Wiring S464G1007

To Addressable Pull Station


Next Document 52145 I56-3811-001
Addressable
From Device
FACP
SLC
SLC
S464G1007 Addressable Pull Station
Document 52145 I56-3811-001
1 2 3 4
Description STRIP GAUGE

The S464G1007 Addressable pull station is a non-coded, dual-action manual pull station
with a key-lock reset feature. It provides an intelligent fire alarm control panel (FACP)
with one addressable alarm initiating input. Reference SLC document 51932 (Honeywell
form #95-7675) for pull station compatibility with fire alarm control panels. The address-
able module is housed inside the pull station. The S464G1007 meets the ADAAG controls
and operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5
lb. maximum pull force to activate the pull station. Operating instructions are molded into
the pull station handle along with Braille text. Molded Terminal numbers are also present.

P0193-00
P0267-00
Ratings
Normal Operating Voltage: 24 VDC.
Average Operating Current (LED Flash): 375 µA.
Maximum Operating Current (LED On): 5 mA.
Temperature Range: 32° F - 120° F (0° C - 49° C).
Relative Humidity Range: 10% - 93% non-condensing.

Installation CAUTION! Do not detach the door of the pull station during installation. The door of
The S464G1007 Addressable pull station can be surface mounted to an SB-10 or SB-I/O the pull station cannot be reattached to the backplate after the backplate has already been
surface backbox or semi-flush mounted on a standard single-gang, double-gang or 4″ (10.16 installed onto an electrical box..
cm) square electrical box. The optional BG-TR trim ring can be used if the S464G1007 is
to be semi-flush mounted. CAUTION!
Install the Honeywell S464G1007 addressable pull station in accordance with these instructions,
Operation applicable NFPA standards, national and local Fire and Electrical codes and the requirements
To activate the dual-action pull station, push in and pull down on the handle. The word of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conduct-
‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta- ed in accordance with the appropriate NFPA standards. Failure to follow these directions may
tion is reset. result in failure of the device to report an alarm condition. Honeywell is not responsible for
devices that have been improperly installed, tested or maintained.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station. ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to an object, the
Resetting the Pull Station maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space
1. Insert the key into the lock and rotate 1/4 turn counterclockwise. allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
2. Open the door until the handle returns to normal. 54 inches (137.16 cm).
3. Close and lock the door.

NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Open-
ing the door will not activate or deactivate the alarm switch. (over for Programming information)
Setting the S464G1007 Address
The S464G1007 Addressable pull station is factory preset with address ‘00.’ Set the address
for the pull station by turning the rotary address switches on the addressable module mounted
inside the pull station. Only one device per address is allowed. Multiple modules may not
be set to the same address on the Signaling Line Circuit. Once the address is set, record it
in the space provided on the product ID label located inside the pull station.

ROTARY ADDRESS SWITCHES

LED
LED OPERATION
Normal:
Flash RED
Alarm:
Steady RED
15 0 0
14 1 1
Note: LED is visible 13 2 2
through translucent
4 3 2 1
12 3
3
handle. 11
4 4
10 5 5
9 8
9 8
7 6 7 6
TENS ONES

Note – Opening the


L
pull station door
R MA
will not activate or NO
deactivate the alarm
switch.
ACT
IVAT
ED
P/N50997 REV-A LOOP ADDRESS

M
UL NOTIFIER
NBG-12
PRODUCT Series
AHDHDH
IDENTIFICATION
UL Approved Label
LISTED
23424
NON-CODED
LABEL
Here
FIRE ALARM BOX Made in
U.S.A.
P0105-00

REFER TO DOCUMENT