Conzerv EM6400NG+ Series: Multi-Function Power & Energy Meters
Conzerv EM6400NG+ Series: Multi-Function Power & Energy Meters
Technical datasheet
se.com/in
Power and energy meters EM6400NG+ multi-function meters
Functions and characteristics
Accurate measurements of THD and individual harmonics (complying with IEC61557-12) helps in
monitoring the power quality. It enables the users to capture abnormalities in the system with date and
time stamp. Further to facilitate the readings, the EM6400NG+ has a large LED display for
simultaneous monitoring of multiple electrical parameters. Cyber security features to enable safe and
secure Digital India.
Main characteristics:
b Easy to install: Mounts using two clips and no tools are required. Compact meter with maximum of
73 mm depth, connectable up to 480 +/- 10% AC Volts L-L without voltage transformers for installations
compliant with measurement category III, and double insulated.
b Easy to operate: Test LED at the front panel can be used for test and calibration of the meter at site
or laboratory. Heart beat LED indicates the normal functioning of the meter and communication status
if connected to RS485 network.
bb LED display: Intuitive navigation with self-guided, three buttons, LEDs of height ~14.2 mm (0.55 in),
and three lines of concurrent values. Two columns of LEDs given on the either side of the meter’s front
panel indicates the parameter name chosen for display.
bb Energy standards: Active energy Class 0.5S/ Class 0.2+1 as per IEC 62053-22, Active energy
Class 1.0 as per IEC 62053-21. Reactive energy Class 1.0 & Class 2.0 as IEC 62053-24 & IEC
62053-23 respectively. Tested in accordance with IEC 62052-11 standard for -
v 5 A, I-nominal
v 1 A, I-nominal (field settable).
bb Power quality analysis: The EM6400NG+ offers THD measurements and Individual harmonics up
to 15th order for voltage and current parameters, per-phase basis.
Model reference Commercial reference
bb Load management: Peak demands of all the four demand parameters (W, VA, VAR, Amps) with
EM6400NG+ POP
Cl 1.0
METSEEM6400NGPOCL1 date and time of occurrence.
EM6400NG+ POP bb Billing: Tenant billing/utility meter cross check (where local regulations are not applicable).
METSEEM6400NGPOCL5
Cl 0.5S
EM6400NG+ RS485 bb Load timer: Load timer (Run Hrs) monitors and advises maintenance requirements.
METSEEM6400NGRSCL1
Cl 1.0
bb Password: Field configurable password for securing set up information and prevents tampering of
EM6400NG+ RS485
METSEEM6400NGRSCL5 integrated values.
Cl 0.5S
EM6400NG+ RS485 bb Cyber security: Option for disabling RS485 port through front panel keys against unauthorized
METSEEM6400NGRSCL2
Cl 0.2
access. This feature can also be used for toggling between the RTU devices in case of limited
availability of nodes in software system.
bb Display: Auto scaling, 9+3 digits for energy, and 4 digits for other parameters.
bb Green premium: EOL, REACH, PEP, RoHS compliance
2
Power and energy meters EM6400NG+ multi-function meters
Functions and characteristics
General
Use on LV and MV systems with PT/CT ratio programmable at site
Basic metering with THD, Individual Harmonics, RTC, and min/max readings
Demand values
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time
Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
Demand sync methods Thermal, Timed, Command Sync, and Clocked Sync
Display
Bright red colour LED display, 7 segment LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row,
Auto range
Communication
Pulse Output: Rate of pulse can be configured for selected energy parameters
RS485 serial channel connection Industry standard Modbus RTU protocol
Integration with any Modbus compatible SCADA/ DCS/ PMS/ EMS/ BAS/ BMS software
Native Plug and Play support for Schneider Electric energy management system software -
StruxureWare Power Monitoring Expert, StruxureWare PowerSCADA Expert along with ION Setup
programming support
Min/Max values
Meter records Minimum & Maximum values for 8 parameters, viz., V L-L, V L-N, Amps, PF, Hz, W,
VA, VAR with date and time stamp. Values can be reset separately in set up mode
Diagnostics
Diagnostic page indicates the healthiness of communication system, all LED test, device serial
number and OS & RS version
Page Lock
Page Lock & Un-Lock features: Once commonly referred page is enabled for Lock feature, the
display returns to Locked page in 4 minutes of inactive time
Suppression current
To disregard induced or negligible current flowing in the circuit, minimum value of current detection
can be settable from 5 to 99 mA, default is 5 mA
Quadrant based VARh
Available through communication
3
Power and energy meters EM6400NG+ multi-function meters
Functions and characteristics
Electrical characteristics
Type of measurement True RMS, 64 samples per cycle
Measurement accuracy
Current, Phase ±0.5%
Voltage L-N, L-L ±0.5%
Power Factor ±0.01
Power ±0.5%
Frequency ±0.05%
Class 0.5S and Class 0.2+1 as per IEC 62053-22 and Class 1.0 as per
Real Energy
IEC 62053-21 for both CT nominal of 5 A and 1 A+2
IEC 62053-23 Class 2.0 when Wh Class is 1.0 and IEC 62053-24 Class
Reactive Energy
1.0 when Wh Class is 0.5S/0.2
EM6400NG+ series multi-function power meter - rear THD and Individual Class 5.0 as per IEC 61557-12 for THD and individual harmonics up to
Harmonic, V & A 15th
Input-voltage
VT primary 999 kV L-L max, starting voltage depends on VT ratio
U nominal 277 V L-N/480V L-L
Measured V with full range 35 to 600 V AC L-L
Permanent overload 750 V AC L-L
Impedance => 5 MΩ
Frequency range 50/60 Hz +/-5%
VA burden < 0.2 VA at 240 V AC L-N
Input-current
Primary adjustable 1 A to 32768 A
CT ratings
Secondary 1 A or 5 A I-nominal
Measured Amps with over
5 mA to 6 A
range & Crest Factor
Withstand Continuous 12 A, 50 A at 10 sec/hr
Impedance < 0.3 MΩ
Frequency range 50/60 Hz +/-5%
VA Burden < 0.1 VA at 6A
AC control power
Operating range 44- 277 V AC ± 10%
Burden < 6 VA at 277 V L-N
Frequency 50/60 Hz nominal
100 ms typical at 120 V AC and maximum burden
Ride-through time
100 ms typical at 277 V AC and maximum burden
DC control power
Operating range 44-277 V DC ± 10%
Burden < 2 W at 277 V DC
Ride-through time 50 ms typical at 125 V DC and maximum burden
Real time clock
Ride-through time 3 years
Displays update
Instantaneous 1s
Demand 15 s
Harmonics 5s
Wiring configuration
1ph, 2w, LN
1ph, 2w, LL
1ph, 3w, LL with N (2phase)
3ph, 3w, Delta, Ungrounded
3ph, 3w, Delta, Corner Grounded +3
3ph, 3w, Wye, Ungrounded +3
User programmable 3ph, 3w, Wye Grounded +3
3ph, 3w, Wye, Resistance Grounded +3
3ph, 4w, Open Delta, Center-Tapped +3
3ph, 4w, Delta, Center-Tapped +3
3ph, 4w, Wye, Ungrounded +3
3ph, 4w, Wye Grounded
3ph, 4w, Wye, Resistance Grounded +3
+1
Class 0.2S accuracy is applicable in 3ph,4w configuration
+2
For 1 A CT nominal, additional error of ±1% from 50 mA to 150 mA, ±2% for current > 10 mA to < 50 mA
+3
Through communication
4
Power and energy meters EM6400NG+ multi-function meters
Functions and characteristics
Mechanical characteristics
Weight ~ 600 gms (21 oz)
IP degree of protection IP51 front side, IP30 meter body as per IEC 60529
Material Polycarbonate meets UL 94V-0 flammability rating
96 x 96 x 73 mm (3.78 x 3.78 x 2.87 in) maximum (depth of
Dimensions W x H x D the meter from housing mounting flange) and 13 mm (0.51 in)
(protrusion of meter from housing flange)
Mounting position Vertical
Max 40 V DC, 20 mA
20 ms ON time
Pulse Output (POP)
Configurable pulse weight from 1 to 9999000 pulses/k_h
(kWh, kVAh, or kVARh)
Isolation 2.5 kV RMS, double insulated
Password protected for set-up & clearing energy and Min/Max
Protection features
data
Display language English
Printed installation guide (QSG) with meter and user guide in
Technical publication
soft format
+4
Tested as per IEC 61326-1 standard
5
Power and energy meters EM6400NG+ multi-function meters
Functions and characteristics
Current,
3-ph unbalance Current
Voltage+3
Demand parameters b b
(W, VA, VAR, Amps) (no timestamp)
Date and timestamp for peak demand+3
+3
Through communication
6
Power and energy meters EM6400NG+ multi-function meters
Functions and characteristics
Conzerv EM6400NG
(3.78)
96.0
(3.56)
90.44
62.76 110.1
(2.47) (4.33)
77.01
(3.0)
89.81
(3.53)
Negative indicator
OK Enter key
x 1000 indicator
Retainer clip
RS-485 communications/
D1+, D0-
POP terminals
Protective cover
7
Schneider Electric India Pvt. Ltd.
Corporate Office
9th Floor, DLF Building No.10,
Tower C, DLF Cyber City, Phase II,
Gurgaon - 122002, Haryana.
Tel: 0124 3940400, Fax: 0124 4222036
www.se.com/in
Customer Care Centre
Toll-free numbers: 1800 103 0011, 1800 425 4272
General number: 0124 4222040
Email: [email protected]