3 Phase 4 Wire LT Operated CT Dual Source Meter: User Manual
3 Phase 4 Wire LT Operated CT Dual Source Meter: User Manual
3 Phase 4 Wire LT Operated CT Dual Source Meter: User Manual
2. Standards Applicable
Accuracy : IEC62053-21 (Class 1.0)
Radio Interference : CISPR22
Fast Transient Burst : IEC61000-4-4
Surge Withstand : IEC61000-4-5
ESD : IEC61000-4-2
Impulse Voltage : IEC62052-11
3. Dual Energy Registers
Two separate energy registers are provided, one for EB (Electricity Board supply) and another for
G(Generator Supply).Normally meter accumulates energy in EB register. Whenever the DG sensing
signal (10 to 60V dc /20 to 300V ac) is present, meter accumulates energy in G register. Separate
LED indication is provided on the meter front Panel,which glows when DG sensing signal is present.
4. Power On Display
Display check will be the first display when meter is powered ON.
Followed by meter serial number and then firmware version will be displayed.
5. Display Modes
1) Auto Scroll Mode
By default meter will be in auto-scroll mode. All the display
parameters will be scrolling automatically in this mode. Scrolling
period for two energy parameters is 8 sec and 2 sec for all other
parameters.
2) Toggle Mode
Press and hold SELECT Key to move to Energy-toggle mode. The display
will alternately show“Generator energy”(indicated “G” on LCD display)
and “Electricity Board energy” (indicated“Eb” on LCD display. There is
no time out period in this mode. To exit from this mode press up/down
key.
3) Manual Scroll Mode
Press UP/DOWN Key to Scroll Manually. In this mode all the parameters
can be scrolled through manually. If no key is pressed for 1 minute,it
will go back to auto scroll mode.
4) Freeze Mode
To see the selected parameter continuously,press up & down buttons together
for 2 seconds. There is no time out period for freeze mode.Press up or down
button to come out of Freeze mode.The meter will go back to its previous
scroll mode(auto/manual).Freeze mode is not available in toggle mode.
6. Display Parameters
1.Cumulative Energy KWh
3. Average Voltage
4. Average Current
6. Frequency
7. R Phase Voltage
8. Y Phase Voltage
9. B Phase Voltage
21. Slave id
22. Baud rate
23. Parity
Note:
· Power on duration will be incremented only when Phase voltage is present. Time will not be
incremented if meter is powered on in Aux voltage without any phase voltage
· Press SELECT key and DOWN key together to see the RS-485 parameters(last 3 Display parameters)
7.Entering in to Programming Mode
Press and hold the SELECT and scroll UP key together to move
to the Programming Mode. Press scroll DOWN key (used as
Escape key in programming mode) to come out from the
programming mode. “ESCAPE” will be displayed.
-Setting slave Id
-Set Password
Meter will not record energy when it is in programming mode.Time out period of 2 min is
provided for programming mode.
9. Password Setting
In the Programming Menu, press and hold scroll UP key
to get “Set Pass” and then press SELECT key
Press UP key to change the blinking digit. Press UP and SELECT key
together to shift to next digit. Press SELECT key to save the password
10.Programming CT/PT ratio
In the Programming Menu, press and hold scroll UP key to get
“Ct Pt Ratio” and then press SELECT key.
·CT RATIO * PT RATIO should not exceed 999999, if exceeded the meter will display “dAtA Err”
·Pulse Rate = 2500 imp / kWh (for CT * PT ratio = 1).
·Pulse rate will vary if CT/PT ratio is changed
·When CTPT Ratio is programmed ≥1000, energy in Mwh (Mega watthour) will be displayed as “kkWh”
.Decimal points on the display format will be changed according to the CTPT ratio programmed.
11. Reset Power On Time
In the Programming Menu, press and hold scroll UP to get “Set SL Id”
and then press SELECT key.
Press UP key to increment the SL Id value. Press together UP and
SELECT key to shift to next digit. Press select key to set the id.
Slave id can be set from 1 to 247.
Note: Once the parameters are set, press the DOWN key to come out of the programming mode.
“ESCAPE” will be displayed.This is followed by a “rEstArt” message and the meter gets restarted.
st
For address 07 to 17,23 if MSB (1 word) is 1 then 2's complement of the value is to be
taken.
Read write Parameters:
(Supported by function code 6 and 16 for writing and by function code 3 for reading)
Meter Address 1 1
42,385
Baud Rate
42,386
2->1200; 3->2400; 4-> 1 1
4800; 5->9600; 6->19200
Parity
42,387 0->None; 1->Odd; 2->Even 1 1
15. Warranty
Larsen & Toubro warrants that 3 Phase 4 Wire kWh Meter type Gemini is free from defects in workmanship
and material . Larsen & Toubro obligation under this warranty shall be for a period of 1 year from the
date of sale subject to the following terms and conditions provided the notice of defects and
satisfactory proof thereof is given to Larsen & Toubro by its customer within the warranty period.
1. Larsen & Toubro shall provide only repairs for the sold item.
2. Defective parts shall be serviced or replaced by Larsen & Toubro.
This warranty does not cover any defect in the product caused by accident, misuse, mishandling
includes improper electrical, mechanical installation), tamper, neglect, alteration/modification/
substitution of any of the components or parts or any attempt of internal adjustment by unauthorized
service personnel. For applicability of warranty, Larsen & Toubro shall be the sole judge. Under no
circumstance shall Larsen & Toubro Limited be liable for any consequential or resulting injury or for loss,
damage or expense directly or indirectly from the use of this product.The foregoing warranty is in lieu
of all other warranties expressed or implied and is the sole and exclusive remedy for any claim arising
from any defect in the product.
16. Disclaimer
Sufficient care is taken to provide all information regarding the product but Larsen & Toubro
does not claim any responsibility for the damage caused by using the product directly or indirectly.
17. Precautions
1.The device must be installed, wired and serviced only by qualified personnel
2.Prior to any work on the device, de-energize the connected circuits before meter
installation and disconnection.
3.Always use an appropriate voltage detection device to confirm the absence of voltage
4.Always supply the device with the correct rated voltage.
5.Failure to take these precautions could cause serious injuries