Gas Detection System
Gas Detection System
UODa F O M A -T 3 4 W
O P ER A TIO N
MANUAL
♦ Range of warranty
1. The period of warranty for this product is one year from the date of delivery.
2. Defects arising in the equipment caused by faults in manufacturing within the period of
warranty -excluding consumables-will be replaced -parts only- or repaired free of charge.
3. Contact your distributor if defects occur.
4. Invoices will be issued for the actual cost of repairs or replacement parts'within the
period of warranty in the following cases:
* Faults arising from method of usage other than those stipulated in this manual.
* Faults arising from the device having been upgraded or repaired by people other*than*the
manufacturer or distributor.
* Faults arising from natural disasters or accidents not related to the product.
* the replacement of consumable products.
♦ Safety precautions
This manual categorizes procedures in accordance with the following levels of risk involved
in order to prevent unexpected danger to operators and other personel, and damage to assets.
Ensure that these items are observed for safety reasons.
A Warning This indicates that failure to observe the contents of the item or
mistaken use may result in death or serious injury.
O F i x detecting part of sumpling inlet of each measuring point at the place where inflammable gas
tends to stay.
O l n case that even if standard gas is supplied to gas detecting part, alarm is not given or
adjustment is impossible to carry out, it may be a trouble of sensor.
Replace the sensor in accordance with instruction manual of alarm meter or analizer. When
the same phenomena remains after replacement, it is a trouble of alarm unit. Repairing'
should be required. If operation is being kept without repairing, serious accident may be
possibly caused and dangerous.-
O T h e sensor consists of a detection element and a comparison element.
When replacing sensor, never fail to replace it in pairs.
Oft'hen alarm unit and gas detector are installed, refer to this instruction manual and that
of each detector. If wiring is made wrong, alarm unit or detector operates wrong or is
broken occasionally.
O l n case of suction type detector, if specifications of tube; length, inner diameter, etc.
are not correct, readings may be wrong occasionally. „
♦Meanings of terminology
1) Explosion-protected construction
Construction applied to electrical apparatus to prevent ignition of the surrounding
explosive atmosphere by such apparatus.
2) Hazardous areas
Terms representing group of area concerning explosion-protection; an area where hazardous
atmosphere exists or there is a fear of its existing.
4) Detection principle
Principle of detecting existence of gas,- and converting it to electric signal.
5) Sampling system
System which sucks air to be measured automatically from sampling points and leads to
gas analyzer.
6) Fresh air
The environmental air not including inflammable gas to be measured (in case of this
.instrument, used for zero adjustment gas).
8) Zero adjustment
Adjusting indication of alarm unit to zero with fresh air.
.5Й Indicator alarm unit, gas alarm meter or gas analyzer, refer to separate volume instruction
manual j’.
CONTENTS
I T E M ' PAGE
со 00 00
6 . Piping ...... . • -
7. Wiring ..........
8 . Gas flow system ■ • * <
9. Power supply ......... ................................... ................ .. 10
1 0. Adjustment - _ • • • • ■ ................... .............. ........................... 1 1
10-1 Adjustment of inflammable gas detector
10-2 Adjustment of Oxygen detector
10-3 Adjustment of inflammable gas detector in panel
1 1 . Method of collecting calibration gas ■ ............................................. 1 3
11-1 Method of collecting calibration gas from calibration gas cylinder.
11- 2 Gas collecting method from the spray cylinder
1 2. Operation ............................... . ............ ' ................. 15
12- 1 Changingover measuring points
12-2 High alarm operation
12-2-1 Inflammable gas (H. C)
12-2-2 Oxygen (Ог)
12-2-3 inflammable gas detection in panel
12-3 Trouble alarm operation of unit
12-3-1 Inflammable gas (H. C)
12- 3-2 Oxygen (Ог)
12-4 Pump failure operation
12-5 Power supply failure
12- 6 Error code table of alarm unit
1 3. Maintenance ........ ..................................... ....................... 2 0
13- 1 Gas alarm panel
13-2 Replacing a paper filter for air filter
13-3 Maintenance of suction pump
13-4 Replacement of sensor
13— 4— 1 Inflammable gas (H. C)
13-4-2 Oxygen (Ог)
1 4. Cautions for use ................................................................. 2 2
1. General
This system detects the inflammable gas in the air by applying the principle of catalytic
combustion method, and transmits an alarm when the gas concentration reaches a preset alarm level
(PUMP ROOM— »10%LEL. IN PANEL— 30%LEL) or above, and detects the oxygen in the air by applying the
principle of galvanic cell method, and transmits an alarm when the oxygen concentration reaches a
preset alarm level (PUMP ROOM— 18%) or less.
The GAS ALARM PANEL is set up in the CARGO CONTROL ROOM and where piping is arranged to where
gas is collected.
The sample gas is sucked by a pump in the equipment through the piping, and measured.
The equipment uses two-way solenoid valves to measure 4 points (PUMP ROOM) by switching each
point successively.
One(l) point in panel is monitored by gas detector continuously.
2. SPECIFICATIONS
1
2-2 Д 1 а т unit specification (PUMP-ROOM — H. C)
- 2 -
2-4 Alarm meter specification (IN PANEL)
If the air containing an inflammable gas comes into contact with a catalyzer- heated appreciably,
the molecules of the inflammable gas react on oxygen in the air(catalytic combustion reaction),
producing reaction heat (catalytic combustion heat).
The produced heat is proportional to the concentration.of the gas providing that the
concentration of the inflammable gas is low enough for a perfect combustion.
Accordingly, a Wheatstone bridge is formed by using two filaments whose electric resistance is
the same as shown in Fig. 3-1 . ' ’
One filament is exposed to the gas to be measured (detection side Fl), and the other is sealed in
clean air (comparison side F2).
The bridge is preheated up by electric current to a particular temperature at which the gas will
produce a catalytic combustion.
If the inflammable gas touches the detection side filament, the temperature of Fl will go up by
the combustion heat, increasing its electric resistance, producing an electric current between A
and В on the bridge, by which gas concentration can be detected.
The diaphragm galvanic cell is a system in which heterogeneous electric conductors (at least one
of them must be an electrolyte or ionic conductor like an electrolytic solution) are connected in
series and the chemical compositions of the end phase are the same.
The construction model of the oxygen sensor applying the diaphragm galvanic cell is shown in
Fig. 3-2.
Ог -
Ml М2
~o Ml : Gold (Cathode)
М2 : Lead (Anode)
S : Electrolytic solution
( 1)
O 2 + 4 H ‘ + 4 e" ^ 2 Н г О (Acid electrolyte)
Os'+ 2 H 2O + 4 e ' — ♦ 4 O H (Alkaline electrolyte)
In electrochemistry, the electrode from which positive charges move toward a solution is called
an anode (positive electrode), while that where positive charges move from the solution to the
electrode phase is called a cathode (negative electrode).
. From this reason, with the oxygen sensor, the gold electrode side is called a cathode (negative
electrode), and the lead electrode side is called an anode (positive electrode).
For a gas penetrating membrane, that of fluororesin or the like is used through which"oxygen gas
easily passes.
Between the membrane"and the cathode is formed a thin electrolytic layer, the oxygen gas having
passed through the membrane is dissolved in the electrolytic layer.
The dissolved oxygen produces a reduction reaction on the cathode and concurrently an oxidation
reaction on the anode, thus a reduction current flows in proportion to the oxygen concentration.
An oxygen concentration is readable from the terminal potential on the load resistance connected
between the anode and cathode external to the sensor.
This electric potential is called the output of the oxygen sensor.
Since the electric potential is proportional to the concentration of oxygen, the concentration of
oxygen can be determined by measuring the electric potential at that time.
The above is a reaction principle of the oxygen sensor.
The products on the lead electrode are dissolved into the electrolytic solution by the following
reaction..
ЙЪеп Pb(CIO* ) 2 has been saturated, it is precipitated oh the surface of the lead electrode.
If the whole surface is covered with it, no more electrode reaction would proceed,when the life
of the’electrode would be over.
By surveying age-based characteristics of oxygen sensors in the past, we can guarantee the life
of the oxygen sensor for about one year.
- 5 -
4. Designation
- 6 -
s 4-2 Gas alarm panel inside
5. Installation - .
The installation place should be free from mechanical vibrations, corrosive gases, and dust;
with little variation in temperature,humidity, close to the normal temperature and himidity.
ffal1-mounted
The panel should be fixed at four places.
- 7 -
6. Piping
A copper tube. 6mni in 0. D., is used from gas collector to the alarm panel.
Clean each tube by blowing dry air through it to remove metal chips, dust and other foreign
matter before joining it to the alarm panel: otherwise gas may not be sucked in or may be retarded
in sucking. Further, be sure that each system has been joined properly when cleaning the piping. .
Arrange the piping with a minimum bends and without sharp corners to avoid retardation in sucking.
For the exhaust piping, use a copper tube, 15mm in 0. D., arranging it to a safe place where there
is no possibility to catch fire.
IN P-A N E L
SH-H!
PI HI
- 8 -
8. Gas flow system
SIIlkC
®. 2-way solenoid valve for switching from measurement to calibration gas (SVC)
Turn the 'MEAS. -CALIB.' select switch to "CALIB. ' to suck in the calibration gas.
© Gas collector(GD-PE)
Excepts dust in the sample gas.
© Detector (RD(S))
Detects the inflammable gas leaking into the PUMP ROOM.
© D e t e c t o r (RD)
Monitors inflammable gas leakage in the GAS DETECTION PANEL.
9. Power supply
Ensure wiring and piping are correct before closing the main switch, furthen sach switch is under
the following condition(factory setting)
(3) Turn the power supply switch of the alarm meter (FA-470) to ON position.
— * The pilot of the alarm meter lights up and digital meter indicates around *0".
(4) Turn the power supply switch (USW) of the"alarm unit to ON position.
— * POWER LEDs 'PW' (green) and 'MAINT' (orange) of the inflammable gas alarm unit(KU-7/F) light -
up and digital meter indicates around “0” .
POWER LEDs 'PW' (green) and 'MAINT' (orange) of the oxygen alarm unit(KU-7/G) light up and
digital meter indicates around “20. 9” .
(5) Press the maintenance switches of both inflammable gas alarm meter and oxygen alarm meter, to
release maintenance mode, provided that indication is stabilized.
(6) Each sampling point is successively switchedover every two minutes at auto mode.
10 -
fo. Adjustment
(1) Set the inflammable gas alarm unit and oxygen alarm unit in maintenance mode by pressing MAINT
switch. (Maintenance mode : When "MAINT'(orange) lights up.)
(2) Turn MEAS./CALIB. switch on the front panel to 'CALIB, ' position.
(3) Refer to operation manuals of alarm unit, alarm meter for further details.
Make adjustment when the power supply switch is turned on for the first time or when the
inflammable gas detector is replaced.
t
(1) Zero adjustment
Ф Let the clean air be sucked from the calibration gas inlet(CALIB. INLET).
© After the digital indication of the alarm unit (KU-7/F) has been stabilized, adjust the
indication of the digital meter to “0” by turning ZERO adjustment volume (ZERO)-.
(D Collect calibration gas into gas bag and the like, and let the calibration gas be sucked from
calibration gas inlet(CALIB. INLET).
® After the digital indication of the alarm unit has been stabilized, adjust SPAN volume of the
alarm unit(KU-7/F) so that the digital meter indicates the same value as the gas concentration
%LEL of calibration gas cylinder, provided that gas concentration is converted by the
under-mentioned formula.
%LEL = Calibration gas concentration Lower explosion limit of Calibration gas X 100 .
Make ajustment’when the power supply switch is turned on for the first time or when the
oxygen sensor is replaced.
ф Let the nitrogen gas(100vol%) be sucked from the calibration gas inlet(CALIB. INLET).
© Connect the voltmeter between the sensor board’s TP1 (-) and TP2(+) current check terminals,
and rotate the volume (VRl) on the sensor board, then the voltage between the terminals is
adjusted to DC0. 2V, and the output current will be calibrated to DC4mA.
® When making adjustment of above item © , adjust meter indicator to ' 0' by turning ZERO
adjustment volume "ZERO' of Model KU-7/G alarm unit.
11 -
*(2) Span adjustment
Ф Let the clean air be sucked from the calibration gas inlet.
© Connect the voltmeter between the sensor board's TP1 (-) and TP2(+) current check terminals,
and rotate the volume (VR2) on the sensor board, then the voltage between the terminals is
adjusted to DCO. 87V, and the output current willbe calibrated to DC17.4mA.
© When making adjustment of above item © , adjust meter indicator to '20.9* by turning SPAN
adjustment volume 'SPAN' of- Model KU-7/G alarm unit.
Make ajustment when the power supply switch is turned on for the first time or when the
inflammable gas detector'is replaced.
ф Let the clean air be sucked from the calibration gas inlet(CALIB. INLET).
© After the digital indication of the alarm unit has been stabilized, adjust the indication of
the digital meter to “0” by turning ZERO adjust volume(ZERO).
Ф Collect calibration gas into gas bag and the like , and let the calibration gas supply onto
detector with chamber by calibration pump , etc.
© After the digital indication of the alarm meter has been stabilized, adjust SPAN volume of
the alarm meter(FA—470) so that the digital meter indicates the same value as the gas
concentration %LEL of calibration gas cylinder.
XLEL = Calibration gas concentration •¥• Lower explosion limit of Calibration gas X 100
- 12 -
11. Method of collecting calibration gas.
In collecting the calibrating gas, connect a gas bag with a three-way cock directly to the
regulator of the gas cylinder.
© Close the stop valve of the regulator' and rotate the pressure regulating screw in the
direction of “CLOSE” , then open the main valve of the cylinder.
The pressure gauge for high-pressure indicates the internal pressure of the cylinder.
© Regulate the pressure of the low-pressure at 0.5 Kg/cm2 by means of the pressure
regulating screw.
© Open the stop valve to‘ discharge a necessary quantity of the gas.
• © Close the main valve of the cylinder and open the stop valve to discharge the residual gas from
, the gas regulator after collecting gas has been completed.
Fig. ll-l Method of collecting calibration gas from calibration gas cylinder
13 -
§
H-2. Gas collecting method from the spray cylinder
© Possible to take out about three bags of gas from one gas cylinder.
© After collecting gas, close the glass cock so that the gas in the gas bag may not escape.
14 -
12. Operation
® One alarm unit measures gas concentration of PUMP ROOM by changeingover sample gas in order.
Gas measurement is carried out by sucking.a sample gas from each of four measuring points
in order through a solenoid valve.
There are two methods, automatic and manual, in changingover measuring points.
Measuring point lamp indicates the point of which measuring is being made at that time.
© Operation is stopped in case of gas concentration alarm , pump failure or alarm unit
failure while AUTO/MANUAL changing over.
(Operation starts again when the alarm or failure is released.)
(1) Automatic changeover operation with the measuring point AUTO/MANUAL switch in “AUTO”
position, measuring points are changed-over automatically every 2 minutes.
(2) Manual changeover operation with the measuring point AUTO/MANUAL switch in “MANUAL”
position, measuring points are changed-over each time when the measuring point selector
switch is pressed, thus selecting the measuring point to be measured continuously.
(Changeover operation should be made under 109SLEL of the preset alarm level after-resetting
alarming.)
When the inflammable gas concentration exceeds the alarm set point (10%LEL),the .ALARM UNIT
will operate as follows.
Press alarm 'reset switch “AL. RESET” on the GAS DETECTING PANEL one time and the alarm
buzzer stops, but the alarm is not released until gas concentration falls below the alarm
setting level.
Input it between 3 and 4 when you do a buzzer stop from the the outside.
The alarm is released by pressing the alarm reset switch “AL. RESET” once again after gas
concentration has fallen below the alarm setting level (10%LEL), then LED lamp(ALl) turns
off.
15 -
12-2-2 Oxygen (Oz)
When the oxygen concentration decreases to the alarm set point (18%) or less, the ALARM
UNIT will operate as follows.
ф The gas concentration low alarm LED(ALl) of the alarm unit flickers in red,and the bar
meter LED for the alarm set point also flickers to give an alarm.
© The alarm buzzer will be sounded.
© Sampling point measures continuously the same place where the alarm is given.
@ The external alarm contacts will be actuated.
NO. 1 samp, point : Between terminal NO. 7 and 8 : closed — * open
. NO. 2 samp, point : Between terminal NO. 9 and 10 : closed — ► open
N0.3 samp, point :'Between terminal N0.11 and 12 : closed — * open
N0.4 samp, point.: Between terminal N0:13 and 14 : closed — » open
Press alarm reset switch “AL. RESET” on the GAS DETECTING PANEL one time arid the alarm
buzzer stops, but the alarm is not released until gas concentration has exceeds the alarm
setting level.
Input it between 3 and 4 when you do a buzzer stop from the outside.
The alarm is released by pressing the alarm reset switch “AL. RESET” once again after gas
concentration has exceeded the alarm setting level (18%), then LED lamp(ALl) turns .off and
the external alarm contacts return.
When the inflammable gas concentration exceeds the alarm set point (30%LEL),the ALARM UNIT
will operate as follows.
Press alarm reset switch “RESET" of the gas alarm meter (FA-470) and the alarm buzzer
stops.
Input it between 3 and 4 when you do a buzzer stop from the outside.
The alarm is released by pressing the alarm reset switch “AL. RESET” once again after gas
concentration has fallen below the alarm setting (30%LEL), then LED lamp (ALARM) turns off
and power supply except in-panel detection.