0% found this document useful (0 votes)
397 views12 pages

Deutz MWM TEM System

The document provides a system manual for an intelligent selection unit (IAE) that allows remote access and monitoring of multiple DEUTZ MWM TEM ÿþýüûúùýø systems through a single modem. The IAE connects to up to 12 TEM systems and can also connect up to two central operating terminals. It provides password protected remote access to any of the TEM systems without needing local intervention at the site. If faults occur, the IAE can also send alarm signals to a control room. The system uses a modular design for flexibility and can be adapted to individual application needs.

Uploaded by

Abbas Partovi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
397 views12 pages

Deutz MWM TEM System

The document provides a system manual for an intelligent selection unit (IAE) that allows remote access and monitoring of multiple DEUTZ MWM TEM ÿþýüûúùýø systems through a single modem. The IAE connects to up to 12 TEM systems and can also connect up to two central operating terminals. It provides password protected remote access to any of the TEM systems without needing local intervention at the site. If faults occur, the IAE can also send alarm signals to a control room. The system uses a modular design for flexibility and can be adapted to individual application needs.

Uploaded by

Abbas Partovi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

System Manual

DEUTZ MWM
TEM ÿþýüûúùýø System
TBG 616/620/632
Intelligent Selection Unit
System Description

All rights reserved. We reserve the right to modify the product


designs and specifications described herein without prior notice.
Reprint and reproduction of any kind are not permitted without
written authorization.

Last revised on 17.05.99


H:\TEMEVO\HANDBUCH\AKTUELL\IAE\IAE_V6E.DOC

System supplier:
Motoren-Werke Mannheim AG
Carl-Benz-Str.5
D-68167 Mannheim
DEUTZ MWM
TEM ÿþýüûúùýø System

Table of contents:
1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Features of performance . . . . . . . . . . . . . . . . . . . . . . 4

3 System concepts . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4 Remote access to multiple TEM-Evo systems . . . . . . . . . . . . . 7

5 Central operating terminal . . . . . . . . . . . . . . . . . . . . . . 7

6 Fault Message option . . . . . . . . . . . . . . . . . . . . . . . . 8

7 Equipment design / modular concept . . . . . . . . . . . . . . . . . 9

8 Attachment technique and mechanics . . . . . . . . . . . . . . . 10

9 Configuration possibilities . . . . . . . . . . . . . . . . . . . . . 11

10 Diagnostics possibilities . . . . . . . . . . . . . . . . . . . . . 11

11 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
11.1 Access protection by callback . . . . . . . . . . . . . . . . . . . . 12
11.2 Disabling remote access . . . . . . . . . . . . . . . . . . . . . 12
11.3 Protecting configuration . . . . . . . . . . . . . . . . . . . . . . 12

12 Site-specific requirements . . . . . . . . . . . . . . . . . . . . . 12

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 2


DEUTZ MWM
TEM ÿþýüûúùýø System

1 Overview
The intelligent selection unit (IAE) is an additional feature of the modem system for TEM-Evolution
which can be used for both new and existing plants.

The modem system for TEM-Evo allows remote control and remote maintenance or diagnostics of
TEM-Evo plants via the common analog telephone network and using the new functions Visualization
(operation like at TEM-Evo operating terminal) and Remote Programming (for reloading updated
control programs).

If one plant includes several TEM-Evo systems, there is generally one single modem for all systems
installed. To allow access to all gensets, the default connection between the modem and the TEM-Evo
systems uses a selection unit which is switched manually using a rotary switch. This is the reason why
operators have to be present on-site if multiple TEM-Evo systems have to be accessed.

The intelligent selection unit allows to avoid this restriction as it is told by the modem which genset the
caller wants to connect to. No manual operation is necessary any more.

Due to the modular design of the IAE and to the microprocessor used, several tasks other than just
switching to the gensets can be done, such as the connection of up to two central operating terminals
or the automatic submission of fault messages via modem to a service control system.

Thanks to its flexibility the intelligent selection unit can also be used for TEM systems (for detailed
information see the “intelligent selection unit for TEM“ system manual) and even for systems of other
manufacturers such as boiler control systems or similar.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 3


DEUTZ MWM
TEM ÿþýüûúùýø System

2 Features of performance
• Remote access to the connected TEM-Evo systems without local intervention

• Protected access via modem using password and call-back functions

• Connection of central operating terminals which can access the connected TEM-Evo systems using
the function keys of the operating terminal or a manual rotary switch

• In case of a fault or an alarm, an alarm signal is sent to a control room (only for option “Fault
message“).

• Versatile and user friendly Windows management program and clear status display for the
monitored systems available; it allows flexible processing of incoming alarm signals such as calling
the task force outside office hours via city call (for further details see the “Remote Monitoring
System - RMS“ system manual)

• Modular design allowing low-cost adjustment to each single application case

• Easy upgrade of existing modem systems already installed

• Optional disabling of the access to TEM-Evo controls via modem (for service purposes)

• Data transfer between the central operating terminals via modem, e.g., for loading updated
visualization programs

• Up to 12 TEM-Evo controls can be attached, and the Central Operating Terminal option provides
attachment for up to 8 (two central operating terminals) or 10 (one central operating terminal) TEM-
Evo controls.

• The flexible adjustment possibilities permit execution of related tasks such as for TEM systems;
solutions are also provided for systems from other manufacturers (boiler plants or similar).

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 4


DEUTZ MWM
TEM ÿþýüûúùýø System

3 System concepts
Figure 1 shows the basic system design of a plant including an intelligent selection unit (IAE) and two
central operating terminals (BR).

TES 1 TES 2

FAE FAE

X 1 1x m X 2 1x m

BR M1 1x m M2 1x m BR

TES 3 .. 8/10/12

24 V
IAE NT/Modem

2 x TEM Evo

2 x TEM Evo

2 x TEM Evo

2 x TEM Evo

1 x BR

1 x BR

ca. 0,7 m
230 V
ca. 1,5 m

Modem
ca. 3 m

IAE

TAE
O1 1x m
O2 1x m
WS
WS N1 1x m

N2 1x m
BR

BR

Figure 1: IAE system concepts, full version

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 5


DEUTZ MWM
TEM ÿþýüûúùýø System

Each TEM-Evo system in a plant is equipped with an additional module (function selection unit FAE)
which allows to select the operating mode of communication between the TEM-Evo system and the
local operating terminals and the modem attached to the IAE or the central operating terminals.

The function selection unit can be mounted on a rail and has two ports to be connected to the control
unit: one port for visualization and one port for programming. The intelligent selection unit (IAE) can
remotely set the required operating mode of the function selection unit. Furthermore, the access to the
TEM-Evo system via the IAE can be stopped using the function selection unit, if this is required during
service.

The distance between the TEM-Evo systems and the IAE can be up to 100 m.

For the fault message option the IAE has two additional 24 V inputs for each TEM-Evo system which
the IAE uses to receive fault and alarm messages. These signals are usually triggered by the intelligent
strip terminal of the TEM-Evo system.

The modem which is connected to the analog telephone network is placed directly next to the IAE.

Up to two central operating terminals can be connected to the IAE; the distance between these
operating terminals and the IAE can be at most 100 m. Only one data line is required to connect the
operating terminals; the TEM-Evo systems can also be selected for visualization using this data line.
Then, the TEM-Evo system which is to be displayed on the central operating terminal can be selected
using function keys at the operating terminal.

Another way of selecting a TEM-Evo system than using function keys of the operating terminal consists
of using a separate selector switch connected to the IAE and which allows to select the TEM-Evo
system to be displayed on the central operating terminal.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 6


DEUTZ MWM
TEM ÿþýüûúùýø System

4 Remote access to multiple TEM-Evo systems


If a plant includes more than one TEM-Evo system you can choose the TEM-Evo system which you
want to visualize via modem. The IAE receives a switching command via modem.

If the IAE does not receive any switching command, it will be checked if the remote access is enabled.
A switch on the IAE allows the remote access via modem to be generally disabled. This takes into
account the need for security of many site operators, who generally disconnect the modem from the
telephone network or the power supply so that no fault messages can be issued any more.

If no operating terminal with higher priority is connected to the selected TEM-Evo system when a
switching command is received, the IAE switches through to the selected TEM-Evo system, which
allows visualization via modem.

If the selected TEM-Evo system has an own (local) operating terminal, the local operating terminal is
disconnected from the control system; thus, visualization is not possible any more. This avoids
contradictory commands being sent to the TEM-Evo control system by the operator of the local TEM-
Evo system operating terminal operator and the central operating terminal operator.

5 Central operating terminal


If a site has multiple TEM-Evo systems, a central operating terminal is installed at a central position
such as in the control room, in addition to the operating terminals of the individual TEM-Evo systems.
This central operating terminal allows access to all gensets.

The IAE supports up to two operating terminals of this kind which can be installed e.g. in a control
room and on the control station in the engine room.

The TEM-Evo system that you want to visualize on the central operating terminal can be selected
either using switching commands which are issued via function keys from the display or using a
manual selector connected to the intelligent selection unit.

The modem and the operating terminals which are connected to the IAE follow a priority order. If two
devices try to access the same TEM-Evo system at the same time, the device with the higher priority
will be connected to the TEM-Evo system.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 7


DEUTZ MWM
TEM ÿþýüûúùýø System

6 Fault Message option


When faults or alarms occur the connected TEM-Evo systems can notify the IAE that a message has
to be sent to a service control station.

As soon as the IAE recognizes an occurring fault it dials the set number of the modem of the service
control station. If the establishment of a connection fails, the dialing process is repeated. If the
connection with the set telephone number definitely fails, an alternative phone number can be dialed
and the message is sent to this number. This alternative number can be e.g. the phone number of the
service control station of a near subsidiary.

Often customers want to be informed when a fault occurs. In this case settings can be made to have a
message sent to a second phone number at the same time as the message is sent to the control
station. If this number is busy the attempt to issue the message is repeated several times.

When the connection to the control stations concerned is established, the IAE issues a message which
identifies the site and tells the reason of the call. It also specifies the time the fault occurred. If more
than one messages are pending before the connection to the control station is established all
messages will be submitted in one go.

If a modem connection is already active when a fault occurs, the system waits for disconnection before
it tries to issue the message. When the genset is changed and the disconnection has taken place, the
IAE informs the caller connected via the modem about any faults which have not yet been indicated.

In case of a voltage loss occurring before the IAE had the opportunity to indicate the fault, another
attempt will be made to inform the control station when the voltage has come back.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 8


DEUTZ MWM
TEM ÿþýüûúùýø System

7 Equipment design / modular concept


The intelligent selection unit IAE consists of a housing containing an intelligent back-panel wiring. This
housing can accommodate additional modules which the TEM-Evo systems and the central operating
terminals can be connected to using the front-panel plug-type connectors. The IAE design allows
variable extension with growing requirements.

The following modules resp. extension levels are available for the intelligent selection unit:

• Voltage supply with attachment for the modem, switch for remote access release, displays e.g. for
permanent alarm calls, self test errors
This module is already contained in the IAE basic version.

• Attachment component for TEM-Evo controls (without fault message option)


Allows to connect the data lines to two TEM-Evo controls which can be accessed via modem and
from the central operating terminals (operating terminal connection option).
Provides displays for data transfer from and to the connected TEM-Evo controls.

• Attachment component for TEM-Evo controls (with fault message option)


Allows to connect the data lines to two TEM-Evo controls which can be accessed via modem and
from the central operating terminals (operating terminal connection option). The controls can display
pending faults or alarms via two digital 24 V inputs. In case of a fault or an alarm, a central control
station can be automatically informed via modem.
Provides displays for data transfer from and to the connected TEM-Evo controls and fault and alarm
messages.

• Attachment component for the operating terminal


Allows to connect an operating terminal which can be used to access the connected TEM-Evo
systems. The TEM-Evo system to be visualized can be selected using the function keys on the
operating terminal or using a manual selector switch.
This module has eight 24 V digital inputs which can be used to connect the selector switch.
Provides displays for the data transfer from and to the connected operating terminal and for the
switching input status.

Altogether, at most six attachment components for TEM-Evo controls and central operating terminals
can be integrated, up to two components of which can be allocated to operating terminals.

In a maximum extension design without a central operating terminal, twelve TEM-Evo controls can be
attached (6 modules for every two TEM-Evo controls). For each connected central operating terminal,
the number of TEM-Evo controls that can be connected is less two, i.e., the number is 10 with one
central operating terminal and 8 with two central operating terminals.

It is not planned to retrofit these attachment modules for TEM-Evo systems to the fault
message option. If this option is required later the attachment modules have to be replaced.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 9


DEUTZ MWM
TEM ÿþýüûúùýø System

8 Attachment technique and mechanics


Data and control lines as well as the power supply are attached via screwed front-panel plug-in type
connectors.

The modem is connected via a sub D connector; the connection line is shipped with the system.

The intelligent selection unit is in a housing with the dimensions of 200 mm x 150 mm x 150 mm (W x
H x D when wall mounted).

The housing can be mounted on a 35 mm rail conforming to DIN EN 50 022 or directly wall mounted
using wall brackets.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 10


DEUTZ MWM
TEM ÿþýüûúùýø System

9 Configuration possibilities
The configuration of the intelligent selection unit can be executed remotely via modem. This allows the
different parameters and settings to be variable.

These parameters can easily be modified using any common terminal program.

The parameters are saved according to special levels using passwords. So only the system supplier
can modify system sensitive settings.

The following parameters can be set:

• Equipment features of the intelligent selection unit

• Characteristics of the telephone port used (extension line, switched line etc.)

• Priority between the modem and the connected central operating terminal, if both are requesting the
same TEM-Evo control is required

• Passwords for parameter and setting modifications

• Polarity allowing to indicate faults and alarms

• Release of the message function separately for each genset connected in order to avoid permanent
faulty message triggering during service periods

• Phone number to submit a fault or alarm message, generally a service control station. An
alternative number can be configured, if required, to be called when the main number is not
available.

• Second phone number to be called at the same time as the main number when a fault or an alarm
has occurred

• Number and time interval between attempts to issue messages if a control station is not available

The configuration is stored in a fixed storage area and it is voltage loss proof.

10 Diagnostics possibilities
The intelligent selection unit offers different procedures of self-diagnostics and error recognition which
can be queried remotely via modem.

For initiation and debugging as well as for displaying the operating status the IAE displays several
panels which allow to draw conclusions about possible errors. These include in particular panels for
data transfer and the digital input status.

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 11


DEUTZ MWM
TEM ÿþýüûúùýø System

11 Security

11.1 Access protection by callback


TEM-Evo systems of a plant are accessed via the modem installed on-site. This site modem is
selected from the office via a modem for software packages (PC-Mod type). This access is password
protected with callback to ensure that only authorized users have access to the plants. If you want to
access a plant you have to logon to the modem system using a user ID defined by the supplier. After
that, this callback number associated to the user ID is called back. This guarantees the highest
security even if another user knows the access ID.

11.2 Disabling remote access


The intelligent selection unit has a release switch which can be used to disable remote access to the
TEM-Evo systems. This may be necessary when service tasks are carried out or when an operator
wants to control access to his TEM-Evo gensets.

If a caller attempts to connect to a TEM-Evo system he receives a message telling him that remote
access is disabled. There is no point in checking again with the operator. If a modem connection is
active when the switch is activated, this connection is interrupted with an error message.

In spite of the remote access being disabled, the intelligent selection unit can continue sending fault
messages to a control station (fault message option) or can be remotely configured.

11.3 Protecting configuration


Setting modifications of the intelligent selection unit are protected by a multiple level security concept
which requires knowledge of individual passwords. System sensitive settings may only be modified by
the system supplier.

12 Site-specific requirements
The following site-specific requirements have to be met to operate the intelligent selection unit:

• Voltage supply 24 V DC (± 15 %, max. 0.5 V residual ripple), power consumption < 1 A, fuse
protection 3 A

• Direct in-dialing enabled telephone connection with full exchange line authorization in order to allow
the callback when the logon succeeded and to optionally issue alarm calls

Intelligent Selection Unit IAE Last revised on: 17.05.1999 Page 12

You might also like