690V Motor Details
690V Motor Details
690V Motor Details
Rating
Kw Cos Rated Fuse Y/ Rated Fuse Y/ Rated Fuse Y/ Rated Fuse Y/ Rated Fuse Y/
Motor starting A Motor starting A Motor starting A Motor starting A Motor starting A
Current D.O.L Current D.O.L Current D.O.L BS Current D.O.L Current D.O.L
A A A A A A A A A A
BS
The maximum size is determined by the requirements of the switchgear or overload relay
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-
cooled motors.
D.O.L. starting : maximum starting current 6 x rated motor current. Maximum starting time : 5 s.
Y/ starting : maximum starting current 2 x rated motor current. Maximum starting time : 15 s.
set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/ starting are also valid for 3-phase motors with slip-ring rotors.
For higher rated currents, starting currents / longer starting times, larger fuses will be required.
Table is valid for 'slow' / 'gL' fuses (DIN VDE 0636)
For NH fuses with aM characteristic, fuses = rated current selected.