The VMC Inspection Team completed a remote inspection of for VMA-49842-01C and VMA-49842-03C
on January 20, 2021 and VMA-48842-02C and VMA-49842-04C on February 5, 2021. Your Certificates
of Compliance have been consolidated and renewed. Enclosed, please find a copy of the comprehensive
report. The certificates will also be posted to our listing site. Please be sure to link to
www.IBCApproval.com for greater visibility of your certifications.
Sincerely,
Cheryl Matthews
Engineering Administrator
Enclosure
Quality Assurance - IBC Special Seismic Certification Inspection Report
PURPOSE
To maintain business continuity while under travel restrictions imposed during the 2020 Covid19
pandemic, the recertification of AKSA Special Seismic Certifications, the VMA-49842-01C through VMA-
49842-04C was conducted remotely via Microsoft Teams. The purpose of the inspection was to ensure
the inspected product(s) complied with the certification issued by VMC Group as per Section 1703.5.2 of
2006 through 2012. The inspection encompassed review of the engineering processes, manufacturing
processes and product documentation identified for APD 600-kilowatt to 2000-kilowatt diesel generator
sets with John Deere or Mitsubishi engines.
SCOPE
The remote inspections included AKSA USA representatives, Stephen Dy, Electrical Engineer and Efe
Parker, General Manager. Inspection of the China facility also included Samer Chen, Research &
Development Manager and Dennis Ruan, Quality Control Assurance Manager. Inspection of the Turkey
facility also included Omer Saner, Production Manager, Eminali Saral, Research & Development
Manager, Gokhan Erkan, Quality Manager and Selim Kuris, Operations Planning and Costing Manager.
The inspector led the meeting by providing an inspection overview, reviewing safety procedures, and
discussing the inspection itinerary. Inspected labeled units were as follows: China model APD-ULJ-30-
400, serial number CD4045L325557 and Turkey, model ULM800, serial number, 29962 and model
ULJ275, serial number L140467.
At the close of the meeting, the inspector expressed gratitude to the hosts and explained the next steps in
the inspection procedure: a comprehensive evaluation of the inspection results, a final determination of
compliance status and the communication of this decision.
CONCLUSION
VMA-49842-01C, 02C, 3C & -04C are recertified and will be consolidated into two VMAs, VMA-49842-
01C and VMA-49842-03C, as outlined in the proposal. The expiration will be set to November 30, 2023.
Revised Certificates of Compliance will be updated and linked to www.ibcapproval.com.
AUTHORIZATION
REVISION HISTORY
Certification No.
Certification Parameters:
The nonstructural products (mechanical and/or electrical components) listed on this certificate are CERTIFIED1 FOR SEISMIC APPLICATIONS
in accordance with the following building code2 releases.
This certification includes the open and enclosed generator sets and when installed with or without sub-base or remote fuel tank. The generator
set and included options shall be a catalogue design and factory supplied. The generator set and applicable options shall be installed and
attached to the building structure per the manufacturer supplied seismic installation instructions. This certification excludes all non-factory
supplied accessories, including but not limited to mufflers, isolation/restraint devices, remote control panels, remote radiators, pumps and other
electrical/mechanical components.
3. Refer to the manufacturer supplied installation drawings for anchor requirements and mounting considerations for seismic applications. Required anchor
locations, size, style, and load capacities (tension and shear) may be specified on the installation drawings or specified by a 3rd party. Mounting requirement
details such as anchor brand, type, embedment depth, edge spacing, anchor-to-anchor spacing, concrete strength, special inspection, wall design, and
attachment to non-building structures must be outlined and approved by the Engineer of Record for the project or building. Structural walls, structural floors,
and housekeeping pads must also be seismically designed and approved by the project or building Structural Engineer of Record to withstand the seismic
anchor loads as defined on the installation drawings. The installing contractor is responsible for observing the installation detailed in the seismic installation
drawings and the proper installation of all anchors and mounting hardware.
4. For this certificate and certification to remain valid, this certificate must correspond to the “Seismic Certification Label” found affixed to the unit by the factory.
The label ensures the manufacturer built the unit in conformance to the IBC seismic design criteria set forth by the Certified Seismic Qualification Agency, VMC
Group, and meets the seismic design levels claimed by this certificate.
5. Mechanical, Electrical, and Plumbing connections to the equipment must be flexibly attached as to not transfer load through the connection. The structural
integrity of any conduit, cable trays, piping, ductwork and/or flexible connections is the responsibility of others. This certification does not guarantee the
equipment will remain compliant to NEMA, IP, UL, or CSA standards after a seismic event.
6. This certificate applies to units manufactured at:
No. 19 Tongjiang North Road, Changzhou New District, Changzhou, China,
Rüzgarlıbahçe Mah. Selvi Çıkmazı No:10 Kavacık – Beykoz 34805 İstanbul – Türkiye
7. This project follows VMC Group’s ISO-17065 Scheme for Product Certification of Nonstructural Components.
John P. Giuliano, PE
President, VMC Group
Certification No.
Certification Parameters:
The nonstructural products (mechanical and/or electrical components) listed on this certificate are CERTIFIED1 FOR SEISMIC APPLICATIONS
in accordance with the following building code2 releases.
APD-ULJ* 30-400 Tier 3 205.7 77.3 112.1 27,310 Rigid Mounting Open/Enclosed
From Unit Base To On Tank
APD-ULJ500 500 Tier 2 314.0 77.3 148.1 38,190 Rigid Structure Open/Enclosed
APD-ULJ* 30-400 N/A 205.7 77.3 112.1 13,240 Rigid Mounting Open/Enclosed
Off Tank;
From Unit Base To
APD-ULJ500 500 N/A 205.7 77.3 112.1 13,760 With Remote Tank Open/Enclosed
Rigid Structure
Note: 1. See Certification Report for Enclosure options and materials
This certification includes the open and enclosed generator sets and when installed with or without sub-base or remote fuel tank. The generator
set and included options shall be a catalogue design and factory supplied. The generator set and applicable options shall be installed and
attached to the building structure per the manufacturer supplied seismic installation instructions. This certification excludes all non-factory
supplied accessories, including but not limited to mufflers, isolation/restraint devices, remote control panels, remote radiators, pumps and other
electrical/mechanical components.
3. Refer to the manufacturer supplied installation drawings for anchor requirements and mounting considerations for seismic applications. Required anchor
locations, size, style, and load capacities (tension and shear) may be specified on the installation drawings or specified by a 3rd party. Mounting requirement
details such as anchor brand, type, embedment depth, edge spacing, anchor-to-anchor spacing, concrete strength, special inspection, wall design, and
attachment to non-building structures must be outlined and approved by the Engineer of Record for the project or building. Structural walls, structural floors,
and housekeeping pads must also be seismically designed and approved by the project or building Structural Engineer of Record to withstand the seismic
anchor loads as defined on the installation drawings. The installing contractor is responsible for observing the installation detailed in the seismic installation
drawings and the proper installation of all anchors and mounting hardware.
4. For this certificate and certification to remain valid, this certificate must correspond to the “Seismic Certification Label” found affixed to the unit by the factory.
The label ensures the manufacturer built the unit in conformance to the IBC seismic design criteria set forth by the Certified Seismic Qualification Agency, VMC
Group, and meets the seismic design levels claimed by this certificate.
5. Mechanical, Electrical, and Plumbing connections to the equipment must be flexibly attached as to not transfer load through the connection. The structural
integrity of any conduit, cable trays, piping, ductwork and/or flexible connections is the responsibility of others. This certification does not guarantee the
equipment will remain compliant to NEMA, IP, UL, or CSA standards after a seismic event.
6. This certificate applies to units manufactured at:
No. 19 Tongjiang North Road, Changzhou New District, Changzhou, China,
Rüzgarlıbahçe Mah. Selvi Çıkmazı No:10 Kavacık – Beykoz 34805 İstanbul – Türkiye
7. This project follows VMC Group’s ISO-17065 Scheme for Product Certification of Nonstructural Components.
John P. Giuliano, PE
President, VMC Group