Manual Multiranger en
Manual Multiranger en
multiranger
100/200
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
others, and to protect the product and the connected equipment. These warning notices are
accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with
established safety practices and standards.
Unit Repair and Excluded Liability:
• The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
• All new components are to be provided by Siemens Milltronics Process Instruments Inc.
• Restrict repair to faulty components only.
• Do not reuse faulty components.
Warning: This product can only function properly and safely if it is correctly transported, stored,
installed, set up, operated, and maintained.
Technical Publications
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: [email protected]
Table of Contents
The MultiRanger 100 and 200 ...............................................................................................................1
mmmmm
MultiRanger 100 ............................................................................................................................1
MultiRanger 200 ............................................................................................................................1
The Manual ...............................................................................................................................................1
Manual Symbols ............................................................................................................................2
Configuration Examples ...............................................................................................................2
Specifications ...............................................................................................................................................3
Installation ......................................................................................................................................................8
Mounting ...................................................................................................................................................8
Mounting Locations ......................................................................................................................8
Mounting Instructions ..................................................................................................................9
Wall Mount ........................................................................................................................... 9
Cable routed through a conduit: .................................................................................... 10
Panel Mount ....................................................................................................................... 11
Mounting the Enclosure .................................................................................................. 12
MultiRanger Board .....................................................................................................................13
Installing the Battery ..................................................................................................................13
Installing SmartLinx Card ..........................................................................................................14
Wiring ..............................................................................................................................................................15
Terminal Board .......................................................................................................................................16
Cables .......................................................................................................................................................16
Transducers ............................................................................................................................................17
Relays .......................................................................................................................................................17
Temperature Sensor .............................................................................................................................18
mA Input [MR 200 only] .......................................................................................................................18
mA Output ...............................................................................................................................................18
Level System Synchronization ...........................................................................................................19
Power .......................................................................................................................................................19
Digital Communications .......................................................................................................................20
RS-232 Serial Connection ..........................................................................................................20
RS-485 Serial Connection ..........................................................................................................20
Discrete Inputs................................................................................................................... 20
Operating the MultiRanger ..................................................................................................................21
RUN Mode ..............................................................................................................................................21
Readings in RUN Mode .......................................................................................................................22
Status Parameters ................................................................................................................................23
Controlling the Display .........................................................................................................................24
Adjusting the primary reading for four-digit LCD readout:...................................... 24
Auxiliary Reading ........................................................................................................................24
Multiple Readings [MR 200 only] ............................................................................................25
PROGRAM Mode ..................................................................................................................................26
Starting PROGRAM Mode ..................................................................................................................26
i
Hand Programmer .......................................................................................................................26
Programmer Keys ........................................................................................................................27
Dolphin Plus ............................................................................................................................................28
Table of Contents
ii
mA I/O ..............................................................................................................................................................48
mA Input [MR 200] ................................................................................................................................48
Table of Contents
mA Output ...............................................................................................................................................48
Volume [MR 200] ........................................................................................................................................50
mmmmm
Readings ..................................................................................................................................................50
Tank Shape and Dimensions ..............................................................................................................50
Characterization Chart [MR 200] .......................................................................................................51
Example Chart ..............................................................................................................................51
MultiRanger 200 only .................................................................................................................52
Alarms .............................................................................................................................................................53
Level ..........................................................................................................................................................53
Setting Simple Level Alarms .....................................................................................................54
Rate [MR 200] .........................................................................................................................................54
In Bounds/ Out of Bounds Range [MR 200] ....................................................................................55
Cable Fault ..............................................................................................................................................55
Temperature [MR 200] ..........................................................................................................................55
Loss of Echo (LOE) .................................................................................................................................56
Pump Control ...............................................................................................................................................57
Setting a Pump Down Group ..............................................................................................................57
Setting a Pump Up (Reservoir) Group ..............................................................................................58
Other Pump Control Algorithms .........................................................................................................60
Set Relays to ALTERNATE DUTY BACKUP [MR 200] ..........................................................60
Set Relays to FIXED DUTY ASSIST ........................................................................................60
Set Relays to FIXED DUTY BACKUP [MR 200] .....................................................................61
Set Relays to ALTERNATE DUTY SERVICE [MR 200] ..........................................................61
Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200] ............................................62
Optional Pump Controls .......................................................................................................................62
Starting Pumps by Rate of Level Change [MR 200] ............................................................62
Rotating Pumps by Service Ratio [MR 200] ..........................................................................63
Totalizing Pumped Volume [MR 200] ......................................................................................64
Setting Independent Failsafe Controls ...................................................................................64
Setting a Pump to Run On [MR 200] .......................................................................................65
Setting the Pump Start Delays [MR 200] ...............................................................................65
Reducing Wall Cling [MR 200] ..................................................................................................65
Grouping Pumps [MR 200] ........................................................................................................66
Setting a Flush Valve [MR 200] ................................................................................................66
Relay Controlled by Communications ....................................................................................67
Tracking Pump Usage ..........................................................................................................................67
Rake (Screen) Control [MR 200] ........................................................................................................68
Setting a Rake Control .........................................................................................................................68
iii
Setting the Common Parameters ............................................................................................69
Set Relay 1 (Operate Rake) .......................................................................................................69
Set Relays 2 to 4 (Level Alarms) ..............................................................................................69
Table of Contents
iv
Communications Installation .............................................................................................................92
Wiring Guidelines ..................................................................................................................................92
Table of Contents
Ports 1 and 2 .................................................................................................................................92
Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locations ..................................................92
Port 1: RS-232 RJ-11 Jack ..........................................................................................................93
mmmmm
Port 2: RS-485 ...............................................................................................................................93
Configuring Communication Ports (Parameters) ...........................................................................94
Modbus Register Map ............................................................................................................................97
Word Order (R40,062) ..........................................................................................................................98
Map ID (R40,063) ....................................................................................................................................98
Product ID (R40,064) ..............................................................................................................................99
Point Data (R41,010 – R41,031) ............................................................................................................99
Totalizer (R41,040 – R41,043) ................................................................................................................99
Input/Output (R41,070 – R41,143) ...................................................................................................... 100
Discrete Inputs (R41,070) ....................................................................................................... 100
Relay Outputs (R41,080) ........................................................................................................... 100
mA Input (R41,090) [MR 200] .................................................................................................. 100
mA Output (R41,110-41,111) ..................................................................................................... 100
Pump Control (R41,400 – R41,474) ......................................................................................... 100
Pump ON Setpoint (R41,420 – R41,425) ................................................................................ 100
Pump OFF Setpoint (R41,430 – R41,435) ...............................................................................101
Pumped Volume (R41,440 – R41,443) [MR 200] ...................................................................101
Pump Hours (R41,450 – R41,461) ...........................................................................................101
Pump Starts (R41,470 – R41,475) ............................................................................................101
Parameter Access (R43,998 – R46,999) ............................................................................... 102
Parameter Indexing ................................................................................................................. 102
Indexing the Parameter Access Area....................................................................... 102
Reading Parameters ................................................................................................................ 103
Global Index Method (P782 = 0).................................................................................. 103
Parameter Specific Index Method (P782 = 1) ......................................................... 104
Writing Parameters .................................................................................................................. 104
Global Index Method (P782 = 0).................................................................................. 104
Parameter Specific Index Method (P782 = 1).......................................................... 104
Format Words (R46,000 to R46,999) ............................................................................................... 105
Global Index Method (P782 = 0) ............................................................................................ 105
Parameter-Specific Index Method (P782 = 1) .................................................................... 105
Format Registers ...................................................................................................................... 105
Data Types .................................................................................................................................................. 107
Numeric Values .................................................................................................................................. 107
Bit Values .............................................................................................................................................. 107
Unsigned Double Precision Integer (UINT32) ............................................................................ 107
Split Values .......................................................................................................................................... 108
Text Messages .................................................................................................................................... 109
Relay Function Codes (P111 Only) ..................................................................................................110
Error Handling ...........................................................................................................................................112
Modbus Responses ............................................................................................................................112
v
Error Handling ......................................................................................................................................112
Communication Troubleshooting ...................................................................................................114
Table of Contents
Generally ...............................................................................................................................................114
Specifically ............................................................................................................................................114
mmmmm
vi
Range Calibration (P650 to P654) ....................................................................................................180
Temperature Compensation (P660 to P664) ..................................................................................183
Rate (P700 to P708) ............................................................................................................................185
Table of Contents
Measurement Verification (P710 to P713) ....................................................................................189
Transducer Scanning (P726 to P729) .............................................................................................192
mmmmm
Display (P730 to P739) .......................................................................................................................193
SmartLinx Reserved (P750 to P769) ...............................................................................................196
Communications (P770 to P782) .....................................................................................................196
SmartLinx Hardware Testing (P790 to P795) ................................................................................199
Echo Processing (P800 to P807) ......................................................................................................201
Advanced Echo Processing (P815 to P825) ................................................................................. 205
Advanced TVT Adjustment (P830 to P835) .................................................................................. 209
Advanced Shot Adjustment (P840 to P852) ..................................................................................214
Test (P900 to P913) ..............................................................................................................................217
Measurement (P920 to P927) .......................................................................................................... 220
Master Reset (P999) ......................................................................................................................... 223
General Appendix A: Index Types ................................................................................................. 225
Index types ........................................................................................................................................... 225
General Appendix B–Technical Reference ............................................................................. 226
Transmit Pulse ..................................................................................................................................... 226
Echo Processing ................................................................................................................................. 226
TVT (Time Varying Threshold) curves ........................................................................................... 227
Auto False-Echo Suppression ............................................................................................... 227
Distance Calculation ......................................................................................................................... 228
Sound Velocity .................................................................................................................................... 228
Scanning ............................................................................................................................................... 229
Volume Calculation [MR 200] .......................................................................................................... 229
Universal, Curved [MR 200] ................................................................................................... 230
Flow Calculation ................................................................................................................................. 230
Universal, Linear [MR 200] ..................................................................................................... 231
Universal, Curved [MR 200] ................................................................................................... 231
Maximum Process Speed ................................................................................................................ 232
General Appendix C: Troubleshooting ........................................................................................ 233
Common Problems Chart ................................................................................................................. 233
Noise Problems ................................................................................................................................... 234
Determine the Noise Source ................................................................................................. 235
Non-Transducer Noise Sources ........................................................................................... 235
Common Wiring Problems ..................................................................................................... 236
Reducing Electrical Noise ...................................................................................................... 236
Reducing Acoustical Noise .................................................................................................... 236
Measurement Difficulties ................................................................................................................. 237
Flashing LOE Display ............................................................................................................... 237
Adjust Transducer Aiming ........................................................................................... 237
Increase Failsafe Timer Value .................................................................................... 238
Install a Transducer with a Narrower Beam........................................................... 238
Use Dolphin Plus to Debug Echo................................................................................ 238
Fixed Reading ...................................................................................................................................... 238
vii
Obstructions in the Sound Beam ......................................................................................... 238
Nozzle Mountings .................................................................................................................... 238
Set the MultiRanger to Ignore the Bad Echo .................................................................... 239
Table of Contents
viii
The MultiRanger 100 and 200
MultiRanger 100/200
The MultiRanger is available in two models, MultiRanger 100 and MultiRanger 200, and is
mmmmm
designed for a variety of applications:
• water and wastewater
• storage tanks, for measuring liquids, slurries, and solids
• hoppers, ore bunkers, flotation cells
MultiRanger 100
The MultiRanger 100 is a single or dual-point level, one, three, or six relay measurement
device. It is equipped with digital communications and offers the latest in echo
processing technology and diagnostic features.
MultiRanger 200
The MultiRanger 200 is a single or dual-point, three or six relay device that offers both
level and volume measurement. It has Open Channel Monitoring capabilities, a larger
number of advanced pump control algorithms, and is equipped with digital
communications. It offers the latest in echo processing technology and diagnostic
features.
The Manual
The manual provides instruction for both MultiRanger 100 and MultiRanger 200 models.
For your convenience, the manual uses MultiRanger 100 features as its standard content.
Additional MultiRanger 200 features are clearly marked.
The manual is designed to help you get the most out of your MultiRanger, and it provides
information on the following:
If you have any questions, comments, or suggestions about the manual contents, please
email us at [email protected].
Alternating Current
mmmmm
Direct Current
Configuration Examples
The configuration examples used in this manual illustrate the versatility of the
MultiRanger. Because there is often a range of ways to approach an application, other
configurations may also apply.
In all examples, substitute your own application details. If the examples do not apply to
your application, check the applicable parameter reference for the available options.
Should you require more information, please contact your Siemens Milltronics
representative. For a complete list of Siemens Milltronics representatives, go to
www.siemens.com/processautomation.
DC version
• 12-30 V DC, 20W1
Specifications
• fuse: F3: 2 AG, Slow Blow, 2A, 250V
mmmmm
Transmitter fuse
• F1: Belling Lee, L754, 4000A HRC, ceramic type, 100mA, 250V
Mounting
Location
• indoor / outdoor
Altitude
• 2000 m max.
Ambient temperature
• -20 to 50 °C (-5 to 122 °F)
Relative humidity
• Wall Mount: suitable for outdoors (Type 4X / Nema 4X, IP65 Enclosure)
• Panel Mount: suitable for outdoors (Type 3 / Nema 3, IP54 Enclosure)
Installation category
• II
Pollution degree
• 4
Accuracy
• 0.25% of maximum range or 6 mm (0.24”), whichever is greater
Resolution
• 0.1% of program range1 or 2 mm (0.08”), whichever is greater
Memory
Specifications
Programming
Primary
• handheld programmer
Secondary
• PC running SIMATIC PDM
• PC running Dolphin Plus software
Display
• back lit LCD
Temperature Compensation
• Range: -50 to 150 °C (-58 to 302 °F)
Source
• integral transducer sensor
• TS-3 temperature sensor
• programmable fixed temperature
Temperature Error
Sensor
• 0.09 % of range
1.
Program range is defined as the empty distance from the face of the transducer
(P006) plus any range extension (P801).
Outputs
Transducer drive
• 315 V peak
mA Analog
MultiRanger 100/200:
Single or Dual point versions include two mA outputs
Specifications
• 0-20 mA
• 4-20 mA
mmmmm
• 750 ohm maximum
• Resolution of 0.1%
• Isolated
Relays1
• One:
• 1 control
• Three:
• 2 control
• 1 alarm control
• Six:
• 4 control
• 2 alarm control
• All relays rated 5A at 250 V AC, non-inductive
Control Relays
• 1, 2 or 4 Form A, NO relays (numbers 1, 2, 4, 5)
Alarm Relay
• 0, 1 or 2 Form C, NO, or NC relay (numbers 3, 6)
Communication
• RS-232 running Modbus RTU and ASCII via RJ-11 connector
• RS-485 running Modbus RTU and ASCII via terminal blocks
Optional
• SmartLinx® compatible
1.
All relays are certified only for use with equipment that fails in a state at or
under the rated maximums of the relays.
Discrete (2)
• 10-50 V DC switching level
• logical 0 = < 0.5 V DC
• logical 1 = 10 to 50 V DC
• 3 mA maximum draw
Enclosure
Specifications
Wall Mount
mmmmm
Panel Mount
• 278 mm (10.93") x 198 mm (7.8") Width dimension includes flange.
• Type 3 / Nema 3 / IP54
• Polycarbonate
Weight
• Wall mount: 1.37 kg (3.02 lb)
• Panel mount: 1.5 kg (3.3 lb)
Approvals
• See product nameplate
Compatible Transducers
• Echomax series and STH series
Transducer Frequency
• 44 kHz
1.
For watertight applications, use only approved, suitable size hubs in the
enclosure’s conduit holes.
Note: The MultiRanger is to be used only in the manner outlined in this instruction
manual or protection provided by the equipment may be impaired.
Specifications
mmmmm
Notes:
• Installation must only be performed by qualified personnel, and in accordance
with local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
All field wiring must have insulation suitable for at least 250 V.
Mounting
mmmmm
Mounting Locations
Recommended
• Ambient temperature is always within -20 to 50 °C (-5 to 122 °F)
• MultiRanger display window is at shoulder level, unless most interaction is through
a SCADA system
• Easy access for hand programmer is provided
• Cable length requirements are minimal
• Mounting surface is free from vibration
• Leave is sufficient room to swing unit lid open and have clear access.
• A place for a laptop computer is provided for on-site Dolphin Plus configuration
Avoid
• Exposure to direct sunlight. (Provide a sun shield to avoid direct sunlight.)
• Proximity to high voltage/current runs, contacts, SCR or variable frequency motor
speed controllers
Note: When routing cable through a conduit, please follow the Cable Routing
instructions on page 10 before mounting the MultiRanger.
Wall Mount
Enclosure Dimensions
14.9 mm 160.3 mm 91 mm
(0.58") (6.325") (3.58")
15.2 mm 130 mm 4.3 mm dia.
(0.6") (5.125") (0.17") 6.6 mm
four mounting (0.26")
holes
lid screws
(6)
240 mm
(9.45")
Installation
227 mm
(8.93")
mmmmm
Mounting the Enclosure
1. Remove the lid screws and open the lid to reveal the mounting screw holes.
2. Mark and drill four holes in the mounting
mounting screw holes
surface for the four screws (customer supplied).
3. Fasten with a long screwdriver.
Please note:
• Recommended mounting: directly to wall or to
electrical cabinet back panel
• Recommended mounting screws: #6
• If alternate mounting surface is used, it MUST
be able to support four times the weight of the
unit.
Note: For conduit locations and assembly for hazardous mounting in Class 1 Div 2
applications, please see Drawing 23650314 in General Appendix G: Conduit Entry
for Class 1, Div 2 Applications on page 251.
Note: Where more holes are required than are supplied in the enclosure, follow
the Cable routed through a conduit steps.
Cutout Dimensions
Installation
mmmmm
Cutout Instructions
1. Select a place for the unit and fasten the template onto the panel (use tape or
tacks).
2. Drill the four fastener holes.
3. Make the cutout using the appropriate tools.
4. Mount unit according to the instructions in this manual.
278 mm
(10.93")
Installation
mmmmm
Helpful hint:
• Use tape to hold hexogonal heads in slots while attaching wingnuts.
Battery
RS-232 RJ-11
Connector
TB1
Power Supply
TB2
L2/N L1
2
SYNC
TB3
Female Connector
for SmartLinx Card
1
mA INPUT
SHIELD
SmartLinx Card
RELAY 1
1
4 - 20 mA
OUTPUTS
RELAY 2
2
RELAY 3
TS-3 Terminals
SHIELD
1
RELAY 4
DISCRETE 2
INPUTS
RELAY 5
COM RS-485
RELAY 6 RS485 A
B
Connections
Installation
mmmmm
Installing the Battery
The battery (Rayovac BR2032) has a ten-year life expectancy. Please note the life
expectancy may be reduced by ambient temperature. If the unit loses external and
battery power, a capacitor will power the RAM for about ten minutes.
Installation Steps
1. Open the enclosure lid.
2. Slide the battery into the holder. Be sure to
align the + and – terminals correctly.
3. Close and secure enclosure lid. Battery
+
Note: All parameter values are written to the EEPROM once every hour. The
battery is used to backup Standard Data Logging parameters (P300-P321)
between writes, in case of power failure.
Siemens Milltronics
MultiRanger Transducer(s)
Siemens Milltronics
TS-3 Temperature
Sensor
Laptop running
Dolphin Plus
Customer Alarm,
Pump, or Control
Device
Customer Device,
digital output
Customer Device,
Wiring
analog output
mmmmm
Customer Network or
Modem
SmartLinx Card
TB1
TB2
L2/N L1
TB1
2
TB3
SYNC
1
12-30 V
mA INPUT
DC Version
SHIELD
RELAY 1
1
4 - 20 mA
OUTPUTS
RELAY 2
2
RELAY 3
TS-3
SHIELD
1
RELAY 4
DISCRETE 2
INPUTS
RELAY 5
COM
RELAY 6 RS485 A
Cables
Wiring
mmmmm
white
TRANSDUCER TWO
black
white
TRANSDUCER ONE
black
A 0.1 µF (100V or greater) capacitor is included with the MultiRanger for retrofitting old
MultiRanger Plus installations. Please see MultiRanger 100/200 Installation (for
retrofitting MultiRanger Plus Installations) on page 249.
Relays
Relay contacts are shown in the de-energized position. All relays are handled identically
and can be configured as positive or negative logic using P118.
RELAY 4
RELAY 5
RELAY 6
If the following conditions apply, a separate TS-3 temperature sensor will ensure
optimum accuracy:
• the transducer is exposed to direct sunlight (or other radiant heat source)
• the transducer face and monitored surface temperature differs
• faster response to temperature changes is required
Note
Use a T-S3 Temperature
TEMPERATURE SENSOR
Sensor only. Leave
terminals open (unused) if
TS-3 is not deployed.
mA Output
mmmmm
For more information, consult the mA output parameters (P200 to P219) in the parameter
reference section.
When using multiple ultrasonic level monitors, be sure to run the transducer cables in
separate grounded metal conduits.
When separate conduits are not possible, synchronize the level monitors so that no unit
transmits while another is waiting for echo reception.
Other Siemens
Milltronics Transceiver MultiRanger
Power
Important!
Before applying power to the MultiRanger for the first time, ensure any connected
alarm/control equipment is disabled until satisfactory system operation and
performance is verified.
Wiring
mmmmm
GND L1
L2/N
The MultiRanger can also be directly connected to a computer running Dolphin Plus.
RS-232 RJ-11
TB1 Connector
TB2
L2/N L1
2
TB3
SYNC
1
mA INPUT
SHIELD
RELAY 1
1
4 - 20 mA
OUTPUTS
RELAY 2
2
RELAY 3
TS-3
SHIELD
1
RELAY 4
RELAY 5
DISCRETE
INPUTS
2
RS-485
RELAY 6 RS485
COM
A
Connection
B
(see below)
Discrete Inputs
Discrete inputs have a positive and negative terminal. Requires an external power supply.
RUN Mode
In RUN mode, the MultiRanger detects material level and provides control functions. The
MultiRanger automatically starts in RUN mode when power is applied.
System status is shown on the unit’s LCD, or on a remote communications terminal.
Display
1 2 3 4 5
?
8
1 2 3 4 5 6
14 13 12 11 10 9
Indicator Functions
RUN Mode PROGRAM Mode
1 index type (see below) index type (see next table)
2 index index
3 primary reading parameter value
4 units units
5 hi and hi hi alarm designation auxiliary function
6 level display n/a
7 filling display scroll access tag
8 emptying display scroll access tag
9 lo and lo lo alarm designation n/a
10 relay # programmed relay # programmed
11 relay # activated relay # activated
12 auxiliary reading parameter number
13 normal operation: n/a
Operation
relay
secondary index
mA input or output
+ Hold number key for five seconds to display the number of P311
accumulated pump starts2 for numbered pump.
1.
Distances less than 0.3 m (1 ft) from the transducer face cannot be measured
reliably. Therefore, a 0% reading is not possible during Distance operation.
2.
If the associated relay is programmed for pump control.
Parameter Values
P203 mA Output Value 0 to 22 – Current mA output
P254 Scaled mA Input Value 0 to 9999 – Current mA input after scaling
[MR 200 only]
P275 Scaled Discrete Input Value Shows current value of discrete input,
values vary by DI function
P322 LCD Total Low The last four digits of the totalizer
[MR 200 only]
P323 LCD Total High The first four digits of the totalizer
[MR 200 only]
P341 Run Time The number of days the MultiRanger has
been operating
P342 Start Ups The number of times power has been
cycled
P664 Temperature Current temperature measured by
transducer
P707 Rate Value Current rate of material level change
P708 Volume Rate Display Current rate of material volume change
[MR 200 only]
P729 Scan Time Seconds since last level scan
P806 Echo Strength Strength of primary echo
P920 Reading Measurement Current primary reading
P921 Material Measurement Current level from P007–Span
P922 Space Measurement Empty space above the material level
P924 Volume Measurement Current volume value, if programmed
[MR 200 only]
P925 Flow Measurement (OCM) Current flow value, if OCM programmed
[MR 200 only]
P926 Head Measurement (OCM) Current level, if OCM programmed
[MR 200 only]
P927 Distance Measurement Distance from transducer face to material
Operation
mmmmm
Parameter Action
P060 Decimal Position Sets maximum number of decimals
P061 Convert Reading Scales the reading to fit
P062 Offset Reading Shifts the reading up or down by a fixed amount
Example
To reference the displayed level to sea level, enter the distance in Units (P005), between
Empty (P006) and sea level. (Enter a negative value if Empty is below sea level.)
P006
P007
P062
Sea Level
Reservoir
Auxiliary Reading
The Auxiliary Reading area of the LCD displays parameter values while leaving the
primary reading on screen.
Note: The parameters shown in the auxiliary reading field are indexed as follows:
• global
• by transducer
• by level
Operation
mmmmm
See Parameter Indexing on page 36. All the instructions in the following procedures apply
to the hand programmer and assume that the MultiRanger is activated.
Operation
mmmmm
Notes:
• The battery in the programmer is not
replacable.
• The hand programmer is ordered
separately from Siemens Milltronics Infrared
Port
For your convenience, the
programmer has a magnetic mounting
strip on the back. Keep programmer
nearby for easy access.
Point the programmer at the IR port
above the display and press the keys.
Operation
mmmmm
3 Head
[MR 200 only]
4 Flow based on Head
[MR 200]
5 mA Output
6 Temperature
7 Rate of Change
9 9 N/A
0 0 N/A
Enter Value
Clear to Preset
Operation
mmmmm
Use Dolphin Plus software to configure, monitor, tune, and diagnose the MultiRanger
from a PC or directly in the field with a laptop.
Dolphin Plus is easy to install and easy to use. Just load the software from the CD onto a
desktop PC or Laptop and then set up or modify complete parameter configurations in a
Windows®2environment.
After configuration, you can edit parameters, upload and download parameter sets to
and from disk, and use parameter sets saved from other instruments. You can also work
with echo profiles for fine tuning without the need for special instruments. Built-in Quick
Start features and Help files guide you through the entire process.
monitor communications
Operation
mmmmm
Device Description
To use Process Device Manager (PDM) with MultiRanger 100/200, you need the Device
Description for MultiRanger 100/200, which will be included with new versions of PDM.
You can locate the Device Description in Device Catalog, under Sensors/Level/ Echo/
Siemens Milltronics. If you do not see MultiRanger 100/200 under Siemens Milltronics,
you can download it from our website: www.siemens.com/processautomation. Go to the
MultiRanger product page and click Downloads. After downloading the DD file, you need
to execute DeviceInstall.
Operation
mmmmm
Changing Parameters
Note: If Parameter Value alteration is not permitted, access the Lock parameter
(P000) and enter the security code, (see Security below).
1. Starting in RUN mode, press PROGRAM and then press DISPLAY to put the
unit into PROGRAM mode.
2. Press DISPLAY to select the Parameter Number field.
3. Enter the Parameter Number (e.g. 110). After the third digit is entered, the parameter
value is shown.
4. Enter the new value, and press ENTER . The MultiRanger interprets the value,
either accepting or replacing it with a valid value.
Helpful Hints
• For parameters P001 to P009, press a single digit (1–9) and then press DISPLAY
to show that parameter.
• The ? icon indicates that the MultiRanger has accepted the value but that it conflicts
with other values entered. Double-check your programming.
• By default, the SCROLL arrows show only the Quick Start parameters and
any that have been changed.
• P733 sets all parameters to be scroll-accessed.
Operation
mmmmm
Simulation
P000 Lock also controls how simulations affect control relays. By default, control relays
are unaffected by simulation levels. But if P000 is set to –1, they react to the simulated
level. See Parameters P925–P927 on page 222 for running a simulation.
MR 200 only:
Percentage is also available when showing flow and volume with 100%, based on the
parameter that defines the maximum.
Measurement Maximum
Volume P051
Flow P604
Parameters Types
View Only Parameters
Parameter values indicating status only. They cannot be altered.
Global Values
Parameter values common to all inputs and outputs on the MultiRanger.
When a global parameter is accessed, the index display automatically disappears. When
a non-global parameter is accessed, the index display reappears showing the last index
number.
Operation
mmmmm
Parameter Reset
Returning a parameter to factory default.
1. Display the appropriate parameter number.
2. Display the appropriate index value (if required).
3. Press CLEAR .
4. Press ENTER .
Display Readout
The following readouts are shown when the MultiRanger cannot display a number.
Display Definition
Parameter has not been set
All values not same when viewing index 0
MultiRanger Display
The index number and the index values are displayed above the parameter indicator on
the LCD.
Index Number Index Value
1 2 3 4 5 6
Notes
• Transducers are always indexed when the dual point option is enabled.
• An indexed transducer is commonly referred to as a Point (short for
’Measurement Point’). Point Number refers to indexed transducers.
• To set all indexed values for a parameter to the same value, use index 0.
• MR 200 only: Transducer parameters are indexed only if Operation (P001) is set
to Difference (value=4) or Average (value=5) on a single point MultiRanger.
Primary Index
Example Setting: P111[3] = 52
P111
1 2 3 4 5 6
52
Secondary Index
Parameters with a secondary index permit multiple values for a primary index (point). For
example, a volume calculation based on vessel characterization breakpoints requires a
distinct set of breakpoints for each measured point.
Thus the primary index refers to the measurement point, and each secondary index refers
to a characterization breakpoint value.
1 2
A [6 = 8m]
[6 = 2m] A
B [3 = 5.5m]
[3 = 1.5m] B
C [1 = 2.75m]
[1 = 0.75m] C
Starting Measurement
The MultiRanger startup varies between single and dual point models.
Ring indicates
relay is configured
Index Description
2 indexed by Transducer One or Two
3 indexed by level measurement
1 = Transducer One
2 = Transducer Two
3 = Calculated Level (average or difference)
Index Description
2 indexed by Transducer One or Two
3 indexed by level measurement
1 = Transducer One
2 = Transducer Two
3 = Calculated Level (average or difference)
Measurement Conditions
The following information will help you configure your MultiRanger for optimal
performance and reliability.
Response Rate
The response rate of the device influences the measurement reliability. Use the slowest
rate possible with the application requirements.
The response rate is also important to functions connected to the filling or emptying
indicators.
Failsafe
The failsafe parameters ensure that the devices controlled by the MultiRanger default to
an appropriate state when a valid level reading is not available.
• P070 – Failsafe Timer activates if an error condition is detected. Upon expiration of
the timer, relay status defaults to values based on P071.
• P071 – Failsafe Material Level determines the level reading if the Failsafe Timer
expires and the unit is still in an error condition.
• P129 – Relay Failsafe controls the reaction of each relay. See Relay Failsafe on page
Operation
If Failsafe Operation activates frequently, see the Troubleshooting Appendix on page 233.
General Introduction
Depending on the model, up to six onboard multi-purpose relays are provided on the
MultiRanger. Each relay may be independently assigned to one function and has a
corresponding status icon on the LCD.
The relay functions fall under three modes of operation:
Mode Function
alarm alarm ON = LCD Icon ON = relay coil de-energized
pump pump ON = LCD Icon ON = relay coil energized
miscellaneous contact closed = LCD Icon ON = relay coil energized
Relay Function
Note: The MultiRanger 100 or 200 can be programmed with relays that may not
be installed, depending on the model. To determine the number of relays in your
MultiRanger 100 or 200, open the lid and count the large white relays to the left of
the display.
Alarm
Level
In high alarm, the function goes on when the level rises to the ON setpoint and goes off
when the level lowers to the OFF setpoint. In low alarm, the function goes on when the
level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint.
Relays
temperature rises to the OFF setpoint.
mmmmm
Loss of Echo
The function goes on when the fail-safe timer expires. The function goes OFF when a
valid echo is received (fail-safe timer is reset).
Pump
Level
In pump down, the function goes on when the level rises to the ON setpoint and goes off
when the level lowers to the OFF setpoint. In pump up, the function goes on when the
level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint.
Miscellaneous
Totalizer and Samplers [MR 200]
Refer to Totalizing Pumped Volume on page 64. Relays are normally de-energized, contact
closure is approximately 200 mSec duration.
Setpoint - ON / OFF
If the ON setpoint is higher than the OFF setpoint, the relay operates as:
• high alarm
• pump down control
If the ON setpoint is lower than the OFF setpoint, the relay operates as:
• low alarm
• pump up control
The ON and OFF setpoints can not be the same on an individual relay but may be common
to other relays. The dead band or hysteresis is the difference between the ON and OFF
setpoints. For in and out of bounds level alarms, the hysteresis is set at ± 2 % of span
from either boundary.
Relay Status
mmmmm
Fail-Safe Mode
High Alarm Low Alarm
Fail-Safe High ON OFF
Fail-Safe Low OFF ON
Fail- Safe Hold HOLD HOLD
Upon entering the program mode, all pump control relays will be turned OFF. Alarm relays
will hold their prior status.
Cautions:
• If the relay status can affect plant operation or personnel safety, it is advisable
to override the relay functions or disconnect the relay wiring during calibration
or simulation.
• Keep power disconnected at main breaker when MultiRanger cover is opened.
Relay States
The relays on the MultiRanger are completely programmable, allowing for any control
scheme.
Relay Types
Relay 1,2,4,5 – NO (Form A)
Relay 3,6 – NO / NC (Form C)
P111–Alarm Functions
The alarm function de-energizes the relay coils. During normal operation (no alarms), the
relay coils are energized.
Relays
P112–Relay ON Setpoint
mmmmm
Sets the process point at which the relay is tripped.
P129–Relay Failsafe
Changes how individual relays react to a failsafe condition on the instrument.
Relay Activation
The flexibility of the relay functions ensures that the MultiRanger can support relay
wiring for different systems and applications. Use the following as a guide to the most
common parameters.
application requirements such as timing. P111 Pump and Control functions (see page 136
mmmmm
Relay Failsafe
P129–Relay Failsafe
Adjusts how individual relays react to a failsafe condition. Relays can be set to:
• OFF Control is by P071–Failsafe Material Level
• HOLd Keeps the relay in the current state
• dE De-energizes the relay (default for pump controls)
• En Energizes the relay
Relays
Value # Parameters Affected
mmmmm
Off 0 All relays set to OFF
Wet Well 1 Pump down with the following settings:
Parameter Relay #
1 2 3 4 5 6
1 P111 52 52 1(H) 1(L) 0 0
P112 70% 80% 90% 10% – –
P113 20% 20% 85% 15% – –
Wet Well 2 Pump down with the following level and rate settings:
Parameter Relay #
1 2 3 4 5 6
P111 52 52 1(H) 1(L) 0 0
P112 70% 80% 90% 10% – –
2
P113 20% 20% 85% 15% – –
P121 1
Because the pumps are started by rate, you must change P703 to desired
empty rate.
Reservoir 1 Pump up with the following level settings:
Parameter Relay #
1 2 3 4 5 6
3 P111 52 52 1(H) 1(L) 0 0
P112 30% 20% 90% 10% – –
P113 80% 80% 85% 15% – –
Reservoir 2 Pump up with the following level and rate settings:
Parameter Relay #
1 2 3 4 5 6
P111 52 52 1(H) 1(L) 0 0
P112 20% 20% 90% 10% – –
4
P113 80% 80% 85% 15% – –
P121 1
Because the pumps are started by rate you must change P702 to desired
fill rate.
Screen Differential control of a screen or rake:
Parameter Relay #
1 2 3 4 5 6
5 P110 3 1 2 3 0 0
P111 50 1(H) 1(L) 1(H) – –
P112 80% 90% 10% 90% – –
P113 20% 85% 15% 10% – –
Alarms General alarms at four setpoints:
Parameter Relay #
1 2 3 4 5 6
6 P111 1(H) 1(L) 1(HH) 1(LL) 0 0
P112 80% 20% 90% 10% – –
P113 75% 25% 85% 15% – –
Discrete Inputs
DI State P270 Setting
Normally Open P270 = 2
mmmmm
Normally Closed P270 = 3
mA Output
The MultiRanger has two mA outputs, used to send measurements to other devices.
Configuring the mA output to send a 4 to 20 mA signal scaled from 10% to 90% of span of
the second transducer:
Parameter Index Value Description
mA LI/O
Calibrating 20 mA Output
1. Connect the mA receiving device to the MultiRanger.
2. Put the MultiRanger into PROGRAM mode.
3. Set P911–mA Output Value to 20.0.
4. View the mA level on the receiving device.
5. If there is a discrepancy,
a.Attach ammeter to MultiRanger mA output.
b.Access P215, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and
ENTER . The ammeter should show a value near 20 mA.
c.Enter the exact value displayed on the ammeter into P215 (Index 1 or 2).
d.The ammeter should then read exactly 20.00 mA.
The unit is now calibrated for 20 mA for the receiving device.
Readings
When using volume, readings are given in arbitrary units specified in P051.
The default is 100, which gives a reading in percent of total. Use whatever units you want
here. If the value is too large for the four-digit LCD, use a larger unit.
Example
If a wet well has a maximum capacity of 250,000 liters, use the value 250.0 for P051 and
set the reading in 1000s of liters.
Notes:
mmmmm
• The default reading changes to a range from 0 to 100 (the value in P051)
• Empty (P006) is still measured to the bottom of the tank, not the top of A.
Example Chart
MAX VOLUME
P051
VOLUME (P055)
FLOW
0,0
LEVEL (P054)
Volume
mmmmm
Alarms
mmmmm
Level
The level alarm is the most common. Use this alarm to warn you when your process is in
danger of being upset due to high or low levels.
Generally, the four alarms used are Hi, Hi Hi, Lo, and Lo Lo.
P006
hi hi
hi
P007
lo
lo lo
Prerequisite: You must know the details of your application and substitute the values for
the sample values provided. If you are bench testing the unit, then set your test values to
be the same as the sample values.
Available designations:
Alarm Designation
Hi Hi
Hi
Lo
Lo Lo
Alarms
on one relay.
mmmmm
Setting an Out of Bounds Alarm
Parameter Index Value
P111 5 3
P112 5 1.3
P113 5 0.3
P116 5 0.05
Results:
• Trips alarm above 1.35 m and below 0.25m
• Resets alarm below 1.25 m and above 0.35m
Cable Fault
Activates an alarm if transducer cable circuit enters a shorted or opened state.
The temperature source can be the temperature sensor built into the transducer or an
external TS-3, as set by P660.
MultiRanger
Pump Control
mmmmm
P006
Outflow
Inflow
P007
MultiRanger
P006
P007
Inflow
Outflow
Pump Control
1. Example assumes a single measurement unit. If your MultiRanger has
mmmmm
dual point software installed, some parameters are indexed by two.
P112 1 0.4m Sets the three setpoints for the pump relays.
P112 2 0.3m The first cycle will use these setpoints.
mmmmm
Pump Control
Set the Relay OFF Setpoints [MR 200]
mmmmm
Parameter Index Value Description
P113 0 1.3m By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
Notes:
Pump Control
• Set all pump control relay ON and OFF setpoints to the same value
• If the level is within 5% of Span (P007) of the OFF setpoint, then the next pump
mmmmm
is not started
Notes:
• The MultiRanger will not sacrifice other pumping strategies to ensure that the
ratio is held true
• If the pump relays are set to the same value, then the ratio equals 1:1 and all
pumps are used equally (preset)
When more than one pump is assigned a Pump Service Ratio value (in any time units) and a
pump start is required (P112 Relay Setpoint ON), the pump with the fewest running hours (with
respect to the assigned ratio values) starts.
Conversely, when a pump stop is required (113 Relay Setpoint OFF), the pump with the
most running hours (as compared to the assigned ratio values) stops.
The global failsafe controls are set to hold and Relay Five is set to trigger an alarm bell.
Pump Control
mmmmm
Note: P130 counts when the indexed relay is tripped, not the number of pump
cycles. If the indexed relay only trips once every four pump cycles then the actual
interval of the run-on will be 20 pump cycles, or five cycles of Relay Three.
Level Setpoint ON
The flush valve connects to Relay Four and the watched pump is on Relay One.
Pump Control
be used to force status of some control relays, such as pumps.
mmmmm
Settings:
Transducer
Transducer Two
One Rake
P007 (3)
Max differential
between Point 1 and
Rake (Screen) Control
bargraph and mA
output.
P006[2]
P007[1]
P007[2]
h[1] Flow
Rake
Water Level h[2]
MR 200
mmmmm
Set Relays 2 to 4 (Level Alarms)
P110 2 1 Description
P110 2 1
Sets Relay Two as a high level alarm for
P111 2 1 Transducer One with an ON setpoint of 1.3m
P112 2 1.3 and an OFF setpoint of 1.2m.
P113 2 1.2
P110 3 2
Sets Relay Three as a low level alarm for
P111 3 1 Transducer Two with an ON setpoint of 0.2m
P112 3 0.2 and an OFF setpoint of 0.4m.
P113 3 0.4
P110 4 3 Sets Relay Four as a rake failure alarm as it
P111 4 1 uses the differential level point (3) with an
P112 4 1.0 ON setpoint of 1.0m and an OFF setpoint of
P113 4 0.9 0.9m.
Relay Contacts
Pumped volume is calculated at the end of the pump cycle. Totalized volume given
through a relay set up for totalizer (P111[r]=40) will be given in bursts at this time.
Both the open and closed times for the relay contact are provided by P645 and are preset
to 0.2 seconds. Partial units are added to the next pump cycle.
Example:
Shows a relay set up to make one contact for every cubic metre (m3) of liquid.
P645 P645
Flow Samplers – MR 200
External Totalizers and
Pump Cycle
Totalizer
To set the totalizer to provide relay contact to an external counter, use the following:
Counter Formula
1 Contact per 10P640 units P640 is preset to 0 so the default number of
contacts for a pumped volume cycle is
equivalent to the number of volume units.
Flow Sampler
Based on Volume and Time
To trigger a flow sampler relay based on flow, use P111[r]=41 and set the other
parameters:
Counter Formula
1 Contact per P641 x 10P642 units
2. Exponential (P600 = 1)
For most other weir and flume types. PMD exponents provided by the manufacturer are
entered. Flow is calculated using the exponent (P601) and the maximum values (P603 and
P604).
• Standard Weirs on page 78
• Parshall Flume on page 79
• Leoplod Lagco on page 80
• Cut Throat Flume on page 81
Common Parameters
These Quick Start parameters are required for all installations.
Parameter Index Value Description
P001 G 6 Operation = OCM
P002 G 1 Material = liquid
Open Channel Monitoring
P006
P007
P603 P605
2. Use P801 Range Extension where the Empty level is set to the bottom of the weir,
and above the bottom of the channel. It should be used if the surface monitored can
fall past the Empty (P006) level in normal operation without reporting an LOE. The
value is added to Empty (P006) and can be greater than the range of the transducer.
P006
P007
P603
P801
Open Channel Monitoring
mmmmm
Front View
Side View
Transducer notch angle
P602 P006
P007
P603
P801
h Diagonal View
Flow
Transducer
P006
h Flow
P605 (p)
mmmmm
Plan View
Flow
Side View
P006
P007
P603
P605
Application Information
• Sized by pipe diameter D
• Flume relief is trapezoidal
• Designed to install directly into pipelines and manholes
• Head is referenced to bottom of the throat, not bottom of the pipe
• For rated flows under free flow conditions, the head is measured at a distance of
Open Channel Monitoring
Flow
Point of Measurement
Plan View
P006
D P007
3.0 28 10¾
4.5 41 16¼
MR 200
• H flumes come with a flat or sloping floor. The same flow table can be used because
mmmmm
Standard Weirs
Transducer
3 to 4
hmax
h
Weir Profile
Flows through these weirs can be measured using the Universal Flow Calculation P600 =
4 or 5. See Universal Calculation Support on page 82.
Parshall Flume
Note: C = Converging Dimension.
Plan View C
2
/3 C
Flow
Transducer
P006
Application Information
• Sized by throat width
• Set on solid foundation
• For rated flows under free flow conditions, the head is measured at 2/3 the length of
the converging section from the beginning of the throat section
Open Channel Monitoring
Plan View
Throat
Front View
Converging Diverging
Transducer
Point of Measurement
Side View
0
Head
Application Information
• Designed to be installed directly into pipelines and manholes
• Leopold Lagco may be classed as a rectangular Palmer-Bowlus flume
• Sized by pipe (sewer) diameter
• For rated flows under free flow conditions, the head is measured at a point
upstream referenced to the beginning of the converging section. Refer to the
following table:
Open Channel Monitoring
MR 200
mmmm
m
Application Information
• Similar to Parshall flume except that the floor is flat bottomed and throat has no
virtual length.
• Refer to manufacturer’s specifications for flow equation and point of head
measurement.
Linear
Curved
Head (P610)
Characterization is achieved by entering the head (P610) and corresponding flow (P611),
either from empirical measurement or from the manufacturer's specification. Increasing
the number of defined breakpoints will increase the accuracy of the flow measurement.
Breakpoints should be concentrated in areas exhibiting the higher degrees of non linear
flow. A maximum of 32 breakpoints can be defined. The curve’s end point is always
specified by the parameters Maximum Head (P603) and Maximum Flow (P604) for a
maximum total of 33 breakpoints.
Max. Flow
Flow Breakpoints
Open Channel Monitoring
Zero Flow
Zero Head
Max. Head
Head Breakpoints
MR 200
mmmm
m
Trapezoidal
Example Weirs
These weirs could require universal calculation.
mmmmm
mmmmm
specifications. This test can be run in simulation mode or by varying the level in the
application. The latter is preferred as it more accurately represents running conditions.
However, if it is not possible to do a physical test, a simulation will ensure that control
programming is correct.
Simulation
In simulation mode, the LCD display reacts to the simulated level changes. Alarm relays
will also react to the simulation, but any pump or control relays will not react.
To allow pump or control relays to operate on the simulated level, set P000 to –1.
1. Press ENTER to simulate level rise and fall. At the start of a simulation, the
default rate is 1% of Span / second.
2. Press the ARROW or to adjust the simulated rate of rise or fall. The
maximum rate is 4% of Span / second.
When the level rises to 100% or falls to 0%, it reverses direction at the same rate.
Relays
mmmmm
Use P119 to force a state change and verify that the results are as expected (pump starts,
alarm sounds, etc.).
Discrete Inputs
Use P270 to force the input value and verify that the results are as expected.
1. Go to P270 [DI] where DI = the discrete input to be tested
2. Set P270 to 0 (forced OFF)
3. Go to P275 [DI] to verify that the value is forced
4. Check the state of outputs to ensure that they respond as expected
5. Go to P270 [DI]
6. Set P270 to 1 (forced ON)
7. Go to P275 [DI] to verify that the value is forced
8. Check the state of outputs to ensure that they respond as expected
For further information see Discrete Inputs section on page 47.
mA Output
Use an external device to test the mA output against the measured level. Check that the
mA value changes to reflect the changes in the measured level.
Application Test
If you are testing the application by varying the material level (the preferred test method)
make sure that none of the control devices is connected (or at least that no power is
available to them).
If you are testing the application in simulation mode (and P000 is not –1), then control
relays are not energized and the control devices can remain connected.
While the level is being cycled, check the results of the discrete inputs either by closing
the circuit externally (preferred) or by using P270 Discrete Input Function to force the
input ON or OFF. Try all possible combinations to thoroughly test the setup. For each
combination, run a complete cycle to verify that the relays operate as expected.
Communications
mmmmm
Connection via radio modem, dial-up modem, or leased line modem
Modbus
Modbus is an industry standard protocol used by SCADA and HMI systems. The
MultiRanger uses Modbus to communicate via the RS-485 port. For a description of the
Modbus protocol, contact your local Schneider representative.
Dolphin
Dolphin is a proprietary Siemens Milltronics protocol designed to be used with Dolphin
Plus. For more information on Dolphin Plus or to obtain a copy of the software, please go
to www.siemens.com/processautomation to contact your Siemens Milltronics
representative.
Optional SmartLinx®Cards
The standard MultiRanger unit may also be enhanced with Siemens Milltronics
SmartLinx® communication modules that provide an interface to popular industrial
communication systems.
This manual only describes the built-in communications. For more information on
SmartLinx, please consult the appropriate SmartLinx manual.
Communication Ports
Communications
The MultiRanger comes with two communication ports on the base unit.
mmmmm
RS-232
The RJ-11 jack connects to a laptop computer for the following:
• initial setup
• configuration
• troubleshooting
• periodic maintenance
RS-485
The RS-485 port on the terminal blocks connects into industrial communications wiring
and has the following advantages:
• runs communications cable farther
• allows multiple slave units on the network, addressed by P771 – Network Address
To communicate with equipment requiring RS-485 capability, Siemens Milltronics offers
the RS-485 External Modem Kit. For more information, go to
www.siemens.com/processautomation.
Modbus
The Modbus protocol is supported in the base unit and can be configured using the
Communications parameters P770 to P782.
To set up communications with a Modbus RTU master device on port 2 using RS-485, set
the following parameters:
1.
Allen-Bradley is a registered trademark of Rockwell Automation.
DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
Communications
SmartLinx
mmmmm
Other protocols are available through optional SmartLinx communications modules.
Details on how to install and program these modules are contained in the SmartLinx
documentation.
Dolphin Plus
Dolphin Plus software makes it easy to record and compare parameter sets for all the
MultiRangers in your company. Dolphin Plus uses a proprietary protocol called Dolphin to
communicate with Siemens Milltronics instruments. This protocol is set when P770 = 1.
By default the settings for port 1 (RJ-11 connection) and Dolphin Plus match. These
settings are:
Wiring Guidelines
• the RJ-11 cable maximum length is 3 meters
• RS-485 maximum length is 1,200 meters (4,000 feet)
• use 24 AWG (minimum)
• use good quality communication grade (shielded twisted pairs) cable that is
recommended for RS-485 for port 2 (Belden 9842)
• run the communication cable separately from power and control cables (do not tie
wrap your RS-232 or RS-485 cable to the power cable or have them in the same
conduit)
• use shielded cable and connect to ground at one end only
• follow proper grounding guidelines for all devices on the bus
Note: Improper wiring and incorrect choice of cables are two of the most
common causes of communication problems.
Ports 1 and 2
Comms Installation
RJ-11 Jack
TB1
TB2
L2/N L1
2
TB3
SYNC
1
mA INPUT
SHIELD
RELAY 1
1
4 - 20 mA
OUTPUTS
RELAY 2
2
RELAY 3
TS-3
SHIELD
1
RELAY 4
DISCRETE 2
INPUTS
RELAY 5
RELAY 6 RS485
COM
A
RS-485 Port
B
Comms Installation
6 1
4
RJ-11 on 2 Tx Rx 3
6
3 Rx Tx 2
7
4 SG SG 5
MultiRanger RJ-11 jack
8
mmmmm
6 1 6 1
5 2
4 3
3 4
1 2 5 6
1
1
6
6
6
Port 2: RS-485
To connect the unit to an RS-232 modem:
MultiRanger
Terminal Block
DB 9 DB 9
RS-232 Converter:
5 5 COM
Modem RS-232 to
2 Rx 3 A
RS-485
3 Tx 2 B
COM
RS-485 MultiRanger
Modem
A Terminal Block
B
Port Description
mmmmm
This specifies the rate of communication in Kbaud. Any value may be entered, but the
only values supported are those shown above. The baud rate should reflect the speed of
the connected hardware and protocol used.
P773 Parity
The serial port parity.
Primary Index Communications Port
0 * No Parity
Comms Installation
Values 1 Odd Parity
2 Even Parity
Ensure that the communications parameters are identical between the MultiRanger and
mmmmm
all connected devices, as many modems default to N-8-1.
To use this parameter, ensure that P778 (Modem Available) =1. Ensure that the value is
low enough to avoid unnecessary delays when an unexpected disconnect occurs but
long enough to avoid timeout while you are still legitimately connected. This parameter
value is ignored by the Modbus Master Drivers as they automatically disconnect when
done communicating.
Hanging Up
Comms Installation
If the line is idle and the P779 Modem Inactivity Timeout expires, then the modem is
directed to hang up the line. Ensure that P779 is set longer than the standard polling time
of the connected master device. Set P779 to 0 to disable the inactivity timer.
mmmmm
For more on Parameter Index Location, see Parameter Access on page 102.
Read/
Type Description Start #R 1 Data Type
Write
Word Order 40,062 0/1 R/W
Map ID Register Map Type 40,063 1 0/1 = P782 R/W
ID Siemens Milltronics 40,064 1 4 = Model 200 R
Product Code 6 = Model 100
Single Parameter Access (SPA) R40,090 7 see Appendix A on page 114
Point Reading (3)2 41,010 2 -20,000 to 20,000 R
Data Volume (2)3[MR 200] 41,020 2 -20,000 to 20,000 R
1.
Maximum registers shown; fewer may be used depending on options installed.
2. Varies according to model.
P001 = Average or Difference. In Dual Point Mode, reading 1 and reading 2 are always
available. Point 3 is only available if P001[3]= Average or Difference.
3. 2nd volume available in Dual Point Mode only.
The MultiRanger was designed to make it easy for master devices to get useful
information via Modbus. This chart gives an overview of the different sections. A more
detailed explanation of each section follows below.
Map ID (R40,063)
This value identifies the register map used by the MultiRanger. See P782 Parameter Index
Location on page 96.
See also Parameter Access (R43,998 – R46,999) on page 102 for details.
The measurement registers are 41,010 to 41,012. The MultiRanger uses 41,010 when
configured with a single transducer and 41,010 to 41,012 when configured with two
transducers (P111=4 or 5 only). Two transducers can create three readings because they
can generate an average or differential reading (R41,012) as well as the two level
readings (R41,010 and R41,011).
Available registers:
Data Registers Parameter
Reading 41,010 to 41,012 P920
Volume [MR 200] 41,020, 41,021 P924
Temperature 41,030 and 41,031 P912
mA Output (R41,110-41,111)
The mA output is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). This is displayed in
Modbus Register Types
P911.
Only relays set for pump control (P111 = 50 to 52) are available. These registers have no
effect on relays programmed for other uses.
Note:
• Parameters P000 and P999 are read only. If P000 is set to lock activated then
all of the parameters are read only
• Parameter P999 (Master Reset) cannot be used via Modbus
• See Data Types on page 107 for a description of the different types of data
associated with different parameters
Each parameter register has a corresponding format register that holds the format
information required to interpret the value. See Format Words (R46,000 to R46,999) on
page 105.
Parameter Indexing
Many parameters are indexed. There are two possible indexes: a primary index and a
secondary index. A secondary index is a sub-address of the primary index. Some indexed
parameters affect multiple I/O devices.
The following is an example of a primary index:
P111 is the Relay Control Function. This parameter determines how a relay is controlled
Modbus Register Types
by the MultiRanger (used as an alarm, for pump control, etc.). Because there are up to six
relays on the MultiRanger, P111 is indexed by six to allow each relay to be programmed
independently.
mmmmm
A few parameters also have a secondary index. While a secondary index is important for
setting up the MultiRanger, it is almost never needed through remote communications.
Examples are:
• Transducer 1 is index 1
• Discrete input 2 is index 2
• Relay 5 is index 5
2. Write the secondary index value into R43,998.
This is a value between 0 and 40 that specifies the secondary index on the
parameter. This value is usually 0.
3. Write the desired format value into the appropriate format register. Because the
primary and secondary indexes are already specified, these portions of the format
word are ignored and only the last digit is significant.
See Format Registers on page 115 for details.
4. Read the value from the appropriate parameter register.
A value of 22,222 indicates that an error has occurred. Specify a different format
type and try again.
Writing Parameters
The method of writing parameters is similar to the method of reading them. Become
familiar with Reading Parameters, page 103, before attempting to write any parameters.
To write parameter values to the MultiRanger, follow these steps:
Format Registers
Each format register is made up of three decimal fields:
• decimal offset
• secondary index
• primary index
The primary and secondary indices correspond to those that are used by the parameter.
Examples of using the format word for both the index values and the decimal offset value
are shown below:
To write these values you can use a decimal offset as follows: format word = (primary
index x 1000) + (secondary index x 10) + (decimal).
Modbus Register Types
mmmmm
Numeric Values
Numeric parameter values are the most common. For example, parameter P920
(Reading) returns a number that represents the current reading (either level or volume,
depending on the MultiRanger configuration).
Numeric values are requested or set in units or percent of span, and may be specified
with a number of decimal places.
Numeric values must be in the range –20,000 to +20,000 to be valid. If a parameter is
requested and its value is more than +20,000, the number 32,767 is returned; if it is less
than –20,000, the number –32,768 is returned. If this overflow happens, decrease the
number of decimal places.
If a parameter cannot be expressed in terms of percent of span, or has no meaningful
value, the number 22,222 is returned. Try requesting the parameter in units, or refer to
P005 in the Parameter Reference section on page 124.
Bit Values
Bits are packed into registers in groups of 16 bits (1 word). In this manual, the bits are
numbered from 1 to 16, with bit 1 as the least significant bit (LSB) and bit 16 as the most
significant bit (MSB).
16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
MSB LSB
R41,442 R41,443
16 MSW 1 16 LSW 1
32 32-bit integer value (UINT32) 1
Split Values
Certain parameters are actually a pair of numbers separated by a colon, using this
format: xx:yy.
Data Types
mmmmm
MultiRanger 100
Control Relay Function Code Number P111
General OFF, relay not used 0 0
Undesignated Level Alarm 1 1
Low-Low Level Alarm 2 1 – LL
Low Level Alarm 3 1–L
High Level Alarm 4 1–H
High-High Level Alarm 5 1 – HH
Loss of Echo (LOE) Alarm 20 6
Transducer Cable Fault Alarm 16 7
Pump Fixed Duty Assist 25 50
Alternate Duty Assist 30 52
Control Communication 66 65
MultiRanger 200
Control Relay Function Code Number P111
General OFF, relay not used 0 0
Undesignated Level Alarm 1 1
Low-Low Level Alarm 2 1 – LL
Low Level Alarm 3 1–L
High Level Alarm 4 1–H
High-High Level Alarm 5 1 – HH
In Bounds Alarm 6 2
Out of Bounds Alarm 9 3
Rate of Level Change Alarm 12 4
Temperature Alarm 15 5
Loss of Echo (LOE) Alarm 20 6
Transducer Cable Fault Alarm 16 7
Pump Totalizer 22 40
Flow Sampler 23 41
Fixed Duty Assist 25 50
Fixed Duty Backup 26 51
Alternate Duty Assist 30 52
Pump Alternate Duty Backup 31 53
(con’t) Service Ratio Duty Assist 35 54
Service Ratio Duty Backup 36 55
First In First Out (FIFO) 40 56
Data Types
Communication 66 65
See P111 on page 136 of theParameter Reference section.
Error Handling
mmmmm
Modbus Responses
When polled by a Modbus Master, a slave device will do one of the following:
1. Not reply. This means that something went wrong with the transmission of the
message.
2. Echo back the command with the correct response (see the Modbus specification
for more details). This is the normal response.
3. Return an Exception Code. This reflects an error in the message.
Error Handling
Errors can be traced to two general sources:
1. There is an error in transmission.
OR
2. The host tries to do something that is not a valid action.
In the first case, the MultiRanger does not respond and the master waits for a response
time out error, which causes the master to re-send the message.
In the second case, the response depends on what the host tries to do. In general,
MultiRanger will not give an error to the host request. Various actions and the expected
outcome are as follows:
• If the host reads an invalid register, the host will get an undetermined value back.
• If the host writes an invalid register (a non-existing parameter or a read only
parameter), the value will be ignored and no error response will be made. However,
the current value will not reflect the desired new value.
• If the host writes a read only register, then the value will be ignored and no error
response will be made. However, the current value will not reflect the desired new
value.
• If P000 is activated, then the value will be ignored and no error response will be
made. However, the current value will not reflect the desired new value.
Generally
1. Check the following:
• There is power at the unit
• The LCD is showing the relevant data
• The device can be programmed using the hand programmer
2. Check the wiring pin outs and verify that the connection is correct.
Communications
3. Verify that values in the set-up parameters (P770 to P779) match the settings in the
computer used to communicate with the unit.
mmmmm
4. Check that the port on the computer is correct. Sometimes trying a different Modbus
driver will solve the problem. An easy stand-alone driver called ModScan32 is
available from Win-Tech at www.win-tech.com. This driver is helpful for testing
communications.
Specifically
1. The MultiRanger is set to communicate via a modem but no communication is
returning to the master.
• Check that the parameters are set up correctly and that the correct port is
configured
• Verify the wiring diagram. Note that there is a difference between wiring directly
to a computer and wiring to a modem.
• Verify that the modem is set up correctly. Siemens Milltronics has a series of
Application Guides that may help. Please contact your local Siemens Milltronics
representative for more information on Application Guides.
2. A MultiRanger parameter is set via remote communications, but the parameter
remains unchanged.
• Some parameters can only be changed when the device is not scanning. Try
putting the device in program mode, using the operating mode function.
• Try setting the parameter from the keypad. If it can not be set using the keypad,
check the lock parameter and set it to 1954.
Mapping
Parameter Read and Write (40,090 – 40,097) is a series of eight registers used for reading
and writing parameter values to and from the MultiRanger. The first three registers are
always unsigned integers representing parameters and index values. The second five
registers are the format and value(s) of the parameter.
Communication Appendix A
All parameters normally accessed through the hand-held programmer are available
through these registers.
Address Description
40,090 Parameter (integer)
mmmmm
Reading Parameters
To read parameters through Modbus do the following steps:
1. Send the parameter, its primary index, and its secondary index (usually 0), and
format to registers 40,090 to 40,093.
2. Wait until you can read the written values from the registers (40,090 to 40,093) to
confirm that the operation is complete.
3. Read the value from registers 40,094 and 40,095.
Format Register
Bits Values Description
1-8 0-2 Error Code
9-11 0-7 3-bit number representing decimal offset
12 0/1 direction of offset (0 = right, 1 = left)
13 0/1 Numeric format: Fixed (0) or Float (1)
14 0/1 Read or Write of data, Read (0), Write (1)
15 0/1 Word order: Most Significant Word first (0), Least
Significant Word first (1)
Communication Appendix A
16 Reserved
For example, to format the level reading so that it is shown in percent with two decimal
places shifted left, the format bits would look like this:
mmmmm
Bit
16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Numbers
Bit Values 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0
offset direction to right
most significant first
decimal offset of 2
no error code
fixed format
reserved
read
The value sent to the MultiRanger is 0001001000000000 binary or 512 decimal. The value
512 is sent as an integer to register 40,093 to format the output words 40,094 and 40,095
accordingly.
If the numeric data type is set for integer and the value contains decimal places, they are
ignored. In this situation, use the decimal offset to ensure that you have an integer value
and then write your code to recognize and handle the decimal offset.
Helpful Hints
Please note the following:
• Default values are always indicated with an asterix (*)
• Global values are common for all inputs and outputs on the unit
• Indexed parameters can apply to more than one input or output
• Primary index relates to an input or output
• Secondary index allows for multiple values on an indexed point
Parameters
mmmmm
View only This parameter can not be set, only viewed n/a
Parameter
Breakpoint Indexed by breakpoint
dependent
1. MultiRanger 100: The two level points are: Transducer One and Trans-
ducer Two.
Level point typically has 1 index in Single Point Mode (standard), and 2
indexes in Dual Point Mode (optional).
MultiRanger 200: The three level points are: transducer 1, transducer 2,
and the calculated point which can be difference (P001=4) or average
(P001=5).
Level point typically has 1 index in Single Point Mode (standard), and 2
indexes in Dual Point Mode (optional). A third index is available in both
modes when Operation (P001) is set for DPD (P001=4) or DPA (P001=5).
Parameters
mmmmm
WARNING:
Use this lock as backup security only. It uses a fixed value which can
be discovered by unauthorized personnel.
Access this parameter directly (type 000) and enter any value (except 1954) to secure
programming lock. To unlock the MultiRanger, access this parameter and enter 1954.
P002 Material
Specifies material type.
Single Point Model Dual Point Model
Parameters
Primary Index
Global Transducer
mmmmm
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
P004 Transducer
Specifies the Siemens Milltronics transducer connected to the unit.
Primary Index
Single Point Model Dual Point Model
Global Transducer
0 * No transducer attached (preset for Dual Point)
Parameters
1 ST-25
2 ST-50
mmmmm
100 STH
101 XCT-8
Values
102 * XPS-10 (preset for Single Point Model)
103 XCT-12
104 XPS-15
112 XRS-5
250 mA input [MR 200]
• mA Input (P250 to P260)
• P842 Short Shot Frequency
• P843 Long Shot Frequency
Related
• P844 Short Shot Width
• P845 Long Shot Width
• P852 Short Shot Range
Changing this value automatically changes the units displayed for many parameters.
Existing values are converted and do not have to be re-entered.
P006 Empty
Enter distance in units (P005) from the face of the transducer to the process empty point.
Primary Index Transducer
Range: 0.000 to 9999
Values
Preset: 5.000m (or equivalent depending on units)
Alters • P007 Span
Altered By • P005 Units
• P800 Near Blanking
Related • P921 material Measurement
• P927 Distance Measurement
Setting this value also sets Span (P007) unless Span was already set to another value.
Parameters
Span is preset for a value close to the maximum available. Enter a value reflecting
maximum application range.
Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
transducer face as this is the minimum blanking for most Siemens Milltronics transducers
(some require more blanking – see your transducer manual).
Many other parameters are set as a percentage of span (even if they are entered in
units). The values of these other parameters may change if the span is altered after
installation and the other parameters are measured using a level determined upward
from the Empty level toward the transducer face.
MultiRanger 200
All volumes are based on span so it should be set for the maximum volume point if
volume calculations are needed.
Please note that the volume parameters apply only to the MultiRanger 200.
Use these parameters to enable the MultiRanger to show readings based on vessel or
wet well volume (rather than level)..
2 Cone/Pyramid Bottom
3 Parabola Bottom
Values
6 Flat Ends
Parameters
mmmmm
7 Parabola Ends
10 Universal Curved
• P001 Operation
• P051 Maximum Volume
Alters • Pump Efficiency (P180-P186)
• Pumped Volume Totalizer (P622-P623)
• P920 Reading Measurement
Any volume units can be chosen because volume is calculated from empty to maximum
Parameters
span and is scaled according to the Tank Shape (P050) value. mmmmm
Note: Make sure selected chosen units allow LCD volume display.
Examples:
• If max. volume = 3650 m3, enter 3650
• If max. volume = 267500 gallons, enter 267.5 (thousands of gallons)
more information.
mmmmm
V = (1/3)πr2h V = πr2h
In RUN mode, the decimal position adjusts to prevent the number of digits from exceeding
the display capabilities. To keep the decimal place from shifting, reduce the number of
decimal places to that shown at 100%.
Example:
If 100% is 15m, use two decimal places for sample readings of 15.00 or 12.15.
Examples:
• If the measured value is in feet, enter 0.3333 to display the number of yards
• For simple linear, volume conversions set POO5 to 1 (meters) and then enter the
volume measurement per unit to get the correct conversion. For example, if the
reservoir contains 100 litres per vertical meter, use 100 to get the reading in litres.
Parameters
Notes:
mmmmm
• This method does not calculate volume. It must not be used in place of the
volume parameters if any volume dependent features (such as pump
efficiency) are used. To calculate true volumes see Volume (P050 to P055).
• Avoid entering a value that, when multiplied by the maximum current
Reading, exceeds the display capabilities. If value exceeds four digits, EEEE is
shown.
The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.
When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m.
The reading stays at 4.3m until the switch is de-activated.
Note: Activation of the Level Override is subject to the measurement cycle. This
can add up to four seconds to the overall response time depending on operating
conditions and programming.
P069 Password
Parameters
Holds the current password for P000. Select by typing in 069. You cannot scroll to this
mmmmm
parameter.
Primary Index Global
Range: 0 to 9999
Values
Default: 1954
Related • P000 Lock
This parameter is write-only, and can only be selected by entering 069. To change the
password, unlock the device by entering the current password into P000. Then enter the
new password into P069. To lock the device, enter a password other than the correct one
in P000. While the device is unlocked, the password is visible in P000.
to 9999
Values HI Level goes to maximum span
LO Level goes to 0 span (Empty)
HOLd * Level remains at last reading
• P001 Operation
• P006 Empty
• P007 Span
Related • P111 Relay Control Function
• P112 Relay ON Setpoint
• P113 relay OFF Setpoint
• P129 Relay Failsafe
Select the Failsafe Material Level based upon the relay operation required during failsafe
operation.
Entering a Measurement
To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units
(P005).
Relay reaction
The way in which relay programming reacts to the failsafe level depends on P129 Relay
Failsafe (page 142). By default:
• Alarm relays have P129 = OFF and so react to the Failsafe Material Level.
• Control relays have P129 = dE and so de-energize the relay when the unit enters
Failsafe mode regardless of the Failsafe Material Level.
Select an application that is similar to yours and change the parameters required. If none
suit, then refer to P111 Relay Control Function on page 136.
Note: Programming the relays independently is the most common method used. Parameters
mmmmm
Please note that Difference and Average settings are MultiRanger 200 features.
Primary Index Relay
Range: 1 to 3
1 * Point # 1 = Transducer One
Values 2 Point # 2 = Transducer Two
3 Point # 3 = Difference (P001=4) or Average (P001=5)
[MR 200] [MR 200]
• P003 Maximum Process Speed
• P700 Max Fill rate
Altered by: • P701 Max Empty rate
• P070 Failsafe Timer
• P071 Failsafe Material Level
MultiRanger 200
Please note that these features are only available on the MultiRanger 200.
MultiRanger 200.
mmmmm
MultiRanger 200
Values For P111
Control Type #1 Relay Control
Off 0* Relay set off, no action (preset)
Level 1 Based on level setpoints ON and OFF
When level enters the range between ON and OFF
In Bounds 2
setpoints
When level exits the range between ON and OFF set-
General Out of Bounds 3
points
Rate of Change 4 Based on rate setpoints ON and OFF
Temperature 5 Based on temperature setpoints ON and OFF Parameters
Loss of Echo (LOE) 6 When echo is lost
Cable Fault 7 When the circuit to a transducer is opened
mmmmm
Values
Preset: ----
mmmmm
For most applications, the relay is tripped at this point. For IN-BOUNDS and OUT-OF-
BOUNDS alarms, it is the high point in the specified range. This parameter is set
according to Span (P007) even when another reading, such as volume, is shown on
the LCD.
For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF-
BOUNDS alarms, it is the low point in the specified range. This parameter is set to Span
(P007), even when another reading, such as volume, is shown on the LCD.
The relay contact operation is NORMALLY CLOSED for alarms and NORMALLY OPEN for
controls. See P111 Relay Control Function for more information.
Power Failure
When power is cut to the MultiRanger, its relays fail to the following states:
Relay States
Relay Fail State
Parameters
1,2,4,5 Open
3,6 Open or Closed1
mmmmm
1.
Relays 3 and 6 are Form C types, so you can wire it either
NORMALLY OPEN or NORMALLY CLOSED. Check the wiring
before programming.
To use relays 3 or 6 as general alarm indicators, set P118 to 3 – negative logic and wire
the alarm for normally open operation. When an alarm event occurs (see below) or when
power is cut, the circuit closes and the alarm activates.
Positive Logic
In software, all relays are programmed the same way, with ON setpoints indicating when
to change the relay contact state (open or closed). This parameter allows the reversal of
the operation so that relay contacts can be NORMALLY CLOSED or NORMALLY OPEN.
P118 is preset to 2 which is positive logic.
This parameter tests site wiring and control logic programming. Forcing the relay to an
activated or de-activated state is similar to the MultiRanger detecting an event and
responding to it. Helpful in testing new installations and diagnosing control problems.
1 ON (pump by rate)
• P007 Span
• P111 Relay Control Function
Related
• P132 Pump Start Delay
• Rate (P700 to P708)
Use this function when multiple pumps are to be controlled by rate of level change rather
than by setpoints.
The delay between pump starts is set by P132 Pump Start Delay.
This only applies to any relays set to pump control (P111 = 50 to 56).
Notes:
• The MultiRanger will not sacrifice other pumping strategies to ensure that the ratio
is held true
• If the pump relays are set to the same value then the ratio equals 1:1 and all pumps
are used equally (preset)
Use this for operations independent of the Failsafe Material Level (P070).
2 – in bounds alarm
5 – temperature alarm
Preset: 0.000
To clear sediment in a pump-down wet well, run the pump after the normal OFF setpoint
is reached to force some solid material through. This parameter sets the time between
such events. Only the last pump running can run-on.
Your pump capacity determines the amount of material that can be removed. Choose a
value long enough to clean out the vessel bottom, yet short enough not to run the pump
dry. Also be sure that this value does not overlap with P130 (Interval). The timing should
look something like this:
Use this feature to reduce a power surge from all pumps starting at the same time. This
Parameters
This reduces the surge from the first pump starting immediately on power resumption.
When this delay expires, other pumps will start as per P132.
This value is the range in which the setpoints are allowed to deviate in percent or units.
The Relay Setpoints ON and OFF values are randomly varied inside the range to ensure
that the material level does not consistently stop at the same point.
Level Setpoint ON
Range: 1 to 2
This feature groups pumps (relay points 1 - 6) into groups 1 or 2. It is applied to pump
rotation and occurs independently within each group.
Example
If you need to watch pump Relay One to control a flush valve on Relay Two you would set
P170[2]=1.
Global Relay
mmmmm
Range: 0 to 5
Values
Preset: 0
Enter the MultiRanger relay number of the pump with the flush valve. The activation of
this pump relay drives the usage of the flush system. Both P172 Flush Interval [MR 200]
and P171 Flush Cycles [MR 200] are based on the operation of this relay and controls any
relay set to P111 = 64, Flush Valve.
Range: 0 to 9999
Values
Preset: 0
If three flush cycles are required after every ten pump cycles then:
P172 (Flush Interval) = 10
P171 (Flush Cycles) = 3
Range: 0 to 9999
Values
Preset: 0
To start a new flush cycle every ten times the pumps are run, set this to 10.
0 off
1 0 to 20 mA
Values 2 * 4 to 20 mA
3 20 to 0 mA
4 20 to 4 mA
MultiRanger 100
0 OFF
Parameters
2 space space
3 distance distance
0 OFF
2 space space
3 distance distance
5 flow OCM
6 head
7 volume rate
8 mA input
9 comms input
Values
2 Point 2
MultiRanger 200
1 * Point 1
Values 2 Point 2
3 Point 3
This displays as an Auxiliary Reading when key is pressed in the RUN mode and
does not include adjustments made using Trim features (P214 / P215).
Note: This parameter is applicable only if any mA output has the transducer
Point Number as its input source (see P201 and P202).
P201—mA Function
Action
Settings
Parameters
mA input or
Not Applicable
Communications Input
Adjust this value so the device indicates 4.000 mA when P214 is accessed.
mmmmm
Adjust this value so the device indicates 20.00 mA when P215 is accessed.
1 0 to 20 mA
Values
2 * 4 to 20 mA
Ensure this range corresponds to the output range of the external device. All level
measurements will equate % of Span with the % of the mA range.
• P006 Empty
Related
• P007 Span
When using an external mA signal to determine level, the input range must be scaled to
give accurate results.
• P006 Empty
Related
• P007 Span
Range: 0 to 9999
Parameters
Values
Preset: 1
mmmmm
This number in seconds is used in the damping calculations. Larger values damp more
than smaller values and 0 disables the signal filter.
0 Forced OFF
1 Forced ON
Values
2 * Normally Open – 0 (DI open), 1 (DI closed)
0 Forced OFF
Readings are updated continuously even in PROGRAM mode. The value signals a level
override event.
If the unit is powered up without a temperature sensor connected, the value –50°C is
displayed. This information can help trace problems with both built in and external
Parameters
temperature sensors.
mmmmm
Press CLEAR keys to reset the log after a short circuit on the transducer wiring.
Press CLEAR keys to reset the log after an open circuit on the transducer wiring.
Press CLEAR keys to reset the log after a short circuit on the transducer wiring.
Values
Preset: 150°C
Press CLEAR keys to reset the log after an open circuit on the transducer wiring.
Displays the amount of time in minutes since a relay was last activated.
Primary Index Relay
Related • Relay Function (P111) set for any pump control feature
Parameter measures the length of time since a relay was asserted, most often to
determine how long a pump has been running. Alternatively, it can monitor a relay to
show how long it has been in a state of alarm. It resets every time the relay is activated.
Related • Relay Function (P111) set for any pump control feature
Value is displayed with a floating decimal point (the more figures displayed before the
decimal, the fewer displayed after). It is the value displayed when key is pressed in
the RUN mode.
Related • Relay Function (P111) set for any pump control feature
This value is displayed when key is pressed and held for five seconds in RUN mode.
Example
Parameters
P323 = 0017
mmmmm
P322 = 6.294
Totalizer Display = 00176.294
Totalizer units are dependent upon programming. Enter zero 0 (if required) to reset the
totalizer to zero. Alternatively, enter any other (applicable) value, to preset the totalizer to
the necessary value.
Note: A second point is available only if the Dual Point Feature is enabled.
These features can record up to ten Echo profiles, initiated manually (P330), or
Parameters
automatically (P331 et al). If ten Profiles are already saved, addresses 1 through 10 are mmmmm
filled, the oldest automatically initiated record is overwritten. Manually initiated records
are not automatically overwritten. All records are automatically deleted in the event of a
power interruption.
When a record is displayed, results are based on current programming (which may have
been altered since the record was saved). This permits the effect on the echo profile to be
observed when changing an echo parameter.
Code Description
---- no record
Press ENTER to copy the echo profile record in the buffer and save it in the selected
mmmmm
address in the record library. The parameter value field displays the new record
information.
• Press TRANSDUCER to copy the current echo profile into the buffer for display
on Dolphin Plus
To delete a record
Press CLEAR and then ENTER to delete the echo profile record in the selected
address. The value returns to - - - -.
Range: 0 to 1
Values 0 * Off
1 On
Range: 0 to 2
0 Any transducer
Values
1 * Transducer One
Parameters
2 Transducer Two
mmmmm
MultiRanger 200
This feature is preset to Point Number 1. (Alteration is only required if differential or
average Operation [P001 = 4 or 5] is selected.)
Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Primary Index Global
If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0
LOE is not required for an Auto Profile Record to be saved.
Parameters
mmmmm
The RUN Time value is updated once a day, and cannot be reset. However, in the event of
a power interruption, the counter won’t advance. Therefore, a unit that is powered down
on a regular basis will not have an accurate value.
The MultiRanger measures head as referenced to Empty (P006) or OCM Zero Offset
(P605), when Operation is set for OCM (P001 = 6). Flowrate, based on head (at the point of
measure specified by the Primary Measuring Device fabricator) is also calculated and
displayed on the LCD.
Some Primary Measuring Devices require a longer Range Extension (P801) to avoid
entering the LOE failure state if the water level falls below the zero point of the Primary
Measuring Device. See P801 Range Extension on page 202 for more information.
Use this parameter if the Primary Measuring Device (P600) is set to 1 (exponential). It
creates an exponential curve with end points set by Max Head (P603) and Zero Head
(P604) and with the curve based on the specified exponent.
If P601 = 1, the flow characteristic is a straight line
Where:
Q = flow
K = internal constant
Parameters
H = head
mmmmm
Zero Flow
Zero Head
Max. Head
(P603)
Use the exponent specified by the PMD manufacturer, if available, or the sample value
given below.
ISO 1438/1
1 Notch Angle
2 Discharge Coefficient
ISO 4359
1 Approach width
2 Throat width
3 Hump Height
Index Values for
Supported PMDs
4 Throat Length
5 Velocity coefficient
Parameters
6 Discharge coefficient
mmmmm
Palmer Bowlus
1 Flume width
H Flume
1 Flume height
Use this parameter if the Primary Measuring Device is directly supported (P600=2,3,6,7).
The dimensions required for each PMD vary.
For more information on PMD, see page 72.
• P005 Units
Altered By
• P600 Primary Measuring Device
This represents the highest head level supported by the PMD and works in conjunction
with Maximum Flow (P604) to define the highest point in the exponential curve. Use it
when the Primary Measuring Device (PMD) requires a maximum head and flow
reference point. This would include Exponential, Palmer Bowlus Flume, H-Flume, and
Universal breakpoints.
This represents the flow at the highest head level supported by the PMD. and works in
conjunction with Maximum Head (P603) to define the highest point in the exponential
curve. Use it when the Primary Measuring Device (PMD) requires a maximum head and
flow reference point. This would include Exponential, Palmer Bowlus Flume, H-Flume,
and Universal breakpoints.
Also use this parameter with Time Units (P606) to define the flowrate units. The limitation
of four digits is for the LCD only, and the flowrate value is available with greater precision
through communications.
• P005 Units
Altered By
• P007 Span
• P006 Empty
Related • P801 Range Extension
• P926 Head Measurement
This feature can be used for most weirs and some flumes (e.g. Palmer Bowlus) where the
zero reference is at a higher elevation than the channel bottom.
Transducer
Example
Conditions Enter
• Flowrate display: millions of gallons/day, • 376.5 for Maximum Flow (P604)
• Maximum flowrate is 376,500,000 gallons/day • and 4 for Time Units (P606).
In RUN mode, the number of decimal places displayed is automatically adjusted (if
necessary) to prevent the number of Flowrate digits from exceeding display capabilities.
The maximum number of head decimal places is controlled by Decimal Position (P060).
Note: Set this parameter only when using BS-3680/ISO 4359 Rectangular Flume
or BS-3680/ISO 1438/1 Thin Plate V-Notch Weir (P600 = 6 or 7). Use the default
value of 0 for P608 when P600 = 1 to 5.
Ratiometric (P600=all)
1 litres / second
using this parameter. If needed, absolute PMDs can still use ratiometric (P608=0) to
accommodate other units.
The values in the Span for which flowrates are known. See Universal Calculation Support
on page 82 for how to specify universal flows.
These are the flowrates for the related breakpoints. See Universal Calculation Support on
page 82 for how to specify universal flows.
Flow Breakpoints
Zero Flow
Max. Head
Head Breakpoints
Zero Head
Use this to enter the minimum head in units (P005) or as a percent of span.
• P006 Empty
• P062 Offset Reading
Related
• P605 Zero Head
• P664 Temperature
Use this parameter when the reported head is consistently high or low by a fixed amount.
Before using this feature, verify the following parameters are correct:
• Empty (P006)
• Temperature (P664)
Parameters
• Offset Reading (P062=0) mmmmm
-3 .001
-2 .01
-1 .1
Values 0 * 1
1 10
2 100
3 1000
4 10,000
5 100,000
Values
6 1,000,000
7 10,000,000
Enter the factor (powers of 10 only) by which actual volume is divided, prior to display on
the LCD. Use a value such that the eight-digit totalizer doesn’t roll over between readings.
Parameters
Example:
mmmmm
Note: Set the decimal position during initial commissioning of the MultiRanger
200. If the position is changed later, the totalizer data in P322 and P323 will be
incorrect and must be reset according to the new decimal value.
In RUN mode, the number of decimal places displayed is not automatically adjusted.
When the LCD Total value is so large as to exceed display capabilities, the total rolls over
to 0 and continues incrementing.
2 100
mmmmm
3 1000
Values 4 10,000
5 100,000
6 1,000,000
7 10,000,000
• P001 Operation
• P111 Relay Control Function
Related • P114 Relay Duration Setpoint
• P115 Relay Interval Setpoint
• P645 Relay Duration
Parameter is relevant only if Operation is set to OCM or Pumped Volume (P001 = 6 or 7).
The relays on the MultiRanger have a maximum frequency of 2.5 Hz.
Example:
For a Remote Totalizer update by 1000s of volume units, enter 3.
• P001 Operation
• P111 Relay Control Function
Related
• OCM (P600 to P621)
• P642 Flow Sampler Exponent
MultiRanger relay set for the flow sampler operation Relay Function, P111 = 41).
• P001 Operation
• P111 Relay Control Function
Related
• OCM (P600 to P621)
• P641 Flow Sampler Mantissa
Enter the exponent (Z) for the mantissa (Y) in the formula:
Flow Sampler Increment = Y x 10Z Flow units.
Enter minimum contact closure duration (in seconds) required by the device connected.
For the flow sampler function this value is used for both the ON time of the relay and the
OFF time between contacts.
Sound Velocity: Adjusts speed of sound and changes the measurement calculations.
mmmmm
Do Offset calibration at any steady level unless a Sound Velocity calibration is also done.
If both calibrations are done then do Offset at a known high level and Sound Velocity at a
known low level.
Before using this feature, verify the following parameters are correct:
• Empty (P006)
• Temperature (P664)
• Offset Reading (P062)
• Zero Head Offset (P605), if using OCM
Offset Calibration
Begin with a steady level.
Global Transducer
• P653 Velocity
Related
• P654 Velocity at 20°C
Alternatively, if the amount of Offset Correction required is known, enter the amount to be
added to the Reading before display.
P653 Velocity
The value adjusted based on the Sound Velocity at 20 °C (P654) vs. Temperature (P664)
characteristics of air.
Primary Index
mmmmm
Global Transducer
Alternatively, enter the current sound velocity (if known), or perform a Sound Velocity
Calibration (P651). The units used are m/s if P005 = 1, 2, or 3 (ft/s if P005 = 4 or 5).
• P005 Units
Related • P651 Sound Velocity Calibration
• P653 Velocity
After performing a Sound Velocity Calibration, check this value to verify the acoustic
beam atmosphere is air (344.1 m/s or 1129 ft/s).
Alternatively, if the acoustic beam atmosphere sound velocity at 20°C (68 °F) is known,
and the sound velocity vs. temperature characteristics are similar to that of air, enter the
sound velocity.
The units used are m/s if P005 = 1, 2, or 3 (or ft/s if P005 = 4 or 5).
1 * AUTO
2 Temp Fixed
The MultiRanger uses the TS-3 temperature sensor assigned to the transducer. If one is
not connected, the ultrasonic/temperature transducer is used. If the transducer does not
have an internal temperature sensor, the Temp Fixed (P661) value is used.
If the acoustic beam atmosphere temperature varies with distance from the transducer,
connect a TS-3 Temperature Sensor and ultrasonic / temperature transducers, and select
average.
Enter the temperature (in °C) of the atmosphere within the transducer acoustic beam. If
the temperature varies with distance from the transducer, enter the average temperature.
1 * Transducer One
Use this feature if the temperature measurement from both transducers should be
mmmmm
identical, but one is located close to a radiant heat source. Allocate the temperature
measurement of the other transducer to both transducer Point Numbers.
Enter the number of the Transducer whose temperature measurement will be used for
the distance calculation of the Point Number displayed. When both transducers are
allocated to a Point Number, the temperature measurements from each are averaged.
Value is displayed when is pressed in RUN mode (see Readings in Run Mode on
page 22).
If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the
temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.
• P005 Units
Related • P007 Span
• P071 Failsafe Material Level
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
P003 Value Meters/Minute
1 0.1
2 1
3 10
• P005 Units
Related • P007 Span
• P071 Failsafe Material Level
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
P003 Value Meters / Minute
1 0.1
2 1
3 10
• P005 Units
mmmmm
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Fill Rate (P700).
• P005 Units
Related • P007 Span
• P701 Max Empty Rate
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Empty Rate (P701).
Filtered Output
Interval Output
Values
2 1 minute or 50 mm (2 in)
Enter the time or distance interval over which the Rate Value is to be calculated before
the display updates.
This is automatically altered along with Maximum Process Speed (P003).
This value automatically alters the Rate Update Time (P705) and / or Rate Update
Distance (P706). Alternatively, these parameter values may be altered independently.
• P005 Units
Related
mmmmm
• P007 Span
This is the value displayed when is pressed in the RUN mode as described in the
Readings in RUN Mode chart on page 22.
This value is used internally to calculate inflow in pumped volume applications (P622=3).
Press READING to toggle between percent and volume.
• P007 Span
Related
• P713 Echo Lock Window
This value (in % of Span, P007) is automatically altered when Maximum Process Speed Parameters
(P003) is altered. The higher the value entered, the greater the fluctuation stabilized. mmmmm
0 Off
1 Maximum verification
Values
2 * Material agitator
3 Total lock
If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for maximum
verification or material agitator to avoid agitator blade detection. Ensure the agitator is
always ON while the MultiRanger is monitoring the vessel to avoid stationary blade
detection.
When set for max verification or material agitator, a new measurement outside of the
Echo Lock Window (P713) must meet the sampling criterion (P712).
For total lock, Echo Lock Window (P713) is preset to zero 0. The MultiRanger continuously
searches for the best echo according to the algorithm chosen (P820). If the selected echo
is within the window, the window is then centered about the echo. If not, the window
widens with each successive shot until the selected echo is within the window. The
window then returns to its normal width.
When Echo Lock is OFF , the MultiRanger responds immediately to a new measurement
as restricted by the Max Fill / Empty Rate (P700 / P701); however, measurement reliability
Parameters
is affected.
mmmmm
Format: x:y
Values
x = the number of above echoes
Example:
Setting
• P711 = 2, material agitator
• P712 = 5:2
Result
• a new reading will not be validated unlessfive consecutive measurements higher or
two consecutive measurements lower than the current reading occur
• Resetting P711 returns P712 to the respective preset values
Parameters
• P005 Units
Related
• P711 Echo Lock
0 not required
Values
1 * synchronize level monitors
Use this if another level measurement system is mounted nearby, and they are wired
together on the Sync terminal.
Altered by
mmmmm
This feature may only be used to adjust the delay before the next point is scanned. Enter
the amount of delay in seconds. This value is automatically altered when Maximum
Process Speed (P003) is altered.
Use this if transient acoustic noise within the vessel is causing measurement difficulties
due to echoes from one shot being received on the next. If more than one ultrasonic unit
is installed for redundancy, this value should be 0.
Select OFF to display Auxiliary Readings temporarily. Select HOLd to display Auxiliary
Readings until another Auxiliary Reading is selected or programming mode is entered.
See the Hand Programmer section on page 26 for RUN mode auxiliary readings.
P is pressed in the RUN mode. See the Hand Programmer section on page 26 for RUN
mode auxiliary readings.
Range: 0.5 to 10
Values
Preset: 1.5 seconds
• P001 Operation
Related
• P737 Primary Reading
Use this feature to adjust the delay before the display advances to the next Point Number.
Display scrolling is independent from transducer scanning.
Global
mmmmm
Primary Index
Note: Quick Start parameters (P001 – P007) and those changed from factory
default settings cannot be untagged.
0 Off
Values 1 * On
2 Keypad activated
Range: 0 to 3
When this value indicates TOGGLE, then both readings (default and totalizer) are shown
in the time specified in display delay (P732).
If the maximum time is exceeded, no response will be transmitted, and the action
required may not be completed.
The MultiRanger supports the internationally recognized Modbus standard in both ASCII
and RTU formats. Other protocols are available with optional SmartLinx cards.
Range: 0 to 9999
Values
1 * Preset:
For devices connected with the Siemens Milltronics protocol this parameter is ignored.
For devices connected with a serial Modbus slave protocol, this parameter is a number
from 1-247. The network administrator must ensure that all devices on the network have
unique addresses. Do not use the value 0 for Modbus communications as this is the
broadcast address and is inappropriate for a slave device.
This specifies the rate of communication in Kbaud. Any value may be entered but only the
values shown above are supported. The baud rate should reflect the speed of the
connected hardware and protocol used.
P773 Parity
The serial port parity.
Primary Index Communications Port
0 * No Parity
2 Even Parity
Ensure that the communications parameters are identical between the MultiRanger and
all connected devices. For example, many modems default to N-8-1 which is No parity, 8
data bits, and 1 stop bit.
Range: 5 to 8
8 * Modbus RTU
Range: 1 or 2
Values
1 * Preset:
0 * No modem connected
Values
1 Answer only
To use this parameter, ensure that P778 (Modem Available) = 1. Ensure that the value is
low enough to avoid unnecessary delays when an unexpected disconnect occurs but
long enough to avoid timeout while you are still legitimately connected. This parameter
value is ignored by the Modbus Master Drivers, as they automatically disconnect when
Parameters
done.
mmmmm
Hanging Up
If the line is idle and the P779 Modem Inactivity Timeout expires, then the modem is
directed to hang up the line. Ensure that P779 is set longer than the standard polling time
of the connected master device. 0 disables the inactivity timer.
0 * Global
Values
1 Parameter-Specific
Global (0)
The primary and secondary index values are global (they affect all of the parameter
access area at once) and stored in:
• primary index – R43,999
• secondary index – R43,998
Parameter-Specific (1)
The primary and secondary index values are encoded into the format words found
between R46,000 and R46,999. Each format work corresponds with the R44,000 series
number in the parameter access map. For example, the format register R46,111
corresponds to the parameter P111 and the value is stored in R44,111. If the Modbus
protocol (P770 = 2 or 3) is not used this parameter is ignored.
PASS * No errors
If FAIL or ERR1 is displayed in P790 (Hardware Error), go to P791 (Hardware Error Code)
and P792 (Hardware Error Count) for information about the error.
0 * No error
Values Any
Error code; provide this code to your Siemens
other
Milltronics representative for troubleshooting
value
Range: 0 to 9999
Values Error count; provide this number to your Siemens Milltronics repre-
sentative for troubleshooting.
This parameter is used to identify the protocol when SmartLinx is used. If you are not
using SmartLinx, this parameter is not functional. Please see the associated SmartLinx
mmmmm
0 Read Only
1 * Read/Write
Values
Restricted Access – read only except for P799 which is
2
read/write
• P006 Empty
Related • P007 Span
• P833 TVT Start Min
Use this feature if the surface is reported to be near the transducer face but is in fact
Parameters
much further away. Extend this value when changing transducer location, mounting, or mmmmm
aiming.
Please note that changing the Near Blanking cannot correct measurement problems.
Ensure that Span (P007) < Empty (P006) minus Near Blanking (P800)
• P005 Units
• P006 Empty
Related
• P007 Span
• P004 Transducer
This feature is useful in OCM applications where the Empty level is set to the bottom of
the weir, and above the bottom of the channel, and should be used if the surface
monitored can fall past the Empty (P006) level in normal operation. The value is added to
Empty (P006) and can be greater than the range of the transducer. If the surface
monitored can extend beyond Empty (P006), increase Range Extension (in Units (P005) or
% of Span) such that Empty plus Range Extension is greater than the transducer face to
furthest surface to be monitored distance. This is often the case with OCM when using
weirs and some flumes.
0 * Off
Values
1 Submergence transducer
Parameters
• P006 Empty
mmmmm
When a transducer with a submergence shield is submerged, the shield traps an air
pocket that creates a special echo. The MultiRanger recognizes the echo and advances
the reading to the highest level and operates displays and outputs accordingly. This
feature is effective for when power is returned while the transducer is submerged.
1 Short
Values
2 * Short and long
• P006 Empty
• P805 Echo Confidence
Related
• P804 Confidence Threshold
• P852 Short Shot Range
Increases MultiRanger response when the monitored surface is close to the transducer
face. Select short and long to have short and long acoustic shots fired for each
measurement, regardless of the transducer to surface distance. Select short to have only
short shots fired if the Echo Confidence (P805) produced by a short shot exceeds the
short Confidence Threshold (P804) and the monitored surface is always within the Short
Shot Range (P852).
Range: 0 to 99:0 to 99
Values
Preset: 10:5
Sonic Intelligence®. Values are entered as two numbers separated by a decimal point.
The first number is the short shot confidence and the second number is the long shot
confidence.
Note: The decimal point is replaced with a colon (:) on the display.
y = long (0 to 99)
Use this feature to monitor the effect of transducer aiming, location, and mechanical
transducer / mounting isolation.
Both short and long shot Echo Confidence is displayed. (To display this value in the
auxiliary display while the unit is running, press for 4 seconds.)
Display Description
x:-- short shot confidence value, (long shot not used).
--:y long shot confidence value, (short shot not used).
x:y short and long shot confidence values (both used).
E transducer cable is open or short circuited.
--:-- no shots were processed for Sonic Intelligence® evaluation.
P807 Noise
Displays the average and peak ambient noise (in dB above 1 uV RMS) being processed.
Primary Index Transducer
The noise level is a combination of transient acoustic noise and electrical noise (induced
into the transducer cable or receiving circuitry). See Noise Problems in the
Troubleshooting Section on page 234.
Parameters
mmmmm
Use this to select the algorithm(s) the Sonic Intelligence® echo selection is based on.
Use P805 Echo Confidence (page 204) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm, either by entering the numeric
Parameters
0 Off
Values
1 * On
• P820 Algorithm
• P822 Narrow Echo Filter
Related
• P823 Reform Echo
• P825 Echo Marker Trigger
Use P821 if interference spikes are on the long shot Echo Profile display.
0 = OFF (preset)
Values
greater = wider
• P820 Algorithm
• P821 Spike Filter
Related
• P823 Reform Echo
• P825 Echo Marker Trigger
Use this for transducer acoustic beam interference (e.g. ladder rungs). Enter the width of
false echoes (in ms) to be removed from the long shot Echo Profile. When a value is keyed
Parameters
in, the nearest acceptable value is entered. mmmmm
0 = OFF (preset)
Values
greater = wider
• P002 Material
• P820 Algorithm
Related • P821 Spike Filter
• P822 Narrow Echo Filter
• P825 Echo Marker Trigger
Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates
slightly, though the monitored surface is still. Enter the amount (in ms) of long shot Echo
Profile smoothing required. When a value is keyed in, the nearest acceptable value is
entered.
Range: 5 to 95%
Values
Preset: 50%
• P820 Algorithm
• P821 Spike Filter
Related
• P822 Narrow Echo Filter
Parameters
Use this feature if the reported material level fluctuates slightly, due to a variable rise in
the leading edge of the true echo on the Echo Profile.
Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the
Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo.
This value is preset to 50%.
6 TVT Slopes
Select the TVT type which gives the highest confidence (P805) under all level conditions.
Use this parameter with caution, and do not use TVT Slopes with the bF or bLF Algorithm
(P820).
0 * Off
Values
1 On
Turn the TVT Shaper ON before using P832 and afterwards. Turn the TVT Shaper ON and
OFF while monitoring the effect to pick up the true echo.
Range: -50 to 50
Values
Preset: 0
Use this feature to bias the shape of the TVT curve to avoid selecting false echoes from
fixed objects.
Adjustment to this parameter is best done while viewing the echo profile with Dolphin
Plus. Refer to the Dolphin Plus online help for details.
The TVT curve is divided into 40 breakpoints, accessible by enabling the point number as
the breakpoint index field. Each breakpoint is normalized to a value of 0, as displayed in
the parameter value field. By changing the breakpoint value, up or down, the intensity of
the bias applied to that breakpoint of the curve is respectively changed. By changing the
value of adjacent breakpoints, the effective bias to the shaper can be broadened to suit
the desired correction. In the case of multiple false echoes, shaping can be applied along
different points of the curve. Shaping should be applied sparingly in order to avoid
missing the true echo.
Values
Preset: 50
Enter the minimum TVT Curve start point (in dB above 1 uV RMS).
This feature should only be used if increased Near Blanking (P800) would extend farther
than desired into the measurement range.
Range: 0 to 9999
Values
Preset: 30
Enter the time (in ms) for the TVT Curve to decrease from the TVT Start Min (P833) point
to the TVT Curve baseline.
Use this feature to adjust the slope declination, and use it in conjunction with TVT Start
Duration (when a long flat TVT Type is selected) to ensure the TVT Curve remains above
the false echoes in the middle of the Echo Profile. Alternatively, if TVT Type is set for TVT
Slopes (P830 = 6), preset is 2000.
Parameters
mmmmm
Notes:
• This function works best when the vessel is empty or nearly empty: use it only if
there is a minimum distance of 2 meters from the transducer face to the material.
• Set P837 and P838 during start up, if possible.
• If the vessel contains an agitator, the agitator should be running.
If MultiRanger 100/200 displays a full level, or if the reading fluctuates between a false
high level and a correct level, set P837 to elevate the TVT in this region and to de-
sensitize the receiver from any ‘base noise’ caused by internal transducer reflections,
nozzle echoes, or other vessel false echoes. Set P838 and then P837 (detailed instructions
follow P838).
0 * Off
Use ’learned’ TVT. (See ’learned TVT curve’ in Display
Values 1
after Auto False Echo Suppression on page 213.)
2 Learn
default TVT
true P839
echo Hover Level
Level (db)
false
echo
Parameters
mmmmm
Distance (meters)
Determine the actual distance from the transducer face to the material surface. Subtract
0.5 m from this distance, and enter the result.
Set Up:
1. Perform this function when the vessel is empty or nearly empty.
2. Determine actual distance from transducer face to material level.
3. Select P838 and key in [distance to material level minus 0.5 m].
4. Press ENTER .
5. Select P837.
6. Press 2 and then press ENTER . P837 will revert to 1 (use Learned TVT)
automatically after a few seconds.
TVT curve
material
(learned)
level
Level (db)
false
echo
Parameters
mmmmm
Distance (meters)
Range 0 to 100%
Values
Default 33 (%)
Range: 0 to 100
Values
Preset: 1
Range: 0 to 200
Values
Preset: 5
Range: 0 to 100
Values
Preset: 20
Enter the minimum echo strength (in dB above 1 uV) derived from a short shot to be
considered for evaluation.
Range: 30 to 100
Values
Preset: 50
P901 Memory
Press ENTER to activate the MultiRanger memory test.
Parameters
mmmmm
Primary Index Global
Values F1 RAM
F3 FLASH data
F4 FLASH code
P903 Display
Press ENTER to activate the display test.
All LCD segments and symbols are temporarily displayed.
P904 Keypad
Press ENTER , then press each keypad key in the following sequence:
P P
As each key is pressed, the associated keypad number is displayed. On successful test
completion, PASS is displayed. FAIL is displayed if a key is pressed out of sequence or the
programmer keypad malfunctions.
• P004 Transducer
mmmmm
Altered By
Values 0 to 6
Enter the relay number and then toggle between energized and de-energized, as
required. Enter 0 to toggle all relays at once.
Applies only to relays with P119 = 0 (algorithm control). Use this parameter to confirm that
relay contacts are opening and closing.
This feature is helpful when P119 does not give expected results even though
programming was verified.
Additionally, this feature may be used to enter a desired value. The mA output
Parameters
immediately assumes the value entered regardless of any restrictions programmed. mmmmm
Err is displayed if the transducer is not equipped with an internal temperature sensor.
• P005 Units
Related • P006 Empty
• P007 Span
• P007 Span
Parameters
Related
mmmmm
• P005 Units
Related • P007 Span
• P605 Zero Head
• P005 Units
Related
• P006 Empty
Use this feature prior to initial programming if arbitrary Parameter Values were used
during a bench test, or after upgrading the software. Following a Master Reset, complete
reprogramming is required.
To perform a Master Reset, access P999 and press CLEAR . C.ALL displays until
the reset is complete.
In dual point units, both points can be reset at the same time by setting the index to 00
and pressing the CLEAR keys.
CAUTION: be careful when using this feature. All data for all points will be reset. For
convenience, be sure to record the values you want to re-enter. Parameters
mmmmm
Index types
Name Description # of indexes
Global This parameter applies to the entire unit n/a
View only This parameter can not be set, only viewed n/a
Parameter depen-
Breakpoint Indexed by breakpoint
dent
Dimension Indexed by PMD dimension up to 7
Discrete Input Indexed by discrete input 2
Echo Profile Indexed by stored echo profile 10
Level Point1 Indexed by level point 1, 2 or 3
mA input1 Indexed by mA input 1
mA output1 Indexed by mA output 0 or 2
Comm. Port Indexed by communications port 2
Relay Indexed by relay 3 or 6
Transducer2 Indexed by transducer 1 or 2
1.
MultiRanger 100: The two level points are: Transducer One and Trans-
ducer Two.
Level point typically has 1 index in Single Point Mode (standard), and 2
indexes in Dual Point Mode (optional).
MultiRanger 200: The three level points are: transducer 1, transducer 2,
and the calculated point which can be difference (P001=4) or average
(P001=5).
Level point typically has 1 index in Single Point Mode (standard), and 2
indexes in Dual Point Mode (optional). A third index is available in both
modes when Operation (P001) is set for DPD (P001=4) or DPA (P001=5).
2.
MultiRanger 200: The number of indexes available in Single Point Mode
(standard) is typically 1, but can be expanded to 2 if Operation (P001) is
set for DPD (P001=4) or DPA (P001=5).
In Dual Point Mode (optional), the number of available indexes is
always 2. Appendix A: Index Types
mmmmm
Transmit Pulse
The transmit pulse consists of one or more electrical “shot” pulses, which are supplied to
the transducer connected to the MultiRanger terminals. The transducer fires an acoustic
“shot” for each electrical pulse supplied. After each shot is fired, sufficient time is
provided for echo (shot reflection) reception before the next (if applicable) shot is fired.
After all shots of the transmit pulse are fired, the resultant echoes are processed. The
transmit pulse shot number, frequency, duration, delay, and associated measurement
range are defined by parameters P803 and P840 to P852.
Echo Processing
Echo processing consists of echo enhancement, true echo selection, and selected echo
verification.
Echo Enhancement is achieved by filtering (P821 and P822) and reforming (P823) the echo
profile. The true echo (echo reflected by the intended target) is selected when that
portion of the echo profile meets the evaluation criteria of Sonic Intelligence®.
Insignificant portions of the echo profile outside of the measurement range (Span P006 +
Range Extension P801), below the TVT Curve (P830, and P832 to P835), and less than the
Confidence Threshold (P804) and Short Shot Floor (P851) are automatically disregarded.
The remaining portions of the Echo Profile are evaluated using the Algorithm (P820) and
Short Shot Bias (P850). The Echo Profile portion providing the best Echo Confidence
(P805) is selected.
True echo verification is automatic. The position (relation in time after transmit) of the
new echo is compared to that of the previously accepted echo. When the new echo is
within the Echo Lock Window (P713), it is accepted and displays, outputs, and relays are
updated per the Fuzz Filter (P710) and Rate Parameters (P700 to P703). If the new echo is
outside of the Window, it is not accepted until Echo Lock (P711) requirements are
satisfied.
Cursor
Echo Marker
TVT Curve
Echo Profile
mmmmm
Auto False-Echo Suppression
False echoes can be caused by an obstruction in the beam path (pipes, ladders, chains,
and such). Such false echoes may rise above the default TVT curve.
P838 allows you to set a distance, and P837 then instructs the Probe LU to ’learn’ where
the obstructions/false echoes are within that distance. The new TVT curve is set above
the false echoes, screening them out.
default TVT
true P839
echo Hover Level
Level (db)
false
echo
Distance (meters)
TVT curve
material
(learned)
level
Level (db)
false
echo
Distance (meters)
Sound Velocity
The sound velocity of the transmission medium is affected by the type, temperature, and
vapor pressure of the gas or vapor present. As preset, the MultiRanger assumes the
vessel atmosphere is air at 20°C (68°F). Unless altered, the sound velocity used for the
distance calculation is 344.1 m / s (1129 ft / s).
Variable air temperature is automatically compensated when a Siemens Milltronics
ultrasonic / temperature transducer is used. If the transducer is exposed to direct
sunlight, use a sunshield or a separate TS-3 temperature sensor.
Also, if the temperature varies between the transducer face and the liquid monitored, use
a TS-3 temperature sensor (submerged in the liquid) in combination with an ultrasonic /
temperature transducer. Set Temp Source (P660) for both, to average the transducer and
TS-3 measurements.
Atmosphere composition other than air can pose a challenge for ultrasonic level
measurement. However, excellent results may be obtained by performing a Sound
Velocity Calibration (P651) if the atmosphere is homogeneous (well mixed), at a fixed
temperature, and under consistent vapor pressure.
The MultiRanger automatic temperature compensation is based on the sound velocity /
temperature characteristics of “air” and may not be suitable for the atmosphere present.
If the atmosphere temperature is variable, perform frequent Sound Velocity Calibrations
to optimize measurement accuracy.
Sound Velocity calibration frequency may be determined with experience. If the sound
velocity in two or more vessels is always similar, future calibrations may be performed on
one vessel and the resultant Velocity (P653) entered directly for the other vessel(s).
If the sound velocity of a vessel atmosphere is found to be repeatable at specific
temperatures, a chart or curve may be developed. Then, rather than performing a Sound
Velocity Calibration each time the vessel temperature changes significantly, the
anticipated Velocity (P653) may be entered directly.
mmmmm
changes state to supply the transmit pulse to the other transducer after the Scan Delay
(P727).
Scan Delay is automatically set by Maximum Process Speed (P003). When high speed
scanning is required (sometimes the case for equipment position monitoring), the Scan
Delay may be reduced. Reduce the Scan Delay only as required, otherwise premature
scanning relay fatigue could occur.
MultiRanger 200
When two transducers are connected and configured in a dual point unit, the
MultiRanger will scan each in turn via the scanner relay. When a single point
MultiRanger is programmed for differential or average level Operation (P001 = 4 or 5), two
transducers of the same type must be used.
This calculation creates a cubic spline approximation of the level/volume curve, providing
best results if the curve is non-linear, and there are no sharp angles.
Select at least enough breakpoints from the curve to satisfy the following:
• two breakpoints very near the minimum level
• one breakpoint at the tangent points of each arc
• one breakpoint at each arc apex
• two breakpoints very near the maximum level
For combination curves, enter at least two breakpoints immediately before and after any
sharp angle (as well as one breakpoint exactly at the angle) on the curve.
Flow Calculation
Please note that the Flow Calculation feature is only available on the MultiRanger 200.
The MultiRanger provides numerous OCM flow calculation features (P600 to P611).
If the PMD (primary measuring device) does not match any of the eight preset PMD
calculations, or if a PMD is not used, select a Universal Volume calculation. Use the head/
flow graph or chart provided by the PMD fabricator (or create one based on the PMD or
channel dimensions).
Based on the graph, choose the Universal Flow calculation, and select the head versus
flow breakpoints to be entered (32 max). Generally, the more breakpoints entered, the
greater the flow calculation accuracy.
mmmmm
This flow calculation creates a piece-wise linear approximation of the head/flow curve.
This option provides best results if the curve has sharp angles joining relatively linear
sections.
Enter a Head Breakpoint at each point where the head/flow curve bends sharply (2
minimum). For combination curves (mostly linear but include 1 or more arcs), enter
numerous breakpoints along the arc, for best flow calculation accuracy.
See also Typical Flow Characterization on page 82.
Select at least enough breakpoints from the curve to satisfy the following:
• two breakpoints very near the minimum head
• one breakpoint at the tangent points of each arc
• one breakpoint at each arc apex
• two breakpoints very near the maximum head
If any of these parameters are independently altered, a Maximum Process Speed (P003)
parameter alteration automatically resets the independently altered value.
Slower Maximum Process Speed (P003) provides greater measurement reliability. Faster,
independently set Max Fill (P700) and Max Empty (P701). Rates may be impeded by Echo
Lock (P711), Scan Delay (P727), and Shot Delay (P728) values.
If the setup becomes too confusing use P999 to reset and start again.
Appendix C: Troubleshooting
Symptom Cause Action
Display blank, transducer Check power supply, wiring, or
No power.
not pulsing. power fuse.
Check programmer usage:
mmmmm
No response to program- Obstructed infrared interface, 15 cm (6”) from faceplate
mer. defective programmer. pointed at upper target.
The exact relationship between noise and maximum distance is dependent on the
transducer type and the material being measured. Any average noise level greater than
20 dB is probably cause for concern unless the distance is much shorter than the
maximum for the transducer.
mmmmm
Acoustical Noise
To confirm that the problem is acoustical, place several layers of cardboard over the face
of the transducer. If the noise is reduced, the noise is definitely acoustical.
Appendix C: Troubleshooting
speed drives. Even so, it should not be located near high voltage wires or switch gear.
Try moving the electronics to a different location. Often moving the electronics a few
meters farther from the source of noise will fix the problem. Shielding the electronics is
also an option, but it should be a last resort. Proper shielding is expensive and is difficult
mmmmm
to install properly–the shielding box must enclose the MultiRanger electronics
completely, and all wires must be brought to the box through grounded metal conduit.
Use Dolphin Plus to graphically display Edit the parameter values. Use F1
the echo profile at the installation. to get online help at any time.
Interpret the echo profile and change
relevant parameters.
Press (five times or more to verify stability and overcome any echo lock P711).
Appendix C: Troubleshooting
Increase the Failsafe Timer (P070) value, if failsafe operation will not be compromised by
the larger value.
Try this only if LOE shows for short periods of time.
mmmmm
Install a Transducer with a Narrower Beam
Sometimes the interference echoes from the sides of a vessel can cause the MultiRanger
to lock onto a consistent, incorrect level. Try installing a longer range (narrower beam)
transducer, enter the new transducer model (P004), and (if necessary) optimize aiming
and frequency again.
Always contact your Siemens Milltronics service personnel before selecting a transducer
to solve this type of problem.
Fixed Reading
If the Reading is a fixed value, regardless of the transducer to material surface distance,
ensure the:
1. Transducer acoustic beam is free from obstruction.
2. Transducer is properly aimed
3. Transducer is not in contact with any metal object.
4. Material mixer (if used) is operating while the MultiRanger is operating. If it is
stopped, ensure that the mixer blade is not stopped under the transducer.
Nozzle Mountings
If the transducer is mounted on or in a nozzle, grind smooth any burrs or welds on the
inside or open end (the end that opens into the vessel). If the problem persists, install a
reaches that point extend the Near Blanking (P800) to a distance to just past the
obstruction.
Adjust the TVT to Ignore the Echo
Use Auto False Echo Suppression (P837-P839) to automatically shape around false
echoes.
Wrong Reading
If the Reading is erratic, or jumps to some incorrect value periodically, ensure the:
1. Surface monitored is not beyond the MultiRanger’s programmed range or the
transducer’s maximum range.
2. Material is not falling into the transducer’s acoustic beam.
3. Material is not inside the blanking distance of the transducer.
Liquid Splashing
If the material monitored is a liquid, check for splashing in the vessel. Enter a lower
Maximum Process Speed (P003) value to stabilize the Reading, or install a stilling well.
(Contact Siemens Milltronics or your local distributor.)
Transducer Ringing
Appendix C: Troubleshooting
If the transducer is mounted too tightly, or if it is mounted so that its side touches
something, its resonance characteristics change and this can cause problems.
Normal Ring Down
mmmmm
Ring Down
Echo Profile
TVT curve
Time of Correct Echo
Echo Profile
TVT Curve
Pump Duty
The pump duty indicates in what sequence pumps are started.
mmmmm
Pump Groups
The MultiRanger groups pumps that use identical pumping strategies based on the value
of Relay Control Function (P111). Generally, one group of pumps corresponds to one wet
well or reservoir.
MultiRanger 100
All of these algorithms can be used to start multiple pumps (assist).
The MultiRanger 100 and MultiRanger 200 have three main methods of pump
control:
Fixed
Starts pumps based on individual setpoints and always starts the same pumps in the
same sequence.
Alternate
Starts pumps based on the duty schedule and always leads with a new pump.
Service Ratio
Starts pumps based on user-defined ratio of running time.
Relay Table
The following table shows relay status when each setpoint is reached.
Relays
Index 1 2 3
Setpoints
On 3 On On On
On 2 On On Off
On 1 On Off Off
Off 0 Off Off Off
Relays
Index 1 2 3
Setpoints
On 3 Off Off On
On 2 Off On Off
On 1 On Off Off
Off 0 Off Off Off
mmmmm
On 3 On On On
Setpoints
On 2 On On Off
On 1 On Off Off
Off 0 Off Off Off
Cycle 2 Relays
1 2 3
On 3 On On On
Setpoints
On 2 Off On On
On 1 Off On Off
Off 0 Off Off Off
Cycle 3 Relays
1 2 3
On 3 On On On
Setpoints
On 2 On Off On
On 1 Off Off On
Off 0 Off Off Off
Relay Table
Cycle 1 Relays
1 2 3
On 3 Off Off On
Setpoints
On 2 Off On Off
On 1 On Off Off
0ff 0 Off Off Off
Cycle 2 Relays
Appendix D: Pump Control
1 2 3
On 3 On Off Off
Setpoints
On 2 Off Off On
On 1 Off On Off
mmmmm
On 2 On Off Off
On 1 Off Off On
Off 0 Off Off Off
Please note that this feature applies to the MultiRanger 200 only.
Please note that this feature applies to the MultiRanger 200 only.
The setpoints associated with the relays are grouped so they can be redistributed based
on pump RUN time ratios. The next pump to start or stop is the one with the required time
to actual time ratio.
Over time the number of hours demanded of each pump will conform to the ratios
specified. Usually, the ratios are specified in percent values.
mmmmm
This algorithm starts pumps in the same way as Alternate Duty Assist but uses staggered
OFF setpoints to shut the pumps down. When the first OFF setpoint is reached the FIFO
rule shuts down the first pump started. If the pumps started in sequence 2,3,1 then they
would be shut down in sequence 2,3,1.
Updating Software
To update the software in the MultiRanger, please contact your Siemens Milltronics
representative to obtain the software. For a complete list of representatives, go to
www.siemens.com/processautomation.
WARNINGS:
1. All parameter values will be lost during software upgrade.
Record your current parameters manually or using Dolphin Plus
before upgrade.
2. Disable all pumps and alarms before updating software, as
relays can change state during the software update causing pumps
to turn on or off .
Appendix E: Updating
Transducer
mmmmm
Existing installation
RG62 coaxial cable has been used to make the extension. The level controller might be a
MultiRanger Plus, HydroRanger, HydroRanger Plus or one of our other level controllers.
Transducer
Transducer
Appendix F: Upgrading
mmmmm
Example
In the MultiRanger Plus each relay had a dedicated parameter number for its function,
ON and OFF points.
MultiRanger Plus Relay One
• P-8: Function
• P-9 : ON setpoint
• P-10: OFF setpoint
MultiRanger 100/200 uses P111 for all relays and indexes these parameters.
• P-111: Function
• P-112: ON
• P-113: OFF
The following tables show the differences between the MultiRanger Plus and the
MultiRanger 100/200. They each show one relay programmed as a high alarm, and two
relays programmed for pump control with alternating pump starts:
7ML19981FB05
9.46
NOTES:
1) USE ONLY CONDUIT HUBS CERTIFIED / APPROVED AS TYPE 4X.
2) NON METALLIC ENCLOSURE DOES NOT PROVIDE GROUNDING BETWEEN CONDUIT CONNECTIONS.
USE GROUNDING TYPE BUSHINGS AND JUMPER WIRES.
3) DIMENSIONS INCHES
0.875
Product Group
ULTRASONICS
NONE
14/ AUG / 02
DRILL FOR 3/4” R. CLYSDALE
DRILL FOR 1/2” CONDUIT HUB HINGED 6 X 9 ENCLOSURE WITH
T. ADAM
CONDUIT HUBS 1.688 CONDUIT ENTREES & ASSEMBLE
S. NGUYEN
FOR CLASS 1 DIV 2 APPLICATIONS
3.25 PETERBOROUGH
4.625 23650314
General Appendix G: Conduit Entry for
0
2365031400 1:1 1 2
Page 251
Appendix G
mmmmm
Appendix G
Page 252
DISPLAY
TB2
1
2
BOARD
1.75”, 6-32
REL AY 6
REL AY 5
REL AY 4
REL AY 3
REL AY 2
REL AY 1
NYLON
STANDOFF
1.75” , 6-32
BRASS
STANDOFF
(3 PLACES)
INPUTS
DISCRETE
2
1
RS4 85
1.12” RICHCO
4 - 20 mA
OUTPU TS
mA INP UT
TS-3
L2/N L1
COM
B
A
SYNC
2
1
SHIELD
SHIELD
DUAL LOCKING
TB1
TB3
MINI NYLON POWER
STANDOFF SUPPLY
(4 PLACES) BOARD
CERTIFIED
TYCO ELECTRONICS
MODULAR PLUG
5-641335
(SUPPLIED BY
CUSTOMER)
CERTIFIED MAIN
TYCO ELECTRONICS BOARD
MODULAR JACK
520425-2
(INSTALLED BY
SIEMENS MILLTRONICS)
Product Group
ULTRASONICS
NONE
14/ AUG / 02
R. CLYSDALE
HINGED 6 X 9 ENCLOSURE WITH
T. ADAM
CONDUIT ENTREES & ASSEMBLE
S. NGUYEN
FOR CLASS 1 DIV 2 APPLICATIONS
PETERBOROUGH
23650314 0
2365031400 1:1 2 2
7ML19981FB05
Appendix H: Software Revision History
MultiRanger 100
Soft-
ware Date Changes
Rev.
1.00 08/15/2005 • Pilot Release.
mmmmm
1.03 08/27/2002 • Clarified return message for factory RS232
test.
• Prevent entering of strings with invalid fields
in Dolphin Plus.
• Properly convert ft/sec to m/sec in P654.
• Eliminated rogue watchdog resets from
repeatedly pressing hand programmer enter
while in P901-P90.
• Allow 32 bit read/write as seconds.
• Factory mode lock is written to flash.
• Cleaned up compiler errors and Lint
warnings.
• Modified handling of non-quick start
parameters.
• Modifications for Production Testing.
• Users may now configure the SmartLinx
memory map.
mode.
• Improved Production Testing support.
• Improved reset behaviour.
• Changed default mA trim values.
• Improved functionality of downloading
breakpoints in Dolphin Plus.
1.06 05/27/2004 • RCVR offset limits are no longer handled in
the code.
1.07 08/30/2004 • P060, P005 Dependancy removed.
• Split Values - Parameters with the "xx:yy"
format now being limited properly.
• Temperature Spike - Temperature readings
now being protected from other units’
transmit pulse.
• TVT Shift - A rounding error in the number of
samples, caused the TVT position to shift.
• Auto False Echo Suppression - Device learns
the shape of an empty tank to automatically
suppress false echos.
• SIMATIC PDM Compatability - Device uses
Modbus to communicate with PDM. DDs
required.
mmmmm
command allows Tag, Description, Message,
and Date.
1.09 11/28/2005 • Correction for manual Shaper TVT shift due
to change in velocity.
• Resolved issue of reading some floats as
decimal shifted integers.
• The submergence algorithm now
implemented with the thresholds defined.
• Changes to support single DUART.
1.10 not released
mmmmm
mode.
• Improved Production Testing support.
• Improved reset behaviour.
• Changed default mA trim values.
• Improved functionality of downloading
downloading in Dolphin +.
1.06 05/27/2004 • RCVR offset limits are no longer handled in
the code.
1.07 08/30/2004 • OCM Time Units improvement.
• Totalizer enhancement to prevent a rounding
error puting the totalizer into an unstable
"mode."
• Totalizer - Access to totalizer in OCM mode
from Modbus map (reg 41040).
• P060, P005 Dependancy removed.
• Split Values - Parameters with the "xx:yy"
format now being limited properly.
• Temperature Spike - Temperature readings
now being protected from other units’
transmit pulse.
• TVT Shift - A rounding error in the number of
samples caused the TVT to shift position.
• Auto False Echo Suppression - Device learns
the shape of an empty tank to automatically
suppress false echos.
• SIMATIC PDM Compatability - Device uses
Modbus to communicate with PDM. DDs
required.
Parameter Charts
P052 Tank Dimension A
P053 Tank Dimension L
mmmmm
P054 Level Breakpoints record values on a separate sheet.
P055 Volume Breakpoints record values on a separate sheet.
Reading Value
P060 Decimal Position
P061 Convert Reading
P062 Offset Reading
P064 Reading Override Enable
P065 Reading Override Value
P066 Override Time Delay
P069 Password
Failsafe
P070 Failsafe Timer
P071 Failsafe Material Level
P072 Failsafe Level Advance
Relays
P100 Relay Set Up (G)
P101 Hi Alarm
P102 Lo Alarm
P103 Hi Hi Alarm
[MR 200]
P136 Wall Cling Reduction [MR 200]
P137 Pump Group [MR 200]
Flush Systems
P170 Flush Pump [MR 200]
P171 Flush Cycles [MR 200]
P172 Flush Interval [MR 200]
P173 Flush Duration [MR 200]
mA Outputs
P200 mA Output Range
P201 mA Output Function
P202 mA Output Allocation
mA Output Value / Transducer
P203
(V)
Independent mA Setpoints
P210 0/4 mA Output Setpoint
P211 20 mA Output Setpoint
mA Output Limits
P212 mA Output Min Limit
P213 mA Output Max limit
Parameter Charts
P300 Temp, Transducer max
P301 Temp, Transducer min
mmmmm
P302 Temperature, Sensor max
P303 Temperature, Sensor min
Data Logging - Record Readings
P304 Reading Max
P305 Reading Min
Data Logging - Pump Records
P309 Pump RUN Time
P310 Pump Hours
P311 Pump Starts
P312 Pump Run Ons [MR 200]
Data Logging - Flow Records
P320 Flow Max [MR 200]
P321 Flow Min [MR 200]
LCD Totalizer
P322 LCD Total Low [MR 200]
P323 LCD Total High [MR 200]
Profile Records
P330 Profile Record
P331 Auto Record Enable
Parameter Charts
P701 Max Empty Rate
P702 Filling Indicator
mmmmm
P703 Emptying Indicator
P704 Rate Filter
P705 Rate Update Time
P706 Rate Update Distance
P707 Rate Value
P708 Volume Rate Display [MR 200]
Measurement Verification
P710 Fuzz Filter
P711 Echo Lock
P712 Echo Lock Sampling
P713 Echo Lock Window
Transducer Scanning
P726 Level System Sync
P727 Scan Delay
P728 Shot Delay
P729 Scan Time
Display
P730 Auxiliary Reading
P731 Auxiliary Reading Key
Parameter Charts
P840 Short Shot Number
P841 Long Shot Number
mmmmm
P842 Short Shot Frequency
P843 Long Shot Frequency
P844 Short Shot Width
P845 Long Shot Width
P850 Short Shot Bias
P851 Short Shot Floor
P852 Short Shot Range
P900 Software Revision Number
P901 Memory
P902 Watchdog
P903 Display
P904 Keypad
P905 Transmit Pulse
P906 RS-232 Port
P908 Scanner
P910 Toggle Relays
P911 mA Output Value
P912 Transducer Temperature
P913 Sensor Temperature
routing .......................................................9
cabling guidelines ......................................... 92 external totalizers ..........................................70
calibration F
mA output .............................................. 48 failsafe ..............................................................39
characterization chart .................................. 51 by relay ...................................................44
communication ports fat ring ...............................................................65
configuring ............................................ 94 first in first out (FIFO) ........................... 61, 247
communications ............................................ 89 fixed duty assist ..............................................60
communications installation ....................... 92 flash update ...................................................249
configuration .....................................................2 flow calculation ............................................230
control flow sampler ....................................................71
rake ......................................................... 68 flume
controlling the display .................................. 24 cut throat ................................................81
H flume ....................................................77
M weirs ........................................................78
mA zero head ................................................73
calibrating .............................................. 48 operation
input ........................................................ 48 dual point ................................................38
loops ....................................................... 48 single point ............................................37
output .............................................. 48, 49 options, adding .............................................249
map ID .............................................................. 98 out of bounds ..................................................55
maximum process speed .......................... 232 outputs ................................................................5
maximum separation .................................... 92 P
measurement parameter
difficulties ............................................ 237 relays .......................................................42
dual point ............................................... 38 parameter access
set up ...................................................... 37 data types .............................................107
setting up ............................................... 37 format words .......................................105
SCADA ............................................................. 89 U
scrolling parameters .................................... 31 UINT32 ............................................................107
scum ring See wall cling ............................. 65 units or percent ..............................................32
security ............................................................ 32 universal
service ratio example ..................................................51
applications ........................................... 63 volume ....................................................51
duty assist ........................................... 246 unsigned double precision integer ..........107
duty backup ........................................ 247 updating software ........................................249
simulation ........................................................ 85 V
level cycle .............................................. 85 verify
OCM flow characterization ............... 86 mA output ...............................................49
single measurement ........................... 85 volume ..............................................................50
volume characterization .................... 86 calculation ............................................229
Index
mmmmm
Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. 2006
1954Technology Drive, P.O. Box 4225 Subject to change without prior notice
Peterborough, ON, Canada K9J 7B1
Tel: (705) 745-2431 Fax: (705) 741-0466 Rev. 5.0
Email: [email protected]
*7ml19981FB05*
Printed in Canada