Introduction To Magnetic Circuits
Introduction To Magnetic Circuits
• A magnetic circuit is made up of one or more closed loop paths containing a magnetic
flux. The flux is usually generated by permanent magnets or electromagnets and confined
to the path by magnetic cores consisting of ferromagnetic materials like iron, although
there may be air gaps or other materials in the path.
• Magnetic circuits are employed to efficiently channel magnetic fields in many devices
such
aselectricmotors,generators,transformers,relays,liftingelectromagnets,SQUIDs,galvanomet
ers, and magnetic recording heads.
• The concept of a "magnetic circuit" exploits a one-to-one correspondence between the
equations of the magnetic field in a non saturated ferromagnetic material to that of an
electricalcircuit.
• Using this concept the magnetic fields of complex devices such as transformers can be
quickly solved using the methods and techniques developed for electrical circuits.
A magnetic circuit is made up of magnetic materials having high permeability such as iron, soft
steel, etc. Magnetic circuits are used in various devices like electric motor, transformers, relays,
generators galvanometer, etc.
Magnetising force in the core According to work law, the work done in moving a unit
pole once round the magnetic circuit is equal to the ampere-turns enclosed by the
magnetic circuit.
According to work law, the work done in moving a unit pole once round the magnetic
circuit is equal to the ampere-turns enclosed by the magnetic circuit.
The above equation explains the following points:
1. Directly proportional to the number of turns (N) and current (I).It shows that the
flux increase if the number of turns or current increases and decreases when
either of the two quantitydecreases.NI is the magnetomotive force (MMF).
2. Inversely proportional tol/aµ0µr,where(l/aµ0µr)is known as reluctance. The
lower the reluctance, the higher will be the flux and vice- verse.
Magnet or Electromagnet produces a Magnetic field. The field where the magnet attracts
or repels magnetic materials such as iron, steel, etc. it may be defined as a force on a
moving charge,
F=qxvxB
Where
· F = Force,
· V = Speed of Particles,
The amount of magnetizing force (how much force it has to magnetize, magnetic
materials such as iron, steel, etc) is called Magnetic field strength which is denoted by
(H). It is inversely proportional to the length of wire and directly proportional to the
current passing through it. The SI unit of Magnetic Field Strength is Ampere/meter
(A/m) and it is a vector quantity and the SI formula for Magnetic Field strength is
H = NI / 1c
In simple words, Magnetic field x area perpendicular to the magnetic field (B) is called
Magnetic Flux which is denoted by Φ or Φm or ΦB. Or it is the amount of magnetic field
or magnetic lines of force passing through a surface like conducting area, space, air, etc.
The SI Unit of magnetic flux is Wb (Weber). The Formula for finding magnetic flux in the
SI system is;
Φ = BAc
Where
Ac = area in m2
And CGS unit and formula for Magnetic Flux is Maxwell (M) and Φ = BAc Ac = area in
cm2 respectively.
Magnetization (M)
The state of a material being magnetized or the process in which magnetic materials are
magnetized. It is the density of permanent magnet or electromagnet dipole moments in
magnetic materials. Or the magnetic moment (m) per unit volume (v) by a magnetic
field is called Magnetization. The SI Unit of Magnetization is Ampere/meter (A/m) and it
is also a vector quantity. The SI formula for Magnetization is
M = m/V
Where,
The CGS unit and formula of Magnetization is Emu/cm3 and M = m/V respectively,
where, m = Total magnetic moment, V = volume in cm3 and EMU = Electromagnetic
units. It may also be defined in term of M = (N/V) x m → M = nm ……. (N/V) = n. Where,
“m” is the magnetic moment and “n” is the number density of magnetic moments.
Magnetic Permeability of vacuum
§ The SI unit of Permeability is (H·m−1), or Newton per ampere squared (N·A−2). The SI
unit and formulas of Magnetic Permeability of vacuum is Newton/Ampere2 and µ○ =
4πx10-7 ≈ 1.2566370614 H·m−1 respectively. The CGS unit of magnetic permeability
of vacuum is 1.
Inductance (L)
Inductance is the property of conductor, coil or wire which opposes the change of
current flowing through it. The change of current flowing through a conductor produces
a voltage called Back EMF or Electro motive force.
Even The change of current flowing through a conductor or coil produces voltage
through it which is called Self induced EMF and in any nearby coils or conductors which
is called Mutual inductance. The SI unit of Inductance (L) is Henry “H” and formula is
L = µ○ µ N2 Ac/1c
Where
· N = Turns
· Ac = Area in m2
CGS unit and formula of Inductance is Henry “H” (Joseph Henry) and L = 0.4π
µN2Ac/1c x10-8 respectively
where;
· L = Inductance
· N = Turns
· Ac = Area in cm2
L = µ○ (N2xA)/l
Where:
· L = in Henries
M = μο μrN1N2A/l
Where:
The Electric Potential Difference between two points is called Voltage. Or the work done
per unit charge in a static electric field to move the charge between two points, so the
equation becomes as
Where;
· V = Voltage
· E = Energy in joules
· q = Charge in Coulombs
Or the electric potential energy per unit charge is called Voltage.
The SI unit of Voltage is the Volt (V) or Joules per Coulomb. Where 1V =
1Joule/1Coulomb
V = -N dΦ/dt
Where;
· t = time
Any change in the magnetic field of a coil of wire will cause an emf to be induced in the coil. This
emf induced is called induced emf and if the conductor circuit is closed, the current will also
circulate through the circuit and this current is called induced current.
It states that the magnitude of emf induced in the coil is equal to the rate of change of flux that
linkages with the coil. The flux linkage of the coil is the product of the number of turns in the coil
and flux associated with the coil.
Applications
Magnetic circuits are employed to efficiently channel magnetic fields in many devices such as
1. electric motors
2. generators
3. transformers and relays
4. lifting electromagnets
5. SQUIDs
6. galvanometers and magnetic recording heads.
Self-inductance or in other words inductance of the coil is defined as the property of the coil
due to which it opposes the change of current flowing through it. Inductance is attained by a coil
due to the self-induced emf produced in the coil itself by changing the current flowing through
it.
If the current in the coil is increasing, the self-induced emf produced in the coil will oppose the
rise of current, that means the direction of the induced emf is opposite to the applied voltage.
If the current in the coil is decreasing, the emf induced in the coil is in such a direction
as to oppose the fall of current; this means that the direction of the self-induced emf is
same as that of the applied voltage. Self-inductance does not prevent the change of
current, but it delays the change of current flowing through it.
This property of the coil only opposes the changing current (alternating current) and
does not affect the steady current that is (direct current) when flows through it. The
unit of inductance is Henry (H).
The above expression is used when the magnitude of self-induced emf (e) in the coil and
the rate of change of current (dI/dt) is known.
Putting the following values in the above equations as e = 1 V, and dI/dt = 1 A/s then the
value of Inductance will be L = 1 H.
Hence, from the above derivation, a statement can be given that a coil is said to have an
inductance of 1 Henry if an emf of 1 volt is induced in it when the current flowing
through it changes at the rate of 1 Ampere/second.
From the above discussion, the following points can be drawn about Self Inductance
· The value of the inductance will be high if the magnetic flux is stronger for the
given value of current.
· The value of the Inductance also depends upon the material of the core and the
number of turns in the coil or solenoid.
· The higher will be the value of the inductance in Henry, the rate of change of
current will be lower.
Mutual Inductance :
It is defined as the property of the coil due to which it opposes the change of current in
the other coil, or you can say in the neighbouring coil.
When the current in the neighbouring coil changes, the flux sets up in the coil and
because of this, changing flux emf is induced in the coil called Mutually Induced emf and
the phenomenon is known as Mutual Inductance.
Two coils namely coil A and coil B are placed nearer to each other. When the switch S is
closed, and the current flows in the coil, it sets up the flux φ in the coil A and emf is
induced in the coil and if the value of the current is changed by varying the value of the
resistance (R), the flux linking with the coil B also changes because of this changing
current.
For determining the Mutual Inductance between the two coils, the following expression is used
This expression is used when the magnitude of mutually induced emf in the coil and the rate of
change of current in the neighbouring coil is known.
If emf = 1 volt and dI1/dt = 1 ampere then putting this value in the equation (1) we get the value
of mutual inductance as M=1 Henry
Hence, from the above statement, you can define Mutual Inductance as “the two coils are said to
have a mutual inductance of one Henry if an emf of 1 volt is induced in one coil or say primary
coil when the current flowing through the other neighbouring coil or secondary coil is changing
at the rate of 1 ampere/second”.
The above expression is used when the flux linkage (N2φ12) of one coil due to the current (I1)
flowing through the other coil are known.
The value of Mutual Inductance (M) depends upon the following factors
· Cross-sectional area
When on a magnetic core, two or more than two coils are wound, the coils are said to be
mutually coupled. The current, when passed in any of the coils wound around the
magnetic core, produces flux which links all the coils together and also the one in which
current is passed. Hence, there will be both self-induced emf and mutual induced emf in
each of the coils.
The best example of the mutual inductance is the transformer, which works on the
principle of Faraday’s Law of
Electromagnetic Induction.
A transformer is defined as a passive electrical device that transfers electrical energy from one
circuit to another through the process of electromagnetic induction. It is most commonly used to
increase (‘step up’) or decrease (‘step down’) voltage levels between circuits.
Working principle of electrical power transformer is very easy, it is similar to that of mutual
induction. A transformer is a static (or stationary) piece of apparatus by means of which electric
power in one circuit is transformed into electric power of the same frequency in another circuit.
• It can raise or lower the voltage in a circuit but with a corresponding decrease or increase
in current.
• The physical basis of a power transformer is mutual induction between two circuits linked
by a common magnetic flux. In its simplest form, it consists of two inductive coils which
are electrically separated but magnetically linked through a path of low reluctance as
shown in the figure below.
• The two coils possess high mutual inductance. If one coil is connected to a source of
alternating voltage, an alternating flux is set up in the laminated core, most of which is
linked with the other coil in which it produces mutually-induced e.m.f. (according to
Faraday’s Laws of Electromagnetic Induction = M.dI/dt).
• If the second coil circuit is closed, a current flow in it and so electric energy is transferred
(entirely magnetically)from the first coil to the second coil.
• The first coil, in which electric energy is fed from the a.c.supply mains is called primary
winding and the other from which energy is drawn out, is called secondary winding.
Fig.1 Transformer
• The power transformer consists of two coils having mutual inductance and a laminated
steel core. The two coils are insulated from each other and the steel core. Other necessary
parts are some suitable container for assembled core and windings; a suitable medium
for insulating the core and its windings from its container; suitable bushings(either of
porcelain, oil-filled or capacitor-type) for insulating and bringing out the terminals of
windings from the tank.
• In all types of power transformers, the core is constructed of transformer sheet steel
laminations assembled to provide a continuous magnetic path with a minimum of air-gap
included.
• The steel used is of high silicon content, sometimes heat treated to produce a high
permeability and a low hysteresis loss at the usual operating flux densities. The eddy
current loss is minimised by laminating the core, the laminations being insulated from
each other by a light coat of core-plate varnish or by an oxide layer on the surface.
• The thickness of laminations varies from 0.35 mm for a frequency of 50 Hz to 0.5 mm for
a frequency of 25 Hz. The core laminations (in the form of strips) are joined as shown in
Figure.
It is seen that the joints in the alternate layers are staggered in order to avoid the presence of
narrow gaps right through the cross-section of the core. Such staggered joints are said to be
‘imbricate.
Core Types Transformer: Another recent development is spiral-core or wound-core type, the
trade name being Spiral Core transformer. In the so called core type transformers, the windings
surround a considerable part of the core whereas, in shell type transformers, the core surrounds a
considerable portion of the windings as shown schematically in the figures(a) and (b) respectively.
In the simplified diagram for the core type transformers, the primary and secondary
winding are shown located on the opposite legs (or limbs) of the core, but in actual
construction, these are always interleaved to reduce leakage flux.
As shown in Figure, half the primary and half the secondary winding have been placed
side by side or concentrically on each limb, not primary on one limb (or leg) and the
secondary on the other
HV and LV windings are wound longitudinally along the core alternately. The HV coils
are sandwiched between two LV coils as shown in the figure below
ince, both HV and LV coils are wound on the central limb surface, the quantity of
conductor required for woundings of shell type transformer is less than that of a similar
core type transformer.
The design of shell-type is a bit complex compared to core-type due to its winding structure. Any
defect in the inner windings can only be attended after removing all outer windings hence the
winding maintenance jobs are very hard in shell type transformer.
Transformation Ratio
The transformer transformation ratio or transformer turns ratio (K) is the quotient value
obtained by dividing the number of turns of the primary winding (N1) and the number
of turns of the secondary winding (N2).
Then K = N1/N2
A transformer with an equal number of turns on its primary and secondary windings will have a
secondary voltage only slightly less than the primary applied voltage, and its voltage ratio is said
to be 1:1. If, however, the secondary winding have only one-half as many turns as the primary
winding, the secondary voltage will be only one-half as great as the primary voltage. The voltage
ratio then will be 2:1. The primary and secondary generated electromotive forces are proportional
to the primary and secondary turns respectively.
Losses in transformer
There are various losses exist in a transformer which occur due to the heat present in the losses.
These losses reduce the efficiency of the working of transformer.
• Eddy current loss and hysteresis loss depend upon the magnetic properties of the
material used for the construction of core.
• Hence these losses are also known as core losses or iron losses.
Where
The iron or core losses can be minimized by using silicon steel material for the
construction of the core of the transformer.
When the flux links with a closed circuit, an emf is induced in the circuit and the current
flows, the value of the current depends upon the amount of emf around the circuit and
the resistance of the circuit.
Since the core is made of conducting material, these EMFs circulate currents within the
body of the material.
These circulating currents are called Eddy Currents. They will occur when the
conductor experiences a changing magnetic field.
As these currents are not responsible for doing any useful work, and it produces a loss
(I2R loss) in the magnetic material known as an Eddy Current Loss.
The eddy current loss is minimized by making the core with thin laminations.
· Ke – coefficient of eddy current. Its value depends upon the nature of magnetic material like
volume and resistivity of core material, the thickness of laminations
These losses occur due to ohmic resistance of the transformer windings. If I1 and I2 are the
primary and the secondary current. R1 and R2 are the resistance of primary and secondary
winding then the copper losses occurring in the primary and secondary winding will be I12R1 and
I22R2 respectively.
These losses varied according to the load and known hence it is also known as variable losses.
Copper losses vary as the square of the load current.
Stray Loss
The occurrence of these stray losses is due to the presence of leakage field.
The percentage of these losses are very small as compared to the iron and copper losses so they
can be neglected.
Dielectric Loss
Dielectric loss occurs in the insulating material of the transformer that is in the oil of the
transformer, or in the solid insulations.
When the oil gets deteriorated or the solid insulation gets damaged, or its quality decreases, and
because of this, the efficiency of the transformer gets affected.
Transformer Efficiency:
The Efficiency of the transformer is defined as the ratio of useful output power to the
input power. The input and output power are measured in the same unit. Its unit is
either in Watts (W) or KW. Transformer efficiency is denoted by Ƞ.
Where,
Consider, the x is the fraction of the full load. The efficiency of the transformer regarding x is
expressed as
given power factor the Transformer efficiency depends upon the load current I2. In equation (1),
the numerator is constant and the transformer efficiency will be maximum if the denominator
with respect to the variable I2 is equated to zero
Thus, the transformer will give the maximum efficiency when their copper loss is equal to the iron
loss.
From equation (2) the value of output current I2 at which the transformer efficiency
will be maximum is given as
If x is the fraction of full load KVA at which the efficiency of the transformer is maximum then,
Iron losses = Pi
Therefore
Putting the value of x from the above equation (3) in equation (4) we will get,
The above equation (5) is the maximum efficiency condition of the transformer.
We have seen in this series of tutorials about the transformer, that when the primary winding of a
transformer is energized, it produces a secondary voltage and current at an amount determined
by the transformers turns ratio, (TR). So if a single-phase transformer has a step down turns ratio
of 2:1 and 240V is applied to the high voltage primary winding, we would expect to see an output
terminal voltage on the secondary winding of 120 VAC because we have assumed it to be an
ideal transformer.
However in the real world this is not always true as being a wound magnetic circuit, all
transformers suffer from losses consisting of I2R copper losses and magnetic core losses which
would reduce this ideal secondary value by a few percent to say 117 VAC, and this is normal. But
there is also another value related to transformers (and electrical machines) which also has an
affect on this secondary voltage value when the transformer is supplying full power, and this is
called “regulation”.
Voltage Regulation of single-phase transformers is the percentage (or per unit value) change in
its secondary terminal voltage compared to its original no-load voltage under varying secondary
load conditions. In other words, regulation determines the variation in secondary terminal
voltage which occurs inside the transformer as a result of variations in the transformers
connected load thereby affecting its performance and efficiency if these losses are high and the
secondary voltage becomes too low.
When there is no-load connected to the transformers secondary winding, that is its output
terminals are open-circuited, there is no closed-loop condition, so there is no output load current
(IL = 0) and the transformer acts as one single winding of high self-inductance. Note that the no-
load secondary voltage is a result of the fixed primary voltage and the turns ratio of the
transformer.
Loading the secondary winding with a simple load impedance causes a secondary current to flow,
at any power factor, through the internal winding of the transformer. Thus voltage drops due to
the windings internal resistance and its leakage reactance causes the output terminal voltage to
change.
A transformers voltage regulation change between its secondary terminal voltage from a no-load
condition when IL = 0, (open circuit) to a fully-loaded condition when IL = IMAX (maximum
current) for a constant primary voltage is given as: