoor unit above) 70m
To the 50
Indoor unit 40m(outdoor unit below) +46ºC
first branch:
max 130m 40
Max height
Indoor unit difference
30
between
indoor units: Cooling
18m 20
From the first branch Indoor unit +15.5ºC
to the furthest
indoor unit: 90m*
1 10
Furthest
indoor unit: 0
160m Heating
*1 The difference between the longest and the shortest indoor unit piping
-10

from the first branch must be within 40m. (MAX85m) -15ºC

*2 In case of height difference up to 70m, please contact your dealer. -20


-20ºC
Height difference up to 90m is possible with High Head series.
Please refer to page 56.

Specifications Exterior dimension : Please refer to page37.

Item Model FDC615KXZE1 FDC670KXZE1


280KXZE1 335KXZE1
Combination (FDC)
335KXZE1 335KXZE1
Nominal horse power 22HP 24HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 10
Max current A 42.4
Cooling 61.5 67.0
Nominal capacity kW
Heating 69.0 75.0
Power Cooling 16.20 17.92
Electrical characteristics kW
consumption Heating 16.32 18.08
Exterior dimensions HxWxD mm 1690x2700x720
Net weight kg 544
Refrigerant charge R410A kg 11.0x2
Liquid line ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø28.58(1 1/8")
Capacity connection % 50~130
Number of connectable indoor units 53 58
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

40
Heat pump combination systems
26, 28, 30, 32, 34, 36, 38, 40HP (73.5kW~112.0kW)
Model No. Nominal Cooling Capacity
FDC735KXZE1 (FDC335+FDC400) 73.5kW Blue
FDC800KXZE1 (FDC400+FDC400) 80.0kW Fin
FDC850KXZE1 (FDC400+FDC450) 85.0kW
FDC900KXZE1 (FDC450+FDC450) 90.0kW
FDC950KXZE1 (FDC475+FDC475) 95.0kW
FDC1000KXZE1 (FDC500+FDC500) 100.0kW
FDC1060KXZE1 (FDC500+FDC560) 106.0kW
FDC1120KXZE1 (FDC560+FDC560) 112.0kW

• Connect up to 80 indoor units/up to 130% capacity.


• High efficiency with COP (in cooling) up to 3.7.
• These units employ DC inverter multiport compressors with concentrated winding motor.
• Industry leading total piping length up to 1000m and a maximum pipe run of 160m.
Max: 10m (oil equalizing pipe)
• In case of 26HP
Total length: Outdoor unit Max: 0.4m
1000m
Height difference *2
Max: 5m
To the
50m(outdoor unit above) 70m Range of operation
Indoor unit 40m(outdoor unit below)
first branch: 50
max 130m +46ºC
Max height
40
Indoor unit difference
between
indoor units: 30

Indoor unit 18m Cooling


From the first branch 20
to the furthest +15.5ºC
indoor unit: 90m*
1
Furthest 10
indoor unit:
160m 0

*1 The difference between the longest and the shortest indoor unit piping -10
Heating
from the first branch must be within 40m. (MAX85m)
*2 In case of height difference up to 70m, please contact your dealer. -15ºC
Height difference up to 90m is possible with High Head series. -20
Please refer to page 56. -20ºC

Specifications Exterior dimension : Please refer to page37,39.

Item Model FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1
335KXZE1 400KXZE1 400KXZE1 450KXZE1 475KXZE1 500KXZE1 500KXZE1 560KXZE1
Combination (FDC)
400KXZE1 400KXZE1 450KXZE1 450KXZE1 475KXZE1 500KXZE1 560KXZE1 560KXZE1
Nominal horse power 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 10 16
Max current A 53.2 64 84.8
Cooling 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0
Nominal capacity kW
Heating 82.5 90.0 95.0 100.0 106.0 112.0 119.0 126.0
Power Cooling 19.92 21.92 24.94 27.96 27.96 27.94 30.59 33.24
Electrical characteristics kW
consumption Heating 19.73 21.38 23.19 25.00 26.00 26.98 29.44 31.90
Exterior dimensions HxWxD mm 2048x2700x720
Net weight kg 589 634 740
Refrigerant charge R410A kg 11.0+11.5 11.5x2
Liquid line ø15.88(5/8") ø19.05(3/4")
Refrigerant piping size mm(in)
Gas line ø31.75(1 1/4") [ø34.92(1 3/8")] ø38.1(1 1/2") [ø34.92(1 3/8")]
Capacity connection % 50~130
Number of connectable indoor units 63 69 73 78 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

41
R410A

Heat pump combination systems


42, 44, 46, 48HP (120.0kW~135.0kW)

Model No. Nominal Cooling Capacity


Blue
FDC1200KXZE1 (FDC400+FDC400+FDC400) 120.0kW Fin
FDC1250KXZE1 (FDC400+FDC400+FDC450) 125.0kW
FDC1300KXZE1 (FDC400+FDC450+FDC450) 130.0kW
FDC1350KXZE1 (FDC450+FDC450+FDC450) 135.0kW

• Connect up to 80 indoor units/up to 130% capacity.


• High efficiency with COP (in cooling) up to 3.6.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.

Max: 10m (oil equalizing pipe)

Total length: Outdoor unit Max: 0.4m Range of operation


1000m
50
+46ºC
Height difference *2
Max: 5m 50m(outdoor unit above) 70m
To the 40
Indoor unit 40m(outdoor unit below)
first branch:
max 130m 30
Max height
Cooling
Indoor unit difference 20
between +15.5ºC
indoor units: 10
Indoor unit 18m
From the first branch
to the furthest 0
indoor unit: 90m*
1
Furthest Heating
indoor unit: -10

160m -15ºC
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. (MAX85m)
-20ºC

* Height difference
2 In case of height difference up to 70m, please contact your dealer.
up to 90m is possible with High Head series.
Please refer to page 56.

Specifications Exterior dimension : Please refer to page39.

Item Model FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1


400KXZE1 400KXZE1 400KXZE1 450KXZE1
Combination (FDC) 400KXZE1 400KXZE1 450KXZE1 450KXZE1
400KXZE1 450KXZE1 450KXZE1 450KXZE1
Nominal horse power 42HP 44HP 46HP 48HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 15
Max current A 96
Cooling 120.0 125.0 130.0 135.0
Nominal capacity kW
Heating 135.0 140.0 145.0 150.0
Power Cooling 32.88 35.90 38.92 41.94
Electrical characteristics kW
consumption Heating 32.07 33.88 35.69 37.50
Exterior dimensions HxWxD mm 2048x4050x720
Net weight kg 951
Refrigerant charge R410A kg 11.5x3
Liquid line ø19.05(3/4")
Refrigerant piping size mm(in)
Gas line ø38.1(1 1/2") [ø34.92(1 3/8")]
Capacity connection % 50-130
Number of connectable indoor units 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

42
Heat pump combination systems
50, 52, 54, 56, 58, 60HP (142.5kW~168.0kW)

Model No. Nominal Cooling Capacity


Blue
FDC1425KXZE1 (FDC475+FDC475+FDC475) 142.5kW Fin
FDC1450KXZE1 (FDC475+FDC475+FDC500) 145.0kW
FDC1500KXZE1 (FDC500+FDC500+FDC500) 150.0kW
FDC1560KXZE1 (FDC500+FDC500+FDC560) 156.0kW
FDC1620KXZE1 (FDC500+FDC560+FDC560) 162.0kW
FDC1680KXZE1 (FDC560+FDC560+FDC560) 168.0kW

• Connect up to 80 indoor units/up to 130% capacity.


• High efficiency with COP (in cooling) up to 3.6.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.
Max: 10m (oil equalizing pipe)

Total length: Outdoor unit Max: 0.4m Range of operation


1000m
50
+46ºC
Height difference *2
Max: 5m 50m(outdoor unit above) 70m
To the 40
Indoor unit 40m(outdoor unit below)
first branch:
max 130m 30
Max height
Cooling
Indoor unit difference 20
between +15.5ºC
indoor units: 10
Indoor unit 18m
From the first branch
to the furthest 0
indoor unit: 90m*
1
Furthest Heating
indoor unit: -10

160m -15ºC
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. (MAX85m)
-20ºC

* Height difference
2 In case of height difference up to 70m, please contact your dealer.
up to 90m is possible with High Head series.
Please refer to page 56.

Specifications Exterior dimension : Please refer to page39.

Item Model FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1


475KXZE1 475KXZE1 500KXZE1 500KXZE1 500KXZE1 560KXZE1
Combination (FDC) 475KXZE1 475KXZE1 500KXZE1 500KXZE1 560KXZE1 560KXZE1
475KXZE1 500KXZE1 500KXZE1 560KXZE1 560KXZE1 560KXZE1
Nominal horse power 50HP 52HP 54HP 56HP 58HP 60HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 24
Max current A 127.2
Cooling 142.5 145.0 150.0 156.0 162.0 168.0
Nominal capacity kW
Heating 159.0 162.0 168.0 175.0 182.0 189.0
Power Cooling 41.94 41.93 41.91 44.56 47.21 49.86
Electrical characteristics kW
consumption Heating 39.00 39.49 40.47 42.93 45.39 47.85
Exterior dimensions HxWxD mm 2048x4050x720
Net weight kg 1110
Refrigerant charge R410A kg 11.5x3
Liquid line ø19.05(3/4")
Refrigerant piping size mm(in)
Gas line ø38.1(1 1/2") [ø34.92(1 3/8")]
Capacity connection % 50-130
Number of connectable indoor units 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

43
R410A

Hi-COP series
8~36HP(22.4kW~100.0kW)
Model No. Nominal Cooling Capacity Model No. Nominal Cooling Capacity
FDC224KXZXE1 22.4kW FDC450KXZXE1 (FDC224+FDC224) 45.0kW
FDC280KXZXE1 28.0kW FDC500KXZXE1 (FDC224+FDC280) 50.0kW
FDC335KXZXE1 33.5kW FDC560KXZXE1 (FDC280+FDC280) 56.0kW
FDC615KXZXE1 (FDC280+FDC335) 61.5kW
FDC670KXZXE1 (FDC335+FDC335) 67.0kW
FDC735KXZXE1 (FDC224+FDC224+FDC280) 73.5kW
FDC800KXZXE1 (FDC224+FDC280+FDC280) 80.0kW
High
Efficiency FDC850KXZXE1 (FDC280+FDC280+FDC280) 85.0kW
FDC900KXZXE1 (FDC280+FDC280+FDC335) 90.0kW
FDC950KXZXE1 (FDC280+FDC335+FDC335) 95.0kW
High
FDC1000KXZXE1 (FDC335+FDC335+FDC335) 100.0kW
Higher
Energy
Economy
Savings
Blue
Blue Fin
Fin

• This series can connect indoor unit capacity


up to 160~200%.

kW capacity connection
22.4~45.0 200%

50.0~100.0 160%

• High efficiency with COP (in cooling) up to 4.5.


• These units employ DC inverter multiport compressors FDC224KXZXE1 FDC280KXZXE1
with concentrated winding motor. FDC335KXZXE1
• Industry leading total piping length up to 1000m and a
maximum pipe run of 160m.

Max: 10m (oil equalizing pipe)


Range of operation
Total length: Outdoor unit Max: 0.4m 50
+46ºC
1000m
40
Height difference *2
Max: 5m 50m(outdoor unit above) 70m
To the 30
Indoor unit 40m(outdoor unit below)
first branch:
Cooling
max 130m 20
Max height +15.5ºC
Indoor unit difference
10
between
indoor units:
0
Indoor unit 18m
From the first branch Heating
to the furthest
indoor unit: 90m*
-10
1
Furthest -15ºC
indoor unit: -20
-20ºC
160m
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. (MAX85m)
*2 In case of height difference up to 70m, please contact your dealer.
Height difference up to 90m is possible with High Head series.
Please refer to page 56.

44
Specifications
Item Model FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1
Nominal horse power 8HP 10HP 12HP
Power source 3Phase 380-415V, 50Hz
Starting current A 5
Max current A 21.2 32
Cooling 22.4 28.0 33.5
Nominal capacity kW
Heating 25.0 31.5 37.5
Power Cooling 4.98 6.95 8.68
Electrical characteristics kW
consumption Heating 5.56 6.83 8.39
Exterior dimensions HxWxD mm 1690x1350x720 2048x1350x720
Net weight kg 280 325
Sound pressure level Cooling / Heating dB(A) 56/57 56/56 62/57
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.0 / 22.968 11.5 / 24.012
Liquid line ø9.52(3/8") ø12.7(1/2")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8") ø25.4(1")[ø22.22(7/8")]
Capacity connection % 200
Number of connectable indoor units 29 37 44

Item Model FDC450KXZXE1 FDC500KXZXE1 FDC560KXZXE1 FDC615KXZXE1 FDC670KXZXE1


224KXZXE1 224KXZXE1 280KXZXE1 280KXZXE1 335KXZXE1
Combination (FDC)
224KXZXE1 280KXZXE1 280KXZXE1 335KXZXE1 335KXZXE1
Nominal horse power 16HP 18HP 20HP 22HP 24HP
Power source 3Phase 380-415V, 50Hz
Starting current A 10
Max current A 42.4 53.2 64
Cooling 45.0 50.0 56.0 61.5 67.0
Nominal capacity kW
Heating 50.0 56.0 63.0 69.0 75.0
Power Cooling 10.0 11.8 13.9 15.6 17.4
Electrical characteristics kW
consumption Heating 11.1 12.3 13.7 15.2 16.8
Exterior dimensions HxWxD mm 1690x2700x720 2048x2700x720
Net weight kg 560 605 650 650 650
Refrigerant charge R410A kg 11.0x2 11.0+11.5 11.5x2
Liquid line ø12.7(1/2")
Refrigerant piping size Gas line mm(in) ø28.58(1 1/8")
Oil equalization ø9.52(3/8")
Capacity connection % 200 160
Number of connectable indoor units 60 53 59 65 71

Item Model FDC735KXZXE1 FDC800KXZXE1 FDC850KXZXE1 FDC900KXZXE1 FDC950KXZXE1 FDC1000KXZXE1


224KXZXE1 224KXZXE1 280KXZXE1 280KXZXE1 280KXZXE1 335KXZXE1
Combination (FDC) 224KXZXE1 280KXZXE1 280KXZXE1 280KXZXE1 335KXZXE1 335KXZXE1
280KXZXE1 280KXZXE1 280KXZXE1 335KXZXE1 335KXZXE1 335KXZXE1
Nominal horse power 26HP 28HP 30HP 32HP 34HP 36HP
Power source 3Phase 380-415V, 50Hz
Starting current A 15
Max current A 74.4 85.2 96
Cooling 73.5 80.0 85.0 90.0 95.0 100.0
Nominal capacity kW
Heating 82.5 90.0 95.0 100.0 106.0 112.0
Power Cooling 17.1 19.3 21.1 22.7 24.3 25.9
Electrical characteristics consumption kW
Heating 18.2 19.7 20.6 21.9 23.5 25.1
Exterior dimensions HxWxD mm 2048x4050x720
Net weight kg 885 930 975 975
Refrigerant charge R410A kg 11.0x2+11.5 11.0+11.5x2 11.5x3
Liquid line ø15.88(5/8")
Refrigerant piping size Gas line mm(in) ø31.75(1 1/4")[ø34.92(1 3/8")] Ø38.1(1/2")[ø34.92(1 3/8")]
Oil equalization ø9.52(3/8")
Capacity connection % 160
Number of connectable indoor units 78 80 80 80 80 80

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

45
R410A

Dimensions
All measurements in mm.

FDC224KXZXE1

Mark Content 224 Installation example


A Refrigerant gas piping connection pipe ø19.05 (Brazing) Dimensions 1 2

B Refrigerant liquid piping connection pipe ø9.52 (Flare) L1 500 Open

C Refrigerant piping exit hole ø88 (or ø100) L2 10(30) 10(30)

D Power supply entry hole ø50 (Right . Left . Front), Long hole 40 x 80 (Bottom) L3 100 100

F Anchor bolt hole M10 x 4 places L4 10(30) Open

G Drain waste water hose hole ø45 x 3 places H1 1500 Open

H Drain hole ø20 x 10 places H2 No limit No limit

K Refrigerant oil equalization piping connection pipe ø9.52 (Flare) H3 1000 No limit

L Carrying in or hole for hanging 230 x 60 H4 No limit Open


() :In case it is the promised installation location
that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

46
FDC280KXZXE1, 335KXZXE1

Mark Content 280 335 Installation example


A Refrigerant gas piping connection pipe ø22.22 (Brazing) ø25.4 (Brazing) Dimensions 1 2

B Refrigerant liquid piping connection pipe ø9.52 (Flare) ø12.7 (Flare) L1 500 Open

C Refrigerant piping exit hole ø88 (or ø100) L2 10(30) 10(30)

D Power supply entry hole ø50 (Right . Left . Front), Long hole 40 x 80 (Bottom) L3 100 100

F Anchor bolt hole M10 x 4 places L4 10(30) Open

G Drain waste water hose hole ø45 x 3 places H1 1500 Open

H Drain hole ø20 x 10 places H2 No limit No limit

K Refrigerant oil equalization piping connection pipe ø9.52(Flare) H3 1000 No limit

L Carrying in or hole for hanging 230 x 60 H4 No limit Open


() :In case it is the promised installation location
that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

47
R410A

Corrosion Protection Treatment series


4~60HP (11.2kW~168.0kW)
Corrosion Protection Treatment series are available with
special coating applied for not only sheet metals but also Sea breeze

small parts in order to prevent salt corrosion caused by


sea breeze in area along coast line (Within approximately Sea

500m from coast line).


Model No. Nominal Cooling Capacity Model No. Nominal Cooling Capacity
FDCS112KXEN6 11.2kW FDCS280KXZE1 28.0kW
FDCS112KXES6 11.2kW FDCS335KXZE1 33.5kW
FDCS140KXEN6 14.0kW FDCS400KXZE1 40.0kW
FDCS140KXES6 14.0kW FDCS450KXZE1 45.0kW
FDCS155KXEN6 15.5kW FDCS475KXZE1 47.5kW
FDCS155KXES6 15.5kW FDCS504KXZE1 50.4kW
FDCS224KXE6G 22.4kW FDCS560KXZE1 56.0kW
FDCS280KXE6G 28.0kW
FDCS335KXE6G 33.5kW

• Combination systems:22~60HP (61.5kW~168.0kW) are the same as that of the


standard KXZ series shown on previous pages.
• Specifications and Dimensions are the same as that of the standard KXZ series shown
on previous pages.
• Non-CE Marking models.

Corrosion resistance performance of high anticorrosion fin


Comparison of weight loss by corrosion
Neutral salt water spray test Acetic acid salt water spray test
0 0
A A
Weight loss of KS128D2 was caused
Weight loss of KS128D2 was caused
Change of weight g/m2

Change of weight g/m2

by elution of hydrophilic layer,


-1 by elution of hydrophilic layer, -3 not by corrosion.
not by corrosion.

-2 -6
B
-3
Weight loss Weight loss
Weight loss of bare material -9 Weight loss of bare material
A 1 was caused by corrosion. A 1 was caused by corrosion.
= =
B 11 Bare material B 48 Bare material
-4 -12
(After 240hrs) (After 240hrs)
KS128D2 KS128D2
B
-5 -15
0 24 48 72 96 120 144 168 192 216 240 0 24 48 72 96 120 144 168 192 216 240
Elapsed time /hrs. Elapsed time /hrs.
<Test conditions> <Test conditions>
JIS Z2371 JIS Z2371
NaC1 concentration : 50g/L NaC1 concentration : 50g/L
pH : 6.5~7.2 pH : 3.1~3.3(adjusted with acetic acid)
temperature : 35°C temperature : 35°C

Appearance comparison before and after KS128D2 Bare Material


acetic acid salt water spray test

at the beginning after 240 hrs. at the beginning after 240 hrs.

48
For outside sheet metals, Cation electrodeposition coating is used for undercoat plus polyester powder coating or
acrylic baked coating for top coat and corrosion protection is applied for heat exchanger, welded parts, fan guard, fin
guard and other major parts.
Preventing corrosion by salt damage or sulfurous acid gas has made service life of this series longer while its exterior
appearance has been greatly improved.
Durability of this series for anticorrosion is about two times that of standard outdoor units under the same conditions.

Additional treatment from the standard series


Micro KXZ
undercoat: Cation electrodeposition coating undercoat: Cation electrodeposition coating
Exterior panel
topcoat: polyester powder coating or acrylic baked coating topcoat: acrylic baked coating

undercoat: Cation electrodeposition coating undercoat: Cation electrodeposition coating


Base plate
topcoat: polyester powder coating or acrylic baked coating topcoat: acrylic baked coating

undercoat: Cation electrodeposition coating


Drain pan
topcoat: acrylic baked coating

Fan motor application of anticorrosion compound application of anticorrosion compound

4~6HP
Fan motor base application of anticorrosion compound
8~12HP application of anticorrosion compound

Fin Precoated Aluminum Blue Fins in high anticorrosion specification Precoated Aluminum Blue Fins in high anticorrosion specification

Heat exchanger pipe application of anticorrosion compound application of anticorrosion compound

Side plate application of anticorrosion compound application of anticorrosion compound

Compressor application of anticorrosion compound application of anticorrosion compound

Accumulator application of anticorrosion compound application of anticorrosion compound

Receiver application of anticorrosion compound application of anticorrosion compound

4~6HP galvanized steel sheet + undercoat: Cation electrodeposition coating


Control box
8~12HP application of anticorrosion compound + topcoat: acrylic baked finish

4~6HP
Baffle plate
8~12HP application of anticorrosion compound

4~6HP galvanized steel sheet + undercoat: Cation electrodeposition coating


Service valve bracket
8~12HP application of anticorrosion compound + topcoat: acrylic baking finish

Screw for exterior panel zinc coating + chromate treatment + fluorine coating zinc coating + chromate treatment + fluorine coating
Screw tap for inside of exterior panel zinc coating + chromate treatment + fluorine coating zinc coating + chromate treatment + fluorine coating
Corrosion protection treatment complies with regulation of The Japan Refrigeration and Air Conditioning Industry Association (JRA9002)

Caution
Even if the outdoor unit is protected with the anti-salt damage treatment, it cannot be perfectly free from rusting.
The following points should be kept in mind during installation and maintenance of the outdoor units.

Installation
(1) When installing the outdoor unit close to the coastal area, provide a windbreak to protect it from direct sea breeze and
salt water splash.
(2) Select a well-drained place to install.
(3) If any scratch or damages occurred on the outdoor unit during installation, repair it carefully.

Maintenance
(1) Clean salt grains on the outdoor unit with fresh water periodically.
(2) Apply rust preventive at regular intervals for maintenance depending on the conditions at the installation place
(consulting with the withstanding capacity).
(3) Confirm reset of screw tap after maintenance, if missing it may cause corrosion occurred from the hole of screw tap.
(4) During prolonged non operation periods, protect the unit with covering.

49
R410A

Dimensions
All measurements in mm.

FDCS112KXEN6, FDCS112KXES6, FDCS140KXEN6, FDCS140KXES6, FDCS155KXEN6, FDCS155KXES6

I II III
L1 Open Open 500

L2 300 5 Open

A L3 150 300 150

L4 5 5 5

40

51
36
B 100

Terminal block

A A
845

F
279
242

110
110

195

195
10

50
50

55
C 50 15
52
C
970 27 50

E
190 580 200

60 60 60 15
20
40

15
103
55

F
370
410

38

C
150

70
50
20
40

262 388
D 40

C 15 50
VIEW A

Mark Content Notes:


A Service valve connection (gas side) ø15.88 (5/8") (Flare) (1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than
B Service valve connection (liquid side) ø9.52 (3/8") (Flare)
15mm.
C Pipe/cable draw-out hole 4 places (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet
D Drain discharge hole ø20 x 3 places faces perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
E Anchor bolt hole M10 x 4 places (5) A wall in front of the blower outlet must not exceed the units height.
F Cable draw-out hole ø30 x 3 places (6) The model name label is attached on the lower right corner of the front panel.

Refrigerant piping
Outdoor unit (HP) 4 5 6 Branch pipes Header pipe

Gas pipe Furthest indoor unit ø15.88


Liquid pipe =<70m ø9.52

DIS-22-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G

50
Dimensions
All measurements in mm.

FDCS224KXE6G, FDCS280KXE6G, FDCS335KXE6G

B L3 I II II
L2 Intake
A L4 L1 Open Open 1500
G Intake L2 300 5 Open

69
L1
Service Outlet L3 300 300 300
space
43
L4
69
51

5 5 5
60
120 Minimum installation space

Terminal block
1675

B
A

C
640(8.10HP)
634(12HP)

F
G
35

553

35
20

174
84

84
194
159

159
84
F C 54 67 F
C 54
55

55

55
51 14 42 50
1080 14 51

195 690 195 E 989


E C 701
50 30 461
421
39
19

30

141
241
321
361
105
520
480

80
D
19
39

Mark Content 224 280 335 Notes:


(1) It must not be surrounded by walls on the four sides.
A Service valve connection of the (2) The unit must be fixed with anchor bolts. An anchor bolt
ø19.05 (3/4") (Flare) ø19.05 (3/4") (Flare) ø19.05 (3/4") (Flare)
attached connecting pipe (gas side) must not protrude more than 15mm.
B Service valve connection (liquid side) ø9.52 (3/8") (Flare) ø9.52 (3/8") (Flare) ø12.7 (1/2") (Flare) (3) Where the unit is subject to strong winds, the blower
outlet shoud face perpendicularly to the dominant wind
C Pipe/cable draw-out hole 4places 4places 4places direction.
D Drain discharge hole ø20 x 4places ø20 x 4places ø20 x 4places (4) Leave a 1m or more space above the unit.
E Anchor bolt hole M10 x 4places M10 x 4places M10 x 4places (5) A wall in front of the blower outlet must not exceed the
units height.
ø30 x 2places (front) ø30 x 2places (front) ø30 x 2places (front)
(6) The model name label is attached on the lower right
F Cable draw-out hole ø45 (side) ø45 (side) ø45 (side) corner of the front.
ø30 x 2places (back) ø30 x 2places (back) ø30 x 2places (back) (7) Connect the Service valve with local pipe by using the
Connecting position of the local pipe. pipe of the attachment.(Gas side only)
G ø19.05 (3/4")(Brazing) ø22.22 (7/8")(Brazing) ø25.4 (1")(Brazing) (8) Mark shows the connecting position of the local
(gas side)
pipe.(Gas side only)

Refrigerant piping
Outdoor unit (HP) 8 10 12 Branch pipes Header pipe

Gas pipe Furthest indoor unit ø19.05 ø22.22 ø25.4(ø22.22)


Liquid pipe =<90m ø9.52 ø12.7
Gas pipe 90m ø22.22 ø25.4(ø22.22)
Liquid pipe =<Furthest indoor unit ø12.7 DIS-22-1G DIS-371-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G
HEAD8-371-2

51
R410A

Dimensions
All measurements in mm.

FDCS280KXZE1, FDCS335KXZE1

Installation example
Dimensions 1 2

L1 500 Open

Mark Content 280 335 L2 10(30) 10(30)

A Refrigerant gas piping connection pipe ø22.22(Brazing) ø25.4(Brazing) L3 100 100

B Refrigerant liquid piping connection pipe ø9.52(Flare) ø12.7(Flare) L4 10(30) Open

C Refrigerant piping exit hole ø88(or ø100) H1 1500 Open

D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (bottom) H2 No limit No limit

F Anchor bolt hole M10 x 4 places H3 1000 No limit

G Drain waste water hose hole ø45 x 3 places H4 No limit Open

H Drain hole ø20 x 10 places () :In case it is the promised installation location
that the outdoor unit is used on conditions with
K Refrigerant oil equalization piping connection pipe ø9.52(Flare) the ambient temperature of 43ºC or more.

L Carrying in or hole for hanging 230 x 60 Installation example


Dimensions 1 2

L1 500 Open

L2 10(30) 200
When more than one unit is installed
L3 100 300

Wall height
H3
L4 10(30) Open

L3 L5 10(30) 400

L6 10(30) 400
Wall height

Wall height

L2 L5 L6 L4
H2

H4

H1 1500 Open
L1 (Unit front side) H2 No limit No limit
Wall height
H1
H3 1000 No limit

H4 No limit Open

() :In case it is the promised installation location


that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

52
Dimensions
All measurements in mm.

FDCS400KXZE1, FDCS450KXZE1, FDCS475KXZE1, FDCS504KXZE1, FDCS560KXZE1

Installation example
Dimensions 1 2

L1 500 Open

L2 10(30) 10(30)

Mark Content 400 450, 475, 500, 560 L3 100 100

A Refrigerant gas piping connection pipe ø25.4(Brazing) ø28.58(Brazing) L4 10(30) Open

B Refrigerant liquid piping connection pipe ø12.7(Flare) H1 1500 Open

C Refrigerant piping exit hole ø88(or ø100) H2 No limit No limit

D Power supply entry hole ø50 (right . left . front), long hole 40 x 80 (bottom) H3 1000 No limit

F Anchor bolt hole M10 x 4 places H4 No limit Open

G Drain waste water hose hole ø45 x 3 places () :In case it is the promised installation location
that the outdoor unit is used on conditions with
H Drain hole ø20 x 10 places the ambient temperature of 43ºC or more.
K Refrigerant oil equalization piping connection pipe ø9.52(Flare) Installation example
L Carrying in or hole for hanging 230 x 60 Dimensions 1 2

L1 500 Open

L2 10(30) 200

L3 100 300
When more than one unit is installed
L4 10(30) Open

Wall height
H3
L5 10(30) 400

L3 L6 10(30) 400

H1 1500 Open
Wall height

Wall height

L2 L5 L6 L4
H2

H4

H2 No limit No limit
L1 (Unit front side) H3 1000 No limit
Wall height
H1
H4 No limit Open

() :In case it is the promised installation location


that the outdoor unit is used on conditions with
the ambient temperature of 43ºC or more.

53
R410A

Water cooled series


8~36HP (22.4~100.0kW)
Model No. Nominal Cooling Capacity Model No. Nominal Cooling Capacity
FDC224KXZWE1 22.4kW FDC730KXZWE1(FDC224×2+FDC280) 73.0kW
FDC280KXZWE1 28.0kW FDC775KXZWE1(FDC224+FDC280×2) 77.5kW
FDC335KXZWE1 33.5kW FDC850KXZWE1(FDC280×3) 85.0kW
FDC450KXZWE1(FDC224×2) 45.0kW FDC900KXZWE1(FDC280×2+FDC335) 90.0kW
FDC500KXZWE1(FDC224+FDC280) 50.0kW FDC950KXZWE1(FDC280+FDC335×2) 95.0kW
FDC560KXZWE1(FDC280×2) 56.0kW FDC1000KXZWE1(FDC335×3) 100.0kW
FDC615KXZWE1(FDC280+FDC335) 61.5kW
FDC670KXZWE1(FDC335×2) 67.0kW

Features Applicable to
1. High efficiency (EER/COP) 1. High-rise Building 2. Glass-exterior facade Building
• Energy saving Reduction of operation cost! - 50m <FDC> , -100m <FDCH> - Possible to hide KXZW units
- 100m or higher in height <FDCW> and to keep fine sight
2. Compact design
• Easy transportation and installation
• Elevator carrying
3. BMS (Building Management System)
• Can use the same BMS as air-cooled KX
• Available to large-scale and fine control
4. Serviceability & Maintenance
• Service and maintenance of main parts
can be done from the front side only 8, 10, 12HP 16, 18, 20, 22, 24HP 26, 28, 30, 32, 34, 36HP
• Useful service tools (Mente-PC, SL-Checker etc.)
Specifications
Item Model FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC450KXZWE1 FDC500KXZWE1 FDC560KXZWE1 FDC615KXZWE1 FDC670KXZWE1
- - - 224KXZWE1 224KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1
Combination (FDC)
- - - 224KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1 335KXZWE1
Nominal horse power 8HP 10HP 12HP 16HP 18HP 20HP 22HP 24HP
Power source 3 Phase 380-415V, 50Hz
Cooling 22.4 28.0 33.5 45.0 50.0 56.0 61.5 67.0
Nominal capacity kW
Heating 25.0 31.5 37.5 50.0 56.0 63.0 69.0 75.0
Cooling 4.23 5.75 8.13 8.49 9.83 11.5 13.7 16.3
Power consumption kW
Heating 4.24 5.10 6.30 8.47 9.27 10.2 11.4 12.6
EER Cooling 5.3 4.9 4.1 5.3 5.1 4.9 4.5 4.1
COP Heating 5.9 6.2 6.0 5.9 6.0 6.2 6.1 6.0
Exterior dimensions HxWxD mm 1100x780x550 (1100x780x550)x2
Sound pressure level dB(A) 48 50 52 50 52 53 54 55
Net weight kg 185 185x2

Item Model FDC730KXZWE1 FDC775KXZWE1 FDC850KXZWE1 FDC900KXZWE1 FDC950KXZWE1 FDC1000KXZWE1


224KXZWE1 224KXZWE1 280KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1
Combination (FDC) 224KXZWE1 280KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1 335KXZWE1
280KXZWE1 280KXZWE1 280KXZWE1 335KXZWE1 335KXZWE1 335KXZWE1
Nominal horse power 26HP 28HP 30HP 32HP 34HP 36HP
Power source 3 Phase 380-415V, 50Hz
Cooling 73.0 77.5 85.0 90.0 95.0 100
Nominal capacity kW
Heating 82.5 90.0 95.0 100 106 112
Cooling 14.2 15.5 17.5 19.5 21.7 24.3
Power consumption kW
Heating 13.8 14.8 15.4 16.4 17.6 18.8
EER Cooling 5.1 5.0 4.9 4.6 4.4 4.1
COP Heating 6.0 6.1 6.2 6.1 6.0 6.0
Exterior dimensions HxWxD mm (1100x780x550)x3
Sound pressure level dB(A) 54 54 55 56 56 57
Net weight kg 185x3
The data is based on the rating condition:
Cooling: Indoor temp. of 27 °C DB,19 °C WB, and heat source unit inlet water temp. of 30 °C, water flow rate 96 L/min
Heating: Indoor temp. of 20 °C DB,15 °C WB, and heat source unit inlet water temp. of 20 °C, water flow rate 96 L/min

54
Heat source units on every floor Heat source units in the machine room
- New building projects - - Renovation projects -
Total piping length : 510m Total piping length : 510m

Max height difference


Water piping Water piping between indoor units:
Cooling tower
Cooling tower 15m

Refrigeration piping 40m


Height difference
between heat source
unit and indoor unit
(heat source unit below)
Indoor unit
Machine room

To the Height
first branch: difference
Heat source
max 130m 50m
unit

From the first


branch to the
furthest indoor
unit: 90m
Furthest indoor unit Furthest indoor unit
from the heat source unit : 160m from the heat source unit : 160m

Dimensions
All measurements in mm.

VIEW A

A
Piping size
Mark Content FDC-KXZWE1 FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1 Connection method
Dimension
A High/low gas line Refer to piping size 224,280 335 High/low gas line ø19.05 ø22.22 ø25.4 Flange
B - Not to use. C1 142 139 Liquid line ø9.52 ø9.52 ø12.7
Flare
C Liquid line C2 322 316 Oil equalization line ø9.52 ø9.52 ø9.52
Refer to piping size
D Oil equalization line
F Water inlet R1 1/4 Installation
example 1
G Water outlet R1 1/4 Dimension
H Drain outlet Rp 1/2,2places L1 600 or more
J Power source intake ø35 L2 20 or more
K Signal wiring intake ø35 L3 500 or more
L Anchor bolt hole ø18,4places L4 20 or more
L5 300 or more

55
R410A

High Head series (100m) cooling only


14~48HP (40.0~136.0kW)
Model No. Nominal Cooling Capacity Model No. Nominal Cooling Capacity
FDCH335CKXE6G-K 33.5 kW(380V) FDCH735CKXE6G (FDCH335-K+FDCH400) 73.5 kW(380V)
FDCH400CKXE6G 40.0 kW(380V) FDCH800CKXE6G (FDCH400x2) 80.0 kW(380V)
FDCH450CKXE6G 45.0 kW(380V) FDCH850CKXE6G (FDCH400+FDCH450) 85.0 kW(380V)
FDCH504CKXE6G 50.4 kW(380V) FDCH900CKXE6G (FDCH450x2) 90.0 kW(380V)
FDCH560CKXE6G 56.0 kW(380V) FDCH960CKXE6G (FDCH450+FDCH504) 96.0 kW(380V)
FDCH560CKXE6G-K 56.0 kW(380V) FDCH1010CKXE6G (FDCH504x2) 101.0 kW(380V)
FDCH615CKXE6G 61.5 kW(380V) FDCH1065CKXE6G (FDCH504+FDCH560) 106.5 kW(380V)
FDCH680CKXE6G 68.0 kW(380V) FDCH1130CKXE6G (FDCH560x2) 113.0 kW(380V)
FDCH1180CKXE6G (FDCH560-K+FDCH615) 118.0 kW(380V)
FDCH335CKXE6G-K & FDCH560CKXE6G-K are only used for combining with other models.
FDCH1235CKXE6G (FDCH615x2) 123.5 kW(380V)
FDCH1300CKXE6G (FDCH615+FDCH680) 130.0 kW(380V)
• Maximum allowable height difference between the outdoor and FDCH1360CKXE6G (FDCH680x2) 136.0 kW(380V)
the indoor unit located at the lowest height position has been
increased from 50m to 100m.
(When the outdoor unit is located at higher position than the
indoor unit)

• Non-CE Marking models. Blue


Fin
Blue
Fin

FDCH335CKXE6G-K
FDCH400CKXE6G
FDCH450CKXE6G FDCH504~680CKXE6G

Max: 10m Outdoor


Total length: unit Max height difference: Range of operation
1000m 0.4m 50

+43ºC
Height
Max: 5m difference
40
To the
Indoor unit 50~100m
first branch: *2
30
max 130m
Max height
Indoor unit difference 20
From the first between Cooling
branch to the indoor units:
furthest Indoor unit 18m
10

indoor unit:
90m *1 0

-5ºC
-10

Furthest indoor unit : 160m


*1 The difference between the longest and shortest indoor unit piping from the first branch
must be within 40m.
*2 In case of less than 50m, the High Head models can not be applied.
In case Indoor unit is higher than outdoor unit, the High Head models can not be applied.

56
Specifications
Item Model FDCH400CKXE6G FDCH450CKXE6G FDCH504CKXE6G FDCH560CKXE6G FDCH615CKXE6G FDCH680CKXE6G
Nominal horse power 14HP 16HP 18HP 20HP 22HP 24HP
Power source 3 Phase 380V, 60Hz
Starting current A 8
Max current A 47
Nominal capacity Cooling kW 40.0 45.0 50.4 56.0 61.5 68.0
Electrical characteristics Power consumption Cooling kW 11.27 12.97 14.73 16.79 20.37 24.98
Exterior dimensions HxWxD mm 1690x1350x720 2048x1350x720
Net weight kg 326 358 377
Sound pressure level Cooling dB(A) 59.5 62.5 61.5 63.0 64.5 65.0
Type/GWP R410A/2088
Refrigerant
Charge kg/TCO2Eq 11.5/24.012
Liquid line ø12.7(1/2") ø15.88(5/8")
Refrigerant piping size mm(in)
Gas line ø25.4(1") [ø28.58(1 1/8")] ø28.58(1 1/8") ø28.58(1 1/8")
Capacity connection % 50~200 50~160
Number of connectable indoor units 36 40 36 40 44 49

Item Model FDCH735CKXE6G FDCH800CKXE6G FDCH850CKXE6G FDCH900CKXE6G


335CKXE6G-K 400CKXE6G 400CKXE6G 450CKXE6G
Combination (FDCH)
400CKXE6G 400CKXE6G 450CKXE6G 450CKXE6G
Nominal horse power 26HP 28HP 30HP 32HP
Power source 3 Phase 380V, 60Hz
Starting current A 16
Max current A 94
Nominal capacity Cooling kW 73.5 80.0 85.0 90.0
Electrical characteristics Power consumption Cooling kW 20.21 22.54 24.24 25.94
Exterior dimensions HxWxD mm 1690x2700x720
Net weight kg 326x2
Refrigerant charge R410A kg 11.5x2
Liquid line ø19.05(3/4")
Refrigerant piping size mm(in)
Gas line ø31.8(1 1/4") [ø34.92(1 3/8")]
Capacity connection % 50~160
Number of connectable indoor units 53 58 61 65

Item Model FDCH960CKXE6G FDCH1010CKXE6G FDCH1065CKXE6G FDCH1130CKXE6G


450CKXE6G 504CKXE6G 504CKXE6G 560CKXE6G
Combination (FDCH)
504CKXE6G 504CKXE6G 560CKXE6G 560CKXE6G
Nominal horse power 34HP 36HP 38HP 40HP
Power source 3 Phase 380V, 60Hz
Starting current A 16
Max current A 94
Nominal capacity Cooling kW 96.0 101.0 106.5 113.0
Electrical characteristics Power consumption Cooling kW 27.70 29.46 31.52 33.58
Exterior dimensions HxWxD mm 2048x2700x720
Net weight kg 326+358 358x2
Refrigerant charge R410A kg 11.5x2
Liquid line ø19.05(3/4") ø22.22(7/8")
Refrigerant piping size mm(in)
Gas line ø31.8(1 1/4")[ø34.92(1 3/8")] ø38.1(1 1/2")
Capacity connection % 50~160 50~130
Number of connectable indoor units 69 59 62 66

Item Model FDCH1180CKXE6G FDCH1235CKXE6G FDCH1300CKXE6G FDCH1360CKXE6G


560CKXE6G-K 615CKXE6G 615CKXE6G 680CKXE6G
Combination (FDCH)
615CKXE6G 615CKXE6G 680CKXE6G 680CKXE6G
Nominal horse power 42HP 44HP 46HP 48HP
Power source 3 Phase 380V, 60Hz
Starting current A 16
Max current A 94
Nominal capacity Cooling kW 118.0 123.5 130.0 136.0
Electrical characteristics Power consumption Cooling kW 37.16 40.74 45.35 49.96
Exterior dimensions HxWxD mm 2048x2700x720
Net weight kg 377x2
Refrigerant charge R410A kg 11.5x2
Liquid line ø22.22(7/8")
Refrigerant piping size mm(in)
Gas line ø38.1(1 1/2")
Capacity connection % 50~130
Number of connectable indoor units 69 72 76 80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.
4. [ ] : Pipe sizes applicable to European installations are shown in parentheses.

57
R410A

Dimensions
All measurements in mm.

FDCH335CKXE6G-K, 400CKXE6G, 450CKXE6G

Mark Content 335-K 400 450 Installation example


A Refrigerant gas piping connection pipe ø25.4(Brazing) ø28.58(Brazing) Dimensions 1 2

B Refrigerant liquid piping connection pipe ø12.7(Flare) L1 500 Open

C Refrigerant piping exit hole ø88(or ø100) L2 10 10

D Power supply entry hole ø50 (Right . Left . Front), Long hole 40 x 80 (Bottom) L3 100 100

F Anchor bolt hole M10, 4 pcs L4 10 Open

G Drain waste water hose hole ø45, 3 pcs H1 1500 Open

H Drain hole ø20, 10 pcs H2 No limit No limit

K Refrigerant oil equalization piping connection pipe ø9.52(Flare) H3 1000 No limit

L Carrying in or hole for hanging 230 x 60 H4 No limit Open

Notes: When more than one unit is installed Installation example


(1) The unit must be fixed with anchor bolts.
(2) Leave a 2m or larger space above the unit. Wall height
Dimensions 1 2
H3
(3) The unit name plate is attached on the lower right corner of L1 500 Open
the front panel. L3
(4) The ports for refrigerant pipe and power cable penetrations L2 10 200
Wall height

Wall height

L2 L5 L6 L4
are covered with half-blanks. Please cut off a half-blank with
H2

H4

L3 100 300
nippers in using these ports.
(5) Use a ø88 port for refrigerant pipe connection. L1 (Unit front side) L4 10 Open
(6) Anchor holes marked “L J” (four holes for M10) are for a Wall height
H2 L5 0 400
renewal installation.
(7) The oil-equalising pipe K should be used when outdoor units L6 0 400
are used in combination. (For 14,16Hp only) H1 1500 No limit

H2 No limit No limit

H3 1000 No limit

H4 No limit No limit

58
Dimensions
All measurements in mm.

FDCH504CKXE6G, 560CKXE6G, 560CKXE6G-K, 615CKXE6G, 680CKXE6G

Mark Content Installation example


A Refrigerant gas piping connection pipe ø28.58(Brazing) Dimensions 1 2

B Refrigerant liquid piping connection pipe ø12.7(Flare) L1 500 Open

C Refrigerant piping exit hole ø88(or ø100) L2 10 10

D Power supply entry hole ø50 (Right . Left . Front), Long hole 40 x 80 (Bottom) L3 100 100

F Anchor bolt hole M10, 4 pcs L4 10 Open

G Drain waste water hose hole ø45, 3 pcs H1 1500 Open

H Drain hole ø20, 10 pcs H2 No limit No limit

K Refrigerant oil equalization piping connection pipe ø9.52(Flare) H3 1000 No limit

L Carrying in or hole for hanging 230 x 60 H4 No limit Open

Notes:
(1) The unit must be fixed with anchor bolts.
(2) Leave a 2m or larger space above the unit.
(3) The unit name plate is attached on the lower right corner of
the front panel.
(4) The ports for refrigerant pipe and power cable penetrations
are covered with half-blanks. Please cut off a half-blank with
nippers in using these ports.
(5) Use a ø88 port for refrigerant pipe connection.
(6) Anchor holes marked “L J” (four holes for M10) are for a
renewal installation.
(7) The oil-equalising pipe K should be used when outdoor units
are used in combination.

59
R410A

Refresh series
8, 10HP(22.4kW • 28.0kW)
If replacing a used unit with a new one, these units can reuse existing piping. Blue
Fin
Model No. Nominal Cooling Capacity
FDCR224KXE6 22.4kW
FDCR280KXE6 28.0kW
<Option>
FDCR-KIT-E : Service valve kit
• Applies to a wide range of pipe sizes (R22, R407C, R410A standard size).
• Meets to a short period of renewal installation.
• Savings on replacement expenses such as scrapping waste material or procuring new pipe.
• Possible to replace the existing unit with a new larger capacity unit.
• Possible to replace plural systems with one system.
For example:Existing 5HP x 2units can be replaced with a new 10HP x 1unit.

5HP x 2 10HP x 1

Note: FDUT15KXE6F-E, FDTC15KXZE1 and FDK15KXZE1


Total length: 510m can not be connected to the above systems.
Outdoor unit

To the Range of operation


Height difference
first branch: 50m(outdoor unit above)
max 130m 40m(outdoor unit below)
Indoor unit 50
+43ºC
40

Max height 30
From the first Indoor unit difference Cooling
branch to the between 20
+15.5ºC
furthest indoor indoor units: 10
unit: 90m 15m
Indoor unit 0
Heating
-10
-15ºC
Furthest -20
indoor unit: 160m -20ºC

Specifications
Item Model FDCR224KXE6 FDCR280KXE6
Nominal horse power 8HP 10HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 20
Cooling 22.4 28.0
Nominal capacity kW
Heating 25.0 31.5
Power Cooling 5.60 8.09
Electrical characteristics consumption kW
Heating 6.03 8.21
Exterior dimensions HxWxD mm 1675x1080x480
Net weight kg 224
Sound pressure level Cooling/Heating dB(A) 58/58 59/60
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 11.5 / 24.012
Liquid line ø9.52(3/8")~ø15.88(5/8")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4")~ø25.4(1") ø22.22(7/8")~ø28.58(11/8")
Capacity connection % 50~130
Number of connectable indoor units 13 16
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.

60
Advanced refresh function
When the existing unit is operable
The existing pipe can be reused by cooling operation only.
Pipe refresh kit and Service valve kit are not required.
1.Implement cooling operation of all indoor units for more than 30 minutes.
2.Implement pump-down after cooling operation.
3.Recover refrigerant and remove the existing outdoor unit and indoor unit.

When the existing unit is not operable 7-segment display


Pipe refresh kit
(FDCR-KIT-E)
The existing pipe can be reused by washing
operation after connecting Refresh outdoor units,
Pipe refresh kit and Service valve kit.
Piping system
Connecting and removing of Refresh outdoor units outdoor unit
indoor unit

and Pipe refresh kit is very easy by use of flexible heat exchanger

pipe and flanges.


high Service valve kit
efficiency
strainer

1.Pipe washing operation is implemented by changing compressor accumulator

dip switch on the outdoor unit PCB. Pipe refresh kit

2.Completing washing is monitored via 7-segment high efficiency refrigerant flow


display on the outdoor unit PCB. strainer

oil separator easy local connection (flexible pipe)


3.As washing operation is about 60 minutes, it can remove the pipe refresh kit after cleaning the used pipe

meet to a required short period of renewal


installation.

Dimensions
All measurements in mm. Service valve kit

Mark Content Notes:


(1) It must not be surrounded by walls on the four sides.
A Service valve connection of the attached connecting pipe (gas side) ø19.05 (3/4") (Flare) (2) The unit must be fixed with anchor bolts. An anchor bolt must not
B Service valve connection (liquid side) ø12.7 (1/2) (Flare) protrude more the 15mm.
C Pipe/cable draw-out hole 4places (3) Where the unit is subject to strong winds, lay it in such a direction that the
blower outlet faces perpendicularly to the dominant wind direction.
D Drain discharge hole ø20 x 4places (4) Leave 1m or more space above the unit.
E Anchor bolt hole M10 x 4places (5) A wall in front of the blower outlet must not exceed the units height.
F1 Cable draw-out hole ø30 (6) The model name label is attached on the lower right corner of the front.
(7) Connect the Service valve with local pipe by using the pipe of the
F2 Cable draw-out hole ø45 attachment.(Gas side only)
F3 Cable draw-out hole ø22 (8) Mark shows the connecting position of the local pipe.(Gas side only)
F4 Cable draw-out hole ø34
G Connecting position of the local pipe. (gas side) ø25.4 (1")(Brazing)

61
R410A

Refrigerant piping
Installation of Interconnecting Pipework
KXZ/KX6 equipment is manufactured to the highest standards of quality and reliability. It is imperative that the method of installation and the materials used
are also to high standards, to ensure trouble free operation and long term reliability.
The interconnecting pipework must be installed by a competent and trained engineer. Refrigeration quality copper tube must be used, soft copper coils or
half-hard straight lengths. The refrigeration quality tube must be soft drawn seamless high grade copper pipe. The copper tube must be selected taking into
account the higher operating pressures of R410A refrigerant, and that high pressures will occur throughout the system because of the reverse cycle operation.
All pipework material used should be EN12735 European standard.
The supplied branch pipe kits, must be used to make connections to indoor units, and the supplied manifold kits must be used to make connections between
outdoor units (where applicable); it is not permitted to use standard fittings such as elbows, tees etc. The branch pipes shall be installed in accordance with
the manufacturer’s instructions, allowing unrestricted flow of refrigerant, and in accordance with European standard E378.
All brazed joints shall be made with dry nitrogen purge to ensure the prevention of oxidisation to the internal surface of the copper pipes.
The ingress of moisture, dirt and any other contaminants to the interior of the copper pipes, and air conditioning units, must be prevented during the
installation procedure.
After the installation of pipework, prior to the connection of the outdoor units, and sealing of insulation joints, the pipework must be pressure tested for
leakage, using dry nitrogen.

Additional Refrigerant
Only R410A refrigerant shall be used, it must be charged by weight only, using electronic scales. The amount of additional refrigerant must be accurately
calculated from the manufacturer’s data, based on the length and diameter of each section of the liquid refrigerant pipework of the system.

The products contains fluorinated greenhouse gases covered by Kyoto protocol.

Single outdoor unit piping examples:

Piping arrangement using header

HEAD8-371-2

90 90 56 56 36 36 36 36

Piping arrangement using


branch pipe kits

56 56 36 36 36 112 112 112

62
Main (Outdoor unit side branching pipe – Indoor unit side first branching pipe) Branch pipes Header pipe
If the longest distance (measured between the outdoor unit and the farthest indoor unit) is
90m or longer (actual length), please change the main pipe size according to the table below.
Outdoor Main pipe size (normal) Pipe size for an actual length of 90m or longer mm inch
unit Gas pipe Liquid pipe Gas pipe Liquid pipe ø9.52 3/8"
280 ø22.22 × t 1.0 ø9.52 × t 0.8 ø12.7 1/2"
ø25.4 (ø22.22) × t 1.0 ø25.4 (ø22.22) × t 1.0 DIS-22-1G/DIS-180-1G HEAD6-180-1G
335 ø12.7 × t 0.8 ø15.88 5/8"
400 ø25.4 (ø28.58) × t 1.0 ø28.58 × t 1.0 Combination outdoor unit manifold
450 ø19.05 3/4"
475 ø12.7 × t 0.8 ø22.22 7/8"
500 ø31.8 × t 1.1
ø28.58 × t 1.0 (ø28.58 × t 1.0) ø25.4 1"
560 ø15.88 × t 1.0
615
670 mm inch
735 ø28.58 11/8"
800 ø31.8 × t 1.1
DIS-371-1G/DIS-540-3 DOS-2A-3
850 ø31.8 11/4" DOS-3A-3
(ø34.92 × t 1.2) ø15.88 × t 1.0 ø19.05 × t 1.0
900 ø34.92 13/8"
950 ø38.1 11/2" Horizontally
1000
1060 ø44.5 13/4"
Good
1120 ø50.8 2" Floor
1200 ø38.1 × t 1.35
1250 (ø34.92 × t 1.2)
1300 ø38.1 × t 1.35 No Good
1350 (ø34.92 × t 1.2) ø22.22 × t 1.0
1425 ø19.05 × t 1.0 Vertically
Floor
1450
1500
1560 No
Floor
1620
1680
Please use C1220T-1/2H for ø19.05 or larger pipes. Floor
Pipe sizes applicable to European installations are shown in parentheses.

Combination outdoor unit piping examples:

Piping arrangement using


branch pipe kits
Oil equalisation
pipe

Outdoor unit branch


piping set (DOS-2A-3)

112 112 90 90 90 140 140 140

Piping arrangement using header Outdoor unit's branch piping set


Outdoor unit Branch piping set
Oil equalisation
For two units (for 615~1120) DOS-2A-3
pipe HEAD8-540-3
For three units (for 1200~1680) DOS-3A-3
Outdoor unit branch
piping set (DOS-2A-3)
Indoor unit's first branch piping set
Total capacity of Header set
Branch piping set
indoor units Model Branches
~179 DIS-22-1G HEAD4-22-1G Max 4 branches
180~370 DIS-180-1G HEAD6-180-1G Max 6 branches
371~539 DIS-371-1G HEAD8-371-2 Max 8 branches
112 112 90 90 90 140 140 140 540~ DIS-540-3 HEAD8-540-3 Max 8 branches

63
R410A

Electrical wiring – power supply


KXZ/KX6 has greatly simplified wiring requirements utilising a ‘polarity-free’ two wire control loop connecting the indoor units.

Power wiring
Cables can be laid through the front, right, left or bottom of the outdoor unit casing.
Separate power supplies should be used for the outdoor unit (3Phase) and the indoor units (1Phase).
Only control wiring is connected from outdoor to indoor unit.

Outdoor unit power supply: 3 phase 4 wiring 380V Distributed, separate power supply system

Earth leakage breaker A Power cable (Main Power cable)[4 cores]


(Impulse withstanding type) Outdoor unit B Signal wire (Super Link wire)[2 cores]
Grounding C Power cable (Indoor unit power cable)
Circuit breaker [2 cores]
wire
for cabling D Remote control cord
[2 cores]
A A

B B

Circuit breaker
for cabling
Indoor unit
Earth leakage breaker
D
R R R R R R Remote control unit

Indoor unit power supply: Single phase 220V

CAUTION
If the earth leakage breaker is exclusively for ground fault protection, then you will need to install a circuit breaker for wiring work.

64
Electrical wiring – control wiring
1. The control wiring is 5 Volt DC, (1) When one outdoor unit is used
non-polarised, two wire connection
notated as ‘A1’ and ‘B1’. This ‘AB’ wiring Outdoor signal line A1 B1
Indoor and outdoor signal lines do not have a polarity.
Any of the connections in the following illustration can be made.
connects outdoor unit to indoor unit and terminal block
indoor unit to indoor unit.
A1 A A1 A
2. This wiring must be a 2-core shielded
cable size 0.75mm2 or 1.25mm2. Indoor signal line A B A B A B B1 B B1 B
0.75mm2 1.25mm2 terminal block
~1000m YES YES
1000~1500m YES NO
(2) When plural outdoor units are used
3. We recommend both ends of the shield
of the cable are connected to ground Outdoor unit Outdoor unit Outdoor unit Outdoor unit Network connector
(earth) at all the indoor units and outdoor
units.
A1·B1 A2·B2 A1·B1 A2·B2 A1·B1 A2·B2 A1·B1 A2·B2
4. When multiple outdoor units are used,
.Connect the signal cable between indoor
and outdoor units and the signal cable Indoor unit Indoor unit
between outdoor units belonging to the A A
same refrigerant line to A1 and B1. B B
.Connect the signal line between outdoor
units on different refrigerant lines to A2 Refrigerant pipe
Indoor unit Indoor unit
and B2.
A A
5. For current specification of 2-core (AB) B B
wiring, please consult your dealer. Signal line

The maximum number of indoor units that can be connected in a system is 128 and it is possible to configure
outdoor units and/or indoor units as an outdoor or indoor unit group connected with each other with two wires.

(3) The signal lines can also be connected using the method shown below.

Important Loop wiring prohibited


Outdoor unit Outdoor unit Outdoor unit

Outdoor unit Outdoor unit Outdoor unit Outdoor unit

The signal lines cannot form a loop,


Indoor unit Indoor unit Indoor unit so the wirings shown as
in the diagram are prohibited.

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

Remote control wiring specifications


For interconnecting wiring between the remote control Outdoor unit
and indoor units (XY wiring) use 2-core cable size
0.3mm2. The maximum length of 2-core cable is 600 A B
metres. Where the 2-core wiring exceeds 100m, use the
wire size detailed on the table below.
A B A B A B A B
Indoor unit Indoor unit Indoor unit Indoor unit
Length (m) Wire size
100 to 200 0.5mm2 x 2 core
Wires can be connected
To 300 0.75mm2 x 2 core
Remote control across different refrigerant
To 400 1.25mm2 x 2 core systems when wired within
1 Superlink system
To 600 2.0mm2 x 2 core

65
R410A

Indoor units
Benefits Summary When using RC-EX3A (Remote control), functions with symbol
However, for RC-E5 (Remote control), functions with
are available.
are not available.
Inverter control technology functions at high efficiency with smooth operation from high speed to low speed.
Inverter technology A smooth sine voltage wave is attained.

Energy-saving
Energy Saving

Since the capacity is controlled automatically based on the outdoor temperature, energy can be saved without losing comfort.

Motion sensor This sensor detects human activity and shifts the temperature setting according to the amount of activity in the room.

This function ensures that when the room is unoccupied for long periods of time, the unit will
Home leave operation maintain a moderate indoor temperature, avoiding extremely hot or cool temperatures.

Set temperature auto return This function allows you to program a preferred set temperature that the unit will return to each time it is operated.

Automatic operation This function automatically selects the required heating or cooling function based on the current room conditions.
Comfort

This function allows you to program periods where the unit will operate with reduced noise levels, perfect for night time
Silent operation and an uninterrupted sleep.
Use the high power function to quickly reach your optimum temperature level when you first turn on the unit. This function will operate
Hi power operation for a maximum of 15 minutes before returning to normal operation.

Flap control system This function allows you to set the upper and lower limit positions of the flap at each air
outlet individually, providing you with complete control over interior air flow.
The vertical louvers on your unit will move up and down continuously during operation. This function allows you to
Vertical auto swing
Air flow

set the up/down swing position of the louver to your preferred operation angle.
Draft Prevention setting provides a comfortable air flow without any draft feeling. Whether cooling or heating a room, the remote con
Draft prevention setting
can be used to instantly suppress any warm or cool drafts. This accurately assists how air flow is directed out of the indoor unit.

Automatic fan speed The unit’s on-board microcomputer continuously monitors the room’s air temperature and adjusts the air flow automatically.

This function allows you to set a pre-determined amount of time between 30 and 240 minutes that
Sleep timer
your unit will operate for before switching off.
Timer

This function lets you to preset the capacity limit during certain periods of the day, minimising
Peak-cut timer energy consumption during peak billing times, thus reducing operation costs.

Weekly timer Set your unit to turn on and off automatically on a weekly basis to suit your usual room usage on each day.

Function Switch From the eight available functions on the unit, this function allows you to set two functions to operate automatically.

Favourite setting Operation mode, set temperature, fan speed and air flow direction automatically adjust to the programmed favourite setting.

This is operable when connecting duct type indoor units equipped with the external static pressure adjustment function.
Static pressure adjustment It will adjust the airflow accordingly based on the connected duct static pressure.
Convenient

Select the language Set the language to be displayed on the remote control.

Air filter The air filter in the unit traps and removes airborne dust particles and other allergens to provide you with a clean air function.

Filter sign This warning alerts when the filter needs to be cleaned.

Outside air intake This function provides clean fresh air into the room through the external air intake, avoiding the constant recycling of internal

The internal microcomputer automatically runs a diagnostic of the system in the event of a malfunction.
Self diagnostics This enables your authorised dealer to isolate and repair any issues.
Others

Built in drain pump The built-in drain pump, allows greater flexibility with installation, offering a great solution for applications with limited space.

The fan unit (comprised of impeller and motor) is easily accessible from either the side or
Improved serviceability bottom of the unit and can be slid out for easy maintenance.

66
FDT FDTC FDTW FDTS FDTQ FDU FDUM FDUT FDUH FDK FDE FDFW FDFL FDFU FDU-F

(71only)
Option Option Option Option Option Option Option Option Option Option

ntrol
Option Option

(71only)

procure procure
. locally locally
Option Option Option

l air. Option

.
Option
*1 *2

*1 : Except 224 • 280 *2 : Except 1800 • 2400

67
R410A

Ceiling Cassette -4way- Remote control (option)


Wired

FDT
RC-EX3A RC-E5 RCH-E3

Wireless
Model No.
FDT28KXZE1
FDT36KXZE1
FDT45KXZE1
FDT56KXZE1 RCN-T-5AW-E2
FDT71KXZE1
FDT90KXZE1
FDT112KXZE1
FDT140KXZE1
FDT160KXZE1

Draft Prevention Panel (Option)

Draft Prevention Panel (Option)

Draft Prevention Panel prevents cold / hot draft being blown Advanced airflow control technology cultivated through
directly on the user. aircraft development.
It is possible to set Draft Prevention Panel for each air outlet.

Draft prevention
Draft prevention panel working
panel not working Cool
Dry

Draft Prevention Panel working

User can position panels by using the remote controller only


(RC-EX3A, RCN-T-5AW-E2) when Draft Prevention Panel is
available.
Draft Prevention Panel placed at off position

Motion Sensor (Option) Improve the aerodynamic performance of the unit

Motion sensor is equipped in New designed component has better aerodynamic


the corner of the panel and perfromance and achieve lower noise.
detects the presence/absence Motion Sensor

and activity of humans in a New design turbo fan Fan guard


room to improve the comfort (standard equipment)
and energy saving performance
of the unit.

LB-T-5W-E

68
Panel select pattern (Option)

8 patterns of panel are avilable. Installation position of Wireless kit and Motion sensor kit

Standard Panel Corner panel with motion sensor


Motion
T-PSA-5AW-E LB-T-5W-E sensor

Draft Prevention Panel


T-PSAE-5AW-E Corner panel with wireless receiver
RCN-T-5AW-E2
Wireless
receiver
① Standard Panel only
①+③ Standard Panel with corner panel with motion sensor *Wireless receiver and Motion sensor can be installed to the position as shown
①+④ Standard Panel with corner panel with wireless receiver
①+⑤ Standard Panel with corner panel with motion sensor & corner panel with wireless receiver
② Draft Prevention Panel only
②+③ Draft Prevention Panel with corner panel with motion sensor
②+④ Draft Prevention Panel with corner panel with wireless receiver
②+⑤ Draft Prevention Panel with corner panel with motion sensor & corner panel with wireless receiver

Individual flap control system

According to room conditions, four directions


of air flow can be controlled individually by
utilizing the flap control system.
Individual flap control is available even after
installation.

Flap can swing within an


Selected
upper and lower flap range upper position
position within can be
selected with a wired
Max swing
remote control. range
※The wireless remote control is not For person who is far For both persons who are Can cool both the kitchen
Selected from the indoor unit feeling hot or cold and the guests
applicable to the Individual flap lower position
control system.

850mm Drain Pump Suitable for High ceilings

Drain can be discharged upwards by 850mm from the ceiling surface. It allows The Powerful blowout
a piping layout with a high degree of freedom. Depending on the installation of ultra high tap carry
location and 185mm flexible hose as a standard equipment supports easy comfortable air flow to
workability. foot even in high
ceiling. It is ideal for
high ceiling offices and
stores, etc., with a
700 Up to
mm 850 mm wide, uniform air flow
throughout the room.
Flexible hose

Easy check of drain pan

Easy inspection of the


condition of the drain pan
is possible by removing Rubber
corner lid only. stopper

drain cap cover drain cap drain pump port

Remove corner lid. Remove drain cap cover and check the condition. Clean up the area around
It is necessary to clean-up, firstly remove the rubber stopper the drain pump port.
to drain water out and secondly remove the drain cap.

69
R410A

Specifications
Item Model FDT28KXZE1 FDT36KXZE1 FDT45KXZE1 FDT56KXZE1 FDT71KXZE1
Nominal cooling capacity kW 2.8 3.6 4.5 5.6 7.1
Nominal heating capacity kW 3.2 4.0 5.0 6.3 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.04-0.04 0.07-0.07 0.08-0.08
consumption kW
Heating 0.04-0.04 0.07-0.07 0.08-0.08
Sound power level dB(A) 49 50 55 62
Sound pressure level dB(A) P-Hi:38 Hi:33 Me:30 Lo:28 P-Hi:38 Hi:33 Me:31 Lo:29 P-Hi:44 Hi:33 Me:31 Lo:29 P-Hi:47 Hi:35 Me:32 Lo:28
Exterior dimensions
mm Unit:236x840x840 Panel:35x950x950
HxWxD
Net weight kg Unit:20 Standard Panel:5 Unit:21.5 Standard Panel:5
Air flow m3/min P-Hi:20 Hi:14 Me:12 Lo:10 P-Hi:20 Hi:14 Me:12 Lo:10 P-Hi:20 Hi:15 Me:13 Lo:10 P-Hi:26 Hi:16 Me:13 Lo:11 P-Hi:28 Hi:17 Me:14 Lo:12
Outside air intake Possible
Panel T-PSA-5AW-E, T-PSAE-5AW-E
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-T-5AW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")

Item Model FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1


Nominal cooling capacity kW 9.0 11.2 14.0 16.0
Nominal heating capacity kW 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.13-0.13 0.14-0.14
consumption kW
Heating 0.13-0.13 0.14-0.14
Sound power level dB(A) 65 66
Sound pressure level dB(A) P-Hi:49 Hi:38 Me:36 Lo:31 P-Hi:49 Hi:39 Me:37 Lo:31 P-Hi:49 Hi:42 Me:39 Lo:32 P-Hi:49 Hi:42 Me:39 Lo:33
Exterior dimensions
mm Unit:298x840x840 Panel:35x950x950
HxWxD
Net weight kg Unit:25 Standard Panel:5
Air flow m3/min P-Hi:37 Hi:25 Me:22 Lo:15 P-Hi:38 Hi:26 Me:23 Lo:17 P-Hi:38 Hi:28 Me:25 Lo:18 P-Hi:38 Hi:29 Me:26 Lo:19
Outside air intake Possible
Panel T-PSA-5AW-E, T-PSAE-5AW-E
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-T-5AW-E2
Installation data Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line:ø15.88(5/8")

1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

70
Dimensions
All measurements in mm.

FDT28KXZE1
36KXZE1
45KXZE1
56KXZE1
71KXZE1

FDT90KXZE1
112KXZE1
140KXZE1
160KXZE1

71
R410A

Remote control (option)


Ceiling Cassette -4way Compact Wired

FDTC NEW
RC-EX3A RC-E5 RCH-E3

Wireless

Model No.
FDTC15KXZE1 Draft Prevention
FDTC22KXZE1 Panel (option) RCN-TC-5AW-E2
FDTC28KXZE1
FDTC36KXZE1
FDTC45KXZE1
FDTC56KXZE1

European design & Flat panel

Integrated ceiling system design 600x600


A grille designed with a unique structure
Thin Panel
and a clean white panel that blends with the
room. This design was invented by
zweigrad GmbH & Co. KG in Germany.
Big Louver

Taking OA (Outside Air) into inside Indoor Unit FDTC


Unique Grille Design
Fresh air can be taken in without
Compact Design optional parts. When the fresh air is OA Spacer 300mm
insufficient, optional parts can be used.
□700 mm → □620 mm
It’s only 14kg OA Spacer TC-OAS-E2(option) OA OA
Joint Duct TC-OAD-E(option) Ceiling
Height of thin panel and main body is only 248 mm allowing it to be a Surface Panel Joint Duct
very easy installation.

Draft Prevention Panel (Option) Motion Sensor (Option)

Draft Prevention Panel prevents cold/hot draft being blown directly on the user. Motion sensor is equipped in the corner
It is possible to set Draft Prevention Panel for each air outlet. of the panel and detects the
presence/absence and activity of Motion Sensor

humans in a room to improve the


Draft prevention comfort and energy saving performance
Draft prevention panel working of the unit.
panel not working Cool
Dry

LB-TC-5W-E
User can position panels by using the remote controller only (RC-EX3A,
Panel select pattern (Option)
RCN-TC-5AW-E2) when Draft Prevention Panel is available.
Individual flap control system 8 patterns of panel are available. Please refer to P69.

According to room temperature Standard Panel Corner panel with motion sensor
conditions, four directions of air TC-PSA-5AW-E LB-TC-5W-E
flow can be controlled individually
Draft Prevention Panel
by following Flap control system. TC-PSAE-5AW-E Corner panel with wireless receiver
Individual flap control is available even after installation. RCN-TC-5AW-E2

Selected
The flap can swing within the range of upper upper position
850mm Drain Pump
and lower flap position selected with wired
remote control. Max swing Drain can be discharged upward by 850 mm from the ceiling surface close to
range
※The wireless remote control is not applicable the indoor unit. It allows a piping layout with a high degree of freedom
to the Individual flap control system. Selected
lower position depending on the installation location.

72
Specifications
Item Model FDTC15KXZE1 FDTC22KXZE1 FDTC28KXZE1 FDTC36KXZE1 FDTC45KXZE1 FDTC56KXZE1
Nominal cooling capacity kW 1.5 2.2 2.8 3.6 4.5 5.6
Nominal heating capacity kW 1.7 2.5 3.2 4.0 5.0 6.3
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.03-0.03 0.04-0.04 0.05-0.05 0.06-0.06
consumption Heating kW 0.03-0.03 0.04-0.04 0.05-0.05 0.06-0.06
Sound power level dB(A) Cooling:47 Heating:46 49 Cooling:54 Heating:53 Cooling:58 Heating:57 60
Sound pressure Cooling P-Hi:33 Hi:30 Me:28 Lo:25 P-Hi:35 Hi:32 Me:29 Lo:25 P-Hi:39 Hi:36 Me:31 Lo:26 P-Hi:43 Hi:39 Me:36 Lo:28 P-Hi:47 Hi:43 Me:39 Lo:31
dB(A)
level Heating P-Hi:33 Hi:30 Me:26 Lo:22 P-Hi:35 Hi:32 Me:29 Lo:25 P-Hi:39 Hi:36 Me:31 Lo:26 P-Hi:43 Hi:39 Me:36 Lo:28 P-Hi:47 Hi:43 Me:39 Lo:31
Exterior dimensions
mm Unit:248x570x570 Panel:10x620x620
HxWxD
Net weight kg Unit:12.5 Standard Panel:2.5 Unit:13 Standard Panel:2.5 Unit:14 Standard Panel:2.5
Cooling P-Hi:8 Hi:7 Me:6 Lo:5 P-Hi:9 Hi:8 Me:7 Lo:6 P-Hi:10 Hi:9 Me:8 Lo:6 P-Hi:12 Hi:10 Me:9 Lo:7 P-Hi:14 Hi:12 Me:10 Lo:8
Air flow m3/min
Heating P-Hi:8 Hi:7 Me:6 Lo:5 P-Hi:9 Hi:8 Me:7 Lo:6 P-Hi:10 Hi:9 Me:8 Lo:6 P-Hi:12 Hi:10 Me:9 Lo:7 P-Hi:14 Hi:12 Me:10 Lo:8
Outside air intake Possible
Panel TC-PSA-5AW-E, TC-PSAE-5AW-E
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-TC-5AW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

Dimensions
All measurements in mm.

73
R410A

Ceiling Cassette -2way- Remote control (option)


Wired

FDTW FDTW28~71

RC-EX3A RC-E5 RCH-E3


Model No.
Wireless
FDTW28KXE6F FDTW90KXE6F
FDTW45KXE6F FDTW112KXE6F
FDTW56KXE6F FDTW140KXE6F
FDTW71KXE6F
RCN-TW-E2
FDTW90~140

Individual flap control system Installation workability

According to room temperature conditions, four directions air Drainage spout


flow can be controlled individually by flap control system.
Due to optimization of outlet design of air flow our new advanced
technology, sufficient air flow is secured and long reach of air Drainage flow test can be
flow is achieved. done easily by use of this
3 drainage spout.

Transparent access hole to drain pan

Condition of the A cross is visible Invisible


bottom of a drain
pan can be checked Cleaning Cleaning
1 2 4 through this not required required
transparent access
The flap can swing within the Selected hole without
range of upper and lower flap upper position removing drain pan. A circumscribes Invisible
position selected with wired circle is visible

remote control.

* The wireless remote control is not


Max swing
range
Motion Sensor
NEW (Option)

applicable to the individual flap Selected Motion sensor is equipped in the corner
Motion Sensor
control system. lower position of the panel and detects the
presence/absence and activity of humans
750mm Drain Pump in a room to improve the comfort and
energy saving performance of the unit.
Drain can be discharged upward by 750mm from the ceiling
surface close to the indoor unit.
It allows a piping layout with a high degree of freedom
depending on the installation location.

Specifications LB-TW-6W

Item Model FDTW28KXE6F FDTW45KXE6F FDTW56KXE6F FDTW71KXE6F FDTW90KXE6F FDTW112KXE6F FDTW140KXE6F


Nominal cooling capacity kW 2.8 4.5 5.6 7.1 9.0 11.2 14.0
Nominal heating capacity kW 3.2 5.0 6.3 8.0 10.0 12.5 16.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.09-0.09 0.10-0.10 0.14-0.14 0.19-0.19
consumption Heating kW 0.09-0.09 0.10-0.10 0.14-0.14 0.19-0.19
Sound power level dB(A) 58 65
Sound pressure level dB(A) P-Hi:42 Hi:38 Me:34 Lo:31 P-Hi:48 Hi:45 Me:41 Lo:37
Exterior dimensions
mm Unit:325x820x620 Panel:20x1120x680 Unit:325x1535x620 Panel:20x1835x680
HxWxD
Net weight kg Unit:20 Panel:8.5 Unit:21 Panel:8.5 Unit:23 Panel:8.5 Unit:35 Panel:13
Air flow m3/min P-Hi:14.5 Hi:12 Me:10 Lo:9 P-Hi:31 Hi:27 Me:23 Lo:20
Outside air intake Possible
Panel TW-PSA-26W-E TW-PSA-46W-E
Air filter, Q’ty Pocket Plastic net x2 (Washable) Pocket Plastic net x3 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-TW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

74
Dimensions
All measurements in mm.

FDTW28KXE6F, 45KXE6F, 56KXE6F, 71KXE6F

VP25 (O.D. 32)


102

650
102

FDTW90KXE6F, 112KXE6F, 140KXE6F

VP25 (O.D. 32)


102

650
102

75
R410A

Ceiling Cassette -1way- Remote control (option)


Wired Wireless

FDTS
Model No.
RC-EX3A RC-E5 RCH-E3
FDTS45KXE6F
FDTS71KXE6F

RCN-TS-E2

Individual flap control system Compact design

Two directions of air flow can be controlled individually by Indoor unit size (W:1,150 x
flap control system. D:565) brings easy installation for
1,200 x 600 ceiling and Panel size
(1,250 x 650) is suitable for 1,200 220mm
x 600 ceiling. Height is the
industry's lowest height level
220mm and weight is 27/28kg
only.

Motion Sensor NEW (Option)

Motion sensor is equipped in the


The flap can swing within the ceiling plane or wall plane and detects
Selected Motion
range of upper and lower flap upper position
the presence/absence and activity of Sensor
position selected with wired humans in a room to improve the
remote control. comfort and energy saving
Max swing performance of the unit.
range

Selected
lower position

*The wireless remote control is not applicable to the individual flap control system.
Wireless remote control
LB-KIT
For wireless remote
control simply attach 600mm Drain Pump
an additional panel
with infrared receiver Drain can be discharged upward by 600mm from the
on the right side of ceiling surface close to the indoor unit.
the main decorative It allows a piping layout with a high degree of freedom
panel. RCN-TS-E2 depending on the installation location.

Specifications
Item Model FDTS45KXE6F FDTS71KXE6F
Nominal cooling capacity kW 4.5 7.1
Nominal heating capacity kW 5.0 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.04-0.04 0.09-0.09
consumption Heating kW 0.04-0.04 0.09-0.09
Sound power level dB(A) 60 61
Sound pressure level dB(A) P-Hi:42 Hi:40 Me:38 Lo:35 P-Hi:49 Hi:46 Me:41 Lo:36
Exterior dimensions
mm Unit:220x1150x565 Panel:35x1250x650
HxWxD
Net weight kg Unit:27 Panel:5 Unit:28 Panel:5
Air flow m3/min P-Hi:13 Hi:12 Me:11 Lo:9.5 P-Hi:17 Hi:15 Me:12 Lo:9.5
Outside air intake Possible
Panel TS-PSA-3AW-E
Air filter, Q’ty Pocket Plastic net x2 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-TS-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

76
Dimensions
All measurements in mm.

77
R410A

Ceiling Cassette -1way Compact-


FDTQ Remote control (option)
Model No. Fits into standard Wired
FDTQ22KXE6F 600 x 600 ceiling
FDTQ28KXE6F
FDTQ36KXE6F
RC-EX3A RC-E5 RCH-E3

Wireless

RCN-KIT4-E2

Compact design

• Comfortable effective cooling for small rooms,


with low fan speed air flow at just 5.4m3/min.

Fresh air
Holes for opening
tapping screws for ducting
(Knock out)
Max.Drain up

250
295~325

285
63
600 or less

35
210

Optional wide panel shown for solid ceiling Condensate drain pump Ultra slim design at just 250mm above the ceiling
included as standard

Specifications
Item Model FDTQ22KXE6F FDTQ28KXE6F FDTQ36KXE6F
Panel Name Direct blow panel Duct panel Direct blow panel Duct panel Direct blow panel Duct panel
Panel mode (Option) TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER
Nominal cooling capacity kW 2.2 2.8 3.6
Nominal heating capacity kW 2.5 3.2 4.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.05-0.07 0.05-0.07 0.05-0.07
consumption Heating kW 0.05-0.07 0.05-0.07 0.05-0.07
Sound power level dB(A) 60
Sound pressure level dB(A) P-Hi:45Hi:41 Me:38 Lo:33 P-Hi:45 Hi:41 Me:38 Lo:33 P-Hi:45 Hi:41 Me:38 Lo:33
Exterior dimensions Unit 250x570x570 250x570x570 250x570x570
HxWxD mm
Panel 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650
Net weight kg Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3
Air flow m3/min P-Hi:8 Hi:7 Me:6 Lo:5 P-Hi:8 Hi:7 Me:6 Lo:5 P-Hi:8 Hi:7 Me:6 Lo:5
Outside air intake Possible
Air filter, Q’ty Pocket Plastic net x1 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are based on the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

78
Dimensions
All measurements in mm.

Direct blow panel (TQ-PSA-15W-E) Direct blow panel (TQ-PSB-15W-E)

Duct panel (QR-PNA-14W-ER) Duct panel (QR-PNB-14W-ER)

* In case of Direct blow panel

Dimension Table Unit:mm Dimension Table Unit:mm

model a b c d model a b c

TQ-PSA-15W-E 625 514 650 580 QR-PNA-14W-ER 625 650 580

TQ-PSB-15W-E 780 514 650 580 QR-PNB-14W-ER 780 650 580

79
R410A

Duct Connected -High Static Pressure- Remote control (option)

FDU
Wired

Model No.
FDU45KXE6F
RC-EX3A RC-E5 RCH-E3
FDU56KXE6F
FDU71KXE6F Wireless
FDU90KXE6F
FDU112KXE6F
FDU140KXE6F
FDU160KXE6F RCN-KIT4-E2

Model No.
FDU224KXZE1
FDU280KXZE1

External Static Pressure(E.S.P) control Thin design

The External Static Pressure (E.S.P.)


can be manually set on the wired 280mm
remote controller. Indoor unit will
control the fan speed to keep rated air Previous Current
flow volume at each fan speed setting. FDU71KXE6F 297 280 17mm less!!
You can set required E.S.P. by wired FDU112/140KXE6F 350 280 70mm less!!
remote controller, calculated with the E.S.P. button RC-E5
set air flow rate and the pressure loss External Static Pressure (E.S.P.)
of the duct. can be set by E.S.P. button. Reduction of sound pressure level

(FDU71KXE6F, in the Lo mode)

Previous
Duct FDU Duct Longer Duct

Ceiling Current 12dB less!!


Keep the same 0 5 10 15 20 25 30 35 40 dB(A)
air flow volume
Previous Current Lo mode
case1 case2 FDU90KXE6F 37 25 12dB(A) less!!
FDU112KXE6F 38 30 8dB(A) less!!
Setting No. No.8 No.9 No.10 No.11 No.12 No.13 No.14 No.15 FDU140KXE6F 39 29 10dB(A) less!!
E.S.P. 80Pa 90Pa 100Pa 110Pa 120Pa 130Pa 140Pa 150Pa
Transparent inspection window
*Range of 80~150 Pa is set at ex-factory default.
Range of 10~200 Pa is available by setting SW8-4 switch on at site. Dirt condition of the bottom of a drain pan can be checked through
this transparent inspection window without removing drain pan.
<Expansion of external static pressure range> (Please refer to P74)
Previous Current
10~130Pa 10~200Pa Improvement of the serviceability
Motion Sensor
NEW (Option)
Fan unit (impeller and motor) can
Pipe
be pulled out from the right side
Motion sensor is equipped in the of the unit. Maintenance can be Fan unit
ceiling plane or wall plane and detects available from the right side or
Motion
the presence/absence and activity of Sensor the bottom side.
humans in a room to improve the (Common for FDUM22~160KXE6F
comfort and energy saving & FDU45~160KXE6F)
performance of the unit.

LB-KIT

80
Specifications
Item Model FDU45KXE6F FDU56KXE6F FDU71KXE6F FDU90KXE6F FDU112KXE6F FDU140KXE6F FDU160KXE6F
Nominal cooling capacity kW 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Nominal heating capacity kW 5.0 6.3 8.0 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.10-0.10 0.24-0.25 0.31-0.32 0.35-0.36 0.42-0.43
consumption Heating kW 0.10-0.10 0.24-0.25 0.31-0.32 0.35-0.36 0.42-0.43
Sound power level dB(A) 60 65
Sound pressure level dB(A) P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:44 Hi:38 Me:36 Lo:30 P-Hi:45 Hi:40 Me:34 Lo:29 P-Hi:47 Hi:40 Me:35 Lo:30
Exterior dimensions
mm 280x750x635 280x950x635 280x1370x740
HxWxD
Net weight kg 29 34 54
Air flow m3/min P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:36 Hi:28 Me:25 Lo:19 P-Hi:39 Hi:32 Me:26 Lo:20 P-Hi:48 Hi:35 Me:28 Lo:22
Maximum external static pressure Pa 200
Outside air intake Possible
Air filter Procure locally
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static pressure of
indoor unit is 60Pa.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

Item Model FDU224KXZE1 FDU280KXZE1


Nominal cooling capacity kW 22.4 28.0
Nominal heating capacity kW 25.0 31.5
Power source 1 Phase 220-240V, 50Hz
Power Cooling 1.16-1.20 1.16-1.20
consumption Heating kW 1.16-1.20 1.16-1.20
Sound pressure level dB(A) P-Hi:52 Hi:50 Me:47 Lo:45
Exterior dimensions
mm 379x1600x893
HxWxD
Net weight kg 89
Air flow m3/min P-Hi:80 Hi:72 Me:64 Lo:56
Maximum external static pressure Pa 200
Outside air intake Possible(on return duct)
Air filter Procure locally
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø9.52(3/8") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø19.05(3/4") Gas line:ø22.22(7/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static pressure of
indoor unit is 72Pa.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

81
R410A

Dimensions
All measurements in mm.

FDU45KXE6F, 56KXE6F

FDU71KXE6F, 90KXE6F

82
FDU112KXE6F, 140KXE6F, 160KXE6F

FDU224KXZE1, 280KXZE1

83
R410A

Duct Connected -Low/Middle Static Pressure-


FDUM Remote control (option)
Model No. Wired
FDUM22KXE6F FDUM71KXE6F
FDUM28KXE6F FDUM90KXE6F
FDUM36KXE6F FDUM112KXE6F
FDUM45KXE6F FDUM140KXE6F
RC-EX3A RC-E5 RCH-E3
FDUM56KXE6F FDUM160KXE6F
Wireless

Filter kit (option)


UM-FL1EF : for 22~56
UM-FL2EF : for 71, 90
UM-FL3EF : for 112, 140, 160
*Filter pressure loss:5pa RCN-KIT4-E2

Automatic external static pressure (E.S.P.) control Thin design


Duct design was simplified. Using DC motor, the most optimum air The height of all FDUM models is only 280mm.
flow volume can be achieved by this automatic control.
Indoor unit will recognize external static pressure by itself 70mm less
automatically and keep rated air flow volume. H 350

E.S.P. button RC-E5 H 280


Duct FDUM Duct Longer Duct
External static pressure

Ceiling
(E.S.P.) can be set by
E.S.P. button.
FDUM112/140KXE6F
Keep the same
19mm less
air flow volume
H 299
case1 case2
H 280
Setting No. No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9 No.10
E.S.P. 10Pa 20Pa 30Pa 40Pa 50Pa 60Pa 70Pa 80Pa 90Pa 100Pa
FDUM22~90KXE6F

Motion Sensor NEW (Option) Transparent inspection window

Motion sensor is equipped in the Motion


Sensor
Dirt condition of the bottom of a drain pan can be checked
ceiling plane or wall plane and detects through this transparent inspection window without
the presence/absence and activity of removing drain pan. (Please refer to P74)
humans in a room to improve the
comfort and energy saving
performance of the unit.

LB-KIT
Specifications
Item Model FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F FDUM45KXE6F FDUM56KXE6F FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6F
Nominal cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Nominal heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.10-0.10 0.20-0.20 0.29-0.29 0.33-0.33 0.45-0.45
consumption Heating kW 0.10-0.10 0.20-0.20 0.29-0.29 0.33-0.33 0.45-0.45
Sound power level dB(A) 60 65
Sound pressure level dB(A) P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:44 Hi:38 Me:36 Lo:30 P-Hi:45 Hi:40 Me:34 Lo:29 P-Hi:47 Hi:40 Me:35 Lo:30
Exterior dimensions
mm 280 x 750 x 635 280 x 950 x 635 280 x 1370 x 740
HxWxD
Net weight kg 29 34 54
Air flow m3/min P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:36 Hi:28 Me:25 Lo:19 P-Hi:39 Hi:32 Me:26 Lo:20 P-Hi:48 Hi:35 Me:28 Lo:22
Maximum external
Pa 100
static pressure
Outside air intake Possible
Air filter Filter kit:UM-FL1EF/UM-FL2EF/UM-FL3EF(option)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static pressure of
indoor unit is 35Pa(22/28/36/45/56/71/90), 60Pa(112/140/160).
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

84
Dimensions
All measurements in mm.

FDUM22KXE6F, 28KXE6F, 36KXE6F, 45KXE6F, 56KXE6F


Space for installation and service
786(Suspension bolts pitch) Select either of two cases to keep space for installation and services. Symbol Content
(Case 1) From side of unit 22,28 36,45,56
Hanger plate for 18 750 18 Model

or more
suspension bolt 4-φ4 4-φ4 Note (b) A Gas piping φ9.52(3/8")(Flare) φ12.7(1/2")(Flare)
284

20
or more
Holes for Holes for B Liquid piping φ6.35(1/4")(Flare)
152 262

100
81 tapping screws Slab
tapping screws VP20(I.D.20,O.D.26)(Standard)
φ124 C1 Drain piping or VP25(I.D.25,O.D.32)
28

Control box (Used with attached socket) Note(2)

1000 or more

or more
H Ceiling 370

20
VP20(I.D.20,O.D.26)(Standard)
F
139

150~
Drain piping

200
C2 or VP25(I.D.25,O.D.32)
Note (a) Pipe (c) (Gravity drainage)
(Used with attached socket)

113
472

Fan unit D Hole for wiring


69 C1 φ170 100~200
G φ170
Notes (a) There must not be obstacle to draw
E Suspension bolts (M10)
(Suspension bolts pitch)

Hole □90 Outside air opening


out fan unit. For fan unit maintenance, F (φ150)(Knock out)
B F G refer to page 29. for ducting
135

(b) Install refrigerant pipes, Air outlet opening


A View M drain pipe,and wiring so as Note (a)
G
for ducting
(φ125)(Knock out)
58 not to cross marked area. H Inspection hole (450X450)
(c) The case that pipes are installed to upper (bottom) of fan unit, Notes(1) The model name label is attached on the lid of the control box.
67 keep space of 60mm or more to upper (bottom) of unit.
(2) Prepare the connecting socket (VP20 or VP25) on site.
(Max. drain lift)

200(Duct dimension)
30 635 30
170 (Duct dimension)

510 65 660(Duct dimension) 65


E 295~325
(Case 2) From bottom of unit
471 46 200 200 200 46
Air supply duct

or more
413 Drain hose piece

100
105
43

1100
41
15

(Accessory)
31
600 or less

(Installed on site) Inspection


175

or more
M
250
280

170

hole

600
76
50

D 620
31

C2
39

Return air duct


55 680(Duct dimension) 55 467 12-φ4
Holes for
tapping screw
Unit:mm

FDUM71KXE6F, 90KXE6F
Space for installation and service
986(Suspension bolts pitch) Select either of two cases to keep space for installation and services.
18 950 18 (Case 1) From side of unit
Hanger plate for
4-φ4 4-φ4 Symbol

or more
suspension bolt 284 Note (b) Content

20
Holes for 152 262 Holes for A Gas piping
or more

φ15.88(5/8")(Flare)
81
100

tapping screws tapping screws Slab B Liquid piping φ9.52(3/8")(Flare)


φ124
28

Control box VP20(I.D.20,O.D.26)(Standard)


C1 Drain piping or VP25(I.D.25,O.D.32)
1000 or more

or more
H Ceiling 370
F (Used with attached socket) Note(2)
139

20
150~
200

VP20(I.D.20,O.D.26)(Standard)
Note (a) Pipe (c)
C2 Drain piping or VP25(I.D.25,O.D.32)
113
472

(Gravity drainage)
69 C1 φ170 100~200
Fan unit (Used with attached socket)
G φ170 D Hole for wiring
(Suspension bolts pitch)

Hole □90 Notes (a) There must not be obstacle to draw E Suspension bolts (M10)
B F G out fan unit. For fan unit maintenance, Outside air opening
135

refer to page 29. F for ducting (φ150)(Knock out)


A View M (b) Install refrigerant pipes,
drain pipe,and wiring so as Air outlet opening
Note (a) G (φ125)(Knock out)
58 not to cross marked area. for ducting
67 (c) The case that pipes are installed to upper (bottom) of fan unit, H Inspection hole (450X450)
(Max. drain lift)

30 635 30 keep space of 60mm or more to upper (bottom) of unit. Notes(1) The model name label is attached on the lid of the control box.
200(Duct dimension)

(2) Prepare the connecting socket (VP20 or VP25) on site.


170 (Duct dimension)

510
E 65 860(Duct dimension) 65
295~325 471
46 4×200=800 46
Air supply duct 413 200 Drain hose piece (Case 2) From bottom of unit
105

(Accessory)
43

41
15

or less

31

(Installed on site)

or more
100
175

1300
M
250
600

170
280
76
50

D Inspection

or more
hole

600
31

C2 467
39

Return air duct 620


14-φ4
55 880(Duct dimension) 55 Holes for
tapping screw

FDUM112KXE6F, 140KXE6F, 160KXE6F


Space for installation and service Symbol Content
1404(Suspension bolts pitch) Select either of two cases to keep space for installation and services. A Gas piping φ15.88(5/8")(Flare)
18 1368 18 (Case 1) From side of unit B Liquid piping φ9.52(3/8")(Flare)
Hanger plate for 284
or more

4-φ4 4-φ4 Note (b) VP20(I.D.20,O.D.26)(Standard)


suspension bolt
20

Holes for Holes for C1 Drain piping or VP25(I.D.25,O.D.32)


81
or more

152 285
100

tapping screws tapping screws Slab (Used with attached socket) Note(2)
28

φ124 Drain piping


VP20(I.D.20,O.D.26)(Standard)
Control box C2 or VP25(I.D.25,O.D.32)
(Suspension bolts pitch)

1000 or more

(Gravity drainage)
or more

H
F Ceiling 370 (Used with attached socket)
20
139

150~
200

D Hole for wiring


Note (a) Pipe (c)
B
113

E Suspension bolts (M10)


530

Fan unit Outside air opening


φ170 100~200
G A φ170 F
for ducting
(φ150)( Knock out)

71 Hole □90 Notes (a) There must not be obstacle to draw Air outlet opening
C1 F G out 2 fan unit. For fan unit maintenance,
refer to page 29.
G
for ducting
(φ125)( Knock out)
180

H Inspection hole
View M (b) Install refrigerant pipes,
drain pipe,and wiring so as Note (a)
(450X450)
Notes(1) The model name label is attached on the lid of the control box.
not to cross marked area. (2) Prepare the connecting socket (VP20 or VP25) on site.
59 (c) The case that pipes are installed to upper (bottom) of fan unit,
keep space of 60mm or more to upper (bottom) of unit.
69
600 or less (Max. drain lift)

30 738 30
235(Duct dimension)
170 (Duct dimension)

635 (Case 2) From bottom of unit


E 295~325 64 1280(Duct dimension) 64
468
Air supply duct 100 4×280=1120 100
405
or more
184.5
134.5

100

280
23.5
24.5

1720

Return air duct


43
15

Inspection
or more

hole
600

M
250
280
45

205

725
92

D
C2 467
24.5

14-φ4
21.5

Drain hose piece


104 1200(Duct dimension) 104 Holes for (Accessory)
tapping screw
(Installed on site)

Improvement of the serviceability


Fan unit (impeller and motor) can be Pipe
pulled out from the right side or the Unit Fan unit
Maintenance
bottom side of the unit. Maintenance hole
can be available from the right side or
Service
the bottom side. space

(mm)

85
R410A

Duct Connected (thin) -Low Static Pressure-


FDUT
Remote control (option)
Wired

Model No.
FDUT15KXE6F-E
FDUT22KXE6F-E
RC-EX3A RC-E5 RCH-E3
FDUT28KXE6F-E
Wireless
FDUT36KXE6F-E
FDUT45KXE6F-E
FDUT56KXE6F-E
FDUT71KXE6F-E
RCN-KIT4-E2

Compact design Lower noise

<FDUT15~56KXE6F-E> Larger outlet for connecting duct <FDUT28KXE6F-E> Previous


L700 x 70mm L860 x 99 (45/56) Previous
Height: 220  200mm Current Current
1dB(A)
20mm less!! 1m
Unit [dB(A)] Down
2dB(A)
[dB(A)] 5dB(A)
Down
1m 30 40
Down 4dB(A)
Access to Down
control 2m 1m 30
1.5m
20
29 28 37
20
Depth: 520  500mm 24 32 30
10 22
Access to control 10 26
Measured based on JIS B 8616
0 0
Access to fan motor Access to fan motor Hi Lo
Hi Lo
Fan speed Fan speed
Previous Model Current Model

Motion Sensor
NEW (Option) Duct kit and filter options

Item Contents for FDUT15/22/28/36KXE6F-E for FDUT45/56KXE6F-E for FDUT71KXE6F-E


Motion sensor is equipped in the
Outlet duct plate 1 UT-SAT1EF UT-SAT2EF UT-SAT3EF
ceiling plane or wall plane and detects
Motion Filter set 2+3 UT-FL1EF UT-FL2EF UT-FL3EF
the presence/absence and activity of Sensor
humans in a room to improve the Filter pressure loss : 5 Pa
comfort and energy saving
performance of the unit. 2 Filter fixing plate

3 Filter
1 Outlet duct plate
LB-KIT ※Applied for 71 only

Specifications
Item Model FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E FDUT45KXE6F-E FDUT56KXE6F-E FDUT71KXE6F-E
Nominal cooling capacity kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1
Nominal heating capacity kW 1.7 2.5 3.2 4.0 5.0 6.0 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.06-0.06 0.07-0.07 0.08-0.08 0.08-0.08
consumption Heating kW 0.06-0.06 0.07-0.07 0.08-0.08 0.07-0.07
Sound power level dB(A) 52 57 58 59
Sound pressure level 1 dB(A) Hi:28 Me:26 Lo:22 Hi:28 Me:26 Lo:22 Hi:33 Me:30 Lo:26 Hi:34 Me:32 Lo:28 Hi:35 Me:33 Lo:30 Hi:35 Me:31 Lo:28
Sound pressure level 2 dB(A) Hi:32 Me:29 Lo:25 Hi:32 Me:29 Lo:26 Hi:37 Me:34 Lo:28 Hi:36 Me:33 Lo:27 Hi:38 Me:33 Lo:29 Hi:41 Me:37 Lo:32
Exterior dimensions
mm 200x750x500 200x950x500 220x1150x565
HxWxD
Net weight kg 21 22 25 31
Air flow (Standard) m3/min Hi:6 Me:5 Lo:4 Hi:7.5 Me:6 Lo:5 Hi:8.5 Me:7 Lo:5.5 Hi:11.5 Me:9 Lo:7 Hi:12.5 Me:9 Lo:7.2 Hi:16 Me:13 Lo:9.5
External Static pressure Pa Standard:10, Max:35 Standard:10, Max:50
Outside air intake Possible from return duct
Air filter Filter set:UT-FL1EF/UT-FL2EF/UT-FL3EF(option)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. External static pressure of
indoor unit is 10Pa.
2. The data of nominal cooling and heating capacity and sound pressure level are measured with 10Pa of external static pressure.
3. The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
4. Sound pressure levels are values when 2m supply duct and 1m return duct are connected.
1 : Mike position is 1.5m below unit, 2 : Mike position is 1m in front and 1m below the air supply duct.

86
Dimensions
All measurements in mm.
FDUT15KXE6F-E, 22KXE6F-E, 28KXE6F-E, 36KXE6F-E

FDUT45KXE6F-E, 56KXE6F-E

FDUT71KXE6F-E

87
R410A

Duct Connected (Compact & Flexible) Remote control (option)


Wired

FDUH
RC-EX3A RC-E5 RCH-E3
Model No.
Wireless
FDUH22KXE6F
FDUH28KXE6F Drain up kit (option)
FDUH36KXE6F (600mm)
UH-DU-E
RCN-KIT4-E2

Filter kit (option)


UH-FL1E

*Filter pressure loss:5pa

Compact and thin size, light weight Quiet operation


Our leading high technology has realized the 570mm The lowest sound level in the industry can ensure
best solution for air conditioning in hotels with comfortable stay and rest in hotels.
compact and thin size units and high energy 257
efficiency. In addition, weight is only 20kg. mm

530m
m

Installation Flexibility
Control box and drain piping can be installed on both side of the unit and air intake Wired remote control
to the unit is available from bottom or back side. Our highest technology can satisfy
diverse installation requirements.
Control box
Simple remote control
Designed specially for
hotel rooms, control
buttons are limited only to
the minimum required
functions such as ON/OFF,
mode, temperature setting
RCH-E3 and fan speed. It is really
(option) simple and easy to use.

Drain piping

Specifications
Item Model FDUH22KXE6F FDUH28KXE6F FDUH36KXE6F
Nominal cooling capacity kW 2.2 2.8 3.6
Nominal heating capacity kW 2.5 3.2 4.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.05-0.07
consumption Heating kW 0.05-0.07
Sound power level dB(A) 60
Sound pressure level dB(A) P-Hi:39 Hi: 33 Me: 30 Lo: 27
Exterior dimensions HxWxD mm 257x570x530
Net weight kg 22
Air flow m3/min P-Hi:8.5 Hi: 7 Me: 6.5 Lo: 6
External static pressure Pa 30
Outside air intake Possible from return duct
Air filter Filter kit:UH-FL1E(option)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
mm(in)
Refrigerant piping size Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

88
Dimensions
All measurements in mm.

53
30.8

83.3
32.5
Symbol Content
Model FDUH22KXE6F,28KXE6F FDUH36KXE6F
A Gas piping ø9.52 (3/8") (Flare) ø12.7 (1/2") (Flare)

(Duct dimension)
B Liquid piping ø6.35 (1/4") (Flare)

100
145
C1,C2 Drain piping VP20(I.D.20, O.D.26) Note (2)
D Hole for wiring ø30

32.5
12-ø4 E Suspension bolts (M10)
Holes for 32 150 150 150 32 F Inspection hole (635X890) Note (3)
tapping screws Supply air duct
27.6 494 27.6
(Duct dimension)

Drain hose piece


(Standard Accessory) 575.2 (Suspension bolts pitch)
(Installed on site) Space for installation and service
145.6 Note(4)
273 255.8
30.8
30.8 F
outlet
Air

66.4
C1

40
95.3

21
66

66
156.8

610
(Suspension bolts pitch)

A 62.1 C2
488

530
B Control box
Note(4) 890
600 100

Unit:mm
21

(D)
Air

68
inlet

12-ø4
549.2 E
Holes for Notes
30

tapping screws ( 1 ) The model name label is attached on the fan case
inside the air return grille.
( 2 ) Prepare the connecting socket (VP20) on site.
160
200

38.2 Air inlet


188.5

(As for drain piping, it is possible to choose C1 or C2)


148.5

( 3 ) When control box is located on the reverse side, Installation


space should be modified to new location.
30
37.6

28.3

32 150 150 150 32 ( 4 ) Control box and Drain hose piece are able to be relocated
D 27.5 494.2 27.5 on the reverse side.

574

Bottom plate
(Able to be located on the back side)

View G

In case of Bottom air intake Simple remote control


50.5 150 150 150 50.5
12-ø4
28.5
30

Holes for
tapping screws
120
18.2 537.6
198.2
160

Air inlet

70 15
30

View G
(After bottom plate is replaced to back side)

89
R410A

Wall Mounted Remote control (option)

FDK Model No. Wired

FDK15KXZE1
FDK22KXZE1
RC-EX3A RC-E5 RCH-E3
FDK28KXZE1
FDK15~56
FDK36KXZE1
FDK45KXZE1 Wireless
FDK56KXZE1
FDK71KXZE1
FDK90KXZE1

RCN-K-E2: RCN-K71-E2:
FDK15~56 FDK71,90
FDK71,90

Elegant Timeless Design Jet Technology

The FDK series air-conditioners have been stylishly designed with FDK models adopt the air flow
rounded contours that fit beautifully into any of Europe’s diverse design that's proven to
interior settings. The design was created by the Italian industrial minimise resistance in a CFD
design studio Tensa srl, based in Milan, to respond to a broad analysis to achieve uniform air
spectrum of local user needs. (15~56KXZE1) conditioning to the furthest
corners of the room.
Flap control system

Selection of flap position is Upper


position
possible. A flap can be set at Fast Slow
Colours in the figure show the air speed.
different angles. Movable

NEW
range

Lower
Motion Sensor (Option)
*The wireless remote control is not applicable to the
flap control system.
position

Motion sensor is equipped in the ceiling


Lateral Swing flap swings from right to left plane or wall plane and detects the
automatically presence/absence and activity of humans in Motion
Up/Down Flap swing a room to improve the comfort and energy Sensor
+ Up saving performance of the unit.
Lateral swing

Left Right

Down

Specifications LB-KIT

Item Model FDK15KXZE1 FDK22KXZE1 FDK28KXZE1 FDK36KXZE1 FDK45KXZE1 FDK56KXZE1 FDK71KXZE1 FDK90KXZE1
Nominal cooling capacity kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1 9.0
Nominal heating capacity kW 1.7 2.5 3.2 4.0 5.0 6.3 8.0 10.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.02-0.02 0.03-0.03 0.04-0.04 0.05-0.05
consumption Heating kW 0.02-0.02 0.03-0.03 0.04-0.04 0.05-0.05
Sound power level dB(A) 54 55 58 Cooling:58 Heating:61 59 61
Sound pressure Cooling P-Hi:38 Hi:34 Me:31 Lo:28 P-Hi:38 Hi:36 Me:32 Lo:28 P-Hi:40 Hi:38 Me:33 Lo:28 P-Hi:43 Hi:41 Me:36 Lo:33 P-Hi:43 Hi:41 Me:36 Lo:33 P-Hi:42 Hi:40 Me:37 Lo:35 P-Hi:44 Hi:42 Me:39 Lo:35
dB(A)
level Heating P-Hi:38 Hi:34 Me:31 Lo:28 P-Hi:38 Hi:36 Me:32 Lo:28 P-Hi:40 Hi:38 Me:33 Lo:28 P-Hi:43 Hi:41 Me:36 Lo:33 P-Hi:44 Hi:42 Me:37 Lo:33 P-Hi:42 Hi:40 Me:37 Lo:35 P-Hi:44 Hi:42 Me:39 Lo:35
Exterior dimensions
mm 290 x 870 x 230 339 x 1197 x 262
HxWxD
Net weight kg 11.5 11 11.5 17
Cooling P-Hi:12 Hi:11 Me:9 Lo:8
Air flow m3/min P-Hi:5.7 Hi:5 Me:4.5 Lo:3.6 P-Hi:8.5 Hi:8 Me:6 Lo:5 P-Hi:11 Hi:10 Me:8 Lo:7 P-Hi:12 Hi:11 Me:9 Lo:8 P-Hi:13 Hi:12 Me:10 Lo:8 P-Hi:21 Hi:19 Me:16 Lo:14 P-Hi:23 Hi:21 Me:19 Lo:16
Heating
Outside air intake Not possible
Air filter, Q’ty Polypropylene net x2 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-K-E2, RCN-K71-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

90
Dimensions
All measurements in mm.

FDK15KXZE1, 22KXZE1, 28KXZE1, 36KXZE1, 45KXZE1, 56KXZE1

Installation board Unit (Service space) 100

100 (Service space)


(Service space)50 142.5 585 142.5
170 530 170
210 450 210
435 435

F 35 60 F 60 35

9
45

45

43
185

190
268
47
47
230 3

13
870

80(Service space)
55 SRK 15, 22, 28 :469 55
D B E A C
SRK 36, 45, 56 :475
528
290

Terminal block 537

Space for installation and service when viewing from the front
60

Outlet for downward piping


13

(Refer to the top view) 45 F


Symbol Content
Gas piping SRK15, 22, 28 9.52(3/8")(Flare)
A
SRK36, 45, 56 12.7(1/2")(Flare)
B Liquid piping 6.35(1/4")(Flare)
C Hole on wall for right rear piping ( 65)
D Hole on wall for left rear piping ( 65)
E Drain hose VP16
F Outlet for piping(on both side)

FDK71KXZE1, 90KXZE1

91
R410A

Ceiling Suspended Remote control (option)

FDE Wired

Model No.
FDE36KXZE1
RC-EX3A RC-E5 RCH-E3
FDE45KXZE1
FDE56KXZE1 Wireless
FDE71KXZE1
FDE112KXZE1
FDE140KXZE1
RCN-E-E2

Flap control system Reduction of weight

Selection of flap Thanks to decreasing the numbers of fan motor from two to one,
position is possible. Upper reduction of weight was achieved.
A flap can be set at position
different angles.
Previous Current
Movable
range FDE71 37 33 4kg less!!
*The wireless remote control
is not applicable to the flap FDE112 49 43 6kg less!!
Lower
control system.
position
FDE140 49 43 6kg less!!

Reduction of sound pressure level (Lo mode) Motion Sensor NEW (Option)

The industry's lowest sound pressure levels were achieved by decreasing air flow Motion sensor is equipped in the panel and detects the
volume, decreasing pressure loss with employment of one fan motor and optimizing presence/absence and activity of humans in a room to
casing and distributor shape. (comparison of previous model) improve the comfort and
dB(A) energy saving Motion
50 5dB 8dB performance of the unit. Sensor
8dB 5dB less!! 43dB less!!
10dB 39dB less!! less!!
39dB
40
36dB less!! 37dB 35dB
34dB
31dB 32dB
30 26dB

20
LB-E

FDE36 FDE45•56 FDE71 FDE112 FDE140

Specifications
Item Model FDE36KXZE1 FDE45KXZE1 FDE56KXZE1 FDE71KXZE1 FDE112KXZE1 FDE140KXZE1
Nominal cooling capacity kW 3.6 4.5 5.6 7.1 11.2 14.0
Nominal heating capacity kW 4.0 5.0 6.3 8.0 12.5 16.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.05-0.05 0.07-0.07 0.10-0.10 0.13-0.13
consumption Heating kW 0.05-0.05 0.07-0.07 0.10-0.10 0.13-0.13
Sound power level dB(A) 60 62 —
Sound pressure level dB(A) P-Hi:46 Hi:38 Me:31 Lo:26 P-Hi:46 Hi:38 Me:36 Lo:31 P-Hi:46 Hi:38 Me:36 Lo:31 P-Hi:47 Hi:39 Me:37 Lo:32 P-Hi:45 Hi:42 Me:38 Lo:34 P-Hi:48 Hi:43 Me:40 Lo:35
Exterior dimensions
mm 210 x 1070 x 690 210 x 1320 x 690 250 x 1620 x 690
HxWxD
Net weight kg 28 33 43
Air flow m3/min P-Hi:13 Hi:10 Me:7 Lo:5.5 P-Hi:13 Hi:10 Me:9 Lo:7 P-Hi:20 Hi:15 Me:13 Lo:10 P-Hi:28 Hi:25 Me:21 Lo:16.5 P-Hi:32 Hi:26 Me:23 Lo:17
Outside air intake Not possible
Air filter, Q’ty Pocket Plastic net x2 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-E-E3
Installation data Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

92
Dimensions
All measurements in mm. C1,C2

FDE36KXZE1, 45KXZE1, 56KXZE1 D

10
53
290 (Suspension bolts pitch)

135 410 145 Note) The slope of drain piping inside the
24 1022 (Suspension bolts pitch) 24
68 52 unit must take decline of 10mm.
B
A
5

Symbol Content

40
A Gas piping ø12.7 (1/2") (Flare)

31
215
210
173

108
B Liquid piping ø6.35 (1/4") (Flare)
C 1,2 Drain piping VP20 (I.D.20)

53

27

27
40 990 40 15 60 7 D Hole for suspension bolt (M10 or M8)

109
690
20 100 E Back cutout PE cover
1070 195
C1,C2 F Top cutout Plate cover
Air supply 235 Drain hose piece (Accessory, 0.3m) G Hole for drain piping (for left back) (Knock out)
(Installed on site)
271

Space for installation and service Position of top cutout and back cutout
Hole for
0 175 drain piping
12 19 (for left)
20

F
300 or more

100 or more
G
308

150 or more 5 or more Right side cutout


E
C2 75
B
76 Air return grille A C1 110
Obstacle
Remove the cutout using side cutter or similar tool.
135 Make a space of 4000 or more between the units when installing more than one. Note(1)The model name label is attached on the
fan casing inside the air return grille.

C1,C2
53
10

FDE71KXZE1 290 (Suspension bolts pitch) D


135 410 145
24 1272 (Suspension bolts pitch) 24 Note)The slope of drain piping inside the
68 52
B unit must take decline of 10mm.

A
5

Symbol Content
40

A Gas piping ø15.88 (5/8") (Flare)


31
215
210

B Liquid piping ø9.52 (3/8") (Flare)


173

108

C 1,2 Drain piping VP20 (I.D.20)


D Hole for suspension bolt (M10 or M8)
53

27

27

40 1240 40 15 60 7
109

690 E Back cutout PE cover


1320 20 100
Top cutout
195
C ,C
1 2
F
G Hole for drain piping(for left back)
Plate cover
(Knock out)
Air supply 235 Drain hose piece (Accessory, 0.3m)
(Installed on site)
271

Space for installation and service Position of top cutout and back cutout
Hole for
175 drain piping
0
12 19 (for left)
20

F
300 or more

100 or more
G
308

150 or more 5 or more Right side cutout


E
C2 75
B
76 Air return grille A C1 110 Obstacle
Remove the cutout using side cutter or similar tool.
135
Make a space of 4500 or more between the units when installing more than one. Note(1)The model name label is attached on the
fan casing inside the air return grille.

C1,C2
FDE112KXZE1, 140KXZE1
D
53
10

290 (Suspension bolts pitch)

1572 (Suspension bolts pitch) 135 410 145


24 24
68 52 Note) The slope of drain piping inside the
B unit must take decline of 10mm.
Symbol Content
A
5

A Gas piping ø15.88 (5/8") (Flare)


B Liquid piping ø9.52 (3/8") (Flare)
40
255
250

31

C1,2 Drain piping VP20 (I.D.20)


173

108

D Hole for suspension bolt (M10 or M8)


E Back cutout PE cover
53

27

27

40 1540 40 15 60 7
109

690 F Top cutout Plate cover


1620 20 100 G Hole for drain piping (for left back) (Knock out)
195
C ,C
1 2
Air supply 235 Drain hose piece (Accessory, 0.3m)
(Installed on site)
271

Space for installation and service Position of top cutout and back cutout
Hole for
175 drain piping
0
12 19 (for left)
20
300 or more

100 or more F
G
308

150 or more 5 or more Right side cutout


75
E
C2 76 A C1 110 B Obstacle
Air return grille
Remove the cutout using side cutter or similar tool.
135
Make a space of 5000 or more between the units when installing more than one. Note(1)The model name label is attached on the
fan casing inside the air return grille.

93
R410A

Auto air outlet selection

Floor Standing -2way-


FDFW
Model No.
FDFW28KXE6F
FDFW45KXE6F
FDFW56KXE6F

Remote control (option)


Wired Wireless

RC-EX3A RC-E5 RCH-E3


RCN-FW-E2

Sophisticated Design Quiet Operation

With an elegant semi flat front panel in stylish white, the Thanks to optimum balance of air outlet direction and
new series fit in various kinds of rooms and create sufficient air flow volume, the sound level has been
relaxing atmosphere. Choice of wall hanging, floor minimized. The level of FDFW28KXE6F in the cooling lo
standing or behind gallery installation is available. mode is 30dB(A) only.

Flap control system Convenient to use operation

Selection of flap Simultaneous lower and upper air outlets or upper outlet
Upper can be selected by air flow direction button. Further
position is possible. position
A flap can be set at control can be arranged by a remote control.
different angles. Movable
range

*The wireless remote control is


not applicable to the flap Lower
control system. position

(In case of use of wireless remote control)

Specifications
Item Model FDFW28KXE6F FDFW45KXE6F FDFW56KXE6F
Nominal cooling capacity kW 2.8 4.5 5.6
Nominal heating capacity kW 3.2 5.0 6.3
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.02-0.02 0.02-0.02 0.03-0.03
consumption Heating kW 0.02-0.02 0.02-0.02 0.03-0.03
Sound power level dB(A) 55 57 60
Sound pressure level dB(A) Hi:36 Me:34 Lo:30 Hi:38 Me:36 Lo:33 Hi:44 Me:37 Lo:33
Exterior dimensions
mm 600x860x238
HxWxD
Net weight kg 19 20
Air flow (Standard) m3/min Hi:9 Me:8 Lo:7 Hi:11 Me:9 Lo:8
Air filter, Q’ty Polypropylene net x1 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-FW-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

94
Dimensions
All measurements in mm.

95
R410A

Floor Standing (with casing) Remote control (option)


Wired Wireless

FDFL
Floor Standing (without casing) RC-EX3A RC-E5 RCH-E3 RCN-KIT4-E2

FDFU
Model No.
FDFL71KXE6F

FDFU28KXE6F
FDFU45KXE6F
FDFU56KXE6F
FDFU71KXE6F
FDFL FDFU (concealed type)

Compact design at 630mm height Wider airflow for optimum comfort

Specifications
Item Model FDFL71KXE6F FDFU28KXE6F FDFU45KXE6F FDFU56KXE6F FDFU71KXE6F
Nominal cooling capacity kW 7.1 2.8 4.5 5.6 7.1
Nominal heating capacity kW 8.0 3.2 5.0 6.3 8.0
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.09-0.10 0.09-0.10
consumption Heating kW 0.09-0.10 0.09-0.10
Sound power level dB(A) 62 58 60
Sound pressure level dB(A) Hi:43 Me:41 Lo:40 Hi:41 Me:38 Lo:36 Hi:43 Me:41 Lo:40
Exterior dimensions
HxWxD mm 630x1481x225 630x1077x225 630x1362x225
Net weight kg 40 25 32
Air flow (Standard) m3/min Hi:18 Me:15 Lo:12 Hi:12 Me:11 Lo:10 Hi:14 Me:12 Lo:10 Hi:18 Me:15 Lo:12
Air filter, Q’ty Polypropylene net x1 (Washable)
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data Liquid line:ø9.52(3/8") Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø15.88(5/8") Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

96
Dimensions
All measurements in mm.

FDFL

FDFU

Dimension Table Unit:mm

model a b c d e

FDFU28KXE6F, 45KXE6F, 56KXE6F 786 810 722 750 806

FDFU71KXE6F 1071 1095 1007 1035 1091

97
R410A

Outdoor Air Processing unit


Remote control (option)
FDU-F Wired

Model No.
FDU650FKXZE1
FDU1100FKXZE1 RC-EX3A RC-E5 RCH-E3
FDU1800FKXZE1
FDU2400FKXZE1 Wireless

RCN-KIT4-E2

Air conditioning and intake of outdoor air are in the same system Motion Sensor NEW (Option)

Outdoor Air processing unit can be connected in a KXZ system as one Motion sensor is equipped in the ceiling
of the indoor unit series and can create fresh and comfortable air plane or wall plane and detects the
supply together from our high advanced technology. presence/absence and activity of humans in a
room to improve the comfort and energy
saving performance of the unit.
KXZ outdoor unit
Motion
Sensor

indoor unit indoor unit

Outdoor Air
Processing unit office
corridor
refresh room, LB-KIT
air outside rest room
conditioning air supply

Compact design

Compact design at just 280(650,


1100), 379(1800, 2400)mm in
height, high static pressure of
200Pa and the industry's lowest
noise level can meet various kind exhaust air
of installation location for office,
refresh room, restroom and kitchen
of restaurant etc.

outdoor air
supply air

outdoor air

supply air

(1) This unit is the specific unit for processing the outdoor air temperature closer to the room temperature. For conditioning the room temperature a
dedicated air-conditioner is required additionally.
(2) This unit monitors the outdoor air temperature and controls thermostat ON/OFF at the setting temperature by the remote controller, which
indicates the outdoor air temperature for controlling thermostat ON/OFF. When thermostat is turned OFF, the operation is changed to the fan mode
so that unprocessed outdoor air will be blown into the room directly. Therefore place the air outlet port or orient the air outlet direction not to blow
air directly to persons in the room, especially in the small room such as a restroom and/or sanitary hot water supplying room.
(3) It is strictly prohibited to monitor the room temperature by switching to the thermistor at remote controller side and/or the optional remote
thermistor. Otherwise dew formation at air outlet port and/or dew dripping may occur during cooling operation due to the lower outdoor air
temperature. Therefore keep the remote controller of this unit in place closer to the administrator so as not to be touched it freely by the end user.
(4) Dehumidifying operation with this unit is prohibited.
(5) When handing over this unit to the end user, make sure to explain sufficiently about the foregoing cautions, the installation place and usage of
remote control for this unit and the location of the air outlet.

98
Connectivity with Outdoor units
FDU-F series are connectable to 8~60HP outdoor units, not connectable to 4~6HP, KXZ Lite.

Combination with Outdoor units


case Combination
In case OA processing units only The total capacity of FDU-F is 50~100% of outdoor capacity
A are connected with outdoor units. and max quantity of FDU-F is 2 units.
In case both of OA processing units
The total capacity of FDU-F and dedicated air-conditioners is 50~100% of outdoor
B and dedicated air-conditioner capacity and max quantity of FDU-F should be below 30% of outdoor unit capacity.
are connected with outdoor units.

[A] [B] Less than 30%


FDU650FKXZE1 FDU650FKXZE1 FDU650FKXZE1
10HP (5HP) (5HP) 18HP (5HP) 6HP 6HP

(Micro)

Concept (Difference between FDU-F and SAF)


SAF is the energy recovery ventilation unit which can recover heat energy from exhaust air to supply air and "has no air processing
function, but FDU-F is air processing unit which can treat the supply air closer to room temperature by cooling or heating in connection
with KXZ refrigerant system and exhaust air is discharged to outside of the room.

FDU-F OA Processing units

Outside

Exhaust Air
Air Supply

Direct Expansion
Heat Exchanger

SAF

Outside

Air Supply
Exhaust Air

99
R410A

Specifications
Item Model FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1
Nominal cooling capacity kW 9.0 14.0 22.4 28.0
Nominal heating capacity kW 6.5 10.5 16.0 21.5
Power source 1 Phase 220-240V, 50Hz
Power Cooling 0.24-0.25 0.35-0.36 1.16-1.20 1.16-1.20
consumption Heating kW 0.24-0.25 0.35-0.36 1.16-1.20 1.16-1.20
Sound pressure level dB(A) Hi:31 Hi:37 Hi:42 Hi:45
Exterior dimension
mm 280x950x635 280x1370x740 379x1600x893
HxWxD
Net weight kg 34 54 89 89
Air flow (Standard) m3/min Hi:11 Hi:18 Hi:30 Hi:40
External static pressure Pa 200 (at Hi Air flow)
Air filter, Q'ty Procure locally
Remote control(option) wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-KIT4-E2
Installation data mm Liquid line:ø9.52(3/8") Liquid line:ø9.52(3/8") Liquid line:ø9.52(3/8")
Refrigerating piping size (in) Gas line:ø15.88(5/8") Gas line:ø19.05(3/4") Gas line:ø22.22(7/8")
1. The data are measured at 33ºCDB 28ºCWB (68%RH) during cooling and 0ºCDB-2.9ºCWB (50%RH) during heating (no frost).
2. Temperature range of outdoor air must be 20~40ºCDB (32ºCWB) during cooling and 0~24ºCDB during heating.
3. Sound level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to ambient conditions.
4. The factory E.S.P. setting is set within the range of 10 - 120Pa.lf SW8-4 is turned to “ON”, E.S.P. setting range can be changed to 10 - 200 Pa. (with RC-EX3A and RC-E5 only)

Dimensions
All measurements in mm.

FDU650FKXZE1 Symbol Content


A Gas piping ø15.88 (5/8") (Flare)
B Liquid piping ø9.52 (3/8") (Flare)
C1 Drain piping VP25(O.D.32)
C2 Drain piping(Gravity drainage) V20(O.D.26)
D Hole for wiring
E Suspension bolts M10
F Outside air opening for ducting (Knock out)
G Air outlet opening for ducting (Knock out)
H lnspection opening (450X450)

100
FDU1100FKXZE1
Symbol Content
A Gas piping ø15.88 (5/8") (Flare)
B Liquid piping ø9.52 (3/8") (Flare)
C1 Drain piping VP25(O.D.32)
C2 Drain piping(Gravity drainage) V20(O.D.26)
D Hole for wiring
E Suspension bolts M10
F Outside air opening for ducting (Knock out)
G Air outlet opening for ducting (Knock out)
H lnspection opening (450X450)

FDU1800FKXZE1, FDU2400FKXZE1
Content
Symbol
MODEL 1800 2400
A Gas piping ø19.05 (3/4") ø22.22 (7/8")
B Liquid piping ø9.52 (3/8") (Brazing)
C Drain piping(Gravity drainage) VP25(O.D.32)
D Hole for wiring
E Suspension bolts M10
F Inspection hole (450X450)

101
R410A

Fresh Air Ventilation and Heat Exchange unit


SAF-E7
Model No.
SAF150E7
SAF250E7
SAF350E7
SAF500E7
SAF800E7
SAF1000E7

Capturing this waste energy, means the heating/ cooling requirements


Energy Performance of Building Directive - EPBD of the building are reduced, so smaller size plant can be selected,
EPBD limit the amount of electrical/gas power to be used to provide savings can be made in long term energy consumption, and carbon
heating or cooling in commercial buildings. Therefore the building emissions are reduced.
designer needs to select energy efficient heating/cooling equipment,
and to minimise energy losses through ventilation systems.
The SAF recovers heat energy which would otherwise be exhausted Switch box
to atmosphere, and uses this energy to warm the air entering the (option)
building. The reverse happens in warmer climates, where the
exhausted cool air is used to partially cool the incoming air.

Increased external static pressure at UHi air flow

Pa
140
140 140 140 Previous New
120
120
100
105 105 105
80 90 95 90
Remote control
The following functions are newly available.
・ON/OFF Timer – The hour and minute of timer
SAF250E7 SAF350E7 SAF500E7 SAF800E7 SAF1000E7 on/off can be set.
・Filter Sign – Announces the due time for cleaning
the air filter.
Specifications
Item Model SAF150E7 SAF250E7 SAF350E7 SAF500E7 SAF800E7 SAF1000E7
Power source 1 Phase 220-240V, 50Hz
Exterior dimensions
Height x Width x Depth mm 270x970x467 270x882x599 317x1050x804 317x1090x904 388x1322x884 388x1322x1134
Exterior appearance Galvanized steel sheet
Power input W 92-107 108-123 178-185 204-225 360-378 416-432
Running current A 0.42-0.45 0.49-0.51 0.81-0.77 0.93-0.94 1.64-1.58 1.89-1.80
Enthalpy Cooling 63 63 66 62 65 65
exchange
UHi efficiency Heating 70 70 69 67 71 71
Temperature exchange efficiency 75
Enthalpy Cooling 63 63 66 62 65 65
Capacity

exchange
Hi efficiency Heating % 70 70 69 67 71 71
Temperature exchange efficiency 75
Enthalpy Cooling 66 65 71 64 68 70
exchange
Lo efficiency Heating 73 72 73 69 74 76
Temperature exchange efficiency 77 77 78 76 76 79
Motor & Q'ty W 10 x 2 20 x 2 40 x 2 70 x 2 180 x 2 180 x 2
Air handling equipment Fan type & Q’ty Sirocco fan x 2
UHi 150 250 350 500 800 1000
Air flow Hi m3/h 150 250 350 500 800 1000
Lo 120 190 240 440 630 700
UHi 80 105 140 120 140 105
External static pressure Hi Pa 70 95 60 60 110 80
Lo 25 45 45 35 55 75
Net weight kg 25 29 49 57 71 83
Remote control Included
Supply air
Air filter Protection for element (Washable) PS400
Exhaust air

102
Structure (SAF800E7) Principle of operation (simple ventilation) Principle of operation (heat exchanging)
Heat exchanger element Damper FREE COOLING ENERGY RECOVERY

Exhaust Air outdoor indoor Supply Air Exhaust Air outdoor indoor Supply Air

EA RA
(Exhaust Air) (Room Air)
27 ºC 10 ºC 33 ºC 29 ºC

Outside Air Room Air Outside Air Room Air

10 ºC 27 ºC 35 ºC 27 ºC
OA SA
(Outside Air) (Supply Air)
e.g. For cooling
in winter time

Dimensions
All measurements in mm.

SAF150E7, SAF250E7, SAF350E7, SAF500E7 SAF800E7, SAF1000E7


2 5 6 10 9 2 5 6 8 10 9

RA EA RA
EA (Exhaust Air)
(Exhaust Air) (Room Air) (Room Air)

OA SA
OA SA (Outside Air) (Supply Air)
(Outside Air) (Supply Air)

4-13 x 30
11 1 7 4-13 x 30 11 1 7 oblong hole
oblong hole
Applied duct
Model No. Nominal
diameter
Applied duct
SAF150E7 ø100 Nominal
Model No. diameter
SAF250E7
ø150 SAF800E7
4 8 3 12 SAF350E7 ø250
SAF1000E7
SAF500E7 ø200 4
3
12
Dimension table Unit:mm Dimension table Unit:mm
Model A B C E F G H I J K L M N P Model A B C E F G H I J K L M N P
SAF150E7 467 970 49 525
82 303 82 ø98 ø110 SAF800E7 884 940 428
810 135 159 270 1322 85 1250 19 228 612 194 218 388 ø242 ø258
SAF250E7 599 882 95 655 142 315 142 ø164 SAF1000E7 1134 1190 678
19 ø144
SAF350E7 804 1050 978 860 112 580 112 ø164
70 159 182 317
SAF500E7 904 1090 1018 960 132 640 132 ø194 ø210

NO. Name Qt'y


1 Frame 1 Installation reference
2 Adaptor 4 Air supply duct
3 Terminal board 1 Ceiling suspension bolt
4 Inspection Cover 1 Outer air intake duct
5 Fan 2
Pipe hood
6 Motor 2 SA
(Supply Air)
Heat Exchange Element
SAF150E7 1 RA
SAF250E7 1 (Room Air)
7 SAF350E7 2
SAF500E7 2 Inside supply opening
3
EA
SAF800E7 OA (Exhaust Air) (Supply/exhaust air grill)
SAF1000E7 4 (Outside Air) Room intake duct
8 Filter 2 Heat insulation Room intake opening
material (Supply/exhaust air grill)
9 Damper 1
Pipe hood Outside intake duct
10 Damper Motor 1
11 Suspension fitting 4
Note:An inspection port is needed for cleaning the heat exchanger and filter 1 or 2 times a year.
12 Electrical components box 1
Model SAF350E7, SAF500E7 have different fan and
motor locations.

103
R410A

Fresh Air DX Assembly Drain up kit


(option, built-in type)
(600mm)
Remote control
(option)
Wired
DXA-DU-E

RC-E5 RCH-E3

Model No. Wireless


SAF-DX250E6
SAF-DX350E6
SAF-DX500E6
SAF-DX800E6 RCN-KIT4-E2
SAF-DX1000E6

• SAF-DX is a heating or cooling coil incorporating KXZ series controls. It can be used in combination with our SAF series of total heat exchanger.
• Combination of SAF-DX together with other indoor units is possible. The capacity code index of each model is shown below and must be used when
making the system selection. Total capacity code index must be within 100% of outdoor unit capacity code index.
• Remote control option is the same as with other indoor units (see above). Connection to all Superlink controls is also possible.
• Optional condensate lift mechanism is also available (600mm height).
• Return air temp. control or supply air temp. control can be selectable.

RA (Room Air)

OA
(Outside Air)
Total heat SAF-DX
Supply / fresh air temp.
exchanger sensor
Return / fresh air
EA temp.sensor SA (Supply Air)
(Exhaust Air)
Heating or cooling coil

SAF-DX can provide heating or cooling to the fresh air supplied through a 3rd party air handling unit or total heat exchanger such as our SAF series.

Specifications
Item Model SAF-DX250E6 SAF-DX350E6 SAF-DX500E6 SAF-DX800E6 SAF-DX1000E6
Nominal cooling capacity *1 kW 2.0 2.8 3.6 5.6 6.3
Nominal heating capacity *2 kW 1.8 2.2 2.8 4.5 5.6
Capacity code 22 28 36 56 71
Power source 1 Phase 220-240V, 50Hz
Power Cooling 7.2-7.2
consumption Heating W 7.2-7.2
Running Cooling 0.05-0.05
A
current Heating 0.05-0.05
Exterior dimensions
mm 315 x 452 x 422 315 x 537 x 422 315 x 682 x 422 315 x 822 x 422
HxWxD
Net weight kg 12.3 13.6 16.1 18.4
Air flow (Standard) m3/h 250 350 500 800 1000
Internal resistance Pa 38 66
Remote control(option) wired: RC-E5, RCH-E3 wireless: RCN-KIT4-E2
Installation data Liquid line:ø6.35(1/4") Liquid line:ø6.35(1/4") Liquid line:ø9.52(3/8")
Refrigerant piping size mm(in) Gas line:ø9.52(3/8") Gas line:ø12.7(1/2") Gas line:ø15.88(5/8")
(1) The data are measured at the following conditions.
Item Return/fresh air temperature Outdoor air temperature Standards
Operation DB WB DB WB
Cooling*1 27ºC 19ºC 35ºC 24ºC
ISO-T1
Heating*2 20ºC 7ºC 6ºC
(2) This air-conditioner is manufactured and tested in conformity with ISO-T1 "UNITARY AIR-CONDITIONERS".

104
Dimensions
All measurements in mm.

SAF-DX250E6,350E6 SAF-DX500E6

SAF-DX800E6 SAF-DX1000E6

105
R410A

EEV-KIT KXZ
Outdoor units
DX-AHU
• EEV-KIT is the control kit for operating the locally provided
AHU or FCU with direct expansion heat exchanger coils in
connection with the KXZ/KXE6 system.
(AHU : Air Handling Unit, FCU : Fan Coil Unit)
• EEV-KIT is composed of one EEV-Control ASSY and one
EEV-Set.
EEV-KIT

DX : Direct expansion coil

Features
EEV-Control Assy has 2 types.
Refrigeration system EEV-Control Assy System configuration
EEVKIT6-E-M EEVKIT6-E-C
Single Not Use 1 box-Many boxes • Single refrigeration system EEVKIT6-E-C … Possible with multiple
Multiple 1 box (for master) Many boxes(for slave) • Multiple refrigeration system EEVKIT6-E-M (1) + EEVKIT6-E-C …
Possible with multiple (Max32)
EEV-Set Select from following 3 types according to the coil capacity.
Type EEV6-71-E EEV6-160-E EEV6-280-E • EEVKIT6-E-C is common for both single and multiple refrigeration systems
Capacity 22-71 90-160 224-280

Single refrigerant system


• Single refrigeration system is one that can have multiple outdoor units on one refrigerant pipe work circuit.
• There are 2 types of EEV-KIT systems that can be built into the single refrigeration system.
• System A : one EEV-KIT.
• System B : multiple EEV-KIT’s.
System A System B
• This system has only one set of EEV-KIT built into one • System B is a system that has multiple EEV-KIT’s built into one indoor unit
indoor unit with only one heat exchanger. This system can with multiple heat exchangers on one refrigerant circuit.
be applied to an indoor unit whose capacity is up to 10HP. • This system can be applied up to 60HP (for KXZ) 48HP(for KXE6) AHU
capacity.

EEV-Set

EEV-Set×2 sets

FAN FAN

EEV-Control box×2 sets

106
Multiple refrigerant system
Multiple refrigeration system is an AHU system with
1) Multiple independent refrigerant circuits
2) One master control to control the whole system.

Advantages
• Large systems are possible [max capacity 896kW (Indoor unit : 28kW x 32)]
• External control FAN

• Capacity step control


Additional parts over a single refrigeration system
• One master control
The slave EEV control and EEV set are the same as a single refrigeration
system.

Master EEV-KIT
Master EEV-Control box FAN
Slave EEV-KIT #1 Slave EEV-KIT #2 #3 • • • •
Sensor (2pcs)
Slave EEV-Control box Slave EEV-Control box
Heat exchanger temp. Heat exchanger temp.
Return air
temp. sensor
Supply air
Sensor x 3
EEV x 1
Sensor (Thi-R1,R2,R3)
EEV-Set
Sensor x 3
EEV x 1
Sensor (Thi-R1,R2,R3)
EEV-Set
••••
temp. sensor
Thi-A Thi-AF Strainer Strainer Strainer Strainer

Connection to SUPERLINK II
Single refrigeration system

Superlink Adapter
SC-ADNA-E SL4
DX-FCU
Slave1 FDT
Single System A Remote control line
Slave2
KXZ KXZ
DX-FCU
Single System B KXZ
Multiple refrigeration system

Superlink Adapter
SC-ADNA-E SL4
DX-FCU
Master FDT
Remote control line Single System A
Slave1
KXZ KXZ
Slave2 KXZ KXZ
Slave3

Slave4
DX-AHU
Multiple System

107
R410A

Control Systems
<Individual control>
Remote Control line up
indoor unit remote control indoor unit remote control indoor unit remote control indoor unit remote control
RC-EX3A FDT RCN-T-5AW-E2 FDTS RCN-TS-E2 FDE RCN-E-E3
wired all models RC-E5 wireless FDTC RCN-TC-5AW-E2 FDK22~56 RCN-K-E2 FDFW RCN-FW-E2
RCH-E3 FDTW RCN-TW-E2 FDK71 RCN-K71-E2 others* RCN-KIT4-E2
*FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F

Wired remote control (option)


RC-EX3A
Intuitive touch controller with Liquid Crystal Display
User friendly Easy view
•LCD panel with light tap operation •Big LCD with 3.8 inch full dot display
introduced as the industry's first •Back light function
•Simple interface with only three buttons •Multi language display (12 languages)

Setting temperature screen


Operation mode
Operation mode setting screen
Cooling Fan

Dry Heating

Auto

The desired operation mode can You can select the temperature as
be selected by simply tapping desired by tapping button.
this button. Run / Stop

High power operation Energy-saving operation


The highest capacity operation (Max 15 minutes) •Changes set temperature.
•Increasing compressor speed At 28ºC in cooling mode and 22ºC in heating mode, 25ºC in auto mode.
•Increasing air flow volume •Operation correction by outdoor temperature

2. Main functions
Function name Description
Energy-saving operation Since the capacity is controlled automatically based on the outdoor temperature, energy can be saved without losing comfort.
Sleep timer Set the time period from start to stop of operation. The selectable range of setting time is from 30 to 240 minutes (at 10-minuteintervals).
Set temperature auto return The temperature automatically returns to the previously set temperature.
Economy Set ON timer by hour When the set time elapses, the air conditioner starts.
& Set OFF timer by hour When the set time elapses, the air conditioner stops.
Timer Set ON timer by clock The air conditioner starts at the set time.
Set OFF timer by clock The air conditioner stops at the set time.
Weekly timer On or Off timer can be set on a weekly basis.
Peak-cut timer Capacity control can be set by using peak cut function on RC-EX3A for better energy saving. Five-step capacity control is available.
Home leave operation When the unit is not used for a long period of time, the room temperature is maintained at a moderate level, avoiding extremely hot or cool temperatures.
Big LCD & Touch screen panel Large 3.8 inch screen has resulted in improved visibility and operability.
Easy modification of Individual flap control User can visually confirm and set the direction of flaps using the visual display on the remote controller.
Comfort Automatic fan speed *1 The micro-computer automatically adjusts the airflow effectively to follow the changes of return air temperature.
Temp increment setting Temperature increment for the change of the set temp can be changed.
Silent mode Set the period of time to operate the Outdoor unit with prioritizing the quietness.
Function switch The function switch allows user to select and set two functions among available functions.
Favorite setting Operation mode, set temperature, fan speed and air flow direction automatically adjust to the programmed favorite setting.
Adjusting Brightness of the background light The brightness of the background light can be adjusted by 10 stages.
LCD contrast setting This function allows user to adjust LCD display contrast.
Convenience High power operation High Power Mode increases the unit operating ability for 15 minutes to quickly adjust the room temperature to a comfortable level.
Back light setting This convenient function allows user to see controls under low light conditions.
Administrator settings This function only allows specific individuals to operate the unit.
Setting temp range Limited range of setting temperature in the heating or the cooling operation can be selected.
External Input/Output Function The external input/output of indoor unit by remote controller can set input/output based on user needs.
Select the language Set the language to be displayed on the remote control.
USB connection (mini-B) This function allows batch input of schedule timer settings and other settings involving a large amount of data.
Error code display This function allows user to check information displayed when abnormal function of the unit occurs.
Operation data display Displays various types of air conditioner operation data in real time.
Service Contact company display Address of the service contact is displayed.
Filter sign Announces the due time for cleaning of the air filter.
Static pressure adjustment Allows user to adjust duct static pressure using the remote control.
Backup Control Allows for rotation control, fault backup control, and capacity backup control.
*1 Cannot be used when a centralized control remote is connected.
108
Wireless remote control (option)

For wireless control simply insert the infra-red receiver kit on a corner of the panel

RCN-T-5AW-E2 RCN-TC-5AW-E2 RCN-TW-E2 RCN-TS-E2 RCN-K-E2, RCN-E-E3 RCN-FW-E2


RCN-K71-E2

RCN-KIT4-E2

*The wireless remote control is not applicable to the Individual flap control system.

Wired remote control (option)

RC-E5 Run hour meters to facilitate maintenance checking


The RC-E5 controller enables RC-E5 stores operation data when an anomaly occurs and indicates
extensive access to service and the error on the LCD. It also displays cumulative operation hours of
maintenance technical data the air conditioner and compressor since commissioning.
combined with easy to use
Room temperature controlled by the remote control sensor
functions and a clear LCD display.
The temperature sensor is housed in the top
section of the remote control unit. This arrangement
has improved the sensitivity of the remote control
unit’s sensor, which permits more finely
controlled air conditioning.

Weekly timer function as standard Changeable set temperature ranges


RC-E5 provides (as a standard feature) a weekly timer, which RC-E5 allows the upper and lower limits of a set temperature range
allows one-week operation schedules to be registered. A user can to be specified separately.
specify up to four times a day to start/stop the air conditioner. By adjusting a set temperature range, you can ensure energy saving
(Temperature setting is also possible with the timer). air conditioning by avoiding excessive cooling or heating.

Changeable range
Upper limit 20~30ºC(effective for heating operation)
Timer operation
Lower limit 18~26ºC(effective for non-heating operation)

Simple remote control (option) Thermistor (option)

RCH-E3 (wired) SC-THB-E3


Designed specially for hotel rooms, the controller’s buttons are limited only to In case the sensor integrated in the indoor
the minimum required functions such as ON/OFF, mode, temperature setting and unit or in the remote controller is unable to
fan speed. It is really simple and easy to use. sense the room temperature correctly, or
an individual controller in each room is not
Up to 16 units AUTO restart required but a temperature sensor is (as
It can control up to 16 units This function allows starting the air conditioner when a central control
individually, with pressing the automatically when power supply is restored after system is in place),
AIR CON No. button. power failure or by turning on the power switch.
install SC-THB-E3 in
an adequate location 8m
*RCH-E3 is not applicable to the Individual flap control system.
*When RCH-E3 is used, the fan speed setting can only be set to 3 speed settings (Hi-Me-Lo). in the room.

109
R410A

<SUPERLINK - Control System>


Mitsubishi Heavy Industries Thermal Systems has now combined simplicity of installation with our highly sophisticated Superlink- control system, to
offer building owners and occupiers a comprehensive control and management system, while providing complete commissioning and service
maintenance assistance for installers and service engineers. The Superlink- network utilises two wire, non-polar cable - for further details of wiring.
Superlink- is an advanced high speed data transmission system that can connect up to 128 indoor units and 32 outdoor units as a network. Mitsubishi
Heavy Industries Thermal Systems offers a wide range of control options for the Superlink- network to suit any application large or small, as well as
connection to new or existing building management systems. Individual Mitsubishi Heavy Industries Thermal Systems split systems can also be
integrated on to the Superlink- network using SC-ADNA-E.

Central control
SC-SL4-A,-B

  Central Control SC-SL2NA-E


Monitiring PC Capable of control and monitoring up to 64
(Web Browser) indoor units. All operational functions, plus
enable/disable connected remote control.

Web gateway & BACnet gateway


SC-WBGW256

Building Management system


Host computer
Central Control
SC-SL4-AE/BE

Lonworks gateway
SC-LGWNB

Central Control SC-SL1N-E

SUPERLINK E BOARD(SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network option.

Blue
SL E board A A Connected to the terminals for
Abnormal

Blue Superlink signal lines


Run

B B MVVS 0.75 - 1.25mm2


Black
LED2

LED3

X X Connected to the remote control terminals (no


White polarity) (the length should be 600 m or shorter)
Y Y
200 m or shorter 0.5 mm2 x 2 cores
300 m or shorter 0.75 mm2 x 2 cores
ON 400 m or shorter 1.25 mm2 x 2 cores
600 m or shorter 2.0 mm2 x 2 cores
OFF SW3 SW1 SW2

Master/Sub Network address setting switches


address [000]-(127)

110
Lighting Fan

"Micro model" SC-GIFN-E


outdoor units Multi-KX6/KXZ indoor units

Individual On/Off Control

KXZ Outdoor units


Multi-KX6/KXZ indoor units

KXZ twined Outdoor units

Multi-KX6/KXZ indoor units


with individual room control

3-core + earth cable 3-core cable for 3-core cable for 3-core + earth cable
for connecting indoor connecting indoor connecting indoor for connecting indoor
and outdoor units and outdoor units and outdoor units and outdoor units

RACseries

Wireless
remote
control

SC-ADNA-E SC-ADNA-E SC-ADNA-E SC-ADNA-E

SC-BIKN2-E is necessary to connect to wired remote controller.

111
R410A

<Central Control>
SC-SL4-AE/BE Indoor unit 128 units

Mitsubishi Heavy Industries Thermal


Systems introduces the full colour
touch screen central control
SC-SL4-AE/BE, with 9 inch
interactive LCD display. Offers
control, monitoring, scheduling and
service/maintenance functions for up
to 128 indoor units.
Control with PC is available by use
of internet explorer.

Indoor units can be controlled,


scheduled, monitored and either
individually, as groups or as blocks
of groups with the following
functions:
Collective operation output
Control Monitoring Scheduling Administration/Service
Ethernet 10 BASE-T/
Run/Stop / Home leave Operating state Yearly schedule Block definition, Floor layout 100BASE-TX Emergency stop signal input
Mode (cool/heat/fan/dry/Auto) Mode Today's schedule Group definition
Internet
Set temperature Set temperature Detailed daily schedule Unit definition Explorer HUB Watt-hour meter pulse input
Operation permitted/prohibited Room temperature Season setting Time and date setting
Operation permitted/
Fan speeds Alarm history
prohibited
PC requirements: Windows Vista or Windows 7, 8.1, 10
Air direction Fan speed Energy consumption calculation period Monitor resolution 1280 x 1024 or more.
Filter sign reset Air direction Energy consumption, cumulative operation time Web browser requirements: Internet Explorer 11
Demand control (3 steps) Filter sign Flap control setting
Maintenance Operation data monitoring
Emergency stop (1, 2 or back-up)
Outdoor air Data logging (Run / Stop set temperature , room
temperature temperature , outdoor air temperature )

Schedule setting Operation time history


For each group Yearly Schedule Possible to check operation time history for
Schedule settings for each group are possible. Schedule settings for a year are also possible. cooling and heating separately.
The RUN/STOP/HOME LEAVE time, operation The weekday, holiday, special day 1 or special
mode, remote control Lock/Unlock setting, day 2 can be selected and set.
temperature setting, energy setting, and silent
mode can be set up to 16 times per day.

Alarm history High visibility


A maximum of 300 records is displayed for the Increasing in size from 7 to 9 inches
history of error occurrence and restoration in the 250mm
unit of air-conditioner. Contrast between five colours for
It is possible to output the history data to a CSV icon display and black light base
data file. screen has achieved high visibility.
172mm

Green : in operation
23mm Blue : stop
Red : error
9 inch wide LCD Yellow : communication error
Gray : no groups

112
Block layout function Web function
You can monitor and control up to 128 indoor units (Max.128 groups)
from a PC or tablet PC.
Import of floor layout is possible.
(JPEG) Internet
Explorer

Tablet
PC

Possible to move Group


icon to any place in
<Example>
imported layout.
Monitoring and operating air-conditioners in a lecture room of a university
Lecture room Administration room

3 levels of demand control from 2 external inputs


External Wiring terminal block

Not objective Set to D1 Set to D2 Set to D3


Demand
Control Operation Center/ Set temp. Operation Center/ Operation Center/ Set temp. Operation Center/
level Set temp. Remote mode Remote Set temp. mode Remote mode Remote
mode
0 Normal – – – – – – – – – – – –
1 Temp. shift – – – Shift – Center – – – – – –
Fan – – – – Fan Center – Fan Center – – –
2 (1stage)
Fan – – – – Fan Center – Fan Center – Fan Center
3 (2stage)

Demand level 1 – Any indoor unit set to D1 (Demand level 1)has its temperature set point shifted by +2°C in cooling mode or -2°C in heating
mode and cannot be operated from the local remote controller
Demand level 2 – Any indoor unit set to D1 or D2 switch to fan only mode and cannot be operated from the local remote controller
Demand level 3 – Any indoor unit set to D1 or D2 or D3 switch to fan only mode and cannot be operated from the local remote controller

Electric power calculation function: Item Model SC-SL4-AE/SC-SL4-BE


(for SC-SL4-BE only) Ambient temperature during use 0 ~ 40oC
SC-SL4-BE gives electric power consumption data (kWh) for each indoor unit , Power supply 1 Phase 100-240V 50/60Hz
each group , each SUPERLINK-II system , and each watt-hour meter input. Power consumption 9W
External dimensions
(Height x Width x Depth) 172mm x 250mm x 23 (+70) mm

Net weight 2.0kg


Number of
connectable units (indoor units) up to 128 units

LCD touch panel Colour LCD, 9 inches wide


SL (Superlink) signal inputs 1 system (Super link- )
Watt-hour meter pulse input* 8-point, pulse width 80ms or more
Inputs

1 point, non-voltage a contact input


Emergency stop signal input* continuous input (closed, forced stop)
2 point, non-voltage a contact input
Demand signal input* continuous input (closed, demand control)
SC-SL4-BE 1 point, maximum rated current 40mA, DC24 V
Export data by USB / LAN Operation output
All units stop; Open, any unit operating;Close
Outputs

Calculation software Included 1 point maximum rated current 40mA, DC24 V


Watt-hour meter Error output Normal; closed. If even one unit is abnormal; Open
pulse input (Maximum) 8 (Open/closed can be changed)
Max connectable indoor units 128 * The receiving side power supply is DC 12V (10mA).
The air conditioning charges calculations of this unit are not based on OIML, the international standard.
113
R410A

SC-SL1N-E
Start/stop control of up to 16 indoor units either
individually or collectively.
Simple centralised control.

1. The SC-SL1N-E is connected to the Superlink- network via 2-core, non-polar wires (‘AB’ connection).
2. It will monitor and control the start/stop function of up to 16 units, with the sixteen operation button.
3. The unit or group numbers in operation or in need of service are displayed with an LED.
4. Collective start/stop is also available through the simultaneous on/off button.
5. Up to 12 SC-SL1N-E units can be connected to a Superlink- network (consisting of up to 128 indoor
units).
6. If a power failure occurs, the SC-SL1N-E will resume the operation of the system according to a stored
operation condition, once power is restored.

SC-SL2NA-E
Central control of up to 64 indoor units including weekly timer function as standard.

1. The SC-SL2NA-E is connected to the Superlink- network via 2-core, non-polar wires (‘AB’
connection).
2. It will monitor and control the start/stop function of up to16 units, or 16 groups of units, with the
sixteen operation buttons.
3. It also monitors and controls the following functions for individual units, groups of units or the
complete network: operation mode, set point temperature, return air temperature, louvre position,
error code. Air flow and center lock function.
4. The unit or group numbers in operation or in need of service are displayed with an LCD.
5. Collective start/stop is also available through the simultaneous on/off button.
6. If a power failure occurs, the SC-SL2NA-E will resume the operation of the system according to a
stored operation condition, once power is restored.
7. The SC-SL2NA-E can be connected to an external timer to facilitate timed on/off cycles.

Example of control by a center control SC-SL2NA-E SC-GIFN-E Interface kit


• Applicable products
Ventilation fan, Air purifier
• By using SC-GIFN-E together with central control such as SC-SL1N-E,
SC-SL2NA-E and SC-SL4-AE/BE, you can start-stop, operate & monitor
the operation of applicable products.
SL1N-E
Address setting switch
Set address number will
Printed board
SW1 ten's place be the address for
SW2 one's place
SC-SL1N-E,
SC-SL2NA-E,
hundred's SC-SL4-AE/BE
SW3 place

Terminal block
51X 52 52R

1 2 3 4 5 6 7 8 A B

Net work communication line


AC220-240V To A & B terminal block on
SC-SL1N-E,
Anomalous signal input SC-SL2NA-E,
SC-SL4-AE/BE
Operation signal input Net work

Start-Stop command output

An SC-SL2NA-E performs the start/stop control, monitoring and mode setting of up to 64 units. It
is a high quality air conditioner control system that allows up to 64 indoor units to be freely
grouped into 1 to 16 groups.
It allows not only the start/stop control but also the monitoring, display of operation statuses such
as in operation or in need of service and mode setting such as switching of operation modes of
connected units collectively, by group or individually.
• Outer dimensions: H120 x W215 x D25+35*mm.
35* is the measurement including the part contained in a recess.

Note:Please consult dealer for combination of center controls and Building Management Systems interface units.

114
<Building Management Systems>
SC-WBGW256 (Web gateway+BACnet gateway) Production by order

SC-WBGW256 controls and monitors of up to 256 cells (some cells can have two or more indoor units and
total number of indoor units can be up to 256 units) centralised to a network PC using the Superlink- web
gateway. Simple installation is assured with no special software requirements, operation is via Internet
Explorer. A low power embedded CPU and compact flash ROM ensure a large storage capacity with high
reliability (no moving parts such as a PC fan, etc). An IP address filter function combined with three-level user
authentication check also ensures security.
Also, SC-WBGW256 can be used as interface devices that convert Mitsubishi Heavy Industries Superlink-
communication data to BACnet code and are controlled centrally from a building management system.

Additional engineering service cost etc. is required.


Please consult your dealer when using this central control.
[ In case of web gateway ]
SUPERLINK- No. 1 system

128 units
128 cells
Internet
Explorer HUB

Ethernet 10 BASE-T/ 128 cells


SUPERLINK- No. 2 system
100BASE-TX
Emergency stop DI1 128 units
SC-ADNA-E
pulse
Watt meter pulse input
(no-voltage contact x8 points)
PC requirements: Windows 7 or Windows 8.1.
Cell Monitor resolution 1364 x 768.

Users can manage up to 1024 units by connecting the four devices!!

[ In case of BACnet gateway ]


SUPERLINK- No. 1 system
128 units
128 cells
Ethernet 10 BASE-T/100BASE-TX

Network 128 cells


BACnet I/P Protocol.

for SUPERLINK- No. 2 system


lighting Internet
128 units Explorer HUB
SC-ADNA-E
Emergency
sensor
network
Up to 4 WBGW256 can be handled by 1
Cell Internet Explorer Screen
Emergency stop DI1
pulse (max. 256x4=1024 units)
Watt meter pulse input
(no-voltage contact x8 points)

SC-LGWNB (LonWorks gateway) Production by order

SC-LGWNB is an interface device that converts Mitsubishi Heavy Industries Superlink- communication
data to LonWorks code. Control and monitoring functions of the a/c system for up to 96 indoor units
can be integrated to a central control point via the building management system network.

96 units

Network
for
LonWorks network

lighting
(FTT-10)

Emergency Additional engineering service cost etc. is required.


sensor
network Please consult your dealer when using this gateway.

115
Mitsubishi Heavy Industries Thermal Systems VRF inverter multi-system Air-Conditioners
Before starting use
Heating performance Refrigerant leakage

VRF inverter multi-system


The heating performance values (kW) described in the catalogue are the The refrigerant (R410A) used for Air conditioner is non-toxic and in its
values obtained by operating at an outdoor temperature of 7 C and indoor original state.
temperature of 20 C as set forth in the ISO Standards. As the heating However, in consideration of a state where the refrigerant leaks into the
performance decreases the outdoor temperature drops, if the outdoor room, measures against refrigerant leaks must be taken in small rooms
temperature is too low and the heating performance is insufficient, use where the tolerable level could be exceeded. Take measures by installing

Air-Conditioners
other heating appliances as well. ventilation devices, etc.

Indication of sound values Use in snowy areas


The sound values are the values (A scale) measured in a chamber such as Take the following measures when installing the outdoor unit in snowy
an anechoic chamber following the ISO Standards. In the actual installation areas.
state, the value is normally larger than the values given in the catalogue
due to the effect of surrounding noise and echo. Take this into ·Snow prevention
consideration when installing. Install a snow-prevention hood so that the snow does not obstruct the air
intake port or enter and freeze in the outdoor unit.
Use in oil atmosphere
Avoid installing this unit in an atmosphere where oil scatters or builds up, ·Snow piling
such as in a kitchen or machine factory. In areas with heavy snow fall, the piled snow could block the air intake
If the oil adheres to the heat exchanger, the heat exchanging performance port. In this case, a frame that is 50cm or higher than the estimated
will drop, mist may be generated, and the synthetic resin parts may deform snow fall must be installed underneath the outdoor unit.
and break.
Automatic defrosting device
Use in acidic or alkaline atmosphere
High Performance
If the temperature is low, and the humidity is high, frost will stick to the
If this unit is used in acidic atmosphere such as hot spring areas having heat exchanger of the outdoor unit. If use is continued, the heating
high level of sulfuric gases or in alkaline atmosphere including ammonia or performance will drop.
calcium chloride, places where the exhaust of the heat exchanger is sucked The "Automatic defrosting device" will function to remove this frost.
in, or at coastal areas where the unit is subject to salt breezes, the outer
plate or heat exchanger, etc., will corrode. Please ask a dealer or specialist
when you use an air conditioner in places differing from a general
After heating for approx, three to ten minutes, it will stop, and the frost
will be removed. After defrosting, hot air will be blown again. Air-Conditioning

2020
atmosphere. Servicing the air-conditioner
After the air-conditioner is used for several seasons, dirt will build up in
Use in places with high ceilings the air-conditioner causing the performance to drop. In addition to
If the ceiling is high, install a circulator to improve the heat and air flow regular servicing, a maintenance contract by a specialist is
distribution when heating. recommended.

Safety Precautions
Air-conditioner usage target Installation
The air-conditioner described in this catalogue is a dedicated cooling/ Always commission the installation to a dealer or specialist. Improper
heating device for human use. installation will lead to water leakage, electric shocks and fires.
Do not use it for special applications such as the storage of food items, Make sure that the outdoor unit is stable in installation. Fix the unit to
animals or plants, precision devices or valuable art, etc. stable base.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current Usage place
leaks could occur. Do not install in places where combustible gas could leak or where there
are sparks.
Before use Installation in a place where combustible gas could be generated, flow or
Always read the "User’s Manual" thoroughly before starting use. accumulate, or places containing carbon fibers could lead to fires.

Mitsubishi Heavy Industries Thermal Systems, Ltd. 2-3 Marunouchi 3-chome, Chiyoda-ku, Tokyo 100-8332, Japan
( Wholly-owned subsidiary of MITSUBISHI HEAVY INDUSTRIES, LTD.) https://www.mhi-mth.co.jp/en/

Our factories are ISO9001 and ISO14001 certified.


Certified ISO 9001 Certified ISO 14001

ISO 9001 ISO 14001


Certificate:44 100 980813 Certificate:04 104 980813

Certificate Number : JQA-0709 Certificate Number : 4333-2007-AQ-RGC-RvA Certificate Number : YKA4005636 Certificate number : 02117E10160R0M

20KX02E December 2019 F Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. 50Hz
Edited in Japan 20KX02E