Reyrolle 7SR10 Platform: Protecting Grid With Confidence
Reyrolle 7SR10 Platform: Protecting Grid With Confidence
Description
The Reyrolle 7SR10 Argus is an overcurrent and earth fault relay
intended as a simple protection solution for distribution and
industrial applications. It consists of non-directional functions
and additional voltage inputs providing directional functions.
The conformal coating on device electronic modules increases
protection against harmful environmental influences such as
2.2 extreme moisture, corrosive gases and aggressive dust.
Protocols IEC 60870-5-103, DNP3.0 or Modbus RTU Figure 2.2/1 7SR10 Device
Housing Size 4, 4U high – non draw-out case
• 50 Instantaneous overcurrent – phase
Benefits
• 50AFD Arc fault detection
• Circuit-breaker open and close fascia push button • 50G Instantaneous earth fault – measured
• Protection settings can be viewed and edited from the fascia • 50GLC Line check earth fault – measured
• 9 user programmable tri-color LEDs • 50LC Line check
• Cold load protection • 50N Instantaneous earth fault – calculated
• 2 setting groups • 50SEF Instantaneous sensitive earth fault – measured
• Password protection– 2 levels1 • 50SEFLC Line check sensitive earth fault – measured
• User programmable logic aided by 8 virtual inputs/outputs • 51 Time delayed overcurrent – phase
• Self monitoring • 51c Cold load overcurrent – phase
• Circuit-breaker trip and maintenance counter • 51G Time delayed earth fault – measured
• The last 15 fault records are displayed on the relay fascia • 51N Time delayed earth fault – calculated
• Waveform recorder stores 15 records (1 second duration) • 51SEF Time delayed sensitive earth fault – measured
• 20 character x 4 line backlit LCD • 51V Voltage dependent overcurrent – phase
• Up to 1 000 event records with 1 ms resolution • 55 Power factor
Functions
• 59 Overvoltage protection – phase
Protection Functions
• 59N Neutral voltage displacement
• 64H Restricted earth fault protection – high-impedance
• 27 Undervoltage protection – phase
• 67 Directional overcurrent – phase
• 32 Power protection
• 67G Directional earth fault – measured
• 32S Sensitive power protection
• 67N Directional earth fault – calculated
• 37 Undercurrent protection – phase
• 67SEF Directional sensitive earth fault – measured
• 37G Undercurrent earth fault protection – measured
• 67SEF Directional sensitive earth fault – measured 3V0/I0-ϕ
• 37SEF Undercurrent sensitive earth fault protection – meas-
ured • 81 Frequency protection – "f>" or "f<"
• 46NPS Negative sequence overcurrent protection Supervision Functions
• 47NPS Negative sequence overvoltage protection • 46BC Broken conductor protection
• 49 Thermal overload protection • 50BF Circuit-breaker failure protection – 3-pole
Applications
• Feeder overcurrent protection
• Backup protection
• Compact substation
• Protection against harmonic injection into grid by non
conventional sources of energy
• Focused on renewable energy sources
• Industry medium voltage and low voltage applications
Application
The 7SR10 overcurrent relay is a numerical overcurrent protec-
tion relay intended for use in the distribution and industrial
networks. It provides a highly comprehensive functional soft-
[lo_7SR10 directional functional diagram, 4, en_US]
ware package with a range of integral application functions
aimed at reducing installation, wiring, and engineering time. Figure 2.2/3 7SR10 Directional Overcurrent Relay
The 7SR10 consists of overcurrent and earth fault protection
functions with additional voltage inputs providing directional,
voltage, frequency, and power protection functions.
A wide range of measured values can be viewed on the front
LCD or remotely via the communication channel.
The integrated control feature allows the operation of a single
circuit-breaker and the monitoring of it's trip and closed circuits.
Function Matrix
ANSI Functions
7SR1002/3-1***0-2DAO
7SR1002/3-2***0-2DAO
7SR1002/3-1***0-2CAO
7SR1002/3-2***0-2CAO
7SR1004-3**20-2DAO
7SR1004-4**20-2DAO
7SR1004-3**20-2CAO
7SR1004-4**20-2CAO
7SR1004-5**20-2CAO
2.2
PROTECTION
27 Undervoltage protection – phase ■ ■ ■ ■ ■
32 Power protection ■ ■ ■ ■ ■
32S Sensitive power protection ■ ■ ■
37 Undercurrent protection – phase ■ ■ ■ ■ ■ ■ ■ ■ ■
37G Undercurrent earth fault protection – measured ■ ■ ■ ■
37SEF Undercurrent sensitive earth fault protection – measured ■ ■ ■ ■ ■
46NPS Negative sequence overcurrent protection ■ ■ ■ ■ ■ ■ ■ ■ ■
47NPS Negative sequence overvoltage protection ■ ■ ■ ■ ■
49 Thermal overload protection ■ ■ ■ ■ ■ ■ ■ ■ ■
50 Instantaneous overcurrent – phase ■ ■ ■ ■ ■ ■ ■ ■ ■
50AFD Arc flash detection ■ ■ ■ ■ ■ ■ ■ ■ ■
50G Instantaneous earth fault – measured ■ ■ ■ ■
50GLC Line check earth fault – measured ■ ■
50LC Line check ■ ■ ■ ■ ■
50N Instantaneous earth fault – calculated ■ ■ ■ ■ ■ ■ ■ ■ ■
50SEF Instantaneous sensitive earth fault – measured ■ ■ ■ ■ ■
50SEFLC Line check sensitive earth fault – measured ■ ■ ■
51 Time delayed overcurrent – phase ■ ■ ■ ■ ■ ■ ■ ■ ■
51c Cold load overcurrent – phase ■ ■ ■ ■ ■ ■ ■ ■ ■
51G Time delayed earth fault – measured ■ ■ ■ ■
51N Time delayed earth fault – calculated ■ ■ ■ ■ ■ ■ ■ ■ ■
51SEF Time delayed sensitive earth fault – measured ■ ■ ■ ■ ■
51V Voltage dependent overcurrent – phase ■ ■ ■ ■ ■
55 Power factor ■ ■ ■ ■ ■
59 Overvoltage protection – phase ■ ■ ■ ■ ■
59N Neutral voltage displacement ■ ■ ■ ■ ■
64H Restricted earth fault protection – high-impedance ■ ■ ■ ■ ■ ■ ■ ■ ■
67 Directional overcurrent – phase ■ ■ ■ ■ ■
67G Directional earth fault – measured ■ ■
67N Directional earth fault – calculated ■ ■ ■ ■ ■
67SEF Directional sensitive earth fault – measured ■ ■ ■
67SEF Directional sensitive earth fault – measured 3V0/I0-ϕ ■
81 Frequency protection – "f>" or "f<" ■ ■ ■ ■ ■
SUPERVISION
46BC Broken conductor protection ■ ■ ■ ■ ■ ■ ■ ■ ■
50BF Circuit-breaker failure protection – 3-pole ■ ■ ■ ■ ■ ■ ■ ■ ■
60CTS CT supervision ■ ■ ■ ■ ■ ■ ■ ■ ■
60VTS VT supervision ■ ■ ■ ■ ■
74CCS Close-circuit supervision ■ ■ ■ ■ ■ ■ ■ ■ ■
74TCS Trip-circuit supervision ■ ■ ■ ■ ■ ■ ■ ■ ■
81I_THD Total harmonic distortion supervision ■ ■ ■ ■ ■ ■ ■ ■
81HBL2 Inrush current detection 2 ■ ■ ■ ■ ■ ■ ■ ■ ■
CONTROL
ANSI Functions
7SR1002/3-1***0-2DAO
7SR1002/3-2***0-2DAO
7SR1002/3-1***0-2CAO
7SR1002/3-2***0-2CAO
7SR1004-3**20-2DAO
7SR1004-4**20-2DAO
7SR1004-3**20-2CAO
7SR1004-4**20-2CAO
7SR1004-5**20-2CAO
2.2
52 CB Control ■ ■ ■ ■ ■ ■ ■ ■ ■
79 Automatic reclosing ■ ■ ■ ■
86 Lockout ■ ■ ■ ■ ■ ■ ■ ■ ■
User programmable logic ■ ■ ■ ■ ■ ■ ■ ■ ■