Cable Gland Types Px2Krex, Px2Kwrex, Px2Kxrex & PB Variants

1. The document provides installation instructions and technical specifications for cable gland types PX-REX, PX2KREX, PX2KWREX, PX2KXREX, and PB variants for terminating cables in explosive atmospheres. 2. The cable glands have ATEX, IECEx, and cCSAus certification for use in hazardous locations and provide IP66-IP68 ingress protection. 3. The instructions specify proper installation including engaging threads fully, using thread sealant, and following special conditions for safe use.

Uploaded by

Nikhil E A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
239 views2 pages

Cable Gland Types Px2Krex, Px2Kwrex, Px2Kxrex & PB Variants

1. The document provides installation instructions and technical specifications for cable gland types PX-REX, PX2KREX, PX2KWREX, PX2KXREX, and PB variants for terminating cables in explosive atmospheres. 2. The cable glands have ATEX, IECEx, and cCSAus certification for use in hazardous locations and provide IP66-IP68 ingress protection. 3. The instructions specify proper installation including engaging threads fully, using thread sealant, and following special conditions for safe use.

Uploaded by

Nikhil E A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SCAN FOR INSTALLATION VIDEOS

TECHNICAL DATA EXPLOSIVE ATMOSPHERES CLASSIFICATION

INSTALLATION INSTRUCTIONS FOR


CABLE GLAND TYPE : PX-REX ATEX CERTIFICATION No : SIRA 13ATEX1072X, SIRA 13ATEX4078X
INGRESS PROTECTION : IP66, IP67, IP68, Type 4X; Oil Resistant II ATEX CERTIFICATION CODE : ^II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da
PROCESS CONTROL SYSTEM : BS EN ISO 9001 ^II 3G Ex nR IIC Gc,^ IM2 Ex d I Mb, Ex e I Mb
: ISO/IEC 80079-34:2011 IECEx CERTIFICATION No : IECEx SIR 13.0027X
IECEx CERTIFICATION CODE : Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb

CMP CABLE GLAND TYPES PXREX


cCSAus CERTIFICATION NO : 2288626
cCSAus CERTIFICATION CODE
: Class I, Div 1,2, Groups A,B,C,D; Class II, Groups E,F,G, Class III, Div. 1,2; Class I, Zone 1, AEx d IIC Gb, AEx e IIC Gb,
Class I, Zone 2 AEx nR IIC Gc, Class I, Zone 20 AEx ta IIIC Da, NEMA 4 X, Oil Resistant II
INSTALLATION INSTRUCTIONS (Code details depends upon application - please see certificate)
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
1. The cable glands used for terminating braid cable are only suitable for fixed installations. Cables must be effectively clamped to prevent twisting and pulling.
2. According to the CEC wiring code, connectors with metric threads are only suitable for Areas Classified in ZONES unless fitted with an approved Metric to NPT thread conversion adaptor.
3. Wiring method for type of cables that can be used in Class I, Div. 1, 2, and Class I, Zone 1, 2, Classified Areas according to 60079-14 installation wiring method restrictions.
4. Shipboard Cables are for use on Marine Platform or shipboards only and are subject to local authorities having jurisdiction on the installation.
6. CAUTION - To reduce risk of flame propagation, fittings with ISO metric threads require:
a) 5 full threads engaged for gas groups C and D FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP
b) 10 full threads engaged for gas groups A and B
7. When the gland is supplied with metric entry threads, a CMP Entry Thread Washer should be fitted between the connector and the enclosure to prevent the ingress of moisture or dust into the
enclosure. Thread tape must not be applied to the threads.
ARMOUR & SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON PB
8. Before installing the gland, ensure that the gland thread forms and the enclosure thread form are compatible.
ACCESSORIES
VARIANTS) . FOR USE IN EXPLOSIVE ATMOSPHERES.
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :- Locknut, Earth Tag, Serrated Washer, Entry Thread (I.P.) Sealing Washer, Shroud

Outer Seal Tightening Guide


Number of turns GLAND SIZE INCORPORATING EU DECLARATION OF CONFORMITY TO DIRECTIVE [2014/34/EU]
to tighten 20S16 20S 20 25S 25 32 40 50S 50 63S 63 75S 75

CABLE GLAND TYPES


CABLE DIAMETER
0.5 13.2 15.9 20.9 22.0 26.2 33.9
1 12.5 15.3 20.0 21.2 25.4 32.9 40.4 46.7 52.8 59.2 65.9 72.1 78.5
1.5 11.9 14.7 19.0 20.4 24.6 31.9 39.0 45.4 51.4 57.7 64.6 70.6 77.2

PX2KREX, PX2KWREX,
2 11.2 14.2 18.1 19.6 23.8 30.8 37.6 44.1 50.0 56.2 63.4 69.2 75.9
2.5 10.5 13.6 17.2 18.8 23.0 29.8 36.2 42.9 48.7 54.7 62.1 67.7 74.6
3 9.8 13.0 16.2 18.0 22.2 28.8 34.8 41.6 47.3 53.2 60.9 66.3 73.3
3.5 9.2 12.4 15.3 17.2 21.4 27.8 33.5 40.3 45.9 51.6 59.6 64.8 71.9
4 8.5 11.8 14.4 16.4 20.6 26.8 32.1 39.0 44.5 50.1 58.4 63.4 70.6

PX2KXREX & PB VARIANTS


4.5 7.8 11.2 13.4 15.6 19.8 25.7 30.7 37.8 43.2 48.6 57.1 61.9 69.3
5 7.1 10.7 12.5 14.8 19.0 24.7 29.3 36.5 41.8 47.1 55.9 60.5 68.0
5.5 6.5 10.1 12.0 14.0 18.2 23.7 27.9 35.2 40.4 45.6 54.6 59.0 66.7
6 5.8 9.5

Available Entry Threads Armour Range


(Alternate Metric Thread Lengths Number Diameter *Cable Overall Combined Ordering
Across Across
of Over Bedding Cable Grooved Stepped Reference Cable
Cable Available) Flats Corners
Cores Conductors Diameter Diameter Cone (X) Cone (W) Protrusion (Brass Metric) Gland
Gland Standard Option Shroud
Length Weight
Size Thread Thread
Ordering (Kgs)
Metric Length NPT Length NPT Max Max Max Min Max Min Max Min Max Max Max Size **Type
Suffix
(Metric) (NPT)
20s16 M20 15.0 1/2” 19.9 3/4” 11 11.7 11.7 6.1 13.1 0.3 1.0 0.8 1.25 30.5 33.6 62.0 20S16 PX2KREX 1RA PVC06 0.24
20S M20 15.0 1/2” 19.9 3/4” 11 11.7 11.7 9.5 15.9 0.3 1.0 0.8 1.25 30.5 33.6 62.0 20S PX2KREX 1RA PVC06 0.23
20 M20 15.0 1/2” 19.9 3/4” 11 12.6 12.9 12.5 20.9 0.4 1.0 0.8 1.25 30.5 33.6 63.0 20 PX2KREX 1RA PVC06 0.24
25S M25 15.0 3/4” 20.2 1” 21 17.5 17.9 14.0 22.0 0.4 1.2 1.25 1.6 37.5 41.3 69.5 25S PX2KREX 1RA PVC09 0.37

Cable Gland Selection Table


25 M25 15.0 3/4” 20.2 1” 21 17.5 17.9 18.2 26.2 0.4 1.2 1.25 1.6 37.5 41.3 69.5 25 PX2KREX 1RA PVC09 0.37
32 M32 15.0 1” 25.0 1 1/4” 38 23.6 23.9 23.7 33.9 0.4 1.2 1.6 2.0 46.0 50.6 75.0 32 PX2KREX 1RA PVC11 0.57
40 M40 15.0 1 1/4” 25.6 1 1/2” 59 30.0 30.3 27.9 40.4 0.4 1.6 1.6 2.0 55.0 60.5 75.0 40 PX2KREX 1RA PVC15 0.80
50S M50 15.0 1 1/2” 26.1 2” 89 36.6 36.9 35.2 46.7 0.4 1.6 2.0 2.5 60.0 66.0 77.0 50S PX2KREX 1RA PVC18 0.90
50 M50 15.0 2” 26.9 2 1/2” 89 41.0 41.3 40.4 53.0 0.6 1.6 2.0 2.5 70.0 77.0 77.0 50 PX2KREX 1RA PVC21 1.19
63S M63 15.0 2” 26.9 2 1/2” 115 47.9 48.4 45.6 59.4 0.6 1.6 2.0 2.5 75.0 82.5 79.7 63S PX2KREX 1RA PVC23 1.39
63 M63 15.0 2 1/2” 39.9 3” 115 53.7 54.0 54.6 65.8 0.6 1.6 2.0 2.5 80.0 88.0 80.3 63 PX2KREX 1RA PVC25 1.41
75S M75 15.0 2 1/2” 39.9 3” 140 59.9 60.2 59.0 72.0 0.6 1.6 2.0 2.5 90.0 99.0 86.8 75S PX2KREX 1RA PVC28 2.09
75 M75 15.0 3” 41.5 3 1/2” 140 64.2 64.2 66.7 78.4 0.6 1.6 2.5 3.0 100.0 110.0 88.3 75 PX2KREX 1RA PVC30 2.54
90 M90 20.0 3 1/2” 42.8 4” 24.0 75.3 75.6 76.2 90.3 0.8 1.6 3.15 4.0 115.0 126.5 102.1 90 PX2KREX 1RA PVC32 3.71
100 M100 20.0 4” 44.0 5” 24.0 85.6 85.9 86.1 101.4 0.8 1.6 3.15 4.0 127.0 139.7 114.0 100 PX2KREX 1RA LSF33 4.81
Dimensions are displayed in millimetres unless otherwise stated

** Codes shown are for PX2K-REX glands, for PX2KW-REX or PX2KX-REX add “W” or “X” respectively, e.g. 20PX2KWREX1RA, 20PX2KXREX1RA
*Please note that the overall maximum cable bedding diameter for “PB” variants should be reduced by 1mm to allow for the inner lead sheath.

CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards: -
EN60079-0:2012, EN60079-1:2007, EN60079-7:2007, EN60079-15:2010, EN60079-31:2009, BS6121:1989, EN62444:2013
FI402

Revision Revision Revision


David Willcock – Certification Engineer (Authorised Person) Reason Number Date
CMP Products Limited, Cramlington, NE23 1WH, UK IFS 14 18/10/16
24th June 2015
ATEX / IECEx 10 -

CSA / cCSAus 10 -
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

0518
UL 10 -
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: [email protected] • Web: www.cmp-products.com
Notified Body: SIRA Certification Service, Unit 6 Hawarden Industrial Park, Hawarden, CH5 3US, UK

www.cmp-products.com Logos shown for illustration purposes only. Please check certification for details
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES PX2KREX, PX2KWREX,
5. Insert the armour cone (5a or 5b) into the entry item (2) and pass the cable through them and the resin dam until the braid or
PX2KPBREX & PX2KXREX armour contacts the cone and make sure it is evenly spaced around it. Tighten the body (6) metal to metal ensuring all threads are
CABLE GLAND COMPONENTS - It is not necessary to dismantle the cable gland any further than illustrated below used to lock the braid or armour. Do not tighten the outer seal nut at this stage. (On PB variants the earthing device automatically
1. Thread Shield makes contact with the lead sheath).

2. Entry Component 9 5a 7 6 8 Fit the thread shield over the entry threads to protect them prior to installing the resin.
3. Deluge “O” Ring

4. Compound Tube

5a. Grooved Armour Cone (XYZ)

5b. Stepped Armour Cone (W)

6. Body

7. AnyWay Clamping Ring


1 2 3 4 6. Refer to ‘RapidEx Resin’ assembly instructions to fill the gland Compound Tube with the required amount of resin
8. Outer Seal Nut Assembly
5b (1). The resin should not be mixed or applied at temperatures below 5°C (40°F). If the general ambient temperature is
9. Resin Dam below 5°C (40°F) please follow the instructions on CMP TDS 613 before proceeding (available on the CMP website).

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION


1. The PX2K-REX type cable gland is supplied as a Universal Kit with two armour cones, the grooved armour cone (5a) is
suitable for Strip Armour, Tape Armour and Braided Cables, and the stepped cone (5b) is suitable for Wire Armour (SWA) cables.
If the installation only uses cores
The PX2KX-REX gland only has one cone (5a) and the PX2KW-REX only has one cone (5b). (PB Variants have an earthing device (i.e. no cable sheath) at the Resin Dam
for the lead sheath). Ensure Resin Dam is
position of the resin dam then with poor contact
electrical tape must be wrapped in position in the
around the cores at that position with cable cores.
2. Separate the gland components by removing the body and outer seal nut assembly. Pass the body and outer seal nut to make a good seal between the gland and making a
assembly (6),(8), and the AnyWay clamping ring (7) over the cable, outer seal nut first. cores and the resin dam.
good seal against the
inner sheath.
3. Prepare the cable by stripping back the outer sheath and braid / armour to suit the equipment. Expose the braid or armour
further so that it can be formed around the armour cone by cutting back the outer sheath by a length “L”. This length varies
slightly depending upon cable diameter, but typical values are shown below. The inner sheath should be long enough to just
pass through the resin dam when installed. (Typical length of inner sheath is shown as ‘M’ below.) On lead sheathed cables, the
lead sheath should be long enough to just pass through the armour cone when installed.
M
Do not disassemble the gland to inspect the Resin Dam, diagrams are for representation.
CABLE
GLAND SIZE
20S/16, 20S, 20 25S, 25, 32, 40 50S, 50, 63S, 63 75S, 75, 90 7. Once the resin has cured remove the thread shield, loosen the body and remove the assembly from the entry item. Fit the entry
L
item into the equipment.
CABLE STRIP 12 mm 15 mm 18 mm 20 mm
LENGTH “L” (0.472 inches) (0.591 inches) (0.709 inches) (0.787inches) 8. Only using finger pressure, tighten the outer seal nut assembly (6)(8) until light
CABLE
resistance to tightening is met.
35 40 42 50
BEDDING“M”
Then either use the outer seal tightening guide tape or table on the rear of the page to
4. Remove any bedding or fillers from around the cable cores. If the cable cores have screens, these should be unravelled and then determine how much further to tighten the seal using a spanner (using the outer seal
twisted together to form a single core. This single core and/or any drain wires present should be sleeved with some heat shrink tightening guide is recomended).
tubing.
Wrap the outer seal tightening guide tape around the cable to show the amount of
spanner turns needed (as shown here). Make sure the correct side of the outer seal
tightening guide tape is used depending on the cable gland size.
Electrical tape MUST be wrapped around the tips of the cable cores. This is to
ensure the cable cores are together and also to cover any sharp edges that
could potentially tear the Resin Dam during installation.

www.cmp-products.com www.cmp-products.com