3.2 Design Criteria 3.2.1 Dead Load: Calculation Note For Hale Townhouses Rev 0
3.2 Design Criteria 3.2.1 Dead Load: Calculation Note For Hale Townhouses Rev 0
3.2 Design Criteria 3.2.1 Dead Load: Calculation Note For Hale Townhouses Rev 0
SLAB
Reinforced Stone Concrete (23.60kN/m3) 4.720 kPa
Ceramic or Quarry Tile (20mm) on 13mm Mortar Bed 0.770 kPa
Wood Block (75mm) on Mastic, No Fill 0.480 kPa
Oak Hardwood Flooring 0.190 kPa
Terrazzo (38mm) directly on slab 0.910 kPa
Gypsum Board (0.008 kPa) 0.160 kPa
Suspended Steel Channel System 0.100 kPa
Partition Load 1.000 kPa
Electromechanical 0.100 kPa
WALL
Exterior Wall Full Grout (19.60kN/m3/density) 4.360 kPa
Interior Wall Full Grout (16.5kN/m3/density) 4.070 kPa
BEAM
Reinforced Stone Concrete (23.60kN/m3) 1.888 kPa
Restroom loads shall be not less than the load for the occupancy with which they
are associated but need not exceed 2.40 kPa.
ROOFING MATERIALS
18 Gauge Standing Seam Metal Roof 0.140 kPa
CALCULATION NOTE FOR HALE TOWNHOUSES REV 0
FOR SELFWEIGHT
2-L 50 x 50 x 40 = (6.12kg/m)(9.81m/s2)/(1000N/kN) 0.060kN/m
FOR PURLINS
C 100 x 50 x 10 = (10.2kg/m) (9.81m/s2)/(1000N/kN) 0.100kN/m
z (m) Kz
3.4 0.528
6.4 0.633
9.4 0.706
h (m) Kh
9.4 0.706
z (m) Kz qz (kPa)
h (m) Kh qh (kPa)
L 56m
= = 5.6 -0.2
B 10m
B. Roof
h 9.4m
= = 0.94 θ = 7.97°
L 10m