Metering Outdoor Metering
Metering Outdoor Metering
201 202 203 204 205 206 208 209 210 211 212
220kV
220kV OUTGOING LINE-1 220kV OUTGOING LINE -2 220kV TRAFO-1 220kV TRAFO-2 220kV LINE-1 220kV TRAFO-3 220kV BUS PT 220kV TRAFO-4 220kV LIE-2 220kV TRAFO-5 220kV TRAFO-6
BUSCOUPLER
CSE CSE
(KHUMTAI SS) (KHUMTAI SS)
220kV CABLE
ROUTE
1Cx1200Sq.mm XLPE , 2 RUNS/PH 1Cx1200Sq.mm XLPE , 2 RUNS/PH
COPPER POWER CABLE COPPER POWER CABLE
210-CSE
NRL OUTDOOR
SWITCHYARD 205-LA 210-LA
198kV, 10kA, CLASS-III 198kV, 10kA, CLASS-III
205-LE 210-LE
205-89L DS 210-89L DS
3150A, 50kA/3 SEC 3150A, 50kA/3 SEC
1U63-SS21-GIS-100,220kV
205 -VT 81U/O 81DF/DT 60 27 25 27DC 59 210 - VT 81U/O 81DF/DT 60 27 25 27DC 59
GIS, SS#21 220kV/110V/110V 220kV/110V/110V
3 3 3 3 3 3
LOCATION : 220kV GIS CLASS - 0.2 3P , METERING CLASS - 0.2 3P ,
100/50/50 VA 100/50/50 VA
BUILDING
HS HS
205-HS 210-HS
205-89L DS 210-89L DS
3150A, 50kA/3SEC 3150A, 50kA/3SEC
205-LE 210-LE
205-CT-A 210-CT-A
P1 P1
CORE-1 CORE-1
2000/1A 87 B1-PU 2000/1A
CL-PS, CL-PS,
CORE-2 CORE-2
2000/1A 87 B2-PU 2000/1A
CL-PS CL-PS
CORE-3 CORE-3
2000/1A SPARE 2000/1A
CL-PS CL-PS
201-89A DS 3150A, 202-89A DS 3150A, 203-89A DS 3150A, 204-89A DS 3150A, 205-89A DS 3150A, 206-89A DS 3150A, 209-89A DS 3150A, 210-89A DS 3150A, 211-89A DS 3150A, 212-89A DS 3150A,
205-LE 210-LE
50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC
201-89B DS 3150A, 201-LE 202-89B DS 3150A, 202-LE 203-89B DS 3150A, 203-LE 204-89B DS 3150A, 204-LE 205-89B DS 3150A, 206-89B DS 3150A, 206-LE 209-89B DS 3150A, 209-LE 210-89B DS 3150A, 211-89B DS 3150A, 211-LE 212-89B DS 3150A, 212-LE
50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC
220kV, 3150A, 50Hz, 3PH, 50kA FOR 3 SEC, AL BUSBAR
201-CT-B 202-CT-B 203-CT-B 204-CT-B 206-CT-B 208 - 89B DS 209-CT-B 211-CT-B 212-CT-B
207-89B DS 207-89A DS 3150A, 89BE
P1 P1 P1 P1 P1 3150A, 50kA/3SEC 3150A, 50kA/3SEC P1 P1 P1
50kA/3SEC
CORE-6 MFM TVM A+ASS CORE-6 CORE-7 MFM TVM A+ASS CORE-7 CORE-7 CORE-7 CORE-7 CORE-7
1600-1250/1A 1600-1250/1A 600/1A 79 25 BCU 600/1A 600/1A 600/1A 600/1A 600/1A
79 25 BCU 207-BE 207-AE 60 27 25 27DC MFM V+VSS CL-0.5S, ISF, 5
CL-0.2S, ISF,5 CL-0.2S, ISF,5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5
CORE-6 CORE-6 CORE-6 59 CORE-6 CORE-6 CORE-6
CORE-5 87L2 21-2 50 50N 67N CORE-5 50 50N 67 67N
1600-1250/1A 1600-1250/1A 600/1A 600/1A 600/1A 207-CT-B 207-CT-A 600/1A 600/1A 600/1A
67 32 78V 51 51N 50BF 51 51N 50BF 78V FROM SELECTED 208 - BVT-B
CL-PS CL-PS CL-5P20 BUS VT CL-5P20 CL-5P20 P1 P1 TO OUTGOING CL-5P20 CL-5P20 CL-5P20
220kV/110V/110V FEEDER
SAME AS BAY NO. 201
CORE-4 CORE-4 CORE-5 87T1 64R (HV) 24 CORE-5 CORE-5 CORE-6 CORE-1 CORE-5 CORE-5 CORE-5
87L1 21-1 50 50N 67N 3 3 3 METERING
600/1A 600/1A 600/1A 2000/1A 87 B2-CU 2000/1A 87 B1-CU 600/1A 600/1A 600/1A
1600-1250/1A 1600-1250/1A 50 BF 63 TX* 49 CLASS - 0.5 3P ,
67 32 78V 51 51N 50BF CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS
CL-PS CL-PS
A1
SAME AS BAY NO. 301
HS
21. TABULATION FOR INDICATION LAMPS HIGH SPEED EARTHING SWITCH 32 REVERSE POWER PROTECTION 87B-CU BUSBAR DIFFERENTIAL PROTECTION - CENTRALIZED UNIT
CONDITIONS LOCALLY REMOTE S.NO SYSTEM DATA 220kV SYSTEM 33kV SYSTEM
CURRENT TRANSFORMER 50 INSTANTANEOUS OVER CURRENT PROTECTION 87B-PU BUSBAR DIFFERENTIAL PROTECTION - PERIPHERAL UNIT
1. SYSTEM OPERATING VOLTAGE 220kV 33kV
CIRCUIT BREAKER STATUS : ON / OFF OPEN / CLOSED STATUS
50N INSTANTANEOUS OVER CURRENT E/F PROTECTION 95 TRIP CIRCUIT SUPERVISION PROTECTION MAXIMUM OPERATING VOLTAGE OF
LIGHTNING ARRESTOR/SURGE ARRESTER 2. 245kV 36kV
EARTHING SWITCH STATUS EARTHED / OPEN STATUS THE SYSTEM (RMS)
50BF BREAKER FAILURE PROTECTION 95B CT SUPERVISION RELAY
SF6 GAS TO AIR BUSHING ONE MIN. POWER FREQUENCY DRY
CONTROL STATUS MANUAL (TEST)/AUTO/OFF ALARM NON-AUTO 3. 460kV 70kV
51 IDMT OVER CURRENT PROTECTION BCU BAY CONTROL UNIT AND WET WITHSTAND VOLTAGE (RMS)
CIRCUIT BREAKER TRIPPED ALARM CSE - CABLE SEALING END FULL WAVE IMPULSE WITHSTAND
4. 1050kVp 170kVp
51N IDMT EARTH FAULT PROTECTION EPB EMERGENCY PUSH BUTTON VOLTAGE (1.2/50 microsec.)
LOSS OF CONTROL POWER ALARM
VOLTAGE TRANSFORMER 5. RATED SHORT CIRCUIT CURRENT 50kA/1s 40kA/3s
STANDBY EARTH FAULT PROTECTION MFM MULTI-FUNCTION METER
ALL METERING DISPLAY VALUES 51G (HV) MINIMUM CREEPAGE DISTANCE
(TRANSFORMER HV SIDE) 6. 7595 mm 1116 mm
TVM TRI-VECTOR METER (31mm/kV)
TRIP CIRCUIT : HEALTHY / AUTO TRIP / DISPLAY STATUS POWER TRANSFORMER WITH OLTC
7. RATED FREQUENCY 50Hz
TEST / SERVICE STANDBY EARTH FAULT PROTECTION TNC TRIP/NORMAL/CLOSE SWITCH WITH LOST MOTION DEVICE REFERENCE DOCUMENTS
51G (LV) 8. SYSTEM NEUTRAL EARTHING SOLIDLY EARTHED
GAS INSULATED ENCLOSURE (TRANSFORMER LV SIDE) DOC NO DOC TITLE
V VOLTMETER 9. ALTITUDE ABOVE SEA LEVEL 90M TP-1ZZZA-EL-SLD-0001 OVERALL SINGLE LINE DIAGRAM - NREP
22. SEPERATE MASTER TRIP RELAY SHALL BE PROVIDED FOR 220KV GIS INCOMER FEEDERS, TP-1U63A-EL-SLD-0001.01 KEY SINGLE LINE DIAGRAM FOR 220/33kV SYSTEM
59 OVER VOLTAGE PROTECTION A AMETER 10. DESIGN AMBIENT TEMPERATURE 40 DEG C
TRANSFORMER FEEDERS, BUS COUPLER RELAY PANEL FOR BREAKER FAILURE / BUSBAR BUSHING CT (HV & LV) MAIN RECEIVING SUBSTATION (MRSS) SS#21
11. BUS ARRANGEMENT DOUBLE MAIN SINGLE TP-1U63A-EL-EQL-0001.01
PLAN AND SECTIONS
PROTECTION. 60 FUSE FAILURE PROTECTION ASS AMETER SELECTOR SWITCH
MAIN RECEIVING SUBSTATION (MRSS) SS#21
NEUTRAL BUSHING CT (HV & LV) TP-1U63A-EL-EQL-0001.02
23. DISTANCE PROTECTION (21-1 & 21-2) FUNCTION CAN BE UTILIZED AS INDEPENDENT OR AS BACK 63TX VSS
PLAN AND SECTIONS
AUXILIARY RELAY FOR POWER TRANSFORMER VOLTMETER SELECTOR SWITCH
TYPICAL SAS CONNECTIVITY ARCHITECTURE
UP OF DIFFERENTIAL PROTECTION IN CASE OF FAILURE OF REMOTE COMMUNICATION. TP-1U63A-EL-DTL-0001.01
DRAWING FOR 220KV GIS
33kV VACUUM CIRCUIT BREAKER 64R (HV) HV RESTRICTED EARTH FAULT PROTECTION POWER TRANSFORMER MECHANICAL PROTECTION:-
24. ONE NUMBER 24 FIBRE OPTIC CABLE WILL LAID BETWEEN 220KV KHUMTAI SWITCHYARD AND TP-1U63A-EL-DTL-0001.02
TYPICAL SAS CONNECTIVITY ARCHITECTURE
DRAWING FOR 220KV GIS
220KV NREP SWITCHYARD FOR EACH 220KV INCOMER LINE BAY FOR CABLE DIFFERENTIAL 64R (LV) LV RESTRICTED EARTH FAULT PROTECTION 49OA OIL TEMPERATURE INDICATION ALARM
33kV , 3-POSITION MOTOR OPERATED DISCONNECTOR TP-1U63A-EL-LST-0003 SAS I/O LIST FOR 220/33 KV GIS SWITCHYARD
PROTECTION, INTERLOCK INTERTRIP BETWEEN 220KV KHUMTAI SWICHYARD AND 220KV NREP WITH EARTH SWITCH 67 49OT
DIRECTIONAL IDMT OVER CURRENT PROTECTION OIL TEMPERATURE INDICATION TRIP
SWITCHYARD. HENCE, TWO NUMBER 24 FIBRE OPTIC CABLE SHALL BE LAID FOR TWO NUMBER
33kV BUS VOLTAGE TRANSFORMER (DRAWOUT TYPE) 67N NEUTRAL DIRECTIONAL OVERCURRENT PROTECTION 49WA WINDING TEMPERATURE INDICATION ALARM
220KV INCOMING LINE BAYS. THE FIBRE OPTIC CABLE WILL BE TERMINATED TO OFDB PANEL AT
D1 07-03-2022 APPROVED FOR DESIGN BR MN/AKM SVM
BOTH SWITCHYARD (220KV KHUMTAI SWITCHYARD AND 220KV NREP SWITCHYARD). 78V VECTOR SURGE RELAY ( VOLTAGE SHIFT/LOSS OF MAINS) 49WT WINDING TEMPERATURE INDICATION TRIP A1 01-02-2022 ISSUED FOR REVIEW SSN MN/AKM SVM
V CAPACITIVE VOLTAGE DETECTOR Owner
Rev. Date Reason for Issue Prepared Checked Approved Approved
79 AUTO RECLOSURE PROTECTION 63A BUCHHOLZ ALARM
ABBREVIATION:- CABLE TERMINATION/BUSHING 80A DC SUPPLY SUPERVISION RELAY 63T BUCHHOLZ TRIP TECHNIP INDIA LIMITED
1. ECS - ELECTRICAL CONTROL SYSTEM 80B AC SUPPLY SUPERVISION RELAY LOL TRANSFORMER LOW OIL LEVEL NRL's PO NO.: 4300062833-AMA/16.06.2020
CABLE GLAND DOCUMENT NO.: 082176C-163-DW-1662-0001-02
2. SAS - SUBSTATION AUTOMATION SYSTEM 81U/O UNDER FREQUENCY / OVER FREQUENCY PROTECTION PRV PRESSURE RELIEF VALVE
3. TNC - TRIP NEUTRAL CLOSE POWER CABLE 81DF/DT RATE OF CHANGE OF FREQUENCY PROTECTION OSR OIL SURGE RELAY
NUMALIGARH REFINERY LIMITED
4. EPB - EMERGENCY PUSH BUTTON Life Cycle
86 MASTER TRIP RELAY MOG MAGNETIC OIL GAUGE Code:
5. CRP - CONTROL AND RELAY PANEL EMERGENCY PUSH BUTTON PROJECT: NUMALIGARH REFINERY EXPANSION PROJECT 01
87B1 BUSBAR DIFFERENTIAL PROTECTION - 1 Scale:
LOCAL REMOTE SWITCH METERING AND PROTECTION SINGLE LINE NTS
87B2 BUSBAR DIFFERENTIAL PROTECTION - 2 DRAWING TITLE: Drg.Size:
DIAGRAM FOR 220/33KV GIS SUBSTATION A0
Originator/ Drawing Sequence
Contractor Asset Code Disc Type Number Rev. Sheet
205-89L DS 210-89L DS
3150A, 50kA/3 SEC 3150A, 50kA/3 SEC FOR ACTUAL CLEARANCE REFER "SUBSTATION LAYOUT DRAWING".
205-LE 210-LE
LEGENDS:-
205-CT-A 210-CT-A
P1 P1 SYMBOL DESCRIPTION
205-CT-B 210-CT-B
SCOPE LIGHTNING ARRESTOR/SURGE ARRESTER
P2 P2
SF6 GAS TO AIR BUSHING
208 - BVT-A
CORE-4 CORE-4
1600-1250/1A 220kV/110V/110V 1600-1250/1A CSE - CABLE SEALING END
CL-PS 3 3 3 CL-PS
CORE-5 CLASS - 0.5 3P , CORE-5 VOLTAGE TRANSFORMER
1600-1250/1A 100/50/50 VA 1600-1250/1A
CL-PS CL-PS
POWER TRANSFORMER WITH OLTC
CORE-6 CORE-6
1600-1250/1A 1600-1250/1A
CL-0.2S, ISF,5 208 - 89A CL-0.2S, ISF,5 GAS INSULATED ENCLOSURE
P1 DS 3150A, P1
50kA/3 SEC 89AE BUSHING CT
220kV, 3150A, 50Hz, 3PH, 50kA FOR 3 SEC, AL BUSBAR
201-CT-B 202-CT-B 203-CT-B 204-CT-B 206-CT-B 208 - 89B DS 209-CT-B 211-CT-B 212-CT-B V CAPACITIVE VOLTAGE DETECTOR
207-89B DS 207-89A DS 3150A, 89BE
P1 P1 P1 P1 P1 3150A, 50kA/3 SEC 3150A, 50kA/3 SEC P1 P1 P1
50kA/3 SEC
CORE-6 CORE-6 CORE-7 CORE-7 CORE-7 CORE-7 CORE-7 CORE-7 CABLE TERMINATION/BUSHING
1600-1250/1A 1600-1250/1A 600/1A 600/1A 600/1A 600/1A 600/1A 600/1A
CL-0.2S, ISF,5 CL-0.2S, ISF,5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 207-BE 207-AE CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 CL-0.5S, ISF, 5 CABLE GLAND
CORE-5 CORE-5 CORE-6 CORE-6 CORE-6 CORE-6 CORE-6 CORE-6
1600-1250/1A 1600-1250/1A 600/1A 600/1A 600/1A 207-CT-B 207-CT-A 600/1A 600/1A 600/1A
CL-PS CL-PS CL-5P20 CL-5P20 CL-5P20 208 - BVT-B CL-5P20 CL-5P20 CL-5P20 POWER CABLE
P1 P1
CORE-4 CORE-4 220kV/110V/110V
CORE-5 CORE-5 CORE-5 CORE-6 CORE-1 CORE-5 CORE-5 CORE-5
1600-1250/1A 1600-1250/1A 3 3 3
600/1A 600/1A 600/1A 2000/1A 2000/1A 600/1A 600/1A 600/1A PRESENT SCOPE
CL-PS CL-PS CLASS - 0.5 3P ,
CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS
P2 P2 100/50/50 VA FUTURE SCOPE
CORE-4 CORE-4 CORE-4 CORE-4
201-52 CB 202-52 CB CORE-5 CORE-2 CORE-4 CORE-4
3150A, 50kA/3 SEC 3150A, 50kA/3 SEC 600/1A 600/1A 600/1A 2000/1A 2000/1A 600/1A 600/1A 600/1A
201-CT-A 202-CT-A CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS
CL-0.5, ISF, 5 CL-5P20
P2 P2 P2 P2
P2
P2
NOMENCLATURE (220kV SYSTEM):-
P2 CORE-4 CORE-3 209-52 CB P2
CORE-3 CORE-3 204-52 CB 206-52 CB 2000/1A 2000/1A SPARE 3150A,50kA/3SEC 212-52 CB
203-52 CB 211-52 CB
2000/1A SPARE 2000/1A SPARE 3150A,50kA/3SEC 3150A,50kA/3SEC CL-5P20 CL-PS 3150A, 50kA/3SEC 20 1 - 89 A E
3150A,50kA/3SEC 3150A, 50kA/3SEC
CL-PS CL-PS 209-CT-A
CORE-2 CORE-2 204-CT-A 206-CT-A P2 P2 211-CT-A 212-CT-A
203-CT-A P2
2000/1A 2000/1A P2 P2 P2 P2
CL-PS CL-PS P2 CORE-3 EARTH SWITCH
CORE-3 CORE-3 SPARE CORE-3 CORE-3 E,E1,E2-DISCONNECTOR WITH EARTH SWITCH
CORE-3 SPARE SPARE 2000/1A SPARE SPARE
CORE-1 CORE-1 SPARE 2000/1A 2000/1A 2000/1A 2000/1A DISCONNECTOR LOCATION
2000/1A CL-PS
2000/1A 2000/1A CL-PS CL-PS CL-PS CL-PS A-BUS SIDE DICONNECTOR/ISOLATOR (MAIN BUS-1)
CL-PS CORE-2
CL-PS, CL-PS, CORE-2 CORE-2 207-52 CB CORE-2 CORE-2
CORE-2 2000/1A B-BUS SIDE DICONNECTOR/ISOLATOR (MAIN BUS-2)
P1 P1 2000/1A 2000/1A 3150A, 50kA FOR 3SEC 2000/1A 2000/1A
2000/1A CL-PS
CL-PS CL-PS CL-PS CL-PS CL-PS T-TRANSFORMER DISCONNECTOR/ISOLATOR
201-LE 202-LE CORE-1 CORE-1 CORE-1
CORE-1 CORE-1 CORE-1
2000/1A 2000/1A 2000/1A 2000/1A L-INCOMING DISCONNECTOR/ISOLATOR
2000/1A 2000/1A
201-89L DS 202-89L DS CL-PS CL-PS CL-PS CL-PS
HS HS CL-PS CL-PS EQUIPMENT IDENTIFICATION
3150A, 50kA/3 SEC 3150A, 50kA/3 SEC P1 P1 P1 P1 P1 89-DISCONNECTOR/ISOLATOR
P1
201-HS 202-HS 203-LE 204-LE 206-LE 209-LE 211-LE 212-LE
203-89T DS 3150A, 204-89T DS 3150A, 206-89T DS 630A, 209-89T DS 3150A, 211-89T DS 3150A, 212-89T DS 3150A, 52-CB
201 -VT 202 -VT 50kA/3SEC 50kA/3SEC 50kA/1SEC 50kA/3SEC 50kA/3SEC 50kA/3SEC CT-CURRENT TRANSFORMER
220kV/110V/110V 220kV/110V/110V 3150A GAS INSULATED 203-LE 3150A GAS INSULATED 204-LE 3150A GAS INSULATED 206-LE 3150A GAS INSULATED 209-LE 3150A GAS INSULATED 211-LE 3150A GAS INSULATED 212-LE BVT-BUS VOLTAGE TRANSFORMER
3 3 3 3 3 3 BUS DUCT BUS DUCT BUS DUCT BUS DUCT BUS DUCT BUS DUCT
CLASS - 0.2 3P , CLASS - 0.2 3P , LA-LIGHTNING ARRESTER
GAS/AIR BUSHING GAS/AIR BUSHING GAS/AIR BUSHING GAS/AIR BUSHING GAS/AIR BUSHING GAS/AIR BUSHING
100/50/50 VA 100/50/50 VA ES-EARTH SWITCH
3150A, 50kA/3 SEC 3150A, 50kA/3 SEC 3150A, 50kA/3 SEC 3150A, 50kA/3SEC 3150A, 50kA/3SEC 3150A, 50kA/3SEC
201-LA 202-LA HS-HIGH SPEED EARTH SWITCH
203-LA 204-LA 206-LA 209-LA
198kV, 10kA, CLASS-III 198kV, 10kA, CLASS-III 211-LA 212-LA
198kV, 10kA 198kV, 10kA 198kV, 10kA 198kV, 10kA EMVT-ENERGY METERING VOLTAGE TRANSFORMER
3150A GAS INSULATED 3150A GAS INSULATED 198kV, 10kA 198kV, 10kA
BUS DUCT BUS DUCT MCT-METERING CURRENT TRANSFORMER
203-HV BCT 204-HV BCT 206-HV BCT 209-HV BCT
OUTDOOR CORE-1 CORE-1 CORE-1 CORE-1
CSE-CABLE SEALING END
P2 P1 P2 P1 P2 P1 P2 P1
302-LV BCT 302-LV NBCT 305-LV BCT 305-LV NBCT 308-LV BCT 308-LV NBCT 3011-LV BCT NOMENCLATURE (33kV SYSTEM):-
220kV OUTGOING CORE-1, 2500/1A CORE-1, 2500/1A CORE-1, 2500/1A CORE-1, 2500/1A
220kV OUTGOING LINE-1 CL-PS CL-PS CL-PS CL-PS
LINE-2
(TO RAJABARI) CORE-2, 2500/1A CORE-2, 2500/1A CORE-2, 2500/1A CORE-2, 2500/1A
(TO RAJABARI) CL-PS SPARE CL-PS SPARE CL-PS SPARE CL-PS SPARE 30 1 - 52
6Rx1Cx630Sq.mm XLPE/PH
ALUMINUM POWER CABLE
302-VT 89-ES 305-VT 89-ES 308-VT 3011-VT EQUIPMENT IDENTIFICATION
89-ES 89-ES 52-CB
33kV GIS 33kV/110V/110V 33kV GIS 33kV/110V/110V 33kV GIS 33kV/110V/110V 33kV GIS 33kV/110V/110V
3 3 3 3 3 3 3 3 3 3 3 3 CT-CURRENT TRANSFORMER
(1U63-SS21-IBP-101) 89A DS 2500A, (1U63-SS21-IBP-102) CLASS - 0.5 3P ,
(1U63-SS21-IBP-103) (1U63-SS21-IBP-104)
CLASS - 0.5 3P , 40kA/3SEC 89A DS 2500A, CLASS - 0.5 3P , 89A DS 2500A, CLASS - 0.5 3P , 89A DS 2500A,
VT-VOLTAGE TRANSFORMER
40kA/3SEC 40kA/3SEC 40kA/3SEC
100/50/50 VA 100/50/50 VA 100/50/50 VA 100/50/50 VA
LOCATION : 302-CT-A V LOCATION : 305-CT-A V LOCATION : 308-CT-A V LOCATION : 3011-CT-A V 89-DISCONNECTOR/ISOLATOR
P1 P1 P1 P1
33kV GIS BUILDING CORE-1 33kV GIS BUILDING CORE-1 33kV GIS BUILDING CORE-1 33kV GIS BUILDING CORE-1
BAY NUMBER
01 T0 12 - 33kV SYSTEM
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A VOLTAGE LEVEL
CL-PS CL-PS CL-PS CL-PS 30 - 33kV SYSTEM
CORE-2 CORE-2 CORE-2 CORE-2
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A
CL-0.5S CL-0.5S CL-0.5S CL-0.5S
CORE-3 CORE-3 CORE-3 CORE-3
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A
CL-PS CL-PS CL-PS CL-PS
CORE-4
3000-2000/1A SPARE
CORE-4
3000-2000/1A SPARE
CORE-4
3000-2000/1A SPARE
CORE-4
3000-2000/1A SPARE REFERENCE DOCUMENTS
CL-PS CL-PS CL-PS CL-PS DOC NO DOC TITLE
CORE-5 CORE-5 CORE-5 CORE-5 OPERATING CONFIGURATION:-
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A OVERALL SINGLE LINE DIAGRAM - NREP
CL-PS
TP-1ZZZA-EL-SLD-0001
CL-PS CL-PS CL-PS
CORE-6 CORE-6 CORE-6 CORE-6 S.NO EQUIPMENT ISOLATOR - 89A ISOLATOR - 89B CIRCUIT BREAKER
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A MAIN RECEIVING SUBSTATION (MRSS) SS#21
1. 220kV INCOMING LINE-1 ISOLATOR NC - - TP-1U63A-EL-EQL-0001.01
CL-PS CL-PS CL-PS CL-PS PLAN AND SECTIONS
P2 P2 P2 P2
33kV/110V/110V 302-52, 33kV SF6 33kV/110V/110V 305-52, 33kV SF6 33kV/110V/110V 308-52, 33kV SF6 33kV/110V/110V 3011-52, 33kV SF6 2. 220kV TRANSFORMER-1 FEEDER NC NO NC MAIN RECEIVING SUBSTATION (MRSS) SS#21
3 3 3 CB 2500A,40kA 3 3 3 CB 2500A,40kA 3 3 CB 2500A,40kA 3 3 CB 2500A,40kA TP-1U63A-EL-EQL-0001.02
CLASS - 0.5 3P , 89A DS CLASS - 0.5 3P , 89A DS CLASS - 0.5 3P , 89A DS CLASS - 0.5 3P , 89A DS 3. 220kV TRANSFORMER-2 FEEDER NO NC NC PLAN AND SECTIONS
FOR 3SEC FOR 3SEC FOR 3SEC FOR 3SEC
100/50/50 VA 2500A, 302-89, 2500A,40kA / 100/50/50 VA 2500A, 305-89, 2500A,40kA / 100/50/50 VA 2500A, 308-89, 2500A,40kA / 100/50/50 VA 2500A, 3011-89, 2500A,40kA /
4. 220kV GIS BUS VT-1 NC - - METERING AND PROTECTION SINGLE LINE
40kA/3SEC 3SEC 40kA/3SEC 3SEC 40kA/3SEC 3SEC 40kA/3SEC 3SEC TP-1U63A-EL-SCM-0001.01
89-ES 33kV, 2500A, 50Hz, 3PH, 40kA 89-ES 33kV, 2500A, 50Hz, 3PH, 40kA 89-ES 33kV, 2500A, 50Hz, 3PH, 40kA 89-ES 33kV, 2500A, 50Hz, 3PH, 40kA DIAGRAM FOR 220/33KV GIS SUBSTATION
302-89-ES FOR 3 SEC, CU. BUSBAR 305-89-ES FOR 3 SEC, CU. BUSBAR 308-89-ES FOR 3 SEC, CU. BUSBAR 3011-89-ES FOR 3 SEC, CU. BUSBAR 5. 220kV GIS BUS VT-2 - NC -
METERING AND PROTECTION SINGLE LINE
6. 220kV INCOMING LINE-2 ISOLATOR - NC - TP-1U63A-EL-SCM-0001.02
301-89-ES 303-89-ES 304-89-ES 306-89-ES 307-89-ES 309-89-ES 3010-89-ES 3012-89-ES DIAGRAM FOR 220/33KV GIS SUBSTATION
303-89, 304-89, 2500A,40kA / 306-89, 309-89, 3012-89,
301-89, 2500A,40kA / 307-89, 2500A,40kA / 3010-89, 2500A,40kA 7. 220kV TRANSFORMER-3 FEEDER NO NC NC
2500A,40kA / 3SEC 3SEC 2500A,40kA / 3SEC 2500A,40kA / 3SEC 2500A,40kA / 3SEC TYPICAL SAS CONNECTIVITY ARCHITECTURE
3SEC 3SEC / 3SEC TP-1U63A-EL-DTL-0001.01
303-52, 33kV VCB 306-52, 33kV VCB 309-52, 33kV VCB 301-52, 33kV VCB 8. 220kV TRANSFORMER-4 FEEDER NC NO NC DRAWING FOR 220KV GIS
301-52, 33kV VCB 2500A,40kA FOR 304-52, 33kV VCB 2500A,40kA FOR 307-52, 33kV VCB 2500A,40kA FOR 3010-52, 33kV VCB 2500A,40kA FOR
2500A,40kA FOR 3SEC 3SEC 2500A,40kA FOR 3SEC 3SEC 2500A,40kA FOR 3SEC 3SEC 2500A,40kA FOR 3SEC 3SEC
9. 220kV OUTGOING LINE-1 FEEDER NC NO NC TYPICAL SAS CONNECTIVITY ARCHITECTURE
TP-1U63A-EL-DTL-0001.02
301-CT-A 303-CT-A 304-CT-A 306-CT-A 307-CT-A 309-CT-A 3010-CT-A 3012-CT-A 10. 220kV OUTGOING LINE-2 FEEDER NO NC NC
DRAWING FOR 220KV GIS
P2 P2 P2 P2 P2 P2 P2 P2
CORE-5 CORE-5 CORE-5 CORE-5 CORE-5 CORE-5 CORE-5 CORE-5 NORMAL OPERATION
3000-2000/1A SPARE 3000-2000/1A SPARE 3000-2000/1A SPARE 3000-2000/1A SPARE 3000-2000/1A SPARE 3000-2000/1A SPARE 3000-2000/1A SPARE 3000-2000/1A SPARE
CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS 11. 220kV INCOMING LINE-1 FEEDER NC NO NC D2 07-03-2022 APPROVED FOR DESIGN BR MN/AKM SVM
CORE-4 CORE-4 CORE-4 CORE-4 CORE-4 CORE-4 CORE-4 CORE-4 D1 01-02-2022 APPROVED FOR DESIGN SSN MN/AKM SVM
12. 220kV GIS BUSCOUPLER NC NC NO
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A A1 10-01-2022 ISSUED FOR REVIEW SSN MN/AKM SVM
CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS 13. 220kV INCOMING LINE-2 FEEDER NO NC NC Owner
CORE-3 CORE-3 CORE-3 CORE-3 CORE-3 CORE-3 CORE-3 CORE-3 Rev. Date Reason for Issue Prepared Checked Approved Approved
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A LOSS OF INCOMING LINE - 1
CL-5P20 CL-5P20 CL-5P20 CL-5P20 CL-5P20 CL-5P20 CL-5P20 CL-5P20
CORE-2 CORE-2 CORE-2 CORE-2 CORE-2 CORE-2 CORE-2 CORE-2 14. 220kV INCOMING LINE-1 FEEDER NO NO NO
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 15. 220kV GIS BUSCOUPLER NC NC NC TECHNIP INDIA LIMITED
CL-0.5S CL-0.5S CL-0.5S CL-0.5S CL-0.5S CL-0.5S CL-0.5S CL-0.5S
CORE-1 CORE-1 CORE-1 CORE-1 CORE-1 CORE-1 CORE-1 CORE-1 16. 220kV INCOMING LINE-2 FEEDER NO NC NC
3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A 3000-2000/1A
NRL's PO NO.: 4300062833-AMA/16.06.2020
LOSS OF INCOMING LINE - 2
CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS CL-PS DOCUMENT NO.: 082176C-163-DW-1652-0001-01
P1 P1 P1 P1 P1 P1 P1 P1 17. 220kV INCOMING LINE-1 FEEDER NC NO NC
301-LA 303-LA 304-LA 306-LA 307-LA 309-LA 3010-LA 3012-LA
30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 18. 220kV GIS BUSCOUPLER NC NC NC
V V V V V V V V
19. 220kV INCOMING LINE-2 FEEDER NO NO NO NUMALIGARH REFINERY LIMITED
6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH 6Rx1Cx630Sq.mm XLPE/PH
ALUMINUM POWER CABLE ALUMINUM POWER CABLE ALUMINUM POWER CABLE ALUMINUM POWER CABLE ALUMINUM POWER CABLE ALUMINUM POWER CABLE ALUMINUM POWER CABLE ALUMINUM POWER CABLE Life Cycle
PROJECT: NUMALIGARH REFINERY EXPANSION PROJECT Code:
01
Scale:
KEY SINGLE LINE DIAGRAM FOR NTS
DRAWING TITLE: Drg.Size:
301 302 303 304 305 306 307 308 309 3010 3011 3012
220/33kV SYSTEM A0
33kV BAY 33kV BAY Drawing Sequence
33kV 33kV 33kV 33kV 33kV 33kV 33kV 33kV 33kV 33kV 33kV 33kV Originator/
(FUTURE) (FUTURE) Contractor Asset Code Disc Type Number Rev. Sheet
OUTGOING-1 INCOMER-1 OUTGOING-2 OUTGOING-1 INCOMER-1 OUTGOING-2 OUTGOING-1 INCOMER-1 OUTGOING-2 OUTGOING-1 INCOMER-1 OUTGOING-2
TP 1U63A EL SLD 0001.01 D1 01 OF 01