Programming The Loop Detector Vek M4D: Classax-V
Programming The Loop Detector Vek M4D: Classax-V
Programming the
Loop Detector
VEK M4D
Open housing as described in section 4.2 of the manual. Set Way 1 of the DIP switch to ON,
all others to OFF. Leave Jumpers in place (as shown). Close housing.
-2-
1.2 Disable Talk-Only Mode
Remove Jumper
Remove jumper installed in middle position of the "Bus Interface" header on top of the loop
detector.
Connect loop detector to PC via a simple RS-485 adapter. The MD-440 is only listening and
will not affect communication. Do not use interfaces with buffering capabilities, for example a
so-called "serial host" for Ethernet but only simple level converters to avoid timing issues.
-3-
2. Software Settings
Click "Interface"
-4-
The program will now scan the bus for detectors. If everything is ok, it will find Detector 1. If
necessary update "Port Setting". Required parameters are 9600,8,E,1 (even parity!)
-5-
2.3 Switch Off Unused Loops
When the program has recognized failure of loops 2-4, click "Multiplex-Mode".
-6-
Disable loops 2-4, set sampling speed to "x4" and Filter to "ON". Click "Set".
-7-
2.4 Check Frequency
Click "Frequency"
-8-
In case loop 1 has configured correctly and LED1 is not flashing just verify setting under
"Loop 1..4" to be "automatic".
Otherwise select frequency band under "Loop 1..4", click "Set" and then "Request". Repeat
this step with different selections until frequency within selected band is displayed under
"Frequency" and LED1 stops flashing.
If several systems are in use select different frequency bands for adjacent loops.
-9-
2.5 Set Level/Hysteresis
Click "Level/Hysteresis"
- 10 -
Change setting "Loop 1" to "Level: 40" and "Hysteresis : 75%". Click "Set".
- 11 -
2.6 Check Hold Time
- 12 -
Verify that Loop 1 is set to "20 min". In case of changes click "Set".
- 13 -
2.7 Check Output Timing
- 14 -
Set all channels "On-Delay: 0ms", "Off-Delay: 0ms" and "min. Duration: 200ms". In case of
changes click "Set".
- 15 -
2.8 Check Output Mode
- 16 -
Ensure that all channels are set to "Normal mode" and "Loop fault". In case of changes click
"Set".
- 17 -
2.9 Check I/O Matrix
Ensure that the I/O matrix is configured as shown. Otherwise establish shown setting and
click "Set".
- 18 -
2.10 Enable Signature Transmission
- 19 -
Enable "Amplitude Output". Click "Set".
- 20 -
3. Restore Hardware
Reinstall Jumper
Power loop detector down. Re-install jumper on "Bus Interface" header removed in section
1.2. Remover RS-485 connection to PC.
Important notice
All the information contained herein is believed to be accurate and reliable. However, SENSOR LINE assumes no responsibility
for its use or for any infringements of patents or other rights of third parties that may result from its use. No license is granted by
implication or otherwise under any patent rights of SENSOR LINE GmbH.
SENSORLINE shall not be liable for any special, incidental or consequential damages related to the use of the product.
Our product guides and instructions are continuously updated. Make sure you have got the latest edition. For further information
contact the SENSOR LINE technical support team.
- 21 -