IN FLA M M A B LE GAS/OXYGEN ALARM SYSTEM

UODa F O M A -T 3 4 W

O P ER A TIO N
MANUAL

Ensure that this instruction manual.is read thoroughly prior'


to use of the equipment
...

KOKYO RIKAGAKU KOGYO K.K.


♦ Forward
ь
' Thank you very much for purchasing our products.
Inflammable gas / oxygen alarm system (F0MA-T34W) is a fixed type one to detect leakage gas,
oxygen lack and give an alarm in combination.
Before use, read this instruction manual and that of detector in order to use each device
correctly and safely.
Ensure that this manual is stored in a convinient location to enable referral at all times.
Do not use this alarm unit for any purpose other than stated above.

♦ Range of warranty

1. The period of warranty for this product is one year from the date of delivery.
2. Defects arising in the equipment caused by faults in manufacturing within the period of
warranty -excluding consumables-will be replaced -parts only- or repaired free of charge.
3. Contact your distributor if defects occur.
4. Invoices will be issued for the actual cost of repairs or replacement parts'within the
period of warranty in the following cases:

* Faults arising from method of usage other than those stipulated in this manual.
* Faults arising from the device having been upgraded or repaired by people other*than*the
manufacturer or distributor.
* Faults arising from natural disasters or accidents not related to the product.
* the replacement of consumable products.

♦ Safety precautions

This manual categorizes procedures in accordance with the following levels of risk involved
in order to prevent unexpected danger to operators and other personel, and damage to assets.
Ensure that these items are observed for safety reasons.

A Warning This indicates that failure to observe the contents of the item or
mistaken use may result in death or serious injury.

ON e v e r dismantle or upgrade this product.


OA vo id e locating in a dangerous place where an explosion may be expected.
This product is not an explosion-protected type. If it is installed at a dangerous place,
there will be a fear of explosion and the like because of its ignition.
OA f t e r installing this product, never fail to carry out gas adjustment, zero adjustment with
fresh air and sensitivity adjustment with calibration gas of known concentration. If zero
adjustment is made without gas adjustment, it is dangerrous due to errorneous detection and
alarm. Moreover, that may cause damage of instrument.
O W h e n confirming abnormal condition of this instrument, put off power source immediately and
stop using to repair it. It is dangerous to keep on using.
O W h e n the gas detecting panel giving gas alarming, deal with leakage of gas immediately.
O l n order to use this instrument in more proper condition, never fail to conduct daily check
and regular check in accordance with-section 13 ’maintenance' of instruction manual.
ДСашдоп This indicates that failure to observe the contents of the item or
mistaken use may result in injury or damage to property.

O F i x detecting part of sumpling inlet of each measuring point at the place where inflammable gas
tends to stay.
O l n case that even if standard gas is supplied to gas detecting part, alarm is not given or
adjustment is impossible to carry out, it may be a trouble of sensor.
Replace the sensor in accordance with instruction manual of alarm meter or analizer. When
the same phenomena remains after replacement, it is a trouble of alarm unit. Repairing'
should be required. If operation is being kept without repairing, serious accident may be
possibly caused and dangerous.-
O T h e sensor consists of a detection element and a comparison element.
When replacing sensor, never fail to replace it in pairs.
Oft'hen alarm unit and gas detector are installed, refer to this instruction manual and that
of each detector. If wiring is made wrong, alarm unit or detector operates wrong or is
broken occasionally.
O l n case of suction type detector, if specifications of tube; length, inner diameter, etc.
are not correct, readings may be wrong occasionally. „

♦Meanings of terminology

Special terms used in this instruction manual are as follows.

1) Explosion-protected construction
Construction applied to electrical apparatus to prevent ignition of the surrounding
explosive atmosphere by such apparatus.

2) Hazardous areas
Terms representing group of area concerning explosion-protection; an area where hazardous
atmosphere exists or there is a fear of its existing.

3) Concentration of lower explosive limit (%LEL)


Minimum concentration capable of exploding by ignition due to mixture of infllamable gas
and air.

4) Detection principle
Principle of detecting existence of gas,- and converting it to electric signal.

5) Sampling system
System which sucks air to be measured automatically from sampling points and leads to
gas analyzer.

6) Fresh air
The environmental air not including inflammable gas to be measured (in case of this
.instrument, used for zero adjustment gas).

7) Sensitivity adjustment " .


Adjusting indication of alarm unit with calibration gas (span gas) of known concentration.

8) Zero adjustment
Adjusting indication of alarm unit to zero with fresh air.

.5Й Indicator alarm unit, gas alarm meter or gas analyzer, refer to separate volume instruction
manual j’.
CONTENTS

I T E M ' PAGE

1 . General ...............c ............ ......................................... 1


2. Specifications • • ........ ................ ............. ......................... 1
2-1 General specification
2-2 Alarm unit specification (PUMP ROOM - H. C)
2-3 Alarm unit specification •(PUMP ROOM -Ог)
2-4 Alarm meter specification (IN PANEL)
3. Detection principle • ............... ............................... .. * ........ 4
3-1 Catalytic combustion
3- 2 Galvanic cell method
4. Designation ........................................................................ 6
4- 1 Gas alarm panel
4-2 Gas alarm panel inside
5. Installation .................................................... .......... .. . . ■ g
5-1 Installation place
5-2 Installing alarm panel

со 00 00
6 . Piping ...... . • -
7. Wiring ..........
8 . Gas flow system ■ • * <
9. Power supply ......... ................................... ................ .. 10
1 0. Adjustment - _ • • • • ■ ................... .............. ........................... 1 1
10-1 Adjustment of inflammable gas detector
10-2 Adjustment of Oxygen detector
10-3 Adjustment of inflammable gas detector in panel
1 1 . Method of collecting calibration gas ■ ............................................. 1 3
11-1 Method of collecting calibration gas from calibration gas cylinder.
11- 2 Gas collecting method from the spray cylinder
1 2. Operation ............................... . ............ ' ................. 15
12- 1 Changingover measuring points
12-2 High alarm operation
12-2-1 Inflammable gas (H. C)
12-2-2 Oxygen (Ог)
12-2-3 inflammable gas detection in panel
12-3 Trouble alarm operation of unit
12-3-1 Inflammable gas (H. C)
12- 3-2 Oxygen (Ог)
12-4 Pump failure operation
12-5 Power supply failure
12- 6 Error code table of alarm unit
1 3. Maintenance ........ ..................................... ....................... 2 0
13- 1 Gas alarm panel
13-2 Replacing a paper filter for air filter
13-3 Maintenance of suction pump
13-4 Replacement of sensor
13— 4— 1 Inflammable gas (H. C)
13-4-2 Oxygen (Ог)
1 4. Cautions for use ................................................................. 2 2
1. General

This system detects the inflammable gas in the air by applying the principle of catalytic
combustion method, and transmits an alarm when the gas concentration reaches a preset alarm level
(PUMP ROOM— »10%LEL. IN PANEL— 30%LEL) or above, and detects the oxygen in the air by applying the
principle of galvanic cell method, and transmits an alarm when the oxygen concentration reaches a
preset alarm level (PUMP ROOM— 18%) or less.
The GAS ALARM PANEL is set up in the CARGO CONTROL ROOM and where piping is arranged to where
gas is collected.
The sample gas is sucked by a pump in the equipment through the piping, and measured.
The equipment uses two-way solenoid valves to measure 4 points (PUMP ROOM) by switching each
point successively.
One(l) point in panel is monitored by gas detector continuously.

2. SPECIFICATIONS

'2-1 Genera] specification

(1) Model . : F0MA-T34W


(2) Detection gas ' : Inflammable gas and oxygen
(i-BUTANE, PROPANE, HEXANE, HEPTANE)
(3) Principle of detection : H.C — Catalytic combustion method
Ог — Galvanic cell method
(4) Detecting points : PUMP ROOM — 4 points
IN PANEL — 1 point
(5) Detecting method : Selective suction type
(6) Measuring range : H.C I O'— 100%LEL (lower explosion limit) .
i-BUTANE scale
0Z ; 0~ 25 %
(7) Measuring accuracy : H.C : Within ± 5 % of full scale
Ог ; Within ±0. 7% of oxygen density
(8) Gas concentration alarm set point : H.C I PUMP ROOM — 10%LEL (Adjustable)
IN PANEL — 30%LEL (Adjustable)
Ог I PUMP ROOM — 18% (Adjustable)
(9) Gas concentration alarm accuracy : Within ± 2 5 % of alarm set point
(10) Measuring points switching-over : Automatic and manual
(11) Automatic scanning period '■ Within 30min. per cycle
(12) Response time : Within 30sec. (from gas alarm panel inlet)
(13) Gas concentration alarm : Lamp, buzzer
(14) Failure alarm : Lamp, buzzer
(15) External alarm output Alarm contact ■ lb (each 4 points)
Failure contact lb (total)
(16) External output : DC4~20mA (To digtal scaling meter)
(17) Operating temperature and humidity : 0“C ~ 4 5 <t, less than 90%RH
(18) Temperature, humidity and pressure : 0CC ~ 4 5 1C, less than 90%RH, atmospheric pressure
range of sampling gas
(19) Power supply AC110V ± 10V, 60Hz ± 5 % , U
(20) Power consumption : Approx. 100VA
(21) Painting color : Munsell 7.5BG7/2 semi gloss
(22) Tubing : Inside of PANEL ; polyurethane pipe
Outside of PANEL ; copper pipe (0Di*> 6 :GAS INLET)
(0D<M5:GAS OUTLET)
'(22) Ship classification Rules ; ABS

1
2-2 Д 1 а т unit specification (PUMP-ROOM — H. C)

(1) Name : Alarm unit


(2) Model : KU-7/F(RL)
(3) Indicator : 0~100%LEL. LED bar meter and digital meter
(4) Number of alarms installed : 1 point or 2 points setting
(5) Alarm setting : AL1— *■10%LEL, AL2— * Not use
(Both AL1 and AL2 can be set at 5~100%LEL)
• (6) POWER/FAULT LED : Normal time LED(Pff) Green
Fault time ••• LED(PW) Red flickers
(7) Gas alarm LED : Normal time ••• LED(ALl, AL2) Unlit
Alarm time ••• LED(AL1, AL2) Red flickers
(8) External alarm contact : Normal time ••• Open(ALl, AL2)
Fault time Closed(ALl, AL2)
(9) External fault contact : Normal time ••• Open
Fault time ••• Closed
(10) Contact capacity : AC100V, 0.5A; DC30V, IA (resistance load)
(11) Gas concentration output : DC4~20mA
(allowable load resistance must be less than 430Й
including connected cable resistance)_ •
(12) Power supply voltage : Unit power supply DC24V
(13) Allowable voltage variation : .± 10%
(14) External dimensions : W36 X H144 X D176 mm
(15) Painted color : Meter frame Deep blue(maker’s standard)

2-3 Alarm unit specification (PUMP ROOM — Ог)

(1) Name : Alarm unit


(2) Model : KU-7/G(RL)
(3) Indicator : 0~25%, LED bar meter and digital meter
(4) Number of alarms installed : 1 point or 2 points setting
(5) Alarm setting : AL1— *18%, AL2— * Not use
(Both AL1 and AL2 can be set at 3~25%)
• (6)' POIVER/FAULT LED : Normal time ••• LED(PW) Green'
Fault time ••• LED(Pff) Red flickers
(7) Gas alarm LED : Normal time LED(AL1, AL2) Unlit
Alarm time ••• LED(AL1, AL2) Red flickers
(8) External alarm contact : Normal time •••0pen(ALl, AL2)
Fault time •••Closed(ALl, AL2)
(9) External fault contact Normal time •••Open
Fault time Closed
(10) ' Contact capacity : AC1Q0V, 0,5A: DC30V, 1A (resistance load)
(11) Gas concentration output : DC4— 20mA
(allowable load resistance must be less than 430П
including connected cable resistance)
(12) Power supply voltage : Unit power supply DC24V
(13) Allowable voltage variation : ± 10%
(14) External dimensions K36 X H144 X D176 mm
(15) Painted color : Meter frame ••• Deep blue (maker’s standard)

- 2 -
2-4 Alarm meter specification (IN PANEL)

(1) Name Alarm meter


(2) Model FA-470F
(3) Detection gas Gas contained in the air
(4) Principle of detection Catalytic combustion method
(5) Detecting Points 1 point / 1 set
(6) Measuring system Diffusion
(7) Detectable range 0~100%LEL (lower explosion limit)
(8) Indicating accuracy Within ± 5 % of full scale
(9) Gas concentration alarm Lamp, buzzer and external alarm output
(10) Gas concentration alarm set point 3056LEL (for cutting off power supply of the
GAS DETECTING PANEL)
(11) Failure alarm : Lamp, buzzer
(12) External alarm output : Gas concentration alarm (30%LEL)
lab (dry, max. 0. ЗА, at resistance load)
(13) Gas concentration signal : DC 4~-20mA (linear)
Load resistance ••• Max. 250Q
(include cable resistance)
(14) Operating temperature : GAS ALARM METER ; 0' C~45!C
DETECTOR ; O'C— dS'C
(15) Operating humidity and pressure :'90%RH, atmospheric pressure
(16) Power supply : AC110V ± 10V, 60Hz ± 5 % , 1 4>
(17) Power consumption ■- Diffusion type ; Approx. 20 VA
(18) Drip-proof construction : IP22
(19) Explosion-protected Flame proof type of explosion-protected
construction of GAS DETECTOR construction d2G4
s 3. Detection principle
3-1 Catalytic combustion method

If the air containing an inflammable gas comes into contact with a catalyzer- heated appreciably,
the molecules of the inflammable gas react on oxygen in the air(catalytic combustion reaction),
producing reaction heat (catalytic combustion heat).
The produced heat is proportional to the concentration.of the gas providing that the
concentration of the inflammable gas is low enough for a perfect combustion.
Accordingly, a Wheatstone bridge is formed by using two filaments whose electric resistance is
the same as shown in Fig. 3-1 . ' ’
One filament is exposed to the gas to be measured (detection side Fl), and the other is sealed in
clean air (comparison side F2).
The bridge is preheated up by electric current to a particular temperature at which the gas will
produce a catalytic combustion.
If the inflammable gas touches the detection side filament, the temperature of Fl will go up by
the combustion heat, increasing its electric resistance, producing an electric current between A
and В on the bridge, by which gas concentration can be detected.

Fig. 3-1 Basic circuit diagram, for catalytic combustion method

3-2 Galvanic cell method

The diaphragm galvanic cell is a system in which heterogeneous electric conductors (at least one
of them must be an electrolyte or ionic conductor like an electrolytic solution) are connected in
series and the chemical compositions of the end phase are the same.
The construction model of the oxygen sensor applying the diaphragm galvanic cell is shown in
Fig. 3-2.

Ог -

Ml М2
~o Ml : Gold (Cathode)
М2 : Lead (Anode)
S : Electrolytic solution

Fig. 3-2 Construction model of oxygen sensor


The reaction principle of the oxygen sensor is as follows referring to Fig. 3-2 above.
Connect electrodes Ml and М2 with a conductor, supplying oxygen to the surface of Ml, and the
following reduction reaction (l) takes place on Ml side.

( 1)
O 2 + 4 H ‘ + 4 e" ^ 2 Н г О (Acid electrolyte)
Os'+ 2 H 2O + 4 e ' — ♦ 4 O H (Alkaline electrolyte)

Simultaneously an oxidation reaction (2) takes place on М2.

2Pb + 2 H 2O — 2 P bО + 4 H + + 4 e ' (Acid, electrolyte) (2)


2 P b + 2OH" —* 2 P b О + 2 H 2O + 4 e " . (Alkaline electrolyte)

In electrochemistry, the electrode from which positive charges move toward a solution is called
an anode (positive electrode), while that where positive charges move from the solution to the
electrode phase is called a cathode (negative electrode).

. From this reason, with the oxygen sensor, the gold electrode side is called a cathode (negative
electrode), and the lead electrode side is called an anode (positive electrode).
For a gas penetrating membrane, that of fluororesin or the like is used through which"oxygen gas
easily passes.
Between the membrane"and the cathode is formed a thin electrolytic layer, the oxygen gas having
passed through the membrane is dissolved in the electrolytic layer.
The dissolved oxygen produces a reduction reaction on the cathode and concurrently an oxidation
reaction on the anode, thus a reduction current flows in proportion to the oxygen concentration.
An oxygen concentration is readable from the terminal potential on the load resistance connected
between the anode and cathode external to the sensor.
This electric potential is called the output of the oxygen sensor.
Since the electric potential is proportional to the concentration of oxygen, the concentration of
oxygen can be determined by measuring the electric potential at that time.
The above is a reaction principle of the oxygen sensor.

•Age-based characteristics of oxygen sensor ,

The products on the lead electrode are dissolved into the electrolytic solution by the following
reaction..

PbO + 2 Н С Ю , - P.b (C l O d г + НгО ( 3)

ЙЪеп Pb(CIO* ) 2 has been saturated, it is precipitated oh the surface of the lead electrode.
If the whole surface is covered with it, no more electrode reaction would proceed,when the life
of the’electrode would be over.
By surveying age-based characteristics of oxygen sensors in the past, we can guarantee the life
of the oxygen sensor for about one year.

- 5 -
4. Designation

4-1 Gas alarm panel

1~4. Samp, point lamps (green) П. Manual changeover switch


5. Samp, pump failure lamp (orange) 12. Alarm reset switch
6. Alarm unit (PUMP RM - H.C) (KU-7/F) 13. Buzzer
7. Alarm unit (PUMP RM - 02) (KU-7/G) 14.' Flow meter window
8. Alarm meter (IN PANEL) (FA-470) 15: Name plate for panel
9. MEAS.-CALIB. select switch G I 1 ~ 4 Gas inlet
10. Auto-Manual select switch OUT Gas outlet

Fig. 4-1 Gas alarm panel outside view

- 6 -
s 4-2 Gas alarm panel inside

SE Sequencer SV 2-way solenoid valve


' S/F Switch/Fuse VTB Switching regulator
PS Pressure switch RY RELAY
SB Sensor hoard ТВ Terminal board
02 Oxygen sensor RD Detector (IN PANEL)
p j}RD(S) Detector (PUMP RM) ' SP Sampling pump'

Fig. 4-2 Gas alarm panel inside

5. Installation - .

5-1 Installation place

The installation place should be free from mechanical vibrations, corrosive gases, and dust;
with little variation in temperature,humidity, close to the normal temperature and himidity.

5-2 Installing alarm panel

ffal1-mounted
The panel should be fixed at four places.

- 7 -
6. Piping

A copper tube. 6mni in 0. D., is used from gas collector to the alarm panel.
Clean each tube by blowing dry air through it to remove metal chips, dust and other foreign
matter before joining it to the alarm panel: otherwise gas may not be sucked in or may be retarded
in sucking. Further, be sure that each system has been joined properly when cleaning the piping. .
Arrange the piping with a minimum bends and without sharp corners to avoid retardation in sucking.
For the exhaust piping, use a copper tube, 15mm in 0. D., arranging it to a safe place where there
is no possibility to catch fire.

IN P-A N E L

Fig. 6 How to joint a tube

,7. Wiring '

® Connect power source (AC110V) to the gas detecting panel.

SH-H!
PI HI

Fig. 7 External terminal diagram

- 8 -
8. Gas flow system

SIIlkC

Ф ST 1~ 4 Stop valve © NVB Needle valve (By-pass)


© Gl l~ 4 Gas inlet (with flame screen) © Ог Oxygen sensor
® SVI~4 2-way solenoid valve ® FM Flow meter
© SVC 2-way solenoid valve © GD-PE Accumlator
© OUT Gas outlet (with flame screen) © RD(S) Detector
© VP Sampling pump © RD Detector
® PS Pressure switch ® NVT Needle valve (MEAS.)

Fig. 8 Gas flow system

® Stop valve (STI~4)


Closes to shut off gas suction upon detecting when the gas leaks pump room.

© Gas inlet (Gll~4)


With flame screen.

(3) 2-way solenoid valve for switching (SV1~4)


The solenoid valve opens just one flow circuit through current conduction while it is being
measured or purged.

®. 2-way solenoid valve for switching from measurement to calibration gas (SVC)
Turn the 'MEAS. -CALIB.' select switch to "CALIB. ' to suck in the calibration gas.

© Gas outlet (OUT)


(with flame screen)

© Sampling pump (VP)


Sucks the sampling gas
* © Pressure switch (PS)
Detects failure in the sampling pump.

® Needle valve (NVB)


Adjusts flow rate into the by-pass.

(§) Oxygen sensor (Oz)


Measures the oxygen'concentration into the PUMP ROOM.

® Flow meter (FM)


Indicates the flow rate into the detector.

© Gas collector(GD-PE)
Excepts dust in the sample gas.

© Detector (RD(S))
Detects the inflammable gas leaking into the PUMP ROOM.

© D e t e c t o r (RD)
Monitors inflammable gas leakage in the GAS DETECTION PANEL.

® Needle valve (NVT)


Adjusts flow rate into the flow meter.

9. Power supply

Ensure wiring and piping are correct before closing the main switch, furthen sach switch is under
the following condition(factory setting)

Ф Power supply switch (Panel inside) MSW .... OFF


© Power supply switch of the alarm unit USW .... OFF
© Power supply switch of the alarm meter (FA-470) OFF
® Pump switch ’ PSW --- OFF
© 11EAS. /CALIВ switch MSS .... MEAS.
© Auto/Manual switch AMS ___ AUTO

(1) Turn the power supply switch (MSW) to ON position.


— * Sampling point lamp No. 1 (green) lights up.
(This lamp lights up in order of NO. 1 7* NO. 2 NO. 3 — * NO. 4 — ► NO. 1 ••• every two minutes.)

(2) Turn the pump switch (PSW) to ON position.


— » Sucks the sampling gas into the detector.
Adjust the indication of flow meter at, 1.5 Й /min. with needle valve (NVB) on the flow meter.
Open the. needle valve (NVT).

(3) Turn the power supply switch of the alarm meter (FA-470) to ON position.
— * The pilot of the alarm meter lights up and digital meter indicates around *0".

(4) Turn the power supply switch (USW) of the"alarm unit to ON position.
— * POWER LEDs 'PW' (green) and 'MAINT' (orange) of the inflammable gas alarm unit(KU-7/F) light -
up and digital meter indicates around “0” .
POWER LEDs 'PW' (green) and 'MAINT' (orange) of the oxygen alarm unit(KU-7/G) light up and
digital meter indicates around “20. 9” .

(5) Press the maintenance switches of both inflammable gas alarm meter and oxygen alarm meter, to
release maintenance mode, provided that indication is stabilized.

(6) Each sampling point is successively switchedover every two minutes at auto mode.

10 -
fo. Adjustment

(1) Set the inflammable gas alarm unit and oxygen alarm unit in maintenance mode by pressing MAINT
switch. (Maintenance mode : When "MAINT'(orange) lights up.)

(2) Turn MEAS./CALIB. switch on the front panel to 'CALIB, ' position.

(3) Refer to operation manuals of alarm unit, alarm meter for further details.

10-1 Adjustment of inflammable gas detector

Make adjustment when the power supply switch is turned on for the first time or when the
inflammable gas detector is replaced.
t
(1) Zero adjustment

Ф Let the clean air be sucked from the calibration gas inlet(CALIB. INLET).
© After the digital indication of the alarm unit (KU-7/F) has been stabilized, adjust the
indication of the digital meter to “0” by turning ZERO adjustment volume (ZERO)-.

(2) Span adjustment

(D Collect calibration gas into gas bag and the like, and let the calibration gas be sucked from
calibration gas inlet(CALIB. INLET).
® After the digital indication of the alarm unit has been stabilized, adjust SPAN volume of the
alarm unit(KU-7/F) so that the digital meter indicates the same value as the gas concentration
%LEL of calibration gas cylinder, provided that gas concentration is converted by the
under-mentioned formula.

The gas concentration of the inflammable gas cylinder is expressed in vol%.


Convert the gas concentration into %LEL unit in the following manner.

%LEL = Calibration gas concentration Lower explosion limit of Calibration gas X 100 .

Calibration gas concentration % volX___________________ -


Lower explosion limit of isobutane gas(i.8vol%)

( X / 1.8) .X 100 = XLEL

10-2 Adjustment of oxygen detector

Make ajustment’when the power supply switch is turned on for the first time or when the
oxygen sensor is replaced.

(1) Zero adjustment

ф Let the nitrogen gas(100vol%) be sucked from the calibration gas inlet(CALIB. INLET).
© Connect the voltmeter between the sensor board’s TP1 (-) and TP2(+) current check terminals,
and rotate the volume (VRl) on the sensor board, then the voltage between the terminals is
adjusted to DC0. 2V, and the output current will be calibrated to DC4mA.
® When making adjustment of above item © , adjust meter indicator to ' 0' by turning ZERO
adjustment volume "ZERO' of Model KU-7/G alarm unit.

11 -
*(2) Span adjustment

Ф Let the clean air be sucked from the calibration gas inlet.
© Connect the voltmeter between the sensor board's TP1 (-) and TP2(+) current check terminals,
and rotate the volume (VR2) on the sensor board, then the voltage between the terminals is
adjusted to DCO. 87V, and the output current willbe calibrated to DC17.4mA.
© When making adjustment of above item © , adjust meter indicator to '20.9* by turning SPAN
adjustment volume 'SPAN' of- Model KU-7/G alarm unit.

Fig. 10 Output adjustment of the oxygen sensor’s board

10-3 Adjustment of inflammable gas detector in panel

Make ajustment when the power supply switch is turned on for the first time or when the
inflammable gas detector'is replaced.

(1) Zero adjustment

ф Let the clean air be sucked from the calibration gas inlet(CALIB. INLET).
© After the digital indication of the alarm unit has been stabilized, adjust the indication of
the digital meter to “0” by turning ZERO adjust volume(ZERO).

(2) Span adjustment

Ф Collect calibration gas into gas bag and the like , and let the calibration gas supply onto
detector with chamber by calibration pump , etc.
© After the digital indication of the alarm meter has been stabilized, adjust SPAN volume of
the alarm meter(FA—470) so that the digital meter indicates the same value as the gas
concentration %LEL of calibration gas cylinder.

The gas concentration of the inflammable gas cylinder is expressed in vol%.


Convert the gas concentration into XLEL unit in the following manner.

XLEL = Calibration gas concentration •¥• Lower explosion limit of Calibration gas X 100

Calibration gas concentration x v o l X _______________


Lower explosion limit of isobutane gas 1.8volX

(x /1.8) X 100 * MLEL

- 12 -
11. Method of collecting calibration gas.

In collecting the calibrating gas, connect a gas bag with a three-way cock directly to the
regulator of the gas cylinder.

11-1. Method of collecting calibration gas from calibration gas cylinder.

Ф Attach a gas regulator to the cylinder.


Confirm that the cylinder packing is complete and the gas regulator is attached firmly or
the gas leakage is not found.

© Close the stop valve of the regulator' and rotate the pressure regulating screw in the
direction of “CLOSE” , then open the main valve of the cylinder.
The pressure gauge for high-pressure indicates the internal pressure of the cylinder.

© Regulate the pressure of the low-pressure at 0.5 Kg/cm2 by means of the pressure
regulating screw.

® Connect the polyurethane tube with the hose joint.

© Open the stop valve to‘ discharge a necessary quantity of the gas.

• © Close the main valve of the cylinder and open the stop valve to discharge the residual gas from
, the gas regulator after collecting gas has been completed.

© Close the pressure regulating screw.

Fig. ll-l Method of collecting calibration gas from calibration gas cylinder

13 -
§
H-2. Gas collecting method from the spray cylinder

ф Expel air in the gas bag before using.

© Possible to take out about three bags of gas from one gas cylinder.

© After collecting gas, close the glass cock so that the gas in the gas bag may not escape.

® Use a proper length of rubber and plastic tubes.

Fig. 11-2 Gas collecting method from.the spray cylinder

14 -
12. Operation

12-1 Changingover measuring points

® One alarm unit measures gas concentration of PUMP ROOM by changeingover sample gas in order.
Gas measurement is carried out by sucking.a sample gas from each of four measuring points
in order through a solenoid valve.
There are two methods, automatic and manual, in changingover measuring points.
Measuring point lamp indicates the point of which measuring is being made at that time.
© Operation is stopped in case of gas concentration alarm , pump failure or alarm unit
failure while AUTO/MANUAL changing over.
(Operation starts again when the alarm or failure is released.)

(1) Automatic changeover operation with the measuring point AUTO/MANUAL switch in “AUTO”
position, measuring points are changed-over automatically every 2 minutes.

(2) Manual changeover operation with the measuring point AUTO/MANUAL switch in “MANUAL”
position, measuring points are changed-over each time when the measuring point selector
switch is pressed, thus selecting the measuring point to be measured continuously.
(Changeover operation should be made under 109SLEL of the preset alarm level after-resetting
alarming.)

12-2 HIGH alarm operation


12-2-1 Inflammable gas (H. C)

When the inflammable gas concentration exceeds the alarm set point (10%LEL),the .ALARM UNIT
will operate as follows.

(1) When alarm is given :


® The gas concentration high alarm LED(ALl) of the alarm unit flickers in red,and the bar
meter LED for the alarm set point also flickers to give an alarm. •
© The alarm buzzer will be sounded.
© Sampling point measures continuously the same place where the alarm is given.
® The external alarm contacts will be actuated;
NO. I samp, point :Between terminal NO. 7 and 8 : closed — ► open
N0.2 samp, point :Between terminal N0. 9 and 10 : closed — * open
N0.3 samp, point :Between terminal N0.11 and 12 : closed — ► open
NO. 4 sBmp. point :Between terminal NO. 13 and 14 : closed — ► open

(2) When the buzzer is stopped :

Press alarm 'reset switch “AL. RESET” on the GAS DETECTING PANEL one time and the alarm
buzzer stops, but the alarm is not released until gas concentration falls below the alarm
setting level.
Input it between 3 and 4 when you do a buzzer stop from the the outside.

(3) When the alarm is reset :

The alarm is released by pressing the alarm reset switch “AL. RESET” once again after gas
concentration has fallen below the alarm setting level (10%LEL), then LED lamp(ALl) turns
off.

15 -
12-2-2 Oxygen (Oz)

When the oxygen concentration decreases to the alarm set point (18%) or less, the ALARM
UNIT will operate as follows.

(1) When alarm is given :

ф The gas concentration low alarm LED(ALl) of the alarm unit flickers in red,and the bar
meter LED for the alarm set point also flickers to give an alarm.
© The alarm buzzer will be sounded.
© Sampling point measures continuously the same place where the alarm is given.
@ The external alarm contacts will be actuated.
NO. 1 samp, point : Between terminal NO. 7 and 8 : closed — * open
. NO. 2 samp, point : Between terminal NO. 9 and 10 : closed — ► open
N0.3 samp, point :'Between terminal N0.11 and 12 : closed — * open
N0.4 samp, point.: Between terminal N0:13 and 14 : closed — » open

(2) When the buzzer is stopped :

Press alarm reset switch “AL. RESET” on the GAS DETECTING PANEL one time arid the alarm
buzzer stops, but the alarm is not released until gas concentration has exceeds the alarm
setting level.
Input it between 3 and 4 when you do a buzzer stop from the outside.

(3) When the alarm is reset :

The alarm is released by pressing the alarm reset switch “AL. RESET” once again after gas
concentration has exceeded the alarm setting level (18%), then LED lamp(ALl) turns .off and
the external alarm contacts return.

12-2-3 Inflammable gas detection in panel

When the inflammable gas concentration exceeds the alarm set point (30%LEL),the ALARM UNIT
will operate as follows.

(1) When alarm is given : -


ф The gas concentration high alarm LED of the alarm meter flickers in red.
© The alarm buzzer will be sounded.
© The external alarm contacts will be actuated and all of power supply except in-panel
detection.

(2) When the buzzer is stopped :

Press alarm reset switch “RESET" of the gas alarm meter (FA-470) and the alarm buzzer
stops.
Input it between 3 and 4 when you do a buzzer stop from the outside.

(3) When the alarm is reset :

The alarm is released by pressing the alarm reset switch “AL. RESET” once again after gas
concentration has fallen below the alarm setting (30%LEL), then LED lamp (ALARM) turns off
and power supply except in-panel detection.

17 -