200 To 275 kVA Enclosure LEHF 1108-08 (01-07)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

ENCLOSURES

Exclusively from your Caterpillar® dealer

SOUND ATTENUATED
ENCLOSURES
200-275 kVA, 50 Hz
169-250 kVA, 60 Hz
The fully weatherproof Sound Attenuated enclosures
reduce sound levels to a level that is lower than
European Community regulations.
The enclosures incorporate internally mounted
exhaust silencers and are of extremely rugged
construction to withstand the rough handling
common on many construction sites. They
are designed on modular principles with many
Enclosure pictured may include interchangeable components permitting on-site
optional accessories repair.

FEATURES

ROBUST/Highly Corrosion Security And Safety Transportability


Resistant Construction
● Control panel viewing window ● Tested and certified single
● Stainless steel locks and in a lockable access‑door point lifting facility
hinges
● Emergency stop button ● Lifting points on baseframe
● Zinc plated or stainless steel mounted on enclosure‑exterior
fasteners OPTIONAL FEATURE
● Cooling fan and battery
● Body made from steel charging alternator fully ● Oil field type skid with
components treated with guarded dragging points and fork lift
polyester powder coating truck pockets
● Fuel fill and battery can only
Excellent Access For be reached via lockable access
Maintenance doors

● Two large doors on each‑side ● Exhaust silencing system


totally enclosed for
● Radiator fill access plate operator‑safety
● Lube oil and cooling water
drains piped to exterior of the
enclosure

LEHF1108-08 (01/07)
ENCLOSURES
Exclusively from your Caterpillar® dealer

SOUND PRESSURE LEVELS (dBA)


50 Hz at 1500 rpm 60 Hz at 1800 rpm
Sound
Generator Power 15 m 7m 1m 15 m 7m 1m
Duty
Set Model Level
(LWA) 75% 100% 75% 100% 75% 100% 75% 100% 75% 100% 75% 100%
Load Load Load Load Load Load Load Load Load Load Load Load

Prime 98 N/A N/A N/A N/A N/A N/A 67.0 68.0 73.0 73.0 83.0 83.0
GEH175
Standby 98 N/A N/A N/A N/A N/A N/A 67.0 68.0 73.0 73.0 83.0 84.0
Prime 97 54.6 55.0 60.6 61.0 75.8 75.9 68.0 69.0 73.0 74.0 83.0 83.0
GEH220
Standby 97 54.7 55.2 60.7 61.2 75.8 76.0 68.0 69.0 73.0 75.0 83.0 84.0
Prime 97 54.7 55.4 60.7 61.4 75.8 76.0 68.0 69.0 73.0 74.0 83.0 83.0
GEH250
Standby 97 54.9 55.6 60.9 61.6 75.8 76.2 68.0 69.0 73.0 75.0 83.0 84.0
Prime 97 54.7 55.7 60.6 61.7 75.6 76.0 N/A N/A N/A N/A N/A N/A
GEH275
Standby 97 54.9 63.3 60.9 62.3 75.7 76.2 N/A N/A N/A N/A N/A N/A
Levels in accordance with European Noise Directive (2000/14/EC)

D
C

B A

DIMENSIONS AND WEIGHTS


Generator A: B: C: D: *E: Fuel Capacity: Weight:
Set Model mm (in) mm (in) mm (in) mm (in) mm (in) l (US gal) kgs (lb)

GEH175 3894 (153.3) 1300 (51.2) 1875 (73.8) 1996 (78.6) 1700 (66.9) 550 (145) 2797 (6166)
GEH220 3894 (153.3) 1300 (51.2) 1875 (73.8) 1996 (78.6) 1700 (66.9) 550 (145) 2944 (6490)
GEH250 3894 (153.3) 1300 (51.2) 1875 (73.8) 1996 (78.6) 1700 (66.9) 550 (145) 3029 (6678)
GEH275 3894 (153.3) 1300 (51.2) 1875 (73.8) 1996 (78.6) 1700 (66.9) 550 (145) 3094 (6821)

*Clearance required both sides


Weight with lube oil, no coolant, no fuel.

Information contained in this publication may be considered confidential. www.CAT-ElectricPower.com


Market: International Discretion is recommended when distributing.
Materials and specifications are subject to change without notice. © 2007 Caterpillar
LEHF1108-08 (01/07) CAT, CATERPILLAR, their respective logos and "Caterpillar Yellow", as well as corporate and product All rights reserved.
identity used herein, are trademarks of Caterpillar and may not be used without permission. Printed in U.S.A.
278-687

You might also like