Three Phase Circuit
Three Phase Circuit
Generation of three phase system: Consider following 3 phase simple loop generator shown in
figure 1a. Its generated voltage will be as shown in figure 1b.
c2 2400 b1 1.5
1
a1
ω
1200 a2 0.5
ea1a2
0 eb1b2
b2 c1 0 2 4 6 8 10 ec1c2
-0.5
S -1
1200 2400
-1.5
0.5
ea1a2
0 eb1b2
0 2 4 6 8 10
Fig.2a: Phase Sequence R-Y-B
ec1c2
-0.5
-1
1200 2400
-1.5
1.5
0.5
ea1a2
0 eb1b2
0 2 4 6 8 10
Fig.2b: Phase Sequence R-B-Y
ec1c2
-0.5
-1
1200 2400
-1.5
Interconnection of 3-phase supply: The six terminals of three phase winding can be connected
to form any of the below.
N
EY EBR
IB EB Y
IY
EYB
B
Fig.3a
600
-ER 1200
1200 ER
EY -EB
EYB
Fig.3b:
Line voltage from above phasor diagram
ERY ER EY ER ( EY )
Its magnitude
1
E RY E P E P 2 E P E P cos 60 0 E P E P 2 E P
2 2 2 2 2
So
2
E RY 3E P
Similarly
E BR E B ( E R ) E B E R 2 E B E R cos 600 3E P
2 2
EL
Active power of 3 phase =3 EPIPCos ϕ =3 I L Cos ϕ = √3ELIL Cos ϕ W
3
EL
Reactive power of 3 phase =3 EPIPSin ϕ =3 I L Sin ϕ = √3ELIL Sin ϕ VAR
3
EL
Apparent power of 3 phase =3 EPIP =3 IL = √3ELIL VA
3
Line Voltage
Phase
Voltage EBR
IBR IYB IY
Y
EYB Line Voltage
IB B
Fig.4a
ERY, EYB & EBR are called phase voltages.
IRY, IYB & IBR are called phase currents.
From figure it is clear that
ERY+EBR+EBY=0
Line Voltage (EL) = Phase Voltage (EP)
I IBR - IYB IY
R
600
IYB -IBR
IB
Fig.4b
4 www.eedofdit.weebly.com, Prepared by: Nafees Ahmed
Apply KCL at node R
I R I BR I RY I BR ( I RY )
I R I BR I RY 2 I BR I RY cos 60 0
2 2
1
I R I P I P 2 I P I P cos 60 0 I P I P 2 I P
2 2 2 2 2
So
2
I R 3I P
Similarly
I Y I RY ( I YB ) I p I P 2 I p I P cos 60 0 3I P
2 2
I Y I YB ( I BR ) I p I P 2 I p I P cos 60 0 3I P
2 2
IL
Active power of 3 phase =3 EPIPCos ϕ =3 E L Cos ϕ = √3ELIL Cos ϕ W
3
IL
Reactive power of 3 phase =3 EPIPSin ϕ =3 E L Sin ϕ = √3ELIL Sin ϕ VAR
3
IL
Apparent power of 3 phase =3 EPIP =3 E L = √3ELIL VA
3
Example 1: If the phase voltage of a three phase star connected alternator is EP. What will be the
line voltage?
i. When the phases are correctly connected?
ii. When the connection to one phase is reversed?
Solution:
i. Line voltage (EL) = Phase Voltage (EP)
EB - EY EB=ERY - EY=EBR
EBR ERY
600
EY -EB EY -EB
EYB EYB
Fig.5a: Phasor Diagram when phases Fig.5b: Phasor Diagram when connection of
are correctly connected phase R is reversed
ERY ER EY ER ( EY )
Its magnitude
E RY E R EY 2 E R EY cos 120 0
2 2
1
E RY E P E P 2 E P E P cos120 0 E P E P 2 E P
2 2 2 2 2
ERY EP
Similarly
E BR E B ( E R ) E B E R 2 E B E R cos 120 0 E P
2 2
Example 2: Three identical of 20 ohm are connected in star to a 415 V, 3-phase, 50 Hz supply.
Calculate
20Ω
415V
415 V
RP=20Ω
20Ω
RP=20Ω
415V
415 V
Fig.6a
Fig.6a
V 2 415 2
P 4305.625 Watt
Req 40 V 2 V 2 415 2 415 2
P
Rp Rp 20 20
17222.5 Watt
Note: if load is delta connected, voltage terminal (V) of PC will be connected to ground.
N
RP
W2
CC RP Y
M L
B
V
COM PC
W3
CC
M L
COM PC V
Fig.7
Note: If load is delta connected, voltage terminal (V) of PC of all wattmeters will be connected
to ground.
3. Two Wattmeter method:
a. When load is star connected:
W1
CC
M L
1
i1
V
COM PC v1
v3
i2
v2 2
i3
3
W2
CC
M L
COM PC V
Fig.7
V i1
COM PC
v1
v3
i3
i2
v2
W2
CC i2-i1
M L
COM PC V
Fig.7
Instantaneous power given by wattmeter 1
p1=-v3.(i1-i3) ---(1)
Instantaneous power given by wattmeter 2
p2=v2.(i2-i1) ---(2)
Adding (1) & (2)
p1+p2= -v3.(i1-i3)+ v2.(i2-i1)
=-v3i1-v3i3+v2i2-v2i1
=-(v2+v3)i1+v2i2+v3i3
=v1i1+v2i2+v3i3 v1 v2 v3 0 v2 v3 v1
= Total instantaneous power in 3-phase load
Hence a load may be balanced or unbalanced, star connected or delta
connected, total instantaneous power of 3-ϕ load will be the sum of the
instantaneous power given by the two wattmeters.
Since wattmeter measures active power so total active power of 3-ϕ load will be
P= W1+W2
W1= Active power measured by wattmeter 1
W2= Active power measured by wattmeter 2
Determination of power factor: Consider a star connected balanced load
Let
V1= V2 = V3=Vp Phase voltages (RMS)
I1= I2 = I3=Ip Phase currents (RMS)
Reading of wattmeter 1 W1=I1V13Cos(30-ϕ)
=IP√3VP Cos(30-ϕ)
= √3VP IP Cos(30-ϕ) ---(1)
ϕ V1
ϕ 300
I1
I2 0
30
V2 V13
-V3
V23
Fig.3b
Reading of wattmeter 2 W2=I2V23Cos(30+ϕ)
=IP√3VP Cos(30+ϕ)
= √3VP IP Cos(30+ϕ) ---(2)
Hence we can say when power factor angle is greater than 600 one
wattmeter will give negative reading. For obtaining the reading of that wattmeter either
the connection of current coil(CC) or pressure coil(PC) should be changed and reading
will be taken as negative.
Example 3: For a certain load one wattmeter reads 20 KW and other 5 KW after the voltage of
this wattmeter has been reversed. Calculate power and power factor of the load.
Solution:
W W2 20 5 25
Cos Cos tan 1 3 1 Cos tan 1 3 Cos tan 1 3 Cos 70.89 0 0.327
W1 W2 20 5 15
Q 1. Draw connection diagram fro measurement of power in 3-phase Y connected load using two
wattmeter method. In one such experiment the load supplied was 30 KW at 0.7 power factor lagging.
Find the reading of each wattmeter.
Hint: W1+W2=P= 30 KW
W W2
Cos tan 1 3 1 0.7
W1 W2