MIN 2500-6000TL-XE User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

MIN 2500TL-XE

MIN 3000TL-XE
MIN 3600TL-XE
MIN 4200TL-XE
MIN 4600TL-XE
MIN 5000TL-XE
MIN 6000TL-XE

Installation
&
Growatt New Energy Operation Manual
Download
Manual

Shenzhen Growatt New Energy Technology CO.,LTD


No.28 Guangming Road, Shiyan Street, Bao’an District,
Shenzhen, P.R.China
T +86 755 2747 1942
E [email protected]
W www.ginverter.com
GR-UM-192-A-01
Index

1 Notes on this manual


1.1 Validity
1.2 Target Group
1.3 Additional information
1.4 Symbols in this document
1.5 Glossary

2 Safety
2.1 Intended Use
2.2 Qualification of skilled person
2.3 Safety instruction
2.4 Assembly Warnings
2.5 Electrical Connection Warnings
2.6 Operation Warnings

3 Product Introduction
3.1 TL-XE Overview
3.2 Type label
3 . 3 Size and weight
3.4 Storage of Inverter
3.5 The advantage of the unit

4 Unpacking and inspection

5 Installation
5 . 1 Safety instructions
5.2 Selecting the installation location
5.3 Mounting the Inverter
6 Electrical connection 6.1 Safety
11 Trouble shooting
11.1 Error Messages displayed on OLED
6.2 Wiring AC Output 11.2 System fault
6.3 Connecting the second protective 11.3 Inverter warning
conductor 11.4 Inverter fault
6.4 Connecting the PV Array
6.5 Connecting signal cable
6.6 Grounding the inverter
6.7 Active power control with smart
meter , CT or ripple control signal
receiver 12 Manufacturer Warranty
6.8 Connecting the COM PORT
6.9 Electric arc hazards

13 Decommissioning
13 . 1 Dismantling the Inverter
13 . 2 Packing the Inverter
7 Commissioning 13 . 3 Storing the Inverter
7.1 Start the inverter
13 . 4 Disposing of the Inverter
7.2 General setting
7.3 Advanced setting
7.4 Communication interfaces

14 Technical Data
14 . 1 Specification
14 . 2 PV&AC connectors info
8 Start-Up and shut down 14 . 3 Torque
the inverter 8.1 Start-Up the inverter
14 . 4 Accessories
8.2 Shut down the inverter

9.1 Checking Heat Dissipation


15 Compliance Certificates
9 Maintenance and Cleaning
9.2 Cleaning the Inverter
9.3 Checking the DC Disconnect

10 EU Declaration of Conformity 16 Contact


1 Notes on this manual
1.1 Validity
This manual describes the assembly, installation, commissioning and maintenance of the
following Growatt Inverter model: Information that you must read and know to ensure optimal
MIN 2500 TL-XE operation of the system.
MIN 3000 TL-XE Information
MIN 3600 TL-XE
MIN 4200 TL-XE
MIN 4600 TL-XE
MIN 5000 TL-XE 1.4.2 Markings on this product
MIN 6000 TL-XE
Symbol Explanation

1.2 Target Group Electrical voltage!


This manual is for qualified personnel. Qualified personnel have received training and
have demonstrated skills and knowledge in the construction and operation of this
device. Qualified Personnel are trained to deal with the dangers and hazards involved in Risk of fire or explosion!
installing electric devices.

Risk of burns
1.3 Additional information
Find further information on special topics in the download area at www.ginverter.com
The manual and other documents must be stored in a convenient place and be available Operation after 5 minutes
at all times. We assume no liability for any damage caused by failure to observe these
instructions. For possible changes in this manual, GROWATT NEW ENERGY
TECHNOLOGY CO.,LTD accepts no responsibilities to inform the users.
Point of connection for grounding protection

1.4 Symbols in this document


1.4.1 Warings in this document Direct Current (DC)

A warning describes a hazard to equipment or personnel. It calls attention to a procedure


or practice, which, if not correctly performed or adhered to, could result in damage to or
Alternating Current (AC)
destruction of part or all of the Growatt equipment and/or other equipment connected
to the Growatt equipment or personal injury.

Symbol Description The inverter has no transformer.

DANGER indicates a hazardous situation which, if not avoided, will


result in death or serious injury. Read the manual
DANGER

WARNING indicates a hazardous situation which, if not avoided, CE mark.


could result in death or serious injury. The inverter complies with the requirements of the applicable CE
WARNING guidelines.

CAUTION indicates a hazardous situation which, if not avoided,


could result in minor or moderate injury. The inverter must not be disposed of with the household waste.
CAUTION

NOTICE is used to address practices not related to personal injury.


NOTICE
1 2
1.5 Glossary Principle of a PV plant with this MIN TL-XE single-phase inverter:
AC
Abbreviation for "Alternating Current"
DC
Abbreviation for "Direct Current"
Energy
Energy is measured in Wh (watt hours), kWh (kilowatt hours) or MWh (megawatt hours).
The energy is the power calculated over time. IF,for example, your inverter operates at a
constant power of 4600 W for half an hour and then at a constant power of 2300 W for
another half an hour, it has fed 3450Wh of energy into the power distribution grid within Position Description
that hour.
A PV modules
Power
Power is measured in W (watts), kW (kilowatts) or MW (megawatts). Power is an B DC load circuit breaker
instantaneous value. It displays the power your inverter is currently feeding into the
power distribution grid. C Inverter
Power rate
Power rate is the radio of current power feeding into the power distribution grid and the D AC load circuit breaker
maximum power of the inverter that can feed into the power distribution grid.
E Energy meter
Power factor
Power factor is the ratio of true power or watts to apparent power or volt amps. They are F Utility grid
identical only when current and voltage are in phase than the power factor is 1.0. The
power in an ac circuit is very seldom equal to the direct product of the volts and amperes.
In order to find the power of a single phase ac circuit the product of volts and amperes The inverter may only be operated with a permanent connection to the public power
must be multiplied by the power factor. grid. The inverter is not intended for mobile use. Any other or additional use is not
PV considered the intended use. The manufacturer/supplier is not liable for damage caused
Abbreviation for photovoltaic. by such unintended use. Damage caused by such unintended use is at the sole risk of the
Wireless communication operator.
The external wireless communication technology is a radio technology that allows the
inverter and other communication products to communicate with each other. The PV modules Capacitive Discharge Currents
external wireless communication does not require line of sight between the devices and PV modules with large capacities relative to earth, such as thin-film PV modules with
it is selective purchasing. cells on a metallic substrate, may only be used if their coupling capacity does not exceed
1uF. During feed-in operation, a leakage current flows from the cells to earth, the size of
which depends on the manner in which the PV modules are installed (e.g. foil on metal
roof) and on the weather (rain, snow). This "normal" leakage current may not exceed
50mA due to the fact that the inverter would otherwise automatically disconnect from
the electricity grid as a protective measure.

2 Safety 2.2 Qualification of skilled person


This inverter system operates only when properly connected to the AC distribution
2.1 Intended Use network. Before connecting the MIN TL-XE to the power distribution grid, contact the
local power distribution grid company. This connection must be made only by qualified
The unit converts the DC current generated by the photovoltaic (PV) modules to grid- technical personnel to connect, and only after receiving appropriate approvals, as
compliant alternating current and performs single-phase feed-in into the electricity required by the local authority having jurisdiction.
grid.MIN 2500TL-XE, MIN 3000TL-XE, MIN 3600TL-XE, MIN 4200TL-XE, MIN 4600TL-XE,
MIN 5000TL-XE , MIN 6000TL-XE inverters are built according to all required safety rules.
Nevertheless, improper use may cause lethal hazards for the operator or third parties, or
may result in damage to the units and other property.

3 4
2.3 Safety instruction Ø Danger to life due to high voltages in the inverter.
The MIN TL-XE Inverters is designed and tested according to international safety Ÿ There is residual voltage in the inverter. The inverter takes 20
requirements (IEC62109-1, CE, VDE-AR-N4105, CEI0-21, VDE0126-1-1, AS4777); minutes to discharge.
however, certain safety precautions must be observed when installing and operating this
inverter. Read and follow all instructions, cautions and warnings in this installation Ø Persons with limited physical or mental abilities may only work
manual. If questions arise, please contact Growatt's technical services at +86 (0)755 with the Growatt inverter following proper instruction and under
2747 1900. constant supervision. Children are forbidden to play with the Growatt
DANGER
inverter. Must keep the Growatt inverter away from children.

2.4 Assembly Warnings Ø Make all electrical connections (e.g. conductor termination,
fuses, PE connection, etc.) in accordance with prevailing
Ø Prior to installation, inspect the unit to ensure absence of any regulations. When working with the inverter powered on, adhere
transport or handling damage, which could affect insulation to all prevailing safety regulations to minimize risk of accidents.
integrity or safety clearances; failure to do so could result in safety Ø Systems with inverters typically require additional control (e.g.,
hazards. switches, disconnects) or protective devices (e.g., fusing circuit
WARNING
Ø Assemble the inverter per the instructions in this manual. Use care breakers) depending upon the prevailing safety rules.
when choosing installation location and adhere to specified
cooling requirements.
Ø Unauthorized removal of necessary protections, improper use,
WARNING incorrect installation and operation may lead to serious safety and 2.6 Operation Warnings
shock hazards and/or equipment damage.
Ø In order to minimize the potential of a shock hazard due to Ø Ensure all connectors are sealed and secure during operation.
hazardous voltages, cover the entire solar array with dark material Ø Although designed to meet all safety requirements, some parts
prior to connecting the array to any equipment. and surfaces of Inverter are still hot during operation. To reduce
the risk of injury, do not touch the heat sink at the back of the
Ø Grounding the PV modules: The MIN TL-XE is a transformerless Inverter or nearby surfaces while Inverter is operating.
inverter. That is why it has no galvanic separation. Do not ground Ø Incorrect sizing of the PV plant may result in voltages being
the DC circuits of the PV modules connected to the MIN TL-XE. present which could destroy the inverter. The inverter display will
Only ground the mounting frame of the PV modules.If you WARNING read the error message “PV voltage High!”
connect grounded PV modules to the MIN TL-XE, the error Ÿ Turn the rotary switch of the DC Disconnect to the Off position
message "PV ISO Low". immediately.
Ø Comply with the local requirements for grounding the PV Ÿ Contact installer.
CAUTION m o d u l e s a n d t h e P V g e n e r a t o r. G R O WAT T re c o m m e n d s
Ø All operations regarding transport, installation and start-up,
connecting the generator frame and other electrically conductive
including maintenance must be operated by qualified, trained
surfaces in a manner which ensures continuous conduction with
personnel and in compliance with all prevailing codes and
ground in order to have optimal protection of the system and
regulations.
personnel.
Ø Anytime the inverter has been disconnected from the power
network, use extreme caution as some components can retain
charge sufficient to create a shock hazard; to minimize
occurrence of such conditions, comply with all corresponding
safety symbols and markings present on the unit and in this
2.5 Electrical Connection Warnings manual.
CAUTION Ø In special cases, there may still be interference for the specified
Ø The components in the inverter are live. Touching live components application area despite maintaining standardized emission limit
can result in serious injury or death. values (e.g. when sensitive equipment is located at the setup
Ÿ Do not open the inverter except the wire box by qualified persons. location or when the setup location is near radio or television
Ÿ Electrical installation, repairs and conversions may only be carried receivers).In this case, the operator is obliged to take proper
out by electrically qualified persons. action to rectify the situation.
Ÿ Do not touch damaged inverters. Ø Do not stay closer than 20 cm to the inverter for any length of
DANGER time.

5 6
3 Product description
3.1 TL-XE Overview
3.2 Type label
The type labels provide a unique identification of the inverter (The type of product,
Device-specific characteristics, Certificates and approvals). The type labels are on the
left-hand side of the enclosure.

Position Description Position Description

A Cover G AC OUTPUT

B DC SWITCH H VENTILATION VALVE


C LED I PV INPUT +
D OLED J PV INPUT -
E TOUCH BUTTON K USB PORT

F COM Port L SYS COM Port

Symbol on the inverter

Symbol Description Explanation

Touch button.We can switch the OLED


Touch symbol display and set parameter by touching.

Indicates inverter operation status:


Red:Fault.
Inverter status Green:Nomal.
symbol Red leaf flash:Warning or DSP Programming.
Green leaf flash:M3 Programming.

7 8
3.3 Size and weight
More detail about the type label as the chart below:

Model Name MIN 2500 TL-XE MIN 3000 TL-XE MIN 3600 TL-XE

Max input PV voltage 500V 500V 550V

Max input PV current 12.5A/12.5A

Start voltage 100V

MPP voltage range 80V~500V 80V~500V 80V~550V

AC nominal voltage 230V

AC grid frequency 50/60 Hz

Max. apparent power 2500VA 3000VA 3600VA Dimensions and weight

Max ACl output current 11.3A 13.6A 16A Model Height (H) Width (W) Depth (D) Weight

Power factor 0.8leading…0.8lagging MIN 2500-6000 TL-XE 350mm 13.8inch 375mm 14.8inch 160mm 6.3inch 10.8kg
Environmental Protection
Rating IP 65
Operation Ambient -25...+60℃ (-13...+ 140°F)
temperature with derating above 45°C(113°F) 3.4 Storage of Inverter
If you want to storage the inverter in your warehouse, you should choose an appropriate
MIN 4200 MIN 4600 MIN 5000 MIN 6000 location to store the inverter.
Model Name
TL-XE TL-XE TL-XE TL-XE Ø The unit must be stored in original package , and should be stored in a clean and dry
Max input PV voltage 550V place, and be protected from dust and water vapor corrosion.
Ø The storage temperature should be always between -25℃and +60℃. And the
Max input PV current 12.5A/12.5A storage relative humidity can achieve to 100%.
Ø If there are a batch of inverters need to be stored, the maximum layers for original
Start voltage 100V carton is four.
Ø After long term storage, local installer or service department of GROWATT should
MPP voltage range 80V~550V perform a comprehensive test before installation.

AC nominal voltage 230V

AC grid frequency 50/60 Hz 3.5 The advantage of the unit


Ø Maximum efficiency of 98.4%
Max. apparent power 4200VA 4600VA 5000VA 6000VA
Ø Wide input voltage range from 80--550Vdc
Max ACl output current 19A 20.9A 22.7A 27.2A Ø Reactive power regulate
Ø Integrated DC switch
Power factor 0.8leading…0.8lagging Ø Multi MPP controller
Ø DSP controller
Environmental Protection
IP 65 Ø Touch control
Rating
Ø Multi active power control mode
Operation Ambient -25...+60℃ (-13...+ 140°F) Ø Easy installation
temperature with derating above 45°C(113°F)
Ø Intelligent DC arc fault detection(AFCI)
9 10
4 Unpacking and inspection Installation 5
The inverter is thoroughly tested and inspected strictly before delivery. Our inverters 5.1 Safety instructions
leave our factory in proper electrical and mechanical condition. Special packaging
ensures safe and careful transportation. However, transport damage may still occur. The Danger to life due to fire or explosion.
shipping company is responsible in such cases. Thoroughly inspect the inverter upon Ø Despite careful construction, electrical devices can cause fires.
delivery. Immediately notify the responsible shipping company if you discover any Ø Do not install the inverter on easily flammable materials and
damage to the packaging which indicates that the inverter may have been damaged or if where flammable materials are stored.
you discover any visible damage to the inverter. We will be glad to assist you, if required.
When transporting the inverter, the original or equivalent packaging should be used, and
the maximum layers for original carton is four, as this ensures safe transport. Risk of burns due to hot enclosure parts.
Mount the inverter in such a way that it cannot be touched
After opening the package, please check the contents of the box. It should contain the inadvertently.
following, Please check all of the accessories carefully in the carton. If anything missing,
contact your dealer at once. Possible damage to health as a result of the effects of radiation!
ØIn special cases, there may still be interference for the specified
application area despite maintaining standardized emission limit
values (e.g. when sensitive equipment is located at the setup location
or when the setup location is near radio or television receivers).In this
case, the operator is obliged to take proper action to rectify the
situation.
ØNever install the inverter near the sensitive equipment (e.g. Radios,
telephone, television, etc).
ØDo not stay closer than 20 cm to the inverter for any length of time
unless it is absolutely necessary.
ØGrowatt assumes no responsibility for compliance to EMC
regulations for the complete system.

Ø All electrical installations shall be done in accordance with the local and national
electrical codes. Do not remove the casing. Inverter contains no user serviceable
parts. Refer servicing to qualified service personnel. all wiring and electrical
installation should be conducted by a qualified service personnel .
Object Description Quantity Ø Carefully remove the unit from its packaging and inspect for external damage. If you
A Inverter 1 find any imperfections, please contact your local dealer.
Ø Be sure that the inverters connect to the ground in order to protect property and
B Mounting bracket 1 personal safety.
C Quick Guide 1 Ø The inverter must only be operated with PV generator. Do not connect any other
source of energy to it.
D Monitor(Optional) 1
Ø Both AC and DC voltage sources are terminated inside the PV Inverter. Please
COM PORT Signal connector 1 disconnect these circuits before servicing.
E Ø This unit is designed to feed power to the public power grid (utility) only. Do not
SYS COM PORT Signal connector 1 connect this unit to an AC source or generator. Connecting Inverter to external
F Self-tapping screws 3 devices could result in serious damage to your equipment.
Ø When a photovoltaic panel is exposed to light, it generates a DC voltage. When
G Safety-lock screw 1 connected to this equipment, a photovoltaic panel will charge the DC link
H Plastic expansion pipe 3 capacitors.
Ø Energy stored in this equipment's DC link capacitors presents a risk of electric
I PV+/PV- terminal 2/2 shock. Even after the unit is disconnected from the grid and photovoltaic panels,
J PV+/PV-metal terminal 2/2 high voltages may still exist inside the PV-Inverter. Do not remove the casing until at
least 5 minutes after disconnecting all power sources.
K AC connector 1 Ø Although designed to meet all safety requirements, some parts and surfaces of
L Uninstall signal or AC connector tool 1 Inverter are still hot during operation. To reduce the risk of injury, do not touch the
heat sink at the back of the PV-Inverter or nearby surfaces while Inverter is
M Uninstall PV terminal tool 1 operating.
11 12
5.2 Selecting the installation location
Ø This is guidance for installer to choose a suitable installation location, to avoid
potential damages to device and operators.
Ø The installation location must be suitable for the inverter's weight and dimensions
for a long period time.
Ø Select the installation location so that the status display can be easily viewed.
Ø Do not install the inverter on structures constructed of flammable or thermolabile
materials.
Ø Never install the inverter in environment of little or no air flow, nor dust
environment. That may derate the efficiency of the cooling fan of the inverter.
Ø The Ingress Protection rate is IP65 which means the inverter can be installed
outdoors and indoors.
Ø The humidity of the installation location should be 0~100% without condensation.
Ø The installation location must be freely and safely to get at all times.
Ø Vertically installation and make sure the connection of inverter must be downwards.
Never install horizontal and avoids forward and sideways tilt.

Ambient dimensions of one inverter Ambient dimensions of series inverters

Ø There must be sufficient clearance between the individual inverters to ensure that
the cooling air of the adjacent inverter is not taken in.
Ø If necessary, increase the clearance spaces and make sure there is enough fresh air
supply to ensure sufficient cooling of the inverters.

The inverter can't install to solarization,drench,firn location. We suggest that the


inverters should be installed at the location with some cover or protection.

Ø Be sure that the inverter is out of the children's reach.


Ø Don't put any things on the inverter. Do not cover the inverter.
Ø Do not install the inverter near television antenna or any other antennas and
antenna cables.
Ø Inverter requires adequate cooling space. Providing better ventilation for the
inverter to ensure the heat escape adequately. The ambient temperature should be
below 40°C to ensure optimum operation.
Ø Do not expose the inverter to direct sunlight, as this can cause excessive heating and
thus power reduction.
Ø Observe the Min. clearances to walls, other inverters, or objects as shown below:
13 14
Ø Please make sure the inverter is installed at the right place.The inverter can't install 5.3.2 Fixed the inverter on the wall
close to trunk.
Falling equipment can cause serious or even fatal injury, never
mount the inverter on the bracket unless you are sure that the
mounting frame is really firmly mounted on the wall after carefully
checking.
WARNING

Ø Rise up the inverter a little higher than the bracket. Considered the weight of
them.During the process please maintain the balance of the inverter.
Hang the inverter on the bracket through the match hooks on bracket.

5.3 Mounting the Inverter


5.3.1 Mounting the Inverter with bracket

In order to avoid electrical shock or other injury, inspect existing


electronic or plumbing installations before drilling holes.
DANGER

Ø  After confirming the inverter is fixed reliably, fasten one M6 safety-lock sockets
head cap screws on the right or left side firmly to prevent the inverter from being
lifted off the bracket.

Ÿ Fix the mounting bracket as the figure shows. Do not make the screws to be flush to
the wall. Instead, leave 2 to 4mm exposed.

15 16
6 Electrical connection
Decisive Voltage Class (DVC) indicated for ports
The AC wiring step:
Port Name Class
1.Uninstall the parts of the AC connection plug from the accessory bag.
AC Output C
DC Input C

COM&SYS COM Port A

RS485&USB A

6.1 Safety
Danger to life due to lethal voltages!
High voltages which may cause electric shocks are present in the
conductive parts of the inverter. Prior to performing any work on
the inverter, disconnect the inverter on the AC and DC sides

Danger of damage to electronic components due to electrostatic


discharge.
Take appropriate ESD precautions when replacing and installing
the inverter.
WARNING

2.Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve
in sequence, insert cables into connection terminal according to polarities indicates on
6.2 Wiring AC Output it and tighten the screws firmly. Please try to pull out the wire to make sure the it’s well
connected.
Ø You must install a separate single-phase circuit-breaker or other
load disconnection unit for each inverter in order to ensure that
the inverter can be safely disconnected under load.
NOTE :
The inverter has the function of detecting residual current and
protecting the inverter against residual current. If your inverter has to
WARNING equip a AC breaker which has the function of detecting residual
current ,you must choose a AC breaker with the rating residual current
more than 300mA.

You must install a separate single-phase circuit-breaker or other load disconnection unit
for each inverter in order to ensure that the inverter can be safely disconnected under
load.
We suggest you choice the AC breaker rating current in this table:
MIN 2500 TL-XE 16A/230V
MIN 3000 TL-XE 16A/230V
MIN 3600 TL-XE 20A/230V
MIN 4200 TL-XE 25A/230V
MIN 4600 TL-XE 25A/230V
MIN 5000 TL-XE 32A/230V
MIN 6000 TL-XE 32A/230V
17 18
3.Push the threaded sleeve into the socket, Tighten up the cap on the terminal. 5.To remove the AC connector, press the bayonet out of the slot with a small screwdriver
and pull it out,or unscrew the threaded sleeve,then pull it out.

4.Finally, Push or screw the threaded sleeve to connection terminal until both are locked
tightly on the inverter.

Wire suggestion length

Max. cable length


Conductor cross
section
MIN 2500 TL-XE MIN 3000 TL-XE MIN 3600 TL-XE

4 mm² 12AWG 48m 40m 33m

5.2 mm² 10AWG 60m 50m 42m

Max. cable length


Conductor cross
section MIN 4200 TL-XE
MIN 4600 TL-XE MIN 5000 TL-XE MIN 6000 TL-XE

5.2 mm² 10AWG 28m 26m 24m

19 20
6.3 Connecting the second protective conductor
If the inverter is not equipped with a DC switch but this is mandatory in
In some installation countries, a second protective conductor is required to prevent a the country of installation, install an external DC switch.
touch current in the event of a malfunction in the original protective conductor.For The following limit values at the DC input of the inverter must not be
installation countries falling within the scope of validity of the IEC standard 62109, you exceeded:
must install the protective conductor on the AC terminal with a conductor cross-section
of at least 10 mm²Cu.Or Install a second protective conductor on the earth terminal with Types Max current PV1 Max current PV2 Max voltage
the same cross-section as the original protective conductor on the AC terminal. This CAUTION 2500-3000 TL-XE 12.5A 12.5A 500V
prevents touch current if the original protective conductor fails.
3600-6000 TL-XE 12.5A 12.5A 550V

It is suggestiong that connecting eleven PV modules that have an IEC


61730 Class A rating in series as one PV input.

6.4.2 Connecting the PV Array

Danger to life due to lethal voltages!


Before connecting the PV array, ensure that the DC switch and AC
breaker are disconnect from the inverter. NEVER connect or
disconnect the PV connectors under load.
Make sure the maximum open circuit voltage(Voc) of each PV string
is less than the maximum input voltage of the inverter.
DANGER Check the design of the PV plant. The Max. open circuit voltage, which
can occur at solar panels temperature of -10℃ , must not exceed the
Max. input voltage of the inverter.

Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified
personnel can perform the wiring work.
Please don’t connect PV array positive or negative pole to the ground,
6.4 Connecting the PV Array it could cause serious damages to the inverter
Check the connection cables of the PV modules for correct polarity and
6.4.1 Conditions for PV Array WARNING make sure that the maximum input voltage of the inverter is not
exceeded.
The MIN TL-XE single-phase inverter has 2 independent PV input : PV1 & PV2 Notice that
the connectors are in paired (male and female connectors). The connectors for PV arrays
and inverters are VP-D4/MC4 connectors; Connection of PV terminal

21 22
Step 2 Push the threaded sleeve into the socket, Tighten up the cap on the terminal.

Step 3 Push the threaded sleeve to connection terminal until both are locked tightly on
the inverter.

6.5 Connecting signal cable


This series inverter has two 8 Pin signal connectors,one is COM PORT connector,another
is SYS COM PORT connector. Signal Cable Ports as follows:
Uninstall signal connector

Step 1 Press the fasteners and pull it out from the inverter.

Procedure
Step 1 Insert the stripped and bared cable through pressure screw, seal ring, threaded
sleeve in sequence, insert cables into connection terminal according to number indicates
on it and tighten the screws firmly. Please try to pull out the wire to make sure the it's
well connected. Step 2 Insert the H type tool and pull it out from the socket.

23 24
6.6 Grounding the inverter 6.8 Connecting the COM PORT
The inverter must be connected to the AC grounding conductor of the power This series inverter has a 8 Pin COM PORT, this port has the function fo demand response
distribution grid via the ground terminal (PE) . modes, for Australian mode, we can use the 8 Pin COM PORT as inverter DRED
connection, for European modes, we can use the 8 Pin COM PORT as Power Control
Interface(PCI).
Because of the transformerless design, the DC positive pole and DC
negative pole of PV arrays are not permitted to be grounded.
6.8.1 Inverter demand response modes-DRMs(Australia only)
WARNING This series inverter has the function of demand response modes, We use 8Pin COM PORT
as inverter DRED connection.

6.7 Active power control with smart meter , CT or ripple control DRMS application description
signal receiver Ø Only applicable to AS/NZS4777.2:2015.
Ø DRM0-DRM8 are available.
Information

The position of export limitation CT or Meter must between the


Inverter & Load and gird. Damage to the inverter due to moisture and dust penetration
Information Ø Make sure the cable gland has been tightened firmly.
Ø If the cable gland are not mounted properly, the inverter can
CAUTION be destroyed due to moisture and dust penetration. All the
This series inverter has integrated export limitation functionality. To use this function, warranty claim will be invalid.
you can connect smart meter or CT. The smart meter model is Eastron SDM230-Modbus.
The CT Model is TOP 90-S10/SP4(LEM).The primary aperture is 10mm,output cable
length is 5m . The arrow on the CT must pointing towards the inverter,System
6.8.1.1 8Pin socket pin assignment
connection block diagram is as follows:

Pin Assignment for inverters capable


of both charging and discharging
1 +12V
2 GND
3 DRM 1/5
4 DRM 2/6
5 DRM 3/7
6 DRM 4/8
Active power control with a Radio Ripple Control Receiver(RRCR). 7 RefGen
8 Com/DRM0

25 26
6.8.1.2 Method of asserting demand response modes 6.8.2.1 The connector pin assignment and function definition

Socket Asserted by Requirement Pin Description Connect to RRCR


Mode
shorting pins
1 +12V
DRM 0 7 8 Operate the disconnection device Not connected
2 GND
DRM 1 3 8 NA
3 Relay contact 1 input K1 – Relay 1 output
DRM 2 4 8 NA
4 Relay contact 2 input K2 – Relay 2 output
DRM 3 5 8 NA
5 Relay contact 3 input K3 – Relay 3 output
DRM 4 6 8 NA
6 Relay contact 4 input K4 – Relay 4 output
DRM 5 3 7 Do not generate power
DRM 6 4 7 Do not generate at more than 50% of rated power 7 GND Relays common node

DRM 7 5 7 Do not generate at more than 75% of rated power 8 Not connected Not connected

Increase power generation (subject to constraints from


DRM 8 6 7
other active DRMs)
6.8.2.2 The inverter is preconfigured to the following RRCR power levels

PCI Connector(SYS COM PORT)


Active power Cos(φ)
6.8.2 Inverter demand response modes-Power Control Interface(PCI) for EU Pin 3 Pin 4 Pin 5 Pin 6
Short circuit
This series inverter has the function of demand response modes, We use 8Pin COM PORT 0% 1
with Pin7
as Power Control Interface(PCI) for European models.
Short circuit
30% 1
with Pin7
Short circuit 1
60%
with Pin7
Excessive voltage can damage the inverter!
External voltage of PCI PORT don't over +5V. Short circuit
100% 1
with Pin7
WARNING
Active power control and reactive power control are enabled separately

6.9 Electric arc hazards


6.9.1 Arc-Fault Circuit Interrupter(AFCI)

In accordance with the National Electrical Code R, Article 690.11, the inverter has
asystem for the recognition of electric arc detection and interruption. An electric arc
with a power of 300 W or greater must be interrupted by the AFCI within the time
specified by UL 1699B. A tripped AFCI can only be reset manually. You can deactivate
the automatic arc fault detection and interruption (AFCI) via a communication product
in "Installer" mode if you do not require the function. The 2011 edition of the National
Electrical Code R, Section 690.11 stipulates that newly installed PV systems attached to
a building must be fitted with a means of detecting and disconnecting serial electric
arcs (AFCI) on the PV side.
27 28
6.9.2 Danger information If the AFCI self-test is successful, the inverter will switch into the “nominal” mode and
the green LED is permanently lit.
If the AFCI self-test is failed, the following message appears on the display: “Error 425”,
Danger of fire from electric arc
please restart the system, repeat step1 to step3.If the AFCI self-test continues to fail,cut
Only test the AFCI for false tripping in the order described below. off all power supply connection of the inverter,and contact Growatt to solve this
problem.
Do not deactivate the AFCI permanently.

The inverter has double MPPTs, it is recommended for each MPPT to work independently,
do not use parallel wiring at DC side (Parallel wiring can make 2 MPPTs become 1 MPPT,
this can improve the efficiency in some cases). If the MPPTs are parallel wired at inverter it
may cause the AFCI trigger mistakenly.
If an "Error 200" message is displayed, the red LED is permanently lit and the buzzer
alarms, an electric arc occurred in the PV system. The AFCI has tripped and the inverter is
in permanent shutdown.
The inverter has large electrical potential differences between its conductors. Arc flashes
Commissioning 7
can occur through air when high-voltage current flows. Do not work on the product
during operation.

6.9.3 Operation step


Do not disconnect the PV connectors under load.
When the inverter error 200, please follow the steps:
DANGER
Step1: Cut off all power supply connection of the inverter. Turn off the inverter's AC
output breaker, Turn the inverter's PV input DC Switch to position “OFF”, wait for the
display to go out;
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified
personnel can perform the wiring work.
WARNING

Damage to the inverter due to moisture and dust penetration


Ø Make sure the cable gland has been tightened firmly.
Ø If the cable gland are not mounted properly, the inverter can be
destroyed due to moisture and dust penetration. All the warranty
CAUTION claim will be invalid.

Step2: Perform troubleshooting on the system, Check all PV strings for the correct open-
Requirements:
circuit voltage;
Step3: After the fault is rectified, restart the inverter. Turn on the the inverter's AC output ü The AC cable is correctly connected.
breaker, turn the inverter's PV input DC Switch to position “ON”, Waiting for the system ü The PV connectors are correctly connected.
to work properly; ü The country is set incorrectly.

29 30
7.1 Start the inverter 7.2 General setting
7.1.1 Touch control 7.2.1 Set inverter display language
This series inverter provides multi languages. Single touch to select different
Touch Description
language.Double touch to confirm the setting.Set the language as described below:
Single touch Switch display or Number +1
Double
Double touch Enter or confirmation Language touch Language Double touch
Set OK
English English
Three touch Previous menu
Single touch
Double
Confirm Country/Aera or recover touch
Hold 5s
defaut value
General Language Double touch

Advanced German

7.1.2 Set Country/Area


Single touch
Double
touch
Country setting
Language Double touch

Ø Before starts up the inverter, we need to select the right Set Parameter Spanish
Country/Area,if we don't select any Country/Area, the inverter will
run under AS/NZS4777.2 as default for Australia,or run under
Information VDE0126-1-1 for other region after 30s. Multiple single
touch

When inverter powered on, OLED will light automatically. Once the PV power is Language Double touch

sufficient, OLED displays “PV Inverter”,Press the touch key once a second to scroll French
through the different Country, showing on the screen will constantly change.For
example, if you want to choose Germany, press the touch key until the OLED display
shows “VDE0126” ,Press the touch key twice in succession, the OLED shows 7.2.2 Set inverter COM address
Country/Area setting is complete.
The default COM address is 1.We can change COM address as described below:Single
Double touch
touch to switch display or make the number +1.Double touch to confirm the setting. Set
Growatt Country/Area
PV Inverter VDE0126
Set OK inverter COM address as described below:

Single touch Double touch Double touch Double touch


Double touch
Address Address Address Address
Set OK
001 001 00N 0NN
Country/Area Double touch
Single Single Double touch Single Double touch
Single touch Double touch
G99 touch touch touch

Language Address Address Address


Multiple single
English 002 01N 1NN
touch
Double touch
Double touch
Multiple Multiple Multiple
Country/Area Double touch General single touch Double touch
single touch
Double touch single touch

N4105 Advanced

Double touch Address Address Address


00N 0NN NNN
Set Parameter

31 32
7.3 Advanced setting
7.2.3 Set inverter date 7.3.1 Reset Country/Area
Single touch make the number up.Double touch to confirm the setting. Single touch to switch display or make the number +1.Double touch to confirm the
Set inverter date as described below: setting.The password of advanced setting is 123.
Double touch
Double touch Double touch Double touch Country/Area Country/Area Double touch
Date Setting Double touch
Date Setting Date Setting Date Setting Set OK
2019-04-18 2019-04-18 20NN-04-18 20NN-NN-18
Set OK VDE0126 VDE0126
Single touch Single Single Single
touch touch touch
Single touch
Address Double touch
001 Date Setting Date Setting Date Setting
2020-04-18 20NN-05-18 20NN-NN-19
Single touch
Password Country/Area Double touch

Language Multiple Multiple Multiple 123 G99


single touch Double touch single touch Double touch single touch
English
Multiple single
Double touch touch
Date Setting Date Setting Date Setting Double touch
General 20NN-04-18 20NN-NN-18 20NN-NN-NN
Advanced
General Country/Area Double touch

Double touch Advanced N4105

Set Parameter

7.3.2 Export limitation setting


The –XE series inverters can work in anti-backflow mode through external power meter
7.2.4 Set inverter time or CT,the user can set the percentage of power allowed to flow backward through the
OLED, Single touch to switch display or make the number +1.Double touch to confirm
Single touch make the number up.Double touch to confirm the setting. the setting, as described below:
Set inverter time as described below: ExportLimit Double touch
ExportLimit
Double touch

OFF ON Set OK
OFF ON
Multiple single
Double touch Double touch Double touch touch Single touch
Double touch Time Setting Time Setting
Time Setting Time Setting
Set OK Double touch
20:05:00 20:05:00 NN:05:00 NN:NN:00 ExportLimit ExportLImit Rate
Double touch
Country/Aera
Single Single Single VDE0126 OFF ON 000.0%
Single touch touch Double touch touch touch

Double touch Double touch Single


Date Setting Time Setting Time Setting Time Setting Double touch touch

2019-04-18 21:05:00 NN:06:00 NN:NN:01 Double touch


Password Meter ExportLImit Rate
Single touch
123 CT 100.0%
Multiple Multiple Multiple
Address single touch Double touch single touch Double touch single touch Single
001 Double touch touch
Double touch

Time Setting Time Setting Time Setting


Single touch General Meter
NN:05:00 NN:NN:00 NN:NN:NN
Advanced CT
Language
English

Double touch Double touch Double touch


General
ExportLImit Rate ExportLImit Rate ExportLImit Rate
Advanced Set OK
000.0% 0N0.0% 0NN.0%
Single Single Single
touch Double touch Double touch Double touch
touch touch

Set Parameter
ExportLImit Rate ExportLImit Rate ExportLImit Rate
010.0% 0N1.0% 0NN.1%

Multiple single Multiple single Multiple single


touch Double touch touch touch
Double touch Double touch

ExportLImit Rate ExportLImit Rate ExportLImit Rate


33 0N0.0% 0NN.0% 0NN.N%
34
7.3.3 Reset factory 7.4.2 COM Port
TL-XE series inverter provides a 8 pin COM Port connector, The COM Port connector
Perform this operation with caution because all configured parameters signal distribution and function, please refer to section 6.9.
except the current date,time, and model parameters will be restored to
their factory defaults. 7.4.3 USB-A
Information
USB-A port is mainly for connecting monitor or firmware updage:
Single touch to switch display or make the number +1.Double touch to confirm the Through USB connection,we can connect external optional monitor ,for example :Shine
setting. WIFI-X,Shine 4G-X, Shine LAN-X,ect.
And also you can quickly update the software by U disk.
Double touch Double touch
We can monitor as below:
General Reset Factory
NO
Set OK Make sure the △ on the front side, then insert the monitor,fasten the screw.
Advanced YES

Double touch Multiple single


touch Single touch Double touch

Double touch
Password Country/Aera NO
123 VDE0126 YES
Double touch

7.4 Communication interfaces


7.4.1 SYS COM Port

TL-XE series inverter provides a 8 pin SYS COM Port


connector,.The SYS COM Port connector signal
distribution and function are shown in the following
table:

No. Definition Description No. Definition Description


Connect smart meter
1 / / 5 AntiReFlux_A RS485A or External CT
signal positive
Connect smart meter
2 / / 6 AntiReFlux_B RS485B or External CT
signal negative

/ /
3 485A2 7
Connect Min
ShineBus
/ /
4 485B2 8

35 36
8 Start-Up and shut down the inverter EU Declaration of Conformity 10
8.1 Start-Up the inverter
1. Connect the AC breaker of the inverter. With the scope of EU directives:
2.Turn on the dc switch, and the inverter will start automatically when the input voltage •2014/35/EU Low Voltage Directive (LVD)
is higher than 70 V. •2014/30/EU Electromagnetic Compatibility Directive (EMC)
•2011/65/EU RoHS Directive and its amendment (EU)2015/863
Shenzhen Growatt New Energy Technology Co. Ltd confirms that the Growatt inverters
and accessories described in this document are in compliance with the above mentioned
8.2 Shut down the Inverter EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com.

Do not disconnect the PV connectors under load.

DANGER

Shut down the inverter step:


1. Disconect the line circuit breaker from single-phases grid and prevent it from being
reactivated.
Trouble shooting 11
2. Turn off the inverter's DC switch.
3. Check the inverter operating status. Our quality control program assures that every inverter is manufactured to accurate
4. Waiting until LED, OLED have go out, the inverter is shut down. specifications and is thoroughly tested before leaving our factory. If you have difficulty in
the operation of your inverter, please read through the following information to correct
the problem.

11.1 Error Messages displayed on OLED


An error message will be displayed on the OLED screen when a fault occurs. The faults
9 Maintenance and Cleaning consist of system fault and inverter fault.
You may be advised to contact Growatt in some situation, please provide the following
information.
Information concerning the inverter:
9.1 Checking Heat Dissipation Ÿ Serial number
If the inverter regularly reduces its output power due to high temperature, please Ÿ Model number
improve the heat dissipation condition. Maybe you need to clean the heat sink. Ÿ Error message on OLED
Ÿ Short description of the problem
Ÿ Grid voltage
9.2 Cleaning the Inverter Ÿ DC input voltage
If the inverter is dirty, turn-off the AC breaker and DC switch, waiting the inverter shut Ÿ Can you reproduce the failure? If yes, how?
down ,then clean the enclosure lid, the display, and the LEDs using only a wet cloth. Do Ÿ Has this problem occurred in the past?
not use any cleaning agents (e.g. solvents or abrasives). Ÿ What was the ambient condition when the problem occurred?

Information concerning the PV panels:


9.3 Checking the DC Disconnect
Ÿ Manufacturer name and model number of the PV panel
Check for externally visible damage and discoloration of the DC Disconnect and the Ÿ Output power of the panel
cables at regular intervals.If there is any visible damage to the DC Disconnect, or visible Ÿ Voc of the panel
discoloration or damage to the cables, contact the installer. Ÿ Vmp of the panel
Ø Once a year, turn the rotary switch of the DC Disconnect from the On position to the Ÿ Imp of the panel
Off position 5 times in succession. This cleans the contacts of the rotary switch and Ÿ Number of panels in each string
prolongs the electrical endurance of the DC Disconnect.
If it is necessary to replace the unit, please ship it in the original box.

37 38
11.2 System fault 11.3 Inverter warning
System fault (system faults are mainly caused by system instead of inverter, please check
the items as instructed below before replacing inverter). Warning code Meanings Suggestion

1.Check the PV panel polarity.


Error message Description Suggestion 2.Restart the inverter. If the warning
Warning 203 PV1 or PV2 Circuit short still exist, please contact Growatt
1.Restart the invert. customer service to replace the
Residual I High
Leakage current too high 2. If error message still exists, contact POWER board.
Error: 201
Growatt.
1.After shutdown,Check the dry
1. Disconnect the DC switch Warning204 Dryconnect function abnormal Dryconnect wiring.
2.If the error message still exists,
immediately.
The DC input voltage is contact manufacturer.
PV Voltage High 2. Check the voltage of each PV string
exceeding the maximum
Error: 202 with multimerter. 1.Restart the inverter. If the warning
tolerable value.
3. If the voltage of PV string is lower than still exist, please contact Growatt
Warning 205 PV1 or PV2 boost broken
550V, contact Growatt. customer service to replace the power
board.
1. Check if panel enclosure ground
1.Unplug the U disk or monitor.
properly.
2.Re-access U disk or monitor after
2. Check if inverter ground properly.
Warning207 USB over-current shutdown.
3. Check if the DC breaker gets wet.
PV Isolation Low 3.If the error message still exists,
Insulation problem 4. Check the impedance of PV (+) & PV (-)
Error: 203 contact manufacturer.
between ground (must be more than 25
KΩ or 550 KΩ (VDE 0126) . If the error 1.Check if the meter is on.
message is displayed despite the above Inverter communicates
Warning 401 2.Check the inverter and the meter
checking passed, contact Growatt. with Meter abnormal
connection is normal .
1.Restart the inverter. If the warning
AC V Outrange Utility grid voltage is out Utility grid voltage is out of permissible
still exist, please contact Growatt
Error: 300 of permissible range. range. Warning404 EEPROM abnormal customer service to replace the M3
board.
No AC
1.Check AC wiring.
connection No AC connection Firmware version is not
2.Check the status of AC breaker Warning405 1.Uptate the right version firmware
Error: 302 consistent

1.Check the voltage of Neutral and PE.


PE abnormal Voltage of Neutral and PE 2.Check AC wiring.
Error: 303 above 30V. 3.Restart inverter, if error message still
exisits,contact Manufacturer

1.Please switch off DC switch.


2.Check AC wiring, especially neutral
AC F Outrange Utility grid frequency out and ground wire.
Error: 304 of permissible range. 3.Check grid frequency is complied with
local grid standard. 4.Restart inverter, if
problem still exist, Contact Growatt.

Auto Test Failed 1.Restart inverter, repeat Auto Test, if


Auto test didn't pass.
Error: 407 problem still exist, contact Growatt.

39 40
Decommissioning 13
11.4 Inverter fault 13.1 Dismantling the Inverter
1. Disconnect the inverter as described in section.
Error code Meanings Suggestion 2. Remove all connection cables from the inverter.

Error: 402 Output High DCI 1.Restart inverter, if problem still exist, Danger of burn injuries due to hot enclosure parts!
Contact Growatt. Wait 20 minutes before disassembling until the housing has cooled down.
1.Restart inverter, if problem still exist, CAUTION
Error: 404 Bus sample fault
Contact Growatt.
3. Screw off all projecting cable glands.
Relay fault 1.Restart inverter, if problem still exist, 4. Lift the inverter off the bracket and unscrew the bracket screws.
Error: 405
Contact Growatt.
1.If the ambient temperature of inverter is
Error: 408 Over Temperature lower than 60°C, restart inverter, if error 13.2 Packing the Inverter
message still exists, contact Growatt.
1.Restart inverter, if problem still If possible, always pack the inverter in its original carton and secure it with tension belts.
Error: 409 Bus over voltage If it is no longer available, you can also use an equivalent carton. The box must be
exist, Contact Growatt.
capable of being closed completely and made to support both the weight and the size of
1.Restart inverter, if problem still exist, the inverter.
DSP communicates with update the DSP&M3 firmware;
Error: 411
M3 abnormal 2.Change DSP board or M3 board, if
problem still exist, contact Growatt.
13.3 Storing the Inverter
Error: 414 1.Restart inverter,if problem still exist,
EEPROM fault.
contact Growatt.
Store the inverter in a dry place where ambient temperatures are always between -25°C
and +60°C.
The data sampled by the
Error: 417 DSP and redundant M3 is 1.Restart inverter,if problem still exist,
not the same. contact Growatt.

1.Restart inverter,if problem still exist, 13.4 Disposing of the Inverter


Error: 420 GFCI fault.
contact Growatt.
Do not dispose of faulty inverters or accessories together with household
waste. Please accordance with the disposal regulations for electronic waste
which apply at the installation site at that time. Ensure that the old unit and,
where applicable, any accessories are disposed of in a proper manner.

12 Manufacturer Warranty
Please refer to the warranty card.

41 42
14 Technical Data
14.1 Specification

Model 2500 3000 3600 4200 Model 2500 3000 3600 4200
Specifications TL-XE TL-XE TL-XE TL-XE Specifications TL-XE TL-XE TL-XE TL-XE

Input data (PV) Protection devices


Max. recommended PV PV reverse-polarity protection Integrated
power(for module STC) 3500W 4200W 5040W 5880W
PV input switch Integrated
Max. PV voltage 500V 550V
PV surge protection Type II
Start voltage 100V
Insulation resistance
Nominal voltage 360V Integrated
monitoring
MPP voltage range 80-500V 80-500V 80-550V 80-550V
AC surge protection Type III
MPP voltage range at Full AC short-circuit protection Integrated
100V-450V 120V-450V 150V-500V 170V-500V
Power
Ground fault monitoring Integrated
No. of MPP trackers 2
Grid monitoring Integrated
No. of PV strings per MPP
1 Anti-islanding protection Integrated
trackers
Max. input current per MPP Residual-current monitoring
Integrated
trackers 12.5A unit
Max. short-circuit current per General data
16A
MPP trackers Dimensions (W / H / D) in mm 375*350*160
PV overvoltage category Category II Weight 10.8 kg
Output data (AC Grid) Operating temperature range –25 °C ... +60 °C
AC nominal power Noise emission (typical) ≤ 25 dB(A)
2500W 3000W 3600W 4200W
Altitude 2000m
Max. AC apparent power 2500VA 3000VA 3600VA 4200VA
Internal consumption at night <1W
Nominal AC voltage 230V
Topology transformerless
AC voltage range 160-276V
Cooling Natural convection
Norminal AC grid frequency 50/60Hz Protection degree IP65
AC grid frequency range 45-55Hz/55-65Hz Pollution degree outside the
Max. output current 11.3A 13.6A 16A 19A enclosure 3
Inrush current <10A Pollution degree inside the
enclosure 2
Max. output fault current 60A
Max.output overload Relative humidity 0~100%
protection 16A 16A 20A 25A
DC connection VP-D4/MC4(Optional)
Backfeed current 0A AC connection AC connector
Power factor(@nominal power) >0.99
Interfaces
Adjustable power factor 0.8leading… 0.8lagging
THDi Display OLED+LED
<3%
AC grid connection type Single phase(L/N/PE) RS485/USB Integrated
AC overvoltage category Category III WIFI/GPRS/4G/LAN/ RF Optional
Efficiency
Warranty:5/10 years Yes/ Optional
Max. efficiency 98.2% 98.2% 98.2% 98.4%
Euro-eta 97.1% 97.1% 97.2% 97.2%
43 44
Model 4600 5000 6000 Model 4600 5000 6000
TL-XE TL-XE TL-XE TL-XE TL-XE TL-XE
Specifications Specifications
Input data (PV) Protection devices
Max. recommended PV PV reverse-polarity protection Integrated
power(for module STC) 6400W 7000W 8100W
PV input switch Integrated
Max. PV voltage 550V PV surge protection Type II
Start voltage 100V Insulation resistance
Integrated
Nominal voltage 360V monitoring
MPP voltage range 185-550V 80-550V 80-550V AC surge protection Type III
MPP voltage range at Full AC short-circuit protection Integrated
Power 185V-500V 200V-500V 240V-500V
Ground fault monitoring Integrated
No. of MPP trackers 2 Grid monitoring Integrated
No. of PV strings per MPP
1 Anti-islanding protection Integrated
trackers
Residual-current monitoring
Max. input current per MPP Integrated
12.5A unit
trackers
Max. short-circuit current General data
per MPP trackers 16A Dimensions (W / H / D) in mm 375*350*160
PV overvoltage category Category II Weight 10.8 kg
Output data (AC) Operating temperature range –25 °C ... +60 °C
4600W 5000W 6000W Noise emission (typical) ≤ 25 dB(A)
AC nominal power
Max. AC apparent power Altitude 2000m
4600VA 5000VA 6000VA
Internal consumption at night <1W
Nominal AC voltage 230V
Topology transformerless
AC voltage range 160-276V
Cooling Natural convection
Nominal AC grid frequency 50/60Hz Protection degree Ip65
AC grid frequency range 45-55Hz/55-65Hz
Pollution degree outside the
Max. output current 20.9A 22.7A 27.2A 3
enclosure
Inrush current <10A Pollution degree inside the
2
Max. output fault current 60A enclosure
Max.output overload Relative humidity 0~100%
25A 32A 32A
protection DC connection VP-D4/MC4(Optional)
Backfeed current 0A AC connection AC connector
Power factor(@nominal Interfaces
>0.99
power)
Display OLED+LED
Adjustable power factor 0.8leading… 0.8lagging
RS485/USB Integrated
THDi <3%
WIFI/GPRS/4G/LAN/ RF Optional
AC grid connection type Single phase(L/N/PE)
Warranty:5/10 years Yes/ Optional
AC overvoltage category Category III
Efficiency * The AC Voltage Range may vary depending on specific country grid standard.
All specifications are subject to change without notice.
Max. efficiency 98.4%
Euro-eta 97.5%

45 46
Compliance Certificates 15
14.2 PV&AC connectors info  ertificates
C
With the appropriate settings, the unit will comply with the requirements specified in the
PV connectors VP-D4/ MC4 (opt) following standards and directives (dated: April./2019):

M-S30_SD03_S10 001U-A
AC connector VPAC06EP-3S(SC)5 Model Certificates
VPAC06EW-3P(SC)
CE , IEC 62109, IEC62040,G98,G99,TUV, CEI0-21, EN50438,
2500-6000TL-XE
VDE0126,VDE-AR-N4105,IEC62116,IEC61727

14.3 Torque

Enclosure lid screws 0.7N.m

AC terminal 0.6N.m

Signal terminal 0.4N.m

M6 soket head cap screws


for securing the enclosure at
the bracket
2N.m Contact 16
Additional ground screws 2N.m If you have technical problems about our products, contact the GROWATT Serviceline.
We need the following information in order to provide you with the necessary assistance:
Ø Inverter type
Ø Serial number of the inverter
Ø Event number or display message of the inverter
14.4 Accessories Ø Type and number of PV modules connected
Ø Optional equipment
In the following table you will find the optional accessories for your product. If required,
you can order these from GROWATT NEW ENERGY TECHNOLOGY CO.,LTD or your dealer.

Name Brief description


Shine WIFI-X WIFI monitor with USB interface
Shine 4G-X 4G monitor with USB interface
Shine RF-X RF monitor with USB interface
Shine LAN-X LAN monitor with USB interface
RS 485 Meter External energy meter for inverter
CT External CT for inverter

Shipped to a Growatt service centre for repair, or repaired on-site, or exchanged for a Shenzhen Growatt New Energy Technology CO.,LTD
replacement device of equivalent value according to model and age. No.28 Guangming Road, Shiyan Street, Bao’an District,
The warranty shall not cover transportation costs in connection with the return of Shenzhen, P.R.China
defective modules . The cost of the installation or reinstallation of the modules shall also
be expressly exclude as are all other related logistical and process costs incurred by all T +86 755 2747 1942
parties in relation to this warranty claim. E [email protected]
W www.ginverter.com

47 48

You might also like