3 Out Ts Omm Mec HVC 3771 01 Eh 210320947 Omm of Hvac System For Kaw Plant
3 Out Ts Omm Mec HVC 3771 01 Eh 210320947 Omm of Hvac System For Kaw Plant
3 Out Ts Omm Mec HVC 3771 01 Eh 210320947 Omm of Hvac System For Kaw Plant
INDEX
S/No Description Page No
1 Introduction
3
2 Project Location
4
3 List of Equipment’s with Model Numbers
3
4 Product catalogue
5
5 Sequence of Operation
57
6 Operation and Maintenance Manual
59
7 Preventive Maintenance Procedures, Fault Isolation & Repair
Procedures 109
8 Operation and Maintenance Forms
123
9 List of Maintenance Tools & Equipment
129
10 Warranty certificates
131
11 Contact Details
134
12 Spare Parts Lists
138
13 Reference to Related As-Built Drawings
143
#2 1 0 3 2 0 9 4 7
1. INTRODUCTION
The Intent of this manual is to familiarize the maintenance personnel with the operation,
routine maintenance, and minor troubleshooting of the installed system in the building of
Khalid Ibn Alwaleed RO Plant.
Included are the minor repairs and adjustments guidelines necessary to maintain the air
conditioning and ventilation system operating in a satisfactory manner. Used properly, the
instructions included in this manual will extend the useful life of the Mechanical Equipment
in the building, prevent breakdown and maintain Power efficiency.
Air Conditioning and Ventilation system installed in the Building of Khalid Ibn Alwaleed RO
Plant consists of one Roof Top Package AC unit to supply Conditioned air into the Building
through Galvanized Steel sheet rectangular duct system adjusting with Volume dampers and
distributing via Supply air registers. Different Transfer air grilles have been installed in this
building in order to maintain air distribution from RO hall to Control room and Toilet area.
This Roof Top Package Ac unit takes fresh air from outside through sand Trap louver installed
on the return air duct on the roof controlled via manual Volume Control damper.
Roof mounted Exhaust fans connected with duct have been installed to maintain the fresh air
requirements and ventilation requirements of Chemical store room.
3. LIST OF EQUIPMENT.
S/No Product Model No Tag No Quantity Location
(Pcs)
4. PRODUCT CATALOGS
3
#2 1 0 3 2 0 9 4 7
ROOF TOP PACAKGE AC UNIT INSTALLED AT KAW RO PLANT
1 2 3
1
2 Description Values for KAA RO Plant PACU Values for KAW RO Plant PACU
3 MEC-HVC-2589 (BRT3 RO KAA) MEC-HVC-2630 (BRT3 RO KAW)
4 Unit Configuration Data
5 Unit Quantity 1 1
6 Volts-Phase-Hertz 400-3-60 400-3-60
Supply/Return Horizontal Supply / Horizontal Supply /
7 Horizontal Return Only Horizontal Return Only
8 Part Number Model 50TCMD14A2A2-0A0A0 50TCMD12B2A2-0A0A0
9 Cooling Performance
10 Cooling Airflow (m3/h) 7528.0 6894.0 4057 CFM
11 Altitude (m) 620.0 620.0
12 Ent. Air Dry Bulb (C) 25.5 27.3
13 Ent. Air Rel. Hum. (%) 41.9 34.7
14 Lvg. Air Dry Bulb (C) 13.0 14.9
15 Lvg. Air Rel. Hum. (%) 89.0 74.8
16 Cond. Ent. Air Temp (C) 48.0 48.0
17 Gross Cooling Capacity (kW) 34.6 29.5
18 Net Clg. Cap s/Supply Fan (kW) 31.3 26.5
19 Net Sensible Clg. Cap (kW) 29.3 26.5
20 Efficiency w/Fans 1.72 1.79
21 Unit Power Input w/Fans (kW) 18.2 14.8
22 Supply Fan Information
23 Fan Type Centrifugal Centrifugal
24 Drive Belt Belt
25 Fan kit Electromechanical Controller Electromechanical Controller
26 Fan RPM 1065.26 1034.589
27 Total Fan airflow 7528.00 6894.00
28 External static press (Pa) 400 400
29 Fan motor pwr. input (kW) 3.29 2.94
#2 1 0 3 2 0 9 4 7
Performance Summary For MEC-HVC-2630 (BRT3 RO KAW)
Project: BRT3 (RO PACU Selection KAW + KAA) 24-June-19 06/24/2019
Prepared By: 03:03PM
Unit Information
Tag Name: MEC-HVC-2630 (BRT3 RO KAW)
Model Number: 50TCMD12B2A2-0A0A0
Quantity: 1
Refrigerant: R-410A
Power Supply: 400-3-60
Operating Weight: 392 kg
Unit Length: 1252 mm
Unit Width: 2238 mm
Unit Height: 1509 mm
Altitude: 620 m
Performance Information
Cooling Mode
Gross Cooling Capacity: 29.5 kW
Total Sensible Cooling Capacity: 29.5 kW
Compressor Power Input: 10.0 kW
Unit Power Input (with fans): 14.8 kW
Evaporator Coil Leaving Temperature (dry bulb): 13.6 °C
Evaporator Coil Leaving Temperature (wet bulb): 11.8 °C
Number of capacity stages: 2
Acoustic Information
Electric Information
Unit Voltage: 400-3-60 V-Ph-Hz
Minimum Voltage: 360 V
Maximum Voltage: 420 V
Compressor 1 Rates Load Amps: 7.9 A
Compressor 1 Locked Rotor Amps: 66 A
Packaged Rooftop Builder EMEA 1.09e Page 3 of 4
#2 1 0 3 2 0 9 4 7
Performance Summary For MEC-HVC-2630 (BRT3 RO KAW)
Project: BRT3 (RO PACU Selection KAW + KAA) 24-June-19 06/24/2019
Prepared By: 03:03PM
Quality Assurance
Certificate Reg. No:
04 100 950420
50TCM – 60Hz
Unit Size 6.0 – 12.5 Tons
HFC R - 410A Refrigerant
The 50TCM units are single side discharge rooftop cooling unit utilizing electric heat as an option. Units are pre-
wired, pre-charged with R-410A refrigerant, and tested at the factory. These units can be placed on the side of a
building or can be placed on a roof without roof curbs. Each unit is designed to occupy a minimal space. Piping and
drain connections are readily accessible.
Features / Benefits
Every compact one-piece unit arrives fully assembled, charged, tested, and ready to run.
Durable-Dependable Construction
Designed for durability in any climate, the weather-resistant cabinets are constructed of galvanized steel,
bonderized, and all exterior panels are coated with a pre-painted baked enamel finish. The paint finish is non-
chalking, and is capable of withstanding ASTM (American Society for Testing and Materials) B117 500-hour Salt
Spray Test. All internal cabinet panels are primed, permitting longer life and a more attractive appearance for the
entire unit. Totally enclosed condenser-fan motor and permanently lubricated bearings provide additional unit
dependability.
Indoor-Air Quality
Non corrosive sloped condensate pans minimize biological growth in rooftop units in accordance with ASHRAE
(American Society of Heating, Refrigeration and Air Conditioning Engineers) Standard 62-99 (IAQ). 2”inch filters
provide for greater particle reduction in the return air.
Terminal boards, located in the unit control box, facilitate connections to room thermostat, outdoor thermostat(s) and
electric heater. Service panels can be quickly removed, permitting easy servicing. Both power and control
connections are made on the same side of the unit to simplify installation. In addition, color-coded wires permit easy
tracing and diagnostics.
Easy Installation
All units feature base rail design with forklift slots and rigging holes for easier maneuvering. Durable packaging
protects all units during shipment and storage. Convenient side by side openings permit installation very close to
face of buildings or on roof top. The non-corrosive sloped condensate pan minimizes residual condensate in off
cycle. An external, field-supplied P-trap is required. Field-installed electric heaters are available up to 45.9 kW.
#2 1 0 3 2 0 9 4 7
Installation Features
Performance Features
- HFC R-410A non-ozone depleting refrigerant
- ASHRAE 90.1 Compliant
- EER’s up to 12.2
- TXV refrigerant metering device
- Two independent refrigerant circuits, each with a scroll compressor
o
- Low outdoor temperature cooling operation down to 40 F
- Liquid filter drier standard on each circuit
- Non-corrosive sloped condensate drain pan in accordance to ASHRAE 62 standard
- Thermally protected and permanently lubricated condenser and evaporator fan motors
NOTES:
1. Please refer to product nomenclature for ordering information.
2. See application data for assistance.
#2 1 0 3 2 0 9 4 7
Factory Options and Accessories
Connect the rooftop to an existing BAS without complicated translators or adapter modules using the RTU
Open controller. This new controller speaks the 4 most common building automation system languages (BACNET,
Modbus, Johnson N2, and LonWorks). Use this controller when you have an existing BAS.
PremierLink
This CCN controller regulates your rooftop’s performance to tighter tolerances and expanded limits, as well as
facilitates zoning systems and digital accessories. It also unites your Carrier HVAC equipment together on one,
coherent CCN network. The PremierLink can be factory-installed, or easily field-installed.
This accessory protects your compressor by preventing short-cycling in the event of some other failure, prevents
the compressor from restarting for 30 seconds after stopping. Not required with PremierLink, RTU Open, or
authorized commercial thermostats.
Use these differential pressure switches to detect a filter clog or indoor fan motor failure. When used in conjunction
with a compatible unit controller/thermostat, the switches will activate an alarm to warn the appropriate personnel.
The winter start kit by Carrier extends the low ambient limit of your rooftop to 25°F (-4°C). The kit by-passes the low
pressure switch, preventing nuisance tripping of the low pressure switch. Other low ambient precautions may still be
prudent.
Some applications need larger horsepower motors, some need more airflow, and some need both. Regardless of the
case, your Carrier expert has a factory installed combination to meet your application. A wide selection of motors and
pulleys (drives) are available, factory installed, to handle nearly any application.
Electric Heaters
Carrier offers a full-line of field-installed accessory heaters. The heaters are very easy to use, install and are all pre-
engineered and certified.
#2 1 0 3 2 0 9 4 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
5 0 T C M A 0 7 A 2 A 1 - 0 A 0 A 0
Brand/Packaging
0 = Standard
Electrical Options
A = None
Unit Heat Type
50 = Cooling /
Electric Heat RTU
Service Options
0 = None
1 = Sight Glass
Sensor Options
A = None
Indoor Fan Options
1 = Standard Static Option
2 = Medium Static Option
3 = High Static Option
&85%6 :(,*+76',0(16,2167&0'
12-5/8"
8320:
28-5/16"
13-7/8" 8719:
8352:
36 3/8"
5$.% 8924:
36 3/8"
5$.% 8924:
'LPHQVLRQV7&.%
#2 1 0 3 2 0 9 4 7
$&/5&30'(3"7*5: $(
C10329
'LPHQVLRQV7&.%
6HUYLFH&OHDUDQFH
C08337
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes: 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
1. Direct interpolation is permissible. Do not extrapolate. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
2. The following formaulas may be used. - Above 80 F edb, add (corr factor x cfm) to SHC.
tldb = tedb — sensible capacity (Btuh) ENTERING AIR DRY-BULB TEMP (F)
1.10 x cfm 79 78 77 76 75 under 75
BF
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18 Use
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90 formula
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36 shown
0.30 0.76 1.53 2.29 3.05 3.82 below.*
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat.
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to - Interpolation is permissible.
unloaded operation and may be additinally limited to edb and ewb conditions. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
#2 1 0 3 2 0 9 4 7
50TCM - D08 - (230V/400V) - English
Evaporator Air - CFM/BPF
Temp (F)
2250 / 0.074 2625 / 0.093 3000 / 0.117 3375 / 0.144 3750 / 0.173
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 91,678 99,721 107,544 93,488 101,531 109,045 94,807 102,556 109,708 95,815 102,875 109,851 98,274 103,888 110,759
75 SHC 75,057 62,676 50,327 80,406 66,513 52,128 85,072 69,930 53,497 88,196 72,871 54,501 90,122 76,491 56,351
kW 4.43 4.44 4.47 4.43 4.44 4.48 4.44 4.45 4.50 4.44 4.46 4.51 4.44 4.47 4.52
TC 87,335 95,447 103,784 89,296 97,228 105,229 90,630 98,237 105,923 91,882 98,556 106,059 94,322 99,567 106,860
85 SHC 71,448 59,597 47,901 76,780 63,474 49,784 80,932 66,933 51,264 83,832 69,954 52,400 85,427 73,769 54,282
kW 5.06 5.10 5.14 5.09 5.11 5.16 5.10 5.12 5.17 5.10 5.13 5.19 5.11 5.14 5.20
TC 85,235 93,572 102,305 87,137 95,290 103,796 89,007 96,200 104,499 90,650 96,494 104,583 92,732 97,451 105,397
95 SHC 74,681 62,261 49,911 80,380 66,470 52,083 83,867 70,247 53,799 86,052 73,622 55,132 88,696 77,837 57,320
kW 5.79 5.86 5.90 5.83 5.87 5.92 5.85 5.88 5.94 5.85 5.89 5.95 5.87 5.90 5.96
TC 76,889 84,901 93,226 78,959 86,336 94,603 81,070 87,122 95,211 82,562 87,265 95,227 84,639 88,122 95,946
105 SHC 67,145 55,987 44,627 72,116 59,872 46,726 74,894 63,438 48,432 76,402 66,654 49,765 78,324 70,409 51,857
kW 6.38 6.49 6.54 6.43 6.50 6.56 6.48 6.52 6.58 6.50 6.53 6.59 6.51 6.53 6.60
TC 65,832 73,198 80,842 68,531 74,405 82,028 70,462 74,930 82,509 71,755 75,055 82,702 73,574 75,870 83,022
115 SHC 63,672 53,150 42,120 67,366 57,007 44,202 69,679 60,499 45,928 70,958 63,599 47,289 72,757 67,201 49,401
kW 7.10 7.27 7.33 7.20 7.29 7.35 7.26 7.30 7.36 7.28 7.31 7.37 7.30 7.32 7.38
TC 63,140 70,275 77,909 65,949 71,425 79,035 68,000 71,931 79,449 69,266 72,023 79,624 71,018 72,803 79,914
120 SHC 62,150 52,375 41,378 65,795 56,274 43,492 67,842 59,857 45,217 69,105 62,859 46,605 70,853 66,478 48,752
kW 7.75 7.97 8.03 7.88 7.99 8.05 7.96 8.00 8.07 7.99 8.01 8.08 8.01 8.02 8.09
TC 60,388 67,263 74,973 63,380 68,382 76,002 65,483 68,887 76,377 66,711 68,959 76,617 68,436 69,611 76,760
125 SHC 60,094 51,279 40,371 63,376 55,238 42,485 65,479 58,720 44,242 66,707 61,689 45,647 68,432 65,176 47,796
kW 7.94 8.19 8.28 8.09 8.23 8.30 8.19 8.25 8.32 8.24 8.26 8.33 8.26 8.27 8.34
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes: 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
1. Direct interpolation is permissible. Do not extrapolate. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
2. The following formaulas may be used. - Above 80 F edb, add (corr factor x cfm) to SHC.
tldb = tedb — sensible capacity (Btuh) ENTERING AIR DRY-BULB TEMP (F)
1.10 x cfm 79 78 77 76 75 under 75
BF
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18 Use
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90 formula
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36 shown
0.30 0.76 1.53 2.29 3.05 3.82 below.*
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat.
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to - Interpolation is permissible.
unloaded operation and may be additinally limited to edb and ewb conditions. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
#2 1 0 3 2 0 9 4 7
50TCM - D09 - (230V/400V) - English
Evaporator Air - CFM/BPF
Temp (F)
2550 / 0.022 2975 / 0.036 3500 / 0.045 3825 / 0.113 4250 / 0.154
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 107,731 117,058 126,956 110,890 120,294 130,273 114,222 123,374 132,919 116,431 124,907 134,200 119,389 126,535 135,613
75 SHC 97,679 82,191 66,908 105,939 88,273 70,647 114,952 95,566 74,640 118,998 100,007 77,008 122,749 105,521 80,005
kW 5.24 5.26 5.30 5.26 5.27 5.33 5.25 5.28 5.37 5.26 5.29 5.38 5.27 5.30 5.40
TC 102,548 112,233 122,277 105,908 115,296 125,628 109,602 118,176 128,283 111,923 119,676 129,542 114,925 121,164 130,958
85 SHC 95,141 80,116 65,105 103,590 86,279 69,017 111,756 93,604 73,314 114,798 98,104 75,795 118,353 103,678 78,940
kW 5.96 6.03 6.08 6.01 6.04 6.10 6.03 6.06 6.14 6.04 6.06 6.16 6.05 6.08 6.18
TC 96,398 106,782 116,796 100,139 109,715 119,918 104,776 112,422 122,690 107,185 113,745 123,931 110,143 115,236 125,172
95 SHC 92,125 77,769 62,935 100,603 84,010 66,835 107,987 91,458 71,361 110,271 95,931 73,985 113,543 101,459 77,247
kW 6.71 6.87 6.92 6.80 6.88 6.95 6.85 6.90 6.98 6.87 6.91 6.99 6.89 6.92 7.02
TC 88,622 99,996 110,656 93,052 103,193 113,565 98,756 105,865 116,154 101,685 107,155 117,405 104,680 108,549 118,663
105 SHC 87,763 74,915 60,569 95,797 81,362 64,464 101,906 88,889 69,039 104,823 93,383 71,748 108,127 98,939 75,142
kW 7.30 7.57 7.68 7.40 7.63 7.70 7.55 7.65 7.73 7.62 7.66 7.75 7.64 7.67 7.76
TC 79,458 89,348 101,141 84,412 92,386 103,927 89,753 95,351 106,484 92,597 96,742 107,664 95,937 98,300 108,921
115 SHC 82,717 71,179 57,746 89,149 77,759 61,735 94,601 85,557 66,407 97,599 90,054 69,182 101,220 95,805 72,710
kW 8.11 8.35 8.61 8.23 8.43 8.64 8.37 8.53 8.66 8.45 8.57 8.67 8.54 8.60 8.69
TC 77,501 86,725 99,071 82,700 89,720 101,851 88,036 92,523 104,318 90,804 93,995 105,507 94,024 95,650 106,816
120 SHC 80,214 69,307 56,180 85,594 75,917 60,218 91,026 83,615 64,914 93,973 88,171 67,722 97,315 93,861 71,328
kW 8.58 8.80 9.13 8.71 8.89 9.16 8.85 8.97 9.18 8.93 9.02 9.19 9.03 9.07 9.20
TC 74,133 82,172 94,687 79,198 85,013 97,464 84,372 87,781 99,822 87,080 89,183 100,968 90,196 91,145 102,183
125 SHC 76,728 67,438 54,510 81,970 74,000 58,615 87,325 81,705 63,336 90,128 86,178 66,172 93,353 91,283 69,782
kW 9.06 9.27 9.63 9.19 9.35 9.69 9.34 9.44 9.71 9.42 9.48 9.72 9.52 9.55 9.73
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes: 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
1. Direct interpolation is permissible. Do not extrapolate. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
2. The following formaulas may be used. - Above 80 F edb, add (corr factor x cfm) to SHC.
tldb = tedb — sensible capacity (Btuh) ENTERING AIR DRY-BULB TEMP (F)
1.10 x cfm 79 78 77 76 75 under 75
BF
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18 Use
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90 formula
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36 shown
0.30 0.76 1.53 2.29 3.05 3.82 below.*
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat.
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to - Interpolation is permissible.
unloaded operation and may be additinally limited to edb and ewb conditions. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
#2 1 0 3 2 0 9 4 7
50TCM - D12 - (230V/400V) - English
Evaporator Air - CFM/BPF
Temp (F)
3000 / 0.064 3500 / 0.086 4000 / 0.111 4500 / 0.138 5000 / 0.206
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 125,652 135,720 145,622 128,777 139,070 148,363 131,676 141,510 150,551 134,948 143,338 152,324 137,891 144,845 153,784
75 SHC 104,119 86,901 69,703 112,331 93,211 73,055 119,320 99,114 76,250 124,219 104,631 79,253 128,415 109,952 82,133
kW 5.77 5.78 5.86 5.78 5.80 5.89 5.78 5.82 5.92 5.78 5.84 5.94 5.80 5.86 5.96
TC 121,255 131,235 142,103 124,484 134,381 144,904 127,489 136,865 147,044 130,822 138,787 148,728 134,207 140,281 150,090
85 SHC 102,388 85,369 68,760 110,849 91,701 72,399 117,446 97,848 75,767 122,175 103,909 78,996 124,025 109,476 82,113
kW 6.64 6.63 6.68 6.63 6.64 6.72 6.64 6.65 6.74 6.64 6.67 6.77 6.65 6.68 6.79
TC 114,780 126,004 136,795 119,010 128,954 139,805 122,763 131,223 141,986 126,578 133,090 143,594 129,297 134,573 144,919
95 SHC 99,609 83,529 66,950 108,354 89,952 70,870 114,522 96,188 74,497 117,150 102,331 77,957 120,750 107,974 81,261
kW 7.47 7.57 7.61 7.55 7.58 7.63 7.57 7.59 7.65 7.57 7.60 7.68 7.58 7.60 7.69
TC 106,293 118,899 130,530 111,396 122,301 133,492 116,381 124,559 135,694 120,629 126,320 137,357 123,746 127,730 138,580
105 SHC 95,996 80,930 64,808 103,690 87,754 68,841 108,689 94,153 72,674 112,656 100,143 76,316 115,566 105,894 79,815
kW 8.10 8.34 8.44 8.19 8.41 8.45 8.30 8.42 8.47 8.40 8.42 8.48 8.41 8.43 8.50
TC 91,063 101,619 114,535 96,419 104,659 117,275 101,058 107,242 119,335 104,983 109,189 120,942 108,310 110,849 122,204
115 SHC 90,275 77,034 62,134 96,268 84,005 66,266 100,899 90,604 70,241 104,818 96,874 74,058 108,140 102,916 77,771
kW 9.37 9.60 9.92 9.49 9.68 9.94 9.60 9.76 9.95 9.70 9.82 9.96 9.80 9.87 9.98
TC 87,070 96,572 109,882 92,412 99,547 112,886 96,992 101,968 114,894 100,818 103,873 116,465 104,098 105,694 117,712
120 SHC 86,933 75,026 60,428 92,267 81,983 64,749 96,840 88,581 68,772 100,659 94,942 72,664 103,935 100,696 76,467
kW 9.86 10.08 10.45 9.99 10.17 10.52 10.11 10.24 10.54 10.21 10.29 10.55 10.31 10.35 10.56
TC 82,984 91,114 104,678 88,251 94,056 107,715 92,689 96,346 110,008 96,456 98,424 111,542 99,679 100,272 112,748
125 SHC 82,853 72,878 58,561 88,112 79,813 62,962 92,543 86,394 67,144 96,305 92,686 71,082 99,522 98,276 74,922
kW 10.35 10.56 10.94 10.49 10.64 11.04 10.61 10.71 11.12 10.72 10.78 11.13 10.82 10.84 11.14
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes: 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
1. Direct interpolation is permissible. Do not extrapolate. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
2. The following formaulas may be used. - Above 80 F edb, add (corr factor x cfm) to SHC.
tldb = tedb — sensible capacity (Btuh) ENTERING AIR DRY-BULB TEMP (F)
1.10 x cfm 79 78 77 76 75 under 75
BF
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18 Use
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90 formula
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36 shown
0.30 0.76 1.53 2.29 3.05 3.82 below.*
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat.
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to - Interpolation is permissible.
unloaded operation and may be additinally limited to edb and ewb conditions. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
#2 1 0 3 2 0 9 4 7
50TCM - D14 - (230V/400V) - English
Evaporator Air - CFM/BPF
Temp (F)
3700 / 0.084 4100 / 0.093 4550 / 0.104 5300 / 0.116 6000 / 0.158
Air Entering
Evaporator Air - EWB (F)
Condenser (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 156,424 169,175 184,214 159,260 171,869 184,328 161,970 174,348 186,546 166,196 177,655 189,348 170,399 179,946 191,200
75 SHC 136,012 114,016 87,697 143,190 119,109 95,028 150,888 124,563 98,196 161,528 133,334 103,121 167,494 141,057 107,319
kW 8.76 8.80 8.90 8.77 8.81 8.90 8.77 8.82 8.92 8.78 8.85 8.96 8.78 8.87 8.98
TC 149,624 162,980 176,147 152,662 165,645 178,686 155,678 168,162 181,049 160,234 171,267 183,971 164,277 173,573 185,939
85 SHC 132,754 111,548 90,042 140,204 116,771 93,123 148,058 122,368 96,454 157,939 131,470 101,672 164,376 139,545 106,233
kW 9.76 9.84 9.91 9.79 9.85 9.94 9.81 9.86 9.96 9.82 9.89 10.00 9.84 9.91 10.03
TC 144,371 158,951 172,547 147,846 161,517 175,176 151,252 163,887 177,445 156,691 167,138 180,431 160,644 169,321 182,446
95 SHC 128,913 108,599 87,444 136,485 113,833 90,652 143,681 119,621 94,039 152,679 128,903 99,442 158,902 137,060 104,189
kW 10.77 10.96 11.04 10.85 10.98 11.07 10.89 10.99 11.09 10.95 11.02 11.13 10.96 11.03 11.16
TC 131,597 146,195 159,389 135,123 148,477 161,706 139,295 150,609 163,929 144,744 153,540 166,637 148,396 155,703 168,568
105 SHC 122,514 103,438 82,918 129,635 108,577 86,071 135,555 114,330 89,530 143,733 123,398 94,916 149,590 131,514 99,721
kW 11.86 12.16 12.25 11.95 12.18 12.28 12.06 12.20 12.31 12.14 12.22 12.34 12.16 12.24 12.37
TC 118,119 132,253 145,247 121,284 134,568 147,294 126,045 136,547 149,229 130,975 139,186 151,636 136,464 141,116 153,336
115 SHC 111,331 94,426 75,442 117,803 99,542 78,424 122,841 104,960 81,692 130,252 113,551 86,813 132,996 121,176 91,377
kW 13.01 13.46 13.57 13.11 13.48 13.59 13.28 13.50 13.62 13.37 13.53 13.65 13.49 13.54 13.67
TC 113,355 127,031 140,390 117,056 129,459 142,346 121,650 131,510 144,176 128,009 134,091 146,493 132,161 135,945 148,071
120 SHC 109,778 94,362 75,316 116,647 99,699 78,363 121,636 105,290 81,692 127,577 114,104 86,936 131,716 121,789 91,609
kW 13.73 14.22 14.38 13.85 14.30 14.41 14.03 14.32 14.43 14.26 14.34 14.47 14.32 14.36 14.50
TC 108,260 121,323 135,605 112,788 123,852 137,499 117,152 126,219 139,242 123,410 128,933 141,530 127,862 130,875 142,966
125 SHC 107,437 92,347 73,814 112,020 97,762 76,898 117,126 103,584 80,236 123,383 112,599 85,550 127,834 120,276 90,202
kW 14.64 15.13 15.42 14.80 15.24 15.44 14.98 15.33 15.46 15.23 15.37 15.50 15.35 15.39 15.53
LEGEND
BPF — Bypass Factor Ldb — Leaving Dry-Bulb
Edb — Entering Dry-Bulb Lwb — Leaving Wet-Bulb
Ewb — Entering Wet-Bulb TC — Total Capacity (1000 Btuh) Gross
SHC — Sensible Heat Capacity (1000 Btuh) Gross kW — Compressor Motor Power Input
Bold, Italics - Standard Ratings
Notes: 3. The SHC is based on 80 F edb temprature of air entering evaporator coil.
1. Direct interpolation is permissible. Do not extrapolate. - Below 80 F edb, subtract (corr factor x cfm) from SHC.
2. The following formaulas may be used. - Above 80 F edb, add (corr factor x cfm) to SHC.
tldb = tedb — sensible capacity (Btuh) ENTERING AIR DRY-BULB TEMP (F)
1.10 x cfm 79 78 77 76 75 under 75
BF
tlwb = Wet-bulb temprature corresponding to enthalphy of air leaving evaporater coil (hlwb). 81 82 83 84 85 over 85
Correction Factor
hlwb = hewb — total capacity (Btuh) 0.05 1.04 2.07 3.11 4.14 5.18 Use
4.5 x cfm 0.10 0.98 1.96 2.94 3.92 4.90 formula
Where: hewb = Enthaply of air entering evaporator coil. 0.20 0.87 1.74 2.62 3.49 4.36 shown
0.30 0.76 1.53 2.29 3.05 3.82 below.*
4. Cooling capacities are gross and do not include deductions for indoor fan motor heat.
5. Variable Air Volume units will operate down to 70 cfm/ton. Performance at 70 cfm/ton is limited to - Interpolation is permissible.
unloaded operation and may be additinally limited to edb and ewb conditions. *Correction Factor = 1.10 x (1 - BF) x (edb - 80).
#2 1 0 3 2 0 9 4 7
Unit 50TCM - A07 - 230V
Available External Static Pressure (in. wg)
Air flow
0.2 0.4 0.6 0.8 1.0
Rate (CFM)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
1800 822 0.48 0.51 927 0.62 0.66 1018 0.76 0.82 1100 0.91 0.98 1174 1.07 1.15
1950 872 0.58 0.62 973 0.74 0.79 1061 0.89 0.95 1140 1.05 1.13 1213 1.22 1.31
2100 923 0.70 0.75 1019 0.86 0.92 1104 1.03 1.10 1182 1.20 1.29 1253 1.38 1.48
2250 974 0.84 0.90 1067 1.01 1.08 1149 1.18 1.27 1224 1.36 1.46 1294 1.55 1.66
2400 1026 0.99 1.06 1115 1.17 1.26 1195 1.36 1.46 1268 1.55 1.66 1336 1.74 1.87
2550 1079 1.17 1.25 1164 1.36 1.46 1241 1.56 1.67 1312 1.75 1.88 1379 1.96 2.10
2700 1132 1.36 1.46 1214 1.56 1.67 1289 1.77 1.90 1358 1.98 2.12 1422 2.19 2.35
2850 1186 1.58 1.69 1264 1.79 1.92 1336 2.00 2.15 1404 2.23 2.39 1467 2.42 2.63
3000 1240 1.81 1.94 1315 2.03 2.18 1385 2.27 2.43 1451 2.47 2.68 1512 2.70 2.93
Bold, Italics RPM is the factory setting . In range of +- 5 % due to different voltage application (230V and 400V)
The standard belt size may not cover all the above range. Other RPMs require field supplied drive package.
dB – Decibel
NOTES:
1. Measurements are expressed in terms of sound power. Do not compare these values to sound pressure values because sound pressure accounts
for specific environment factors which do not match individual applications. Sound power values are independent of the environment and therefore
2. A–Weighted t sound ratings filter out very high and very low frequencies, to better approximate the response of an “average” human ear.
#2 1 0 3 2 0 9 4 7
50TCM - 230/3/60Hz application Compressor
OFM IFM Electric Heater
No.1 No.2 MCA MOCP
Unit Size Power Supply Drive package
50TCM V / Ph / Hz Indoor Motor P.N. APP
RLA LRA RLA LRA Qty HP FLA HP FLA FLA
CRHEATERXXXXXX (KW)
19 123 - - 1 1/3 2.8 2.4 5.2 - - - 31.8 50
19 123 - - 1 1/3 2.8 2.4 5.2 102A00 6.0 15.6 31.8 50
19 123 - - 1 1/3 2.8 2.4 5.2 104B00 9.6 25.3 38.1 50
Standard
19 123 - - 1 1/3 2.8 2.4 5.2 105A00 14.7 38.5 54.6 60
19 123 - - 1 1/3 2.8 2.4 5.2 104B00, 104B00 19.3 50.5 69.6 70
19 123 - - 1 1/3 2.8 2.4 5.2 104B00, 105A00 24.3 63.8 86.3 90
19 123 - - 1 1/3 2.8 2.9 7.5 - - - 34.1 50
19 123 - - 1 1/3 2.8 2.9 7.5 102A00 6.0 15.6 34.1 50
19 123 - - 1 1/3 2.8 2.9 7.5 104B00 9.6 25.3 41.0 50
A07 230/3/60 Medium
19 123 - - 1 1/3 2.8 2.9 7.5 105A00 14.7 38.5 57.5 60
19 123 - - 1 1/3 2.8 2.9 7.5 104B00, 104B00 19.3 50.5 72.5 80
19 123 - - 1 1/3 2.8 2.9 7.5 104B00, 105A00 24.3 63.8 89.1 90
19 123 - - 1 1/3 2.8 3.7 10 - - - 36.6 50
19 123 - - 1 1/3 2.8 3.7 10 102A00 6.0 15.6 36.6 50
19 123 - - 1 1/3 2.8 3.7 10 104B00 9.6 25.3 44.1 50
High
19 123 - - 1 1/3 2.8 3.7 10 105A00 14.7 38.5 60.6 70
19 123 - - 1 1/3 2.8 3.7 10 104B00, 104B00 19.3 50.5 75.6 80
19 123 - - 1 1/3 2.8 3.7 10 104B00, 105A00 24.3 63.8 92.3 100
13.6 83 13.6 83 2 1/4 1.4 1.7 5.2 - - - 38.6 50
13.6 83 13.6 83 2 1/4 1.4 1.7 5.2 117A00 9.6 25 38.6 50
13.6 83 13.6 83 2 1/4 1.4 1.7 5.2 110A00 14.7 38.5 54.6 60
Standard
13.6 83 13.6 83 2 1/4 1.4 1.7 5.2 111A00 22.8 59.7 81.1 90
13.6 83 13.6 83 2 1/4 1.4 1.7 5.2 112A00 29.4 77 102.8 110
13.6 83 13.6 83 2 1/4 1.4 1.7 5.2 112A00, 117A00 38.9 102 134.0 150
13.6 83 13.6 83 2 1/4 1.4 2.9 7.5 - - - 40.9 50
13.6 83 13.6 83 2 1/4 1.4 2.9 7.5 117A00 9.6 25 40.9 50
13.6 83 13.6 83 2 1/4 1.4 2.9 7.5 110A00 14.7 38.5 57.5 60
D08 230/3/60 Medium
13.6 83 13.6 83 2 1/4 1.4 2.9 7.5 111A00 22.8 59.7 84.0 90
13.6 83 13.6 83 2 1/4 1.4 2.9 7.5 112A00 29.4 77 105.6 110
13.6 83 13.6 83 2 1/4 1.4 2.9 7.5 112A00, 117A00 38.9 102 136.9 150
13.6 83 13.6 83 2 1/4 1.4 4.7 15 - - - 48.4 60
13.6 83 13.6 83 2 1/4 1.4 4.7 15 117A00 9.6 25 50.0 60
13.6 83 13.6 83 2 1/4 1.4 4.7 15 110A00 14.7 38.5 66.9 70
High
13.6 83 13.6 83 2 1/4 1.4 4.7 15 111A00 22.8 59.7 93.4 100
13.6 83 13.6 83 2 1/4 1.4 4.7 15 112A00 29.4 77 115.0 125
13.6 83 13.6 83 2 1/4 1.4 4.7 15 112A00, 117A00 38.9 102 146.3 150
14.5 98 13.7 83 2 1/4 1.4 1.7 5.2 - - - 39.8 50
14.5 98 13.7 83 2 1/4 1.4 1.7 5.2 117A00 9.6 25 39.8 50
14.5 98 13.7 83 2 1/4 1.4 1.7 5.2 110A00 14.7 38.5 54.6 60
Standard
14.5 98 13.7 83 2 1/4 1.4 1.7 5.2 111A00 22.8 59.7 81.1 90
14.5 98 13.7 83 2 1/4 1.4 1.7 5.2 112A00 29.4 77 102.8 110
14.5 98 13.7 83 2 1/4 1.4 1.7 5.2 112A00, 117A00 38.9 102 134.0 150
14.5 98 13.7 83 2 1/4 1.4 2.4 5.2 - - - 39.8 50
14.5 98 13.7 83 2 1/4 1.4 2.4 5.2 117A00 9.6 25 39.8 50
14.5 98 13.7 83 2 1/4 1.4 2.4 5.2 110A00 14.7 38.5 54.6 60
D09 230/3/60 Medium
14.5 98 13.7 83 2 1/4 1.4 2.4 5.2 111A00 22.8 59.7 81.1 90
14.5 98 13.7 83 2 1/4 1.4 2.4 5.2 112A00 29.4 77 102.8 110
14.5 98 13.7 83 2 1/4 1.4 2.4 5.2 112A00, 117A00 38.9 102 134.0 150
14.5 98 13.7 83 2 1/4 1.4 3.7 10 - - - 44.6 50
14.5 98 13.7 83 2 1/4 1.4 3.7 10 117A00 9.6 25 44.6 50
14.5 98 13.7 83 2 1/4 1.4 3.7 10 110A00 14.7 38.5 60.6 70
High
14.5 98 13.7 83 2 1/4 1.4 3.7 10 111A00 22.8 59.7 87.1 90
14.5 98 13.7 83 2 1/4 1.4 3.7 10 112A00 29.4 77 108.8 110
14.5 98 13.7 83 2 1/4 1.4 3.7 10 112A00, 117A00 38.9 102 140.0 150
#2 1 0 3 2 0 9 4 7
50TCM - 230/3/60Hz application Compressor
OFM IFM Electric Heater
No.1 No.2 MCA MOCP
Unit Size Power Supply Drive package
50TCM V / Ph / Hz Indoor Motor P.N. APP
RLA LRA RLA LRA Qty HP FLA HP FLA FLA
CRHEATERXXXXXX (KW)
15.9 110 15.9 110 1 1 6.6 2.4 5.2 - - - 47.6 60
15.9 110 15.9 110 1 1 6.6 2.4 5.2 117A00 9.6 25 47.6 60
15.9 110 15.9 110 1 1 6.6 2.4 5.2 110A00 14.7 38.5 54.6 60
Standard
15.9 110 15.9 110 1 1 6.6 2.4 5.2 112A00 29.4 77 102.8 110
15.9 110 15.9 110 1 1 6.6 2.4 5.2 112A00, 117A00 38.9 102 134.0 150
15.9 110 15.9 110 1 1 6.6 2.4 5.2 112A00, 110A00 45.9 120.3 156.9 175
15.9 110 15.9 110 1 1 6.6 3.7 10 - - - 52.4 60
15.9 110 15.9 110 1 1 6.6 3.7 10 117A00 9.6 25 52.4 60
15.9 110 15.9 110 1 1 6.6 3.7 10 110A00 14.7 38.5 60.6 70
D12 230/3/60 Medium
15.9 110 15.9 110 1 1 6.6 3.7 10 112A00 29.4 77 108.8 110
15.9 110 15.9 110 1 1 6.6 3.7 10 112A00, 117A00 38.9 102 140.0 150
15.9 110 15.9 110 1 1 6.6 3.7 10 112A00, 110A00 45.9 120.3 162.9 175
15.9 110 15.9 110 1 1 6.6 4.7 15 - - - 57.4 70
15.9 110 15.9 110 1 1 6.6 4.7 15 117A00 9.6 25 57.4 70
15.9 110 15.9 110 1 1 6.6 4.7 15 110A00 14.7 38.5 66.9 70
High
15.9 110 15.9 110 1 1 6.6 4.7 15 112A00 29.4 77 115.0 125
15.9 110 15.9 110 1 1 6.6 4.7 15 112A00, 117A00 38.9 102 146.3 150
15.9 110 15.9 110 1 1 6.6 4.7 15 112A00, 110A00 45.9 120.3 169.1 175
19 123 22.4 149 1 1 6.6 2.9 7.5 - - - 60.3 70
19 123 22.4 149 1 1 6.6 2.9 7.5 117A00 9.6 25 60.3 70
19 123 22.4 149 1 1 6.6 2.9 7.5 110A00 14.7 38.5 60.3 70
Standard
19 123 22.4 149 1 1 6.6 2.9 7.5 112A00 29.4 77 105.6 110
19 123 22.4 149 1 1 6.6 2.9 7.5 112A00, 117A00 38.9 102 136.9 150
19 123 22.4 149 1 1 6.6 2.9 7.5 112A00, 110A00 45.9 120.3 159.8 175
19 123 22.4 149 1 1 6.6 3.7 10 - - - 62.8 80
19 123 22.4 149 1 1 6.6 3.7 10 117A00 9.6 25 62.8 80
19 123 22.4 149 1 1 6.6 3.7 10 110A00 14.7 38.5 62.8 80
D14 230/3/60 Medium
19 123 22.4 149 1 1 6.6 3.7 10 112A00 29.4 77 108.8 110
19 123 22.4 149 1 1 6.6 3.7 10 112A00, 117A00 38.9 102 140.0 150
19 123 22.4 149 1 1 6.6 3.7 10 112A00, 110A00 45.9 120.3 162.9 175
19 123 22.4 149 1 1 6.6 4.7 15 - - - 67.8 80
19 123 22.4 149 1 1 6.6 4.7 15 117A00 9.6 25 67.8 80
19 123 22.4 149 1 1 6.6 4.7 15 110A00 14.7 38.5 67.8 80
High
19 123 22.4 149 1 1 6.6 4.7 15 112A00 29.4 77 115.0 125
19 123 22.4 149 1 1 6.6 4.7 15 112A00, 117A00 38.9 102 146.3 150
19 123 22.4 149 1 1 6.6 4.7 15 112A00, 110A00 45.9 120.3 169.1 175
For ordering electric heater: Include complete heater part number in the order placement e.g CRHEATER116A00.
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
#2 1 0 3 2 0 9 4 7
50TCM-400/3/60Hz application Compressor
OFM IFM Electric Heater
No.1 No.2 MCA MOCP
Unit Size Power Supply Drive package
50TCM V / Ph / Hz Indoor Motor P.N. APP
RLA LRA RLA LRA Qty HP FLA HP FLA FLA
CRHEATERXXXXXX (KW)
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 - - - 19.0 30
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 106A00 4.2 6 19.0 30
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 108A00 8 11.5 19.0 30
Standard
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 109A00 9.7 14 21.0 30
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 108A00, 108A00 16 23.1 32.4 35
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 108A00, 109A00 17.7 25.6 35.5 40
10.7 78.0 - - 1 1/3 2.8 3 5 - - - 21.2 30
10.7 78.0 - - 1 1/3 2.8 3 5 106A00 4.2 6 21.2 30
10.7 78.0 - - 1 1/3 2.8 3 5 108A00 8 11.5 21.2 30
A07 400/3/60 Medium
10.7 78.0 - - 1 1/3 2.8 3 5 109A00 9.7 14 23.8 30
10.7 78.0 - - 1 1/3 2.8 3 5 108A00, 108A00 16 23.1 35.1 40
10.7 78.0 - - 1 1/3 2.8 3 5 108A00, 109A00 17.7 25.6 38.3 40
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 - - - 23.7 30
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 106A00 4.2 6 23.7 30
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 108A00 8 11.5 23.8 30
High
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 109A00 9.7 14 26.9 30
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 108A00, 108A00 16 23.1 38.3 40
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 108A00, 109A00 17.7 25.6 41.4 45
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 - - - 22.7 30
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 116A00 9.7 13.9 22.7 30
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 113A00 11.5 16.5 24.1 30
Standard
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 114A00 19.3 27.9 38.4 40
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 115A00 22.9 33.1 44.9 45
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 114A00, 116A00 29 41.8 55.8 60
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 - - - 24.9 30
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 116A00 9.7 13.9 24.9 30
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 113A00 11.5 16.5 26.9 30
D08 400/3/60 Medium
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 114A00 19.3 27.9 41.1 45
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 115A00 22.9 33.1 47.6 50
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 114A00, 116A00 29 41.8 58.5 60
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 - - - 27.4 35
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 116A00 9.7 13.9 27.4 35
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 113A00 11.5 16.5 30.0 35
High
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 114A00 19.3 27.9 44.3 45
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 115A00 22.9 33.1 50.8 60
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 - - - 25.4 30
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 116A00 9.7 13.9 25.4 30
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 113A00 11.5 16.5 25.4 30
Standard
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 114A00 19.3 27.9 38.4 40
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 115A00 22.9 33.1 44.9 45
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 114A00, 116A00 29 41.8 55.8 60
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 - - - 26.8 35
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 116A00 9.7 13.9 26.8 35
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 113A00 11.5 16.5 26.8 35
D09 400/3/60 Medium
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 114A00 19.3 27.9 40.1 45
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 115A00 22.9 33.1 46.6 50
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 114A00, 116A00 29 41.8 57.5 60
8.8 64 8.8 64.0 2 1/4 1.42 3 5 - - - 27.6 35
8.8 64 8.8 64.0 2 1/4 1.42 3 5 116A00 9.7 13.9 27.6 35
8.8 64 8.8 64.0 2 1/4 1.42 3 5 113A00 11.5 16.5 27.6 35
High
8.8 64 8.8 64.0 2 1/4 1.42 3 5 114A00 19.3 27.9 41.1 45
8.8 64 8.8 64.0 2 1/4 1.42 3 5 115A00 22.9 33.1 47.6 50
8.8 64 8.8 64.0 2 1/4 1.42 3 5 114A00, 116A00 29 41.8 58.5 60
#2 1 0 3 2 0 9 4 7
50TCM-400/3/60Hz application Compressor
OFM IFM Electric Heater
No.1 No.2 MCA MOCP
Unit Size Power Supply Drive package
50TCM V / Ph / Hz Indoor Motor P.N APP
RLA LRA RLA LRA Qty HP FLA HP FLA FLA
CRHEATERXXXXXX (KW)
7.9 66 7.9 66 1 1 3.9 2.5 4.2 - - - 25.9 30
7.9 66 7.9 66 1 1 3.9 2.5 4.2 116A00 9.7 13.9 25.9 30
7.9 66 7.9 66 1 1 3.9 2.5 4.2 113A00 11.5 16.5 25.9 30
Standard
7.9 66 7.9 66 1 1 3.9 2.5 4.2 115A00 22.9 33.1 46.6 50
7.9 66 7.9 66 1 1 3.9 2.5 4.2 114A00, 116A00 29 41.8 57.5 60
7.9 66 7.9 66 1 1 3.9 2.5 4.2 115A00, 113A00 34.7 50.1 67.9 70
7.9 66 7.9 66 1 1 3.9 4.7 7.5 - - - 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 116A00 9.7 13.9 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 113A00 11.5 16.5 30.0 35
D12 400/3/60 Medium
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
7.9 66 7.9 66 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
7.9 66 7.9 66 1 1 3.9 4.7 7.5 - - - 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 116A00 9.7 13.9 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 113A00 11.5 16.5 30.0 35
High
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
7.9 66 7.9 66 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
10.7 78.0 11.0 88.0 1 1 3.9 3 5 - - - 33.3 40
10.7 78.0 11.0 88.0 1 1 3.9 3 5 116A00 9.7 13.9 33.3 40
10.7 78.0 11.0 88.0 1 1 3.9 3 5 113A00 11.5 16.5 33.3 40
Standard
10.7 78.0 11.0 88.0 1 1 3.9 3 5 115A00 22.9 33.1 47.6 50
10.7 78.0 11.0 88.0 1 1 3.9 3 5 114A00, 116A00 29 41.8 58.5 60
10.7 78.0 11.0 88.0 1 1 3.9 3 5 115A00, 113A00 34.7 50.1 68.9 70
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 - - - 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 116A00 9.7 13.9 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 113A00 11.5 16.5 35.8 45
D14 400/3/60 Medium
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 - - - 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 116A00 9.7 13.9 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 113A00 11.5 16.5 35.8 45
High
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
For ordering electric heater: Include complete heater part number in the order placement e.g CRHEATER116A00.
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
Application Data
#2 1 0 3 2 0 9 4 7
Min operating ambient temp (cooling)
In mechanical cooling mode, your Carrier rooftop can safely operate down to an outdoor ambient temperature of
40°F (4°C) and 25°F (- 4°C), with an accessory winter start kit.
The maximum operating ambient temperature for cooling mode is 125°F (52°C).
Airflow
Due to Carrier’s internal unit design, air path, and specially designed motors, the full horsepower (maximum
continuous BHP) band, can be used with the utmost confidence. There is no need for extra safety factors, as
Carrier’s motors are designed and rigorously tested to use the entire, listed BHP range without either
nuisance tripping or premature motor failure.
Sizing a rooftop
Bigger isn’t necessarily better. While an air conditioner needs to have enough capacity to meet the load, it doesn’t
need excess capacity. In fact, having excess capacity typically results in very poor part load performance and
humidity control.
Using higher design temperatures than ASHRAE recommends for your location, adding “safety factors” to the
calculated load, and rounding up to the next largest unit, are all signs of oversizing air conditioners. Oversizing can
cause short-cycling, and short cycling leads to poor humidity control, reduced efficiency, higher utility bills, drastic
indoor temperature swings, excessive noise, and increased wear and tear on the air conditioner.
Rather than oversizing an air conditioner, wise contractors and engineers “right-size” or even slightly undersize air
conditioners. Correctly sizing an air conditioner controls humidity better; promotes efficiency; reduces utility bills;
extends equipment life, and maintains even, comfortable temperatures.
Winter start
Carrier’s winter start kit extends the low ambient limit of your rooftop to 25°F (- 4°C). The kit bypasses the low
pressure switch, preventing nuisance tripping of the low pressure switch. Other low ambient precautions may still
be prudent.
#2 1 0 3 2 0 9 4 7
Guide Specifications
System Description
Small-Capacity Self-Contained Air Conditioners (50TCM)
Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing hermetic scroll
compressor(s) for cooling duty and electric for heating duty.
Quality Assurance
1. Unit shall achieve ASHRAE 90.1 minimum efficiency requirements (2015 version).
2. Unit shall be designed to conform to ASHRAE 15, 2001.
3. Unit shall be rated in accordance with AHRI Standards 340/360 and SASO 2874/2016.
4. Unit shall be in compliance with SASO 2874/2016.
5. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
6. Unit casing shall be capable of withstanding 500 hour salt spray exposure per ASTM B117 (scribed
specimen).
7. Unit shall be designed and manufactured in a facility in accordance and registered by ISO 9001:2015.
8. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit
will be stored at the factory, and must be available upon request.
9. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.
Product General
1. Factory assembled, single piece heating and cooling rooftop unit. Contained within the unit enclosure shall
be all factory wiring, piping, controls, and special features required prior to field start up.
2. Unit shall use environmentally safe, Puron refrigerant.
3. Unit shall be installed in accordance with the manufacturer’s instructions.
4. Unit must be selected and installed in compliance with local, state, and federal codes.
5. Interior cabinet surfaces shall be insulated with closed cell foam minimum ½ -in. thick, minimum density
3
3.1lb/ft .
Unit Cabinet
1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a pre
painted baked enamel finish on all externally exposed surfaces.
2 . Unit cabinet exterior paint shall be: film thickness, (dry) 76mm minimum, gloss (per ASTM D523, 60°F):
60, Hardness: H 2H Pencil hardness.
3 . Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or
340/360 minimum exterior sweat criteria.
4. Base of unit shall have a minimum of four locations for thru the base gas and electrical connections
(factory installed or field installed), standard.
5. Base Rail
a) Unit shall have base rails on a minimum of 2 sides.
b) Holes shall be provided in the base rails for rigging shackles to ease maneuvering and overhead rigging.
c) Holes shall be provided in the base rail for moving the rooftop by fork truck.
d) Base rail shall be a minimum of 16 gauge thickness.
6. Condensate pan and connections:
a) Shall be a sloped condensate drain pan made of a non corrosive material.
b) Shall comply with ASHRAE Standard 62.
c) Shall use a 3/4” 14 NPT drain connection, possible either through the bottom or end of the drain pan.
Connection shall be made per manufacturer’s recommendations.
7. Top panel:
Shall be a single piece top panel on 07 size, two piece on 08 thru 14 size.
8. Electrical Connections:
All unit power wiring shall enter unit cabinet at a single, factory prepared, knock out location.
9. Component access panels (standard):
#2 1 0 3 2 0 9 4 7
a) Cabinet panels shall be easily removable for servicing.
b) Unit shall have one factory installed; tool less, removable, filter access panel.
c) Panels covering control box, indoor fan, indoor fan motor, and compressors shall have molded composite
handles.
d) Handles shall be UV modified, composite, permanently attached, and recessed into the panel.
e) Screws on the vertical portion of all removable access panels shall engage into heat resistant, molded
composite collars.
f) Collars shall be removable and easily replaceable using manufacturer recommended parts.
Coils
Standard Aluminum fin Copper Tube Coils:
1. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to
seam- less internally grooved copper tubes with all joints brazed.
2. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995
burst test at 1775 psig.
3. Condenser coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst
test at 1980 psig.
Refrigerant Components
1. Refrigerant circuit shall include the following control, safety, and maintenance features:
a) Refrigerant system shall include fixed orifice or TXV metering system.
b) Fixed orifice metering system shall prevent mal distribution of two phase refrigerant by including multiple
fixed orifice devices in each refrigeration circuit. Each orifice is to be optimized to the coil circuit it serves.
c) Refrigerant filter drier.
d) Service gauge connections on suction and discharge lines.
2. There shall be gauge line access, covered cap:
a) The plug shall be easy to remove and replace.
b) When the plug is removed, the gauge access port shall enable maintenance personnel to route their
pressure gauge lines.
c) This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the
reading with the compressor access panel on.
d) The plug shall be made of a leak proof, UV resistant, composite material.
3. Compressors:
a) Unit shall use one fully hermetic, scroll compressor for each independent refrigeration circuit.
b) Compressor motors shall be cooled by refrigerant gas passing through motor windings.
c) Compressors shall be internally protected from high discharge temperature conditions.
d) Compressors shall be protected from an over temperature and over amperage conditions by an internal,
motor overload device.
e) Compressor shall be factory mounted on rubber grommets.
f) Compressor motors shall have internal line break thermal, current overload and high pressure differential
protection.
g) Crankcase heaters shall not be required for normal operating range, unless provided by compressor
manufacturer due to refrigerant charge limits.
Condenser Fans:
1. Shall be a direct driven propeller type fan.
2. Shall have aluminum blades riveted to corrosion resistant steel spiders and shall be dynamically balanced.
Safeties:
1. Compressor over-temperature, over current.
2. Low pressure switch:
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross wiring of the safety switches between circuits 1
and 2.
b. Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3. High pressure switch:
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross wiring of the safety switches between circuits 1
and 2.
b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Automatic reset, motor thermal overload protector.
Filter Section
1. Filters access is specified in the unit cabinet section of this specification.
2. Filters shall be held in place by a pivoting filter tray, facilitating easy removal and installation.
3. Shall consist of factory installed, low velocity; throw away 2 in. thick fiberglass filters with G4 classification.
4. Filters shall be standard, commercially available sizes.
5. Only one size filter per unit is allowed.
Operating Characteristics
1. Unit shall be capable of starting and running at 125°F (52°C) ambient outdoor temperature, meeting
maximum load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.
2. Compressor with standard controls shall be capable of operation down to 40°F (4°C), ambient outdoor
temperatures. Accessory winter start kit is necessary if mechanically cooling at ambient temperatures
down to 25°F (-- 4°C).
3. Unit shall discharge supply air horizontally as shown on contract drawings.
4. Unit shall be factory configured for horizontal supply and return configurations.
Thermostats
Thermostat must:
1. Energize both “W” and “G” when calling for heat.
2. Have capability to energize 2 different stages of cooling, and 2 different stages of heating.
3. Include capability for occupancy scheduling.
Electrical Requirements
Main power supply voltage, phase, and frequency must match those required by the manufacturer.
Special Features: Options and Accessories
#2 1 0 3 2 0 9 4 7
Open protocol, direct digital controller:
1. Shall be ASHRAE 62-2001 compliant.
2. Shall accept 18-30VAC, 50-60Hz, and consumer 15VA or less power.
3. Shall have an operating temperature range from - 40°F (- 40°C) to 130°F (54°C), 10% - 90% RH (non-
condensing).
4. Shall include built-in protocol for BACNET (MS/TP and PTP modes), Modbus (RTU and ASCII), Johnson N2
and LonWorks. LonWorks Echelon processor required for all Lon applications shall be contained in separate
communication board.
5. Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers
6. Baud rate Controller shall be selectable using a dipswitch.
7. Shall have an LED display independently showing the status of serial communication, running, errors,
power, all digital outputs, and all analog inputs.
8. Shall accept the following inputs: space temperature, set point adjustment, outdoor air temperature, indoor
air quality, outdoor air quality, compressor lock-out, fire shutdown, enthalpy switch, and fan status/filter
status/ humidity/ remote occupancy.
9. Shall provide the following outputs: Fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, heat
stage 3/ exhaust.
10. Shall have built-in surge protection circuitry through solid state polyswitches. Polyswitches shall be used on
in-coming power and network connections. Polyswitches will return to normal when the “trip” condition
clears.
11. Shall have a battery backup capable of a minimum of 10,000 hours of data and time clock retention during
power outages.
12. Shall have built- in support for Carrier technician tool.
13. Shall include an EIA-485 protocol communication port, an access port for connection of either a computer or
a Carrier technician tool, an EIA-485 port for network communication to intelligent space sensors and
displays, and a port to connect an optional LonWorks communications card.
14. Software upgrades will be accomplished by either local or remote download. No software upgrades through
chip replacements are allowed.
PremierLink controller:
1. Shall be ASHRAE 62-2001 compliant.
2. Shall accept 18-32VAC input power.
3. Shall have an operating temperature range from - 40°F (- 40°C) to 158°F (70°C), 10% - 95% RH (non-
condensing).
4. Controller shall accept the following inputs: space temperature, set point adjustment, outdoor air
temperature, indoor air quality, outdoor air quality, indoor relative humidity, compressor lock-out, fire
shutdown, enthalpy, fan status, remote time clock/door switch.
5. Shall accept a CO2 sensor in the conditioned space, and be Demand Control Ventilation (DCV) ready.
6. Shall provide the following outputs: Fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, heat
stage 3/ exhaust/ occupied.
7. Unit shall provide surge protection for the controller through a field installed circuit breaker.
8. Shall be Internet capable, and communicate at a Baud rate of 38.4K or faster
9. Shall have an LED display independently showing the status of activity on the communication bus, and
processor operation.
10. Shall include an EIA-485 protocol communication port, an access port for connection of either a computer or
a Carrier technician tool, an EIA-485 port for network communication to intelligent space sensors and
displays, and a port to connect an optional LonWorks plug-in communications card.
11. Shall have built-in Carrier Comfort Network (CCN) protocol, and be compatible with other CCN devices,
including ComfortLink and ComfortVIEW controllers.
12. Shall have built-in support for Carrier technician tool.
13. Software upgrades will be accomplished by local download. Software upgrades through chip replacements
are not allowed.
14. Shall be shock resistant in all planes to 5G peak, 11ms during operation, and 100G peak, 11ms during
storage.
15. Shall be vibration resistant in all planes to 1.5G @ 20-300 Hz.
16. Shall support a bus length of 4000 ft max, 60 devices per 1000 ft section, and 1 RS-485 repeater per 1000ft
sections.
Manual damper:
Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit up
to 50% outdoor air for year round ventilation.
Head Pressure Control Package:
#2 1 0 3 2 0 9 4 7
1. Controller shall control coil head pressure by condenser fan speed modulation or condenser fan cycling and
wind baffles.
2. Shall consist of solid state control and condenser coil temperature sensor to maintain condensing
temperature between 90°F (32°C) and 110°F (43°C) at outdoor ambient temperatures down to - 20°F
(- 29°C).
Smoke detectors:
1. Shall be a Four Wire Controller and Detector.
2. Shall be environmental compensated with differential sensing for reliable, stable, and drift free sensitivity.
3. Shall use magnet activated test/reset sensor switches.
4. Shall have tool less connection terminal access.
5. Shall have a recessed momentary switch for testing and resetting the detector.
6. Controller shall include:
a) One set of normally open alarm initiation contacts for connection to an initiating device circuit on a fire
alarm control panel.
b) Two Form C auxiliary alarm relays for interface with rooftop unit or other equipment.
c) One Form C supervision (trouble) relay to control the operation of the Trouble LED on a remote test/reset
station.
d) Capable of direct connection to two individual detector modules.
e) Can be wired to up to 14 other duct smoke detectors for multiple fan shutdown applications.
Time Guard:
1. Shall prevent compressor short cycling by providing a 5 minute delay (±2 minutes) before restarting a
compressor after shutdown for any reason.
2. One device shall be required per compressor.
Electric Heat:
1. Heater element open coil resistance wire, nickel chrome alloy, 0.29 inches inside diameter, strung through
ceramic insulators mounted on metal frame. Coil ends are staked and welded to terminal screw slots.
2. Heater assemblies are provided with integral fusing for protection of internal heater circuits. Auto reset
thermo limit controls, magnetic heater contactors (24V coil) and terminal block all mounted in electric
heater control box (minimum 18 ga galvanized steel) attached to end of heater assembly.
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 www.greenheck.com
Performance
Requested Volume (CFM) 200
Actual Volume (CFM) 200
Total External SP (Pa) 100
Fan RPM 1468
Operating Power (kW) 0.03
Elevation (m) 620
Airstream Temp.(C) 50
Air Density (kg/m3) 1.015
Tip Speed (m/sec) 21.234
Static Eff. (%) 32
Motor
Motor Mounted Yes
Size (hp) 1/20 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1550
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of mm
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 1.52 m - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using ANSI/AMCA 301 at 1.52 m
Inlet 71 74 67 60 58 55 48 44 65 53 7.0
Performance
Requested Volume (CFM) 406
Actual Volume (CFM) 406
Total External SP (Pa) 50
Fan RPM 1178
Operating Power (kW) 0.02
Elevation (m) 620
Airstream Temp.(C) 50
Air Density (kg/m3) 1.015
Tip Speed (m/sec) 17.033
Static Eff. (%) 48
Motor
Motor Mounted Yes
Size (hp) 1/15 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1550
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of mm
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 1.52 m - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using ANSI/AMCA 301 at 1.52 m
Inlet 66 66 62 55 51 49 46 39 59 47 4.7
Model: SE1-8-440-D
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
Wall Mounted for Toilet
213
Dimensional
Quantity 21
Weight w/o Acc's (kg) 8
Weight w/ Acc's (kg) 10
Optional Damper (mm) 254 x 254
Wall Opening (mm) 267 x 267
INTERIOR EXTERIOR
EXHAUST AIRFLOW
Performance
Requested Volume (CFM) 100
Actual Volume (CFM) 117
Total External SP (Pa) 68.9
Fan RPM 1550
Operating Power (kW) 0.02
Elevation (m) 620
Airstream Temp.(C) 21
Air Density (kg/m3) 1.115
Tip Speed (m/sec) 16.490
Static Eff. (%) 16
Motor
Motor Mounted Yes
Size (hp) 1/30 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO Static Pressure Calculations
Motor RPM 1550 External SP 50 Pa
Direct Drive RPM Adjustment 18.9 Pa
Efficiency Rating Standard
Total External SP 68.9 Pa
Windings 1
Notes:
All dimensions shown are in units of mm
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 1.52 m - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 1.52 m
Inlet 64 71 55 53 52 47 45 41 59 47 4.9
Damper Configuration:
ID #: Tag: Quantity: W (in.): H (in.): Act Qty: Actuator Model:
2 Mark 1 21 10 10 0
5. SEQUENCE OF OPERATION
3
#2 1 0 3 2 0 9 4 7
The unit is operated from the MDB Panel installed in Control room through circuit breaker. Disconnect
switch is also installed on the roof beside Package ac unit to turn off and on manually in case of
maintenance. The unit is operated from Thermostat installed in the RO Plant area as per required
temperature.
Temperature Control:
Space Conditions are measured by a room mounted digital thermostat and temperature measured values
are transmitted to DDC controller via analog input module which compares the actual values with the
required set point. If the temperature is higher than the set point temperature the DDC controller energize
the compressor.
Fire Smoke Detectors are installed in different areas of Ro Plant Building which relate to Fire Alarm
controller and Fire Alarm Controller relates to MDB Panel. In case of fire or smoke, signal goes to MDB
and MDB Panel shut off the Roof Top Package AC unit.
#2 1 0 3 2 0 9 4 7
6 OPERATION &
MAINTENANCE MANUALS
3
#2 1 0 3 2 0 9 4 7
Package Rooftop Units – 60Hz
Quality Assurance
Certificate Reg. No:
04 100 950420
50TCM – 60Hz
Unit Size 6.0 – 12.5 Tons
HFC R - 410A Refrigerant
The 50TCM units are single side discharge rooftop cooling unit utilizing electric heat as an option. Units are pre-
wired, pre-charged with R-410A refrigerant, and tested at the factory. These units can be placed on the side of a
building or can be placed on a roof without roof curbs. Each unit is designed to occupy a minimal space. Piping and
drain connections are readily accessible.
Physical Data............................................................................................................................................................... 5
Unit Dimensional Drawing ......................................................................................................................................... 6
Follow all the safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached
to the unit. Consult local building codes for special requirements. In absence of local codes, it is recommended that
the USA standard ANSI/NFPA 70, National Electrical Code (NEC), be followed.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on
the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury of death.
WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe
practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or operation.
This machine must be installed in a location that is not accessible to the public and protected against access by
non-authorized people.
Do not remove the skid or the packaging until the unit is in its final position. These units can be moved with a fork
lift truck, as long as the forks are positioned in the right place and direction on the unit.
The units can also be lifted with slings, using only the designated lifting points marked on the unit (labels on the
chassis and a label with all unit handling instructions are attached to the unit). Use slings with the correct capacity,
and always follow the lifting instructions on the certified drawings supplied for the unit.
Safety is only guaranteed, if these instructions are carefully followed. If this is not the case, there is a risk of
material deterioration and injuries to personnel. These units are not designed to be lifted from above.
1.3 – Warranty
Warranty is based on the general terms and conditions of the manufacturer. Any modifications to the design and/or
installation made without discussion with Carrier and without advance written agreement will result in the loss of the
right to any warranty claims and any claim for injury to personnel as a result of these modifications.
#2 1 0 3 2 0 9 4 7
WARNING
ELECTRICALSHOCK HAZARD
WARNING
UNIT OPERATION AND SAFETY HAZARD
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
CAUTION
CUT HAZARD
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing, safety glasses and gloves
when handling parts and servicing furnaces.
#2 1 0 3 2 0 9 4 7
Unit 50TCM A07 D08 D09 D12 D14
Unit Dimensions 41.3x74.3x46.7 41.2x88.1x59.4 49.3x88.1x59.4
Unit Operating weight 606 761 855 866 1078
Refrigeration System
Compressor No.# / Type 1 / Scroll 2 / Scroll
Refrigerant type Puron ® R410A
Circuts No.# 1 2
Charge per Circuit (1-Down/2-Up) -LBS 230V 19.84 6.39 / 6.83 11.30 / 13.27 10.91 / 10.91 13.00 / 13.88
Charge per Circuit (1-Down/2-Up) -LBS 400V 16.53 9.92 / 8.60 11.90 / 11.02 10.91 / 10.91 16.53 / 13.88
Metering Device TXV Acutrol
Filter Drier Qty 1 2
High Pressure Switch (Trip/ Reset)- PSIG 630 / 505
Low Pressure Switch (Trip/ Reset)- PSIG 54 / 117
Condenser Coil*
Coil Type 3/8" Helical Grooved Copper Tube, 0.75" Aluminum Lance Sine Wave fins.
Standard Coil Material Cu/Al
Rows / FPI 2 / 17 1 / 20 2 / 20
Face Area (ft2) 21.3 20.5 25.1
Coil test Pressure (PSIG) 450
Condenser Fan & Motor
Approx. Air Flow Rate (CFM) 4350 7000 10900 10000
Quantity 1 2 1
Diameter (in) / No. of Blades 26 / 3 22 / 3 30 / 3
Motor Type Induction Motor - Totally Enclosed
Motor HP-RPM 1/3 - 825 1/4 - 1100 1 - 1140
Evaporator Coil*
Coil Type 3/8" Helical Grooved Copper Tube, 0.75" Aluminum Lance Sine Wave fins.
Standard Coil Material Cu/Al
Rows / FPI 4 / 15 3 / 15 4 / 15
Face Area (ft2) 7.3 8.9 11.1
Coil test Pressure (PSIG) 350
Drain Pan connection Size (in) 3/4
Return Air Filter Qty / Size (in) 4 / 16x16x2 4 / 16x20x2 4 / 20x20x2
Evaporator Fan
Fan Qty - Fan Shaft Size (in) - Fan Size (in) 1 - 15.9 - 254 x 254 1 - 25.4 - 381 x 381
Fan Type Centrifugal - Forward Blade
Drive Type Belt
Motor Type Induction Motor - Open Drip Proof
Standard Static Drive
Motor Qty 1
Maximum HP (230V/400V) 2.4 / 1.7 1.7 / 1.7 2.4 / 2.5 2.9 / 3.0
FLA (230V/400V) 5.2 / 2.8 5.2 / 4.2 7.5 / 5.0
Efficiency @ Full Load (230V/400V) 80% / 74% 80% / 75% 81% / 75%
RPM Range (230V) 1073 - 1457 489 - 747 518 - 733 591 - 838 652 - 843
RPM Range (400V) 728 - 1035 489 - 747 518 - 733 604 - 819 652 - 843
Motor Shaft Size (230V-400V) (in) 5/8 - 5/8 5/8 - 7/8 7/8 - 7/8
Motor Frame Size(230V/400V) 56Y / 56Y 56Y / 56HZ
Medium Static Drive
Motor Qty 1
Maximum HP (230V/400V) 2.9 / 3.0 2.9 / 3.0 3.7 / 4.7
FLA (230V/400V) 7.5 / 5.0 5.2 / 4.2 10 / 7.5
Efficiency @ Full Load (230V/400V) 81% / 75% 80% / 75% 81% / 76%
RPM Range (230V) 1173 - 1518 733 - 949 690 - 936 838 - 1084
RPM Range (400V) 1073 - 1457 733 - 949 690 - 936 838 - 1084
Motor Shaft Size (230V-400V) (in) 7/8 - 7/8 5/8 - 7/8 7/8 - 7/8
Motor Frame Size(230V/400V) 56Y / 56HZ 56Y / 56Y 56Y / 145TY
High Static Drive
Motor Qty 1
Maximum HP (230V/400V) 3.7 / 4.7 4.7 / 4.7 3.7 / 3.0 4.7 / 4.7
FLA (230V/400V) 10.0 / 7.5 15 / 7.5 10.0 / 5.0 15 / 7.5
Efficiency @ Full Load (230V/400V) 80% / 76% 81% / 76% 80% / 75% 81% / 76%
RPM Range (230V) 1474 - 1788 909 - 1102 838 - 1084 1022 - 1240
RPM Range (400V) 1474 - 1788 909 - 1102 838 - 1084 1013 - 1229
Motor Shaft Size (230V-400V) (in) 7/8 - 7/8
Motor Frame Size(230V/400V) 56Y / 145TY 145TY / 145TY 56Y / 56HZ 145TY / 145TY
#2 1 0 3 2 0 9 4 7
&85%6 :(,*+76',0(16,2167&0'
12-5/8"
8320:
28-5/16"
13-7/8" 8719:
8352:
36 3/8"
5$.% 8924:
36 3/8"
5$.% 8924:
'LPHQVLRQV7&.%
#2 1 0 3 2 0 9 4 7
$&/5&30'(3"7*5: $(
C10329
'LPHQVLRQV7&.%
6HUYLFH&OHDUDQFH
C08337
NOTES:
1. Consider also the effect of adjacent units.
2. Do not install unit in an indoor location.
DIMENSIONS
Max Weight
UNIT A B C
LB KG IN MM IN MM IN MM
50TCMA07 645 293 74.4 1888 38.0 965 41.4 1051
50TCMD08 1410 641 88.0 2235 41.0 1040 41.5 1055
50TCMD09 1525 693 88.0 2235 40.5 1030 49.5 1255
50TCMD12 1565 711 88.0 2235 40.0 1015 49.5 1255
50TCMD14 1720 782 88.0 2235 28.5 725 53.0 1345
NOTES:
1. Remove boards at ends of unit and runners prior to rigging.
2. Rig by inserting hooks into unit base rails as shown. Use bumper boards for spreader bars.
Crub should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig.3
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging.
Unit may be installed directly on wood flooring or on approved roof - covering material when roof curb is used. Do not
install unit in an indoor location. Do not locate air inlets near exhaust vents or sources of contaminated air.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig.3
The 50TCM units with electric heat require a 2-in.clearance for the first 24-in. of ductwork. Outlet grilles must not lie
directly below unit discharge.
NOTE
IMPORTANT
A 90-degree elbow must be provided in drain hole and must be removed in ductwork to comply with UL
(Underwriters’ Laboratories) codes for use with electric heat.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this
before setting the unit in place.
The red drain pan can be tightened with a 1/2-in. square socket drive extension. To use the alternate bottom drain
connection, remove the red drain plug from the bottom connection (use a 1/2-in. square socket drive extension) and
install it in the side drain connection.
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 6
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit
at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4-in.).
NOTE: Check all factory and field electrical connections for tightness. Field--supplied wiring shall conform to the
limitations of 63°F (33°C) rise.
WARNING
ELECTRIC SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize
the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit
ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with local electrical
codes or in absence of local codes, it is recommended that U.S.A standard ANSI/NFPA 70, National Electrical Code be followed.
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction. Do not connect aluminum wire
between disconnect and air conditioning unit. Use copper wire only (See Fig. 7)
When installing units, provide a disconnect switch per NEC (National Electric Code) of adequate size. Disconnect
sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or
local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
All field wiring must comply with the NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the
unit informative plate, connections to the unit power terminal block and equipment ground. Maximum wire size is #4
ga AWG per pole.
Provide a ground-fault and short –circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local
codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size. All field wiring
must comply with NEC and local requirements.
1. Install power wiring conduit through side panel openings. Install conduit between disconnect and control box.
2. Install power lines to terminal block connections.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. On 3 –
phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula
shown in the legend of the Electrical Data Table to determine the percent of voltage imbalance. Operation on improper
lines voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such
operation would invalidate any applicable Carrier warranty.
#2 1 0 3 2 0 9 4 7
Field Control Wiring – The 50TCM unit requires an external temperature control device. This device can be a
thermostat (field--supplied) or a PremierLink controller (field--installed accessory, for use on a Carrier Comfort
Network or as a standalone control)
Thermostat – Install a Carrier--approved accessory thermostat according to installation instructions included with the
accessory. Select a two--stage cooling thermostat. Locate the thermostat accessory on a solid wall in the conditioned
space to sense average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24—v power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the thermostat does not require a 24--v source (no “C” connection
required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation
instructions for additional features which might require additional conductors in the cable.
For wire runs up to 15 m (50 ft.), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For 15 to 23
m (50 to 75 ft.), use no. 16 AWG insulated wire (35_C minimum). For over 23 m (75 ft.), use no. 14 AWG insulated
wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will
require a junction box and splice at the thermostat.
For ordering electric heater: Include complete heater part number in the order placement e.g CRHEATER116A00.
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
#2 1 0 3 2 0 9 4 7
50TCM-400/3/60Hz application Compressor
OFM IFM Electric Heater
No.1 No.2 MCA MOCP
Unit Size Power Supply Drive package
50TCM V / Ph / Hz Indoor Motor P.N. APP
RLA LRA RLA LRA Qty HP FLA HP FLA FLA
CRHEATERXXXXXX (KW)
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 - - - 19.0 30
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 106A00 4.2 6 19.0 30
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 108A00 8 11.5 19.0 30
Standard
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 109A00 9.7 14 21.0 30
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 108A00, 108A00 16 23.1 32.4 35
10.7 78.0 - - 1 1/3 2.8 1.7 2.8 108A00, 109A00 17.7 25.6 35.5 40
10.7 78.0 - - 1 1/3 2.8 3 5 - - - 21.2 30
10.7 78.0 - - 1 1/3 2.8 3 5 106A00 4.2 6 21.2 30
10.7 78.0 - - 1 1/3 2.8 3 5 108A00 8 11.5 21.2 30
A07 400/3/60 Medium
10.7 78.0 - - 1 1/3 2.8 3 5 109A00 9.7 14 23.8 30
10.7 78.0 - - 1 1/3 2.8 3 5 108A00, 108A00 16 23.1 35.1 40
10.7 78.0 - - 1 1/3 2.8 3 5 108A00, 109A00 17.7 25.6 38.3 40
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 - - - 23.7 30
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 106A00 4.2 6 23.7 30
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 108A00 8 11.5 23.8 30
High
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 109A00 9.7 14 26.9 30
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 108A00, 108A00 16 23.1 38.3 40
10.7 78.0 - - 1 1/3 2.8 4.7 7.5 108A00, 109A00 17.7 25.6 41.4 45
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 - - - 22.7 30
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 116A00 9.7 13.9 22.7 30
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 113A00 11.5 16.5 24.1 30
Standard
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 114A00 19.3 27.9 38.4 40
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 115A00 22.9 33.1 44.9 45
7.6 51.8 7.6 51.8 2 1/4 1.42 1.7 2.8 114A00, 116A00 29 41.8 55.8 60
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 - - - 24.9 30
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 116A00 9.7 13.9 24.9 30
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 113A00 11.5 16.5 26.9 30
D08 400/3/60 Medium
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 114A00 19.3 27.9 41.1 45
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 115A00 22.9 33.1 47.6 50
7.6 51.8 7.6 51.8 2 1/4 1.42 3 5 114A00, 116A00 29 41.8 58.5 60
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 - - - 27.4 35
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 116A00 9.7 13.9 27.4 35
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 113A00 11.5 16.5 30.0 35
High
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 114A00 19.3 27.9 44.3 45
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 115A00 22.9 33.1 50.8 60
7.6 51.8 7.6 51.8 2 1/4 1.42 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 - - - 25.4 30
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 116A00 9.7 13.9 25.4 30
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 113A00 11.5 16.5 25.4 30
Standard
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 114A00 19.3 27.9 38.4 40
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 115A00 22.9 33.1 44.9 45
8.8 64 8.8 64.0 2 1/4 1.42 1.7 2.8 114A00, 116A00 29 41.8 55.8 60
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 - - - 26.8 35
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 116A00 9.7 13.9 26.8 35
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 113A00 11.5 16.5 26.8 35
D09 400/3/60 Medium
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 114A00 19.3 27.9 40.1 45
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 115A00 22.9 33.1 46.6 50
8.8 64 8.8 64.0 2 1/4 1.42 2.5 4.2 114A00, 116A00 29 41.8 57.5 60
8.8 64 8.8 64.0 2 1/4 1.42 3 5 - - - 27.6 35
8.8 64 8.8 64.0 2 1/4 1.42 3 5 116A00 9.7 13.9 27.6 35
8.8 64 8.8 64.0 2 1/4 1.42 3 5 113A00 11.5 16.5 27.6 35
High
8.8 64 8.8 64.0 2 1/4 1.42 3 5 114A00 19.3 27.9 41.1 45
8.8 64 8.8 64.0 2 1/4 1.42 3 5 115A00 22.9 33.1 47.6 50
8.8 64 8.8 64.0 2 1/4 1.42 3 5 114A00, 116A00 29 41.8 58.5 60
#2 1 0 3 2 0 9 4 7
50TCM-400/3/60Hz application Compressor
OFM IFM Electric Heater
No.1 No.2 MCA MOCP
Unit Size Power Supply Drive package
50TCM V / Ph / Hz Indoor Motor P.N APP
RLA LRA RLA LRA Qty HP FLA HP FLA FLA
CRHEATERXXXXXX (KW)
7.9 66 7.9 66 1 1 3.9 2.5 4.2 - - - 25.9 30
7.9 66 7.9 66 1 1 3.9 2.5 4.2 116A00 9.7 13.9 25.9 30
7.9 66 7.9 66 1 1 3.9 2.5 4.2 113A00 11.5 16.5 25.9 30
Standard
7.9 66 7.9 66 1 1 3.9 2.5 4.2 115A00 22.9 33.1 46.6 50
7.9 66 7.9 66 1 1 3.9 2.5 4.2 114A00, 116A00 29 41.8 57.5 60
7.9 66 7.9 66 1 1 3.9 2.5 4.2 115A00, 113A00 34.7 50.1 67.9 70
7.9 66 7.9 66 1 1 3.9 4.7 7.5 - - - 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 116A00 9.7 13.9 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 113A00 11.5 16.5 30.0 35
D12 400/3/60 Medium
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
7.9 66 7.9 66 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
7.9 66 7.9 66 1 1 3.9 4.7 7.5 - - - 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 116A00 9.7 13.9 29.2 35
7.9 66 7.9 66 1 1 3.9 4.7 7.5 113A00 11.5 16.5 30.0 35
High
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
7.9 66 7.9 66 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
7.9 66 7.9 66 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
10.7 78.0 11.0 88.0 1 1 3.9 3 5 - - - 33.3 40
10.7 78.0 11.0 88.0 1 1 3.9 3 5 116A00 9.7 13.9 33.3 40
10.7 78.0 11.0 88.0 1 1 3.9 3 5 113A00 11.5 16.5 33.3 40
Standard
10.7 78.0 11.0 88.0 1 1 3.9 3 5 115A00 22.9 33.1 47.6 50
10.7 78.0 11.0 88.0 1 1 3.9 3 5 114A00, 116A00 29 41.8 58.5 60
10.7 78.0 11.0 88.0 1 1 3.9 3 5 115A00, 113A00 34.7 50.1 68.9 70
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 - - - 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 116A00 9.7 13.9 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 113A00 11.5 16.5 35.8 45
D14 400/3/60 Medium
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 - - - 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 116A00 9.7 13.9 35.8 45
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 113A00 11.5 16.5 35.8 45
High
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00 22.9 33.1 50.8 60
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 114A00, 116A00 29 41.8 61.6 70
10.7 78.0 11.0 88.0 1 1 3.9 4.7 7.5 115A00, 113A00 34.7 50.1 72.0 80
For ordering electric heater: Include complete heater part number in the order placement e.g CRHEATER116A00.
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
Unit 50TCM - A07 - 230V
Available External Static Pressure (in. wg)
Air flow
0.2 0.4 0.6 0.8 1.0
Rate (CFM)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
1800 822 0.48 0.51 927 0.62 0.66 1018 0.76 0.82 1100 0.91 0.98 1174 1.07 1.15
1950 872 0.58 0.62 973 0.74 0.79 1061 0.89 0.95 1140 1.05 1.13 1213 1.22 1.31
2100 923 0.70 0.75 1019 0.86 0.92 1104 1.03 1.10 1182 1.20 1.29 1253 1.38 1.48
2250 974 0.84 0.90 1067 1.01 1.08 1149 1.18 1.27 1224 1.36 1.46 1294 1.55 1.66
2400 1026 0.99 1.06 1115 1.17 1.26 1195 1.36 1.46 1268 1.55 1.66 1336 1.74 1.87
2550 1079 1.17 1.25 1164 1.36 1.46 1241 1.56 1.67 1312 1.75 1.88 1379 1.96 2.10
2700 1132 1.36 1.46 1214 1.56 1.67 1289 1.77 1.90 1358 1.98 2.12 1422 2.19 2.35
2850 1186 1.58 1.69 1264 1.79 1.92 1336 2.00 2.15 1404 2.23 2.39 1467 2.42 2.63
3000 1240 1.81 1.94 1315 2.03 2.18 1385 2.27 2.43 1451 2.47 2.68 1512 2.70 2.93
Thermostat – Install a Carrier--approved accessory thermostat according to installation instructions included with the
accessory. Select a two--stage cooling thermostat. Locate the thermostat accessory on a solid wall in the conditioned
space to sense average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24—v power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the thermostat does not require a 24--v source (no “C” connection
required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation
instructions for additional features which might require additional conductors in the cable.
For wire runs up to 15 m (50 ft.), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For 15 to 23
m (50 to 75 ft.), use no. 16 AWG insulated wire (35_C minimum). For over 23 m (75 ft.), use no. 14 AWG insulated
wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will
require a junction box and splice at the thermostat.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the compressor lead wires.
4. Turn on power to the compressor.
5. Check also phase monitor all ok green led before proceeding.
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE
IMPORTANT
For wire runs up to 50 ft, use no. 18 AWG insulated wire. For 50 to 75 ft, use no. 16 AWG insulated wire. For over 75 ft, use no.
14 AWG insulated wire. All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a
junction box and splice at the thermostat.
HEATING, UNITS — (If Accessory or Optional Heater is installed) — upon a call for heating through terminal W1,
IFC and heater contactor no. 1 (HC1) are energized.
#2 1 0 3 2 0 9 4 7
®
Downblast Centrifugal Roof Exhaust 1
#2 1 0 3 2 0 9 4 7
Model G Direct Drive Model GB Belt Drive
Model G is a direct drive downblast GB model fans are belt drive downblast
centrifugal exhaust fan. These fans are centrifugal exhaust fans. These fans are
specifically designed for roof mounted specifically designed for roof mounted
applications exhausting relatively clean applications exhausting relatively clean
air. Performance capabilities range up air. Performance capabilities range up
to 6,300 cfm (10,703 m3/hr) and up to to 44,700 cfm (75,950 m3/hr) and up to
1.75 in. wg (435 Pa) of static pressure. 3.25 in. wg (809 Pa) of static pressure. The
The maximum continuous operating maximum continuous operating temperature
temperature is 180°F (82ºC). G models are available in is 180°F (82ºC). GB models are available in 29 sizes
20 sizes with nominal wheel diameter ranging from 8 to with nominal wheel diameters ranging from 11 to 54
22 inches (203 to 558 mm) (060 - 203 unit sizes). Each inches (279 to 1372 mm) (071-540 unit sizes). Each
fan shall bear a permanently affixed manufacturer’s fan shall bear a permanently affixed manufacturer’s
engraved metal nameplate containing the model nameplate containing the model number and
number and individual serial number. All fans are individual serial number. All fans are UL/cUL Listed
UL/cUL Listed Standard 705. Standard 705.
Unpacking
Verify that all required parts and the correct quantity Figure 3
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped Screws Screws
Lift unit on to the roof utilizing hooks under the lip Curb Cap
of the shroud. Evenly space the hooks around the
shroud using a minimum of four lifting straps. Use
a spreader bar to ensure the straps do not come in GB Belt Drive
contact with the unit (see Figure 1). When lifting the unit on to the roof, use either the
four lifting points on the drive frame or the two lifting
Figure 1 points on the bearing plate if present (see Figure
2 for lifting points). Access to the drive frame is
Spreader Bar accomplished by removing the screws pointed out in
Figure 3. The cover can then be removed and placed
on a flat surface in an area protected from strong
Lifting Strap winds.
When G/GB unit is on the roof, move fan to desired
location using lifting points and fasten securely
through mounting holes in base. Shims may be
necessary depending upon roofing material thickness.
The motor amperage and voltage ratings must be
checked for compatibility to supply voltage prior to
Hook final electrical connection. For G/GB installations, the
electrical supply should be routed through the conduit
chase located between the curb cap and the bottom
of the motor compartment. Wiring must conform to
local and national codes.
®
Downblast Centrifugal Roof Exhaust 3
#2 1 0 3 2 0 9 4 7
Storage Inspection and Maintenance during
Fans are protected against damage during shipment. Storage
If the unit cannot be installed and operated While in storage, inspect fans once per month. Keep a
immediately, precautions need to be taken to prevent record of inspection and maintenance performed.
deterioration of the unit during storage. The user
If moisture or dirt accumulations are found on parts,
assumes responsibility of the fan and accessories
the source should be located and eliminated. At each
while in storage. The manufacturer will not be
inspection, rotate the wheel by hand ten to fifteen
responsible for damage during storage. These
revolutions to distribute lubricant on motor. If paint
suggestions are provided solely as a convenience to
deterioration begins, consideration should be given
the user.
to touch-up or repainting. Fans with special coatings
Indoor may require special techniques for touch-up or repair.
The ideal environment for the storage of fans and Machined parts coated with rust preventive should be
accessories is indoors, above grade, in a low humidity restored to good condition promptly if signs of rust
atmosphere which is sealed to prevent the entry of occur. Immediately remove the original rust preventive
blowing dust, rain or snow. Temperatures should be coating with petroleum solvent and clean with lint-
evenly maintained between 30° to 110°F (-1° to 43°C) free cloths. Polish any remaining rust from surface
(wide temperature swings may cause condensation with crocus cloth or fine emery paper and oil. Do not
and “sweating” of metal parts). All accessories must destroy the continuity of the surfaces. Thoroughly
be stored indoors in a clean, dry atmosphere. wipe clean with Tectyl® 506 (Ashland Inc.) or the
Remove any accumulations of dirt, water, ice or snow equivalent. For hard to reach internal surfaces or for
and wipe dry before moving to indoor storage. To occasional use, consider using Tectyl® 511M Rust
avoid “sweating” of metal parts, allow cold parts to Preventive, WD-40® or the equivalent.
reach room temperature. To dry parts and packages, Removing From Storage
use a portable electric heater to get rid of any
As fans are removed from storage to be installed
moisture buildup. Leave coverings loose to permit air
in their final location, they should be protected and
circulation and to allow for periodic inspection.
maintained in a similar fashion until the fan equipment
The unit should be stored at least 3½ inches (89 mm) goes into operation.
off the floor on wooden blocks covered with moisture
proof paper or polyethylene sheathing. Aisles between
parts and along all walls should be provided to permit
air circulation and space for inspection. Table of Contents
Outdoor General Safety Information . . . . . . . . . . . . . . . . . . . .2
Fans designed for outdoor applications may be stored Receiving, Unpacking, Handling . . . . . . . . . . . . . . . .3
outdoors, if absolutely necessary. Roads or aisles for Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
portable cranes and hauling equipment are needed. Inspection and Maintenance during Storage . . . . . .4
Removing from Storage . . . . . . . . . . . . . . . . . . . . . .4
The fan should be placed on a level surface to prevent Installation
water from leaking into the fan. The fan should be Typical Roof Mounting Installation . . . . . . . . . . . .5
elevated on an adequate number of wooden blocks Typical Motor Wiring Diagram . . . . . . . . . . . . . . .5
so that it is above water and snow levels and has Typical Roof Mounting Installation, Model G . . . .6
enough blocking to prevent it from settling into soft Typical Roof Mounting Installation, Model GB . . .6
ground. Locate parts far enough apart to permit air Mounting for Severe Duty Installation . . . . . . . . . . . .7
circulation, sunlight and space for periodic inspection. Pre-starting Checks . . . . . . . . . . . . . . . . . . . . . . . 8-9
To minimize water accumulation, place all fan parts on Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
blocking supports so that rain water will run off. Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Do not cover parts with plastic film or tarps as these Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . .10
cause condensation of moisture from the air passing Belt and Bearing Maintenance . . . . . . . . . . . . . .10
through heating and cooling cycles. Bearing Lubrication Schedule . . . . . . . . . . . . . .11
Fan wheels should be blocked to prevent spinning Fan Inlet Connections . . . . . . . . . . . . . . . . . . . . . . .11
caused by strong winds. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Maintenance Log. . . . . . . . . . . . . . . . . . . . . . . . . . .14
Our Commitment. . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 4
Vari-Green Wiring
For Vari-Green wiring, refer to the Vari-Green
Motor and Controls Installation, Operation and
Maintenance Manual for complete wiring and
operation instructions.
®
Downblast Centrifugal Roof Exhaust 5
#2 1 0 3 2 0 9 4 7
G Direct Drive GB Belt Drive
Figure 5 - Typical Roof Mounting Installation Figure 6 - Typical Roof Mounting Installation
Disconnect Disconnect
Screws
Damper Damper
1¼ in.
(32 mm)
1¼ in.
(32 mm)
Curb Corner
Anchor Detail
Roof Curb
Model GPF, GPFHL,
GPFHD or Equivalent
18 ga. min.
High wind ratings – 42 in. Tall Max
Seismic ratings – 24 in. Tall Max
Steel Welded Construction
Concrete Steel
Timber Anchoring
Deck Anchoring Deck Anchoring
®
Downblast Centrifugal Roof Exhaust 7
#2 1 0 3 2 0 9 4 7
Pre-Starting Checks WARNING
1. Check all fasteners and setscrews for tightness. Correct direction of wheel rotation is critical.
The wheel should rotate freely and be aligned as Reversed rotation will result in poor air performance,
shown in Figure 7. motor overloading and possible motor burnout.
AVERTISSEMENT
La turbine doit impérativement tourner dans le
Overlap Gap bon sens. Une rotation en sens inverse entraînerait
de mauvaises performances de soufflage, une
surcharge du moteur voire un grillage du moteur.
IMPORTANT
Figure 7 The fan has been checked for mechanical noises at
the factory prior to shipment. If mechanical noise
Overlap Gap
Model Size should develop, suggested corrective actions are
in. (mm) in. (mm)
G 060-095 – 3/32 (2)
offered in the Troubleshooting section.
G 097-163 1/4 (6) – IMPORTANT
GB 071-161 1/4 (6) – Over tightening will cause excessive bearing wear
G 183-243 3/8 (10) – and noise. Too little tension will cause slippage at
GB 180-240 3/8 (10) – startup and uneven wear.
GB 260-540 1/2 (13) –
Model GB Pre-Starting Belt Tension Checks
2. Wheel position is preset and the unit is test run at 6. Always loosen tension enough to install belts
the factory. Movement may occur during shipment without stretching, see Figure 9.
and realignment may be necessary. Do not force belt(s). Forcing the belts will break the
3. Only G model - Centering height alignment can cords and cause belt failure.
be accomplished by loosening the set screws in
the wheel and moving the wheel to the desired
position.
4. Only GB model - Centering can be accomplished
by loosening the bolts holding the drive frame Figure 9
to the shock mounts and repositioning the drive
frame. 7. For units with two groove pulleys, adjust so the
tension is equal in both belts.
Wheel and inlet cone overlap can be adjusted by
loosening the set screws in the wheel and moving 8. If adjustments are made, it is very important to
the wheel to the desired position. check the pulleys for proper alignment. Misaligned
pulleys lead to excessive belt wear vibration, noise
Fan RPM should be checked and verified with a
and power loss, see Figure 10.
tachometer.
CORRECT WRONG WRONG WRONG
5. Check wheel rotation (viewing from the shaft side)
by momentarily energizing
the unit. Rotation should be
clockwise as shown in Figure
8 and correspond to rotation
decal on the unit. Figure 10
If wheel rotation is incorrect, 9. For GB units: Belt tension can be adjusted by
reverse two of the wiring leads loosening four fasteners on the drive frame, see
Clockwise Rotation
or check motor wiring for Figure 11. The motor plate slides on the slotted
single phase. Figure 8 adjusting arms and
drive frame angles
in the same manner.
Four (4) fasteners in
total.
Identical fasteners
on opposing side must
also be loosened.
Figure 11
®
Sidewall Propeller Fans 1
#2 1 0 3 2 0 9 4 7
Sidewall Propeller Fans
Greenheck’s sidewall propeller fan line is the ideal choice for factory and warehouse applications
where high volumes of air and low pressures are required. From general ventilation to industrial
duty, the range of construction and performance capabilities offered represent the most
comprehensive sidewall propeller fan line in the industry.
Performance spans the range between 300 to 87,000 cfm (510 to 147,814 m3/hr) with static
pressures to 1.25 in. wg (249 Pa). Fan sizes range from 8 to 54 inches (203 to 1372 mm) for direct
drive and 20 to 72 inches (508 to 1829 mm) for belt drive. Regardless of fan size, performance or
duty level, all Greenheck sidewall propeller fans are built to perform with the same high standards
of reliability and durability. All models are available in exhaust or supply arrangements.
Models SE1, SS1, SE2, SS2, SCE3, SCS3, SCR3, SBE-1, SBS-1, SBE-2, SBS-2, SBE-3, SBS-3, SBCE, SBCS, and SBCR.
Filtered Supply
Filtered supply wall housings are available in seven sizes for fans ranging from size 24 to
54 inches (610 to 1372 mm). They are designed with the draw-thru concept to achieve the
highest filter and fan efficiencies. Permanent 2-inch (51 mm) washable filters are accessed
through a bolted panel and can be easily removed for cleaning.
®
Sidewall Propeller Fans 3
#2 1 0 3 2 0 9 4 7
Pre Installation Checks Fans mounted to the wall require a different wall
opening (W.O.) size than those mounted in collars or
• Check chart below for correct wall opening wall housings. Propeller-to-damper distance (M) is
dimensions. important to reduce turbulence and damper flutter
• Check motor voltage and amperage rating for which may lead to premature damper failure.
compatibility with electrical supply. Supply wiring Figure 1 and 2 show the wall opening (W.O.) required
must be properly fused and conform to local and for installations with either a wall housing or collar.
national codes.
Figure 3 shows the recommended wall opening (W.O.)
• Motor load amperage must be checked and and the minimum distance (M) suggested between the
compared to nameplate rating to avoid serious fan and damper for direct to wall installations.
damage to motor when speed is increased.
Figure 4 shows the dimensions and wall opening
Wall Opening Requirements (W.O.) required for installations with a filtered supply
Wall opening size and propeller-to-damper distance wall housing.
are two important dimensions for fan installation.
W.O.
W.O.
Wall
Wall Filter
Housing Section INTERIOR EXTERIOR
Optional 90º
Weatherhood
Filters
Filters
Airflow
A
W.O.
Damper
B
Figure 3 - Direct to Wall Installation Figure 4 - Filtered Supply Wall Housing Installation
Wall
Position weatherhood over Optional 90º
Always disconnect, lock and tag power source before Weatherhood
end of wall housing and fasten
installing or servicing. Failure to disconnect power
through mounting holes with
source can result in fire, shock or serious injury.
self-tapping screws. Caulk,
DANGER flash and complete electrical
Pour écarter les risques d’incendie, de choc hook-up to finish installation.
électrique ou de blessure grave, veiller à toujours
débrancher, verrouiller et étiqueter la source de
Wall
courant avant l’installation ou l’entretien.
permanent support
braces are installed.
Mounting
Angles
Secure through
For 3-phase installations, fan rotation can be reversed
Wall
45º
rods, cable, angle, etc. number of turns open. Any increase in fan speed
(supplied by others) as represents a substantial increase in horsepower
shown. required from the motor. Always check motor load
Vertical braces must amperage and compare to nameplate rating when
carry a minimum load of changing fan speed.
500 pounds per support,
and angled (45°) braces a
Wall
45º
®
Sidewall Propeller Fans 5
#2 1 0 3 2 0 9 4 7
DANGER Bearings (for belt drive fans only)
Bearings are the most critical moving part of the
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power fan and should be inspected at periodic intervals.
source can result in fire, shock or serious injury. Locking collars and setscrews, in addition to fasteners
attaching the bearings to the bearing plate, must be
DANGER checked for tightness. In a clean environment and
Pour écarter les risques d’incendie, de choc temperatures above 32ºF (0ºC) and below 200ºF
électrique ou de blessure grave, veiller à toujours (93ºC), fan shaft bearings with grease fittings should
débrancher, verrouiller et étiqueter la source de be lubricated semi-annually using a high-quality
courant avant l’installation ou l’entretien. lithium based grease. If unusual environmental
conditions exist, temperatures below 32ºF (0ºC) and
Routine Maintenance above 200ºF (93ºC), moisture or contaminants, more
frequent lubrication is required.
Once the fan has been put into operation, a periodic
maintenance program should be set up to preserve With the unit running, add grease very slowly with a
the reliability and performance of the fan. Items to be manual grease gun until a slight bead of grease forms
included in this program are belts, bearings, fasteners at the seal. Be careful not to unseat the seal by over
and setscrews, lubrication, and removal of dust and lubricating or using excessive pressure. Bearings
dirt. without grease fittings are lubricated for life.
Maintenance Documentation
Job Information
Job Name: ___________________________________ Service Organization: __________________________________
Address:_____________________________________ Address: _____________________________________________
City: ________________________________________ City: _________________________________________________
State: _______________ Zip: __________________ State: _______________ Zip: __________________________
Phone: ______________________________________ Phone: ______________________________________________
Contact Person: ______________________________ Work Done By: _______________________________________
®
Sidewall Propeller Fans 7
#2 1 0 3 2 0 9 4 7
Parts List
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information
will assist the local Greenheck representative and the factory in providing service and replacement parts. Before
taking any corrective action, make certain unit is not capable of operation during repairs.
CAUTION ATTENTION
A fan manufactured with an explosion resistant La présence d’un moteur antidéflagrant sur un
motor does not certify the entire unit to be explosion ventilateur ne garantit pas que tout l’appareil est
proof. Refer to UL Listing Mark for the fans antidéflagrant. Pour connaître les emplois autorisés
approved usage. de l’appareil, voir son marquage de conformité UL.
1. Fan Panel
1
2. Propeller
3. Drive Frame Channel (2)
2 4. Motor /Bearing Plate
9 8
5. Motor
6. Motor Pulley
7. Shaft Pulley
8. Fan Shaft
9. Bearings (2)
10. Belt
4
10
Exhaust Supply
Airflow Airflow
3 5 6 7
1. Fan Panel
1 2. Propeller
11 3. Drive Frame Channel (2)
9 4. Motor Plate
4 8
5. Motor
7 6. Motor Pulley
2 7. Shaft Pulley
10 8. Fan Shaft
9. Bearings (2)
6
10. Belt
11. Bearing Plate
5
Exhaust Supply
Airflow Airflow
1. Fan Panel
2. Propeller
6 3. Drive Frame/Motor Support
2
4. Motor
5. Riser Blocks (4) - supply fan only
4 6. Shaft Extension - supply fan only
Exhaust Supply
Airflow Airflow
1 3 5
1. Fan Panel
1 2. Propeller
2 3. Drive Frame Channels (2)
4. Motor Plate
5. Motor
Exhaust Supply
Airflow Airflow
3 4 5
®®
Sidewall Propeller Fans 9
#2 1 0 3 2 0 9 4 7
Maintenance Log
Date _______________ Time _________________AM/PM Date _______________ Time _________________AM/PM
Notes: __________________________________________ Notes: __________________________________________
________________________________________________ ________________________________________________
________________________________________________ ________________________________________________
________________________________________________ ________________________________________________
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Sidewall Propeller Fans catalog provides AMCA Publication 410-96, Safety Practices for Users and
additional information describing the equipment, fan Installers of Industrial and Commercial Fans, provides
performance, available accessories, and specification data. additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com
10 479827 • Sidewall Propeller Fans, Rev. 2, October 2008 Copyright 2008 © Greenheck Fan Corporation
#2 1 0 3 2 0 9 4 7
7 PREVENTIVE MAINTENANCE
PROCEDURES, FAULT ISOLATION &
REPAIR PROCEDURES
3
#2 1 0 3 2 0 9 4 7
PACKAGED AC UNIT
CONDENSER COIL — Clean condenser coil annually and as required by location and outdoor-air conditions.
Inspect coil monthly and clean as required.
CONDENSATE DRAIN — Check and clean each year at start of cooling season.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions
require. Refer to Table 1 “Physical Data” type and size.
4.2 – Lubrication
Compressors are charged with the correct amount of oil at the factory.
Replacing Compressor - In the case of a motor burnout, the majority of contaminated will be removed with the
compressor. The rest of the oil is cleaned through the use of suction and liquid line filter driers. A 100% activated
alumna suction line filter drier is recommended but must be removed after 72 hours.
The compressor contains POE oil. POE oil has a high affinity for moisture. Do not remove the compressor’s tube
plugs until ready to insert the unit suction and discharge tube ends. The discharge connection plug should be
removed first before pulling the suction connection plug to allow the dry air pressure inside the compressor to
escape.
2. Ensure that system is not subjected to liquid abuse. Turn the crankcase heater on 12 hours before starting the
compressor.
CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS – The condenser and evaporator-fan motors have
permanently-sealed bearings, so no field lubrication is necessary.
NO CHARGE — Use standard evacuating techniques. After evacuating system, weight in the specified amount of
refrigerant (refer to Table 1).
LOW CHARGE COOLING — Using cooling charging chart according to the size of the unit Add or remove refrigerant
until conditions of the chart are met. Note that charging chart is different from those normally used. An accurate
pressure gage and temperature-sensing device is required. Charging is accomplished by ensuring the proper amount
of liquid sub-cooling. Measure liquid line pressure at the liquid line service valve using pressure gage.
Connect temperature sensing device to the liquid line near the liquid line service valve and insulate it so that outdoor
ambient temperature does not affect reading.
TO USE THE COOLING CHARGING CHART — Use the above temperature and pressure readings, and find the
intersection point on the cooling charging chart. If intersection point on chart is above line, add refrigerant. If
intersection point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge
is adjusted.
NOTE: Indoor-air CFM must be within normal operating range of unit. All outdoor fans must be operating.
#2 1 0 3 2 0 9 4 7
4.8 – Protective Devices
Compressor Protection – Each compressor is internally protected against over temperature.
To reset, manually move the thermostat setting.
Evaporater and Condenser-fan Motor Protection — Each Evaporator and Condenser-fan motor is
internally protected against over temperature.
High and Low-Pressure switches — If either switch trips, it will be automatically reset when fault is cleared.
NOTE
IMPORTANT
After prolonged shutdown or servicing in cold weather, energize the crankcase heaters for 12 hours before starting the
compressors.
Attached at in the section of Spare Parts List at then end of this document
#2 1 0 3 2 0 9 4 7
50TCM - Charging Chart
Charging Chart 50TCMA07 – 6 Ton R-410A Refrigerant
• R-410A refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment
and replacement components are designed to operate with R-410A refrigerant.
• R-410A refrigerant cylinders are rose colored.
• Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
• R-410A refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering
device in the manifold hose when charging into suction line with compressor operating.
• Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low-side retard.
• Use hoses with 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• R-410A refrigerant, as with other HFCs, is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• Do not use liquid-line filter driers with rated working pressures less than 600 psig.
• Do not leave R-410A refrigerant suction line filter driers in line longer than 72 hours.
• Do not install a suction-line filter drier in liquid-line.
• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
• POE oils may cause damage to certain plastics and roofing materials.
• Wrap all filter driers and service valves with wet cloth when brazing.
• A factory-approved liquid-line filter drier is required on every unit.
• Do NOT use an R-22 expansion device.
• If indoor unit is equipped with an R-22 expansion device, it must be changed to a hard-shutoff R-410A
refrigerant expansion device.
• Never open system to atmosphere while it is under a vacuum.
• When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry
nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging.
• All indoor coils must be installed with a hard-shutoff R-410A refrigerant expansion metering device.
• Do not vent R-410A refrigerant into the atmosphere.
• Do not use capillary tube coils.
• Observe all warnings, cautions, and bold text.
#2 1 0 3 2 0 9 4 7
Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and condenser fan will not Power failure. Call power company.
start.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or Replace component.
control relay.
Insufficient line voltage. Determine cause and correct.
Incorrect or faulty wiring. Check wiring diagram and rewire correctly.
Thermostat setting too high. Lower thermostat setting below room
temperature.
Compressor will not start but condenser Faulty wiring or loose connections in compressor Check wiring and repair or replace.
fan runs. circuit.
Compressor motor burned out, seized, or internal over- Determine cause. Replace compressor.
load open.
Defective overload. Determine cause and replace.
Compressor locked out Determine cause for safety trip and reset lockout.
One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Determine cause.
Compressor cycles (other than normally Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and
satisfying thermostat). recharge to nameplate.
Defective compressor. Replace and determine cause.
Insufficient line voltage. Determine cause and correct.
Blocked condenser. Determine cause and correct.
Defective overload. Determine cause and replace.
Defective thermostat. Replace thermostat.
Faulty condenser-fan motor. Replace.
Restriction in refrigerant system. Locate restriction and remove.
Compressor operates continuously. Dirty air filter. Replace filter.
Unit undersized for load. Decrease load or increase unit size.
Thermostat set too low. Reset thermostat.
Low refrigerant charge. Locate leak, repair, and recharge.
Air in system. Recover refrigerant, evacuate system, and
recharge.
Condenser coil dirty or restricted. Clean coil or remove restriction.
Excessive head pressure. Dirty drier filter. Replace filter.
Dirty condenser coil. Clean coil.
Refrigerant overcharged. Recover excess refrigerant.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Air in system. Recover refrigerant, evacuate system, and
recharge.
Condenser air restricted or air short-cycling. Determine cause and correct.
Head pressure too low. Low refrigerant charge. Check for leaks, repair, and recharge.
Restriction in liquid tube. Remove restriction.
Excessive suction pressure. High heat load. Check for source and eliminate.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Refrigerant overcharged. Recover excess refrigerant.
Suction pressure too low. Dirty air filter. Replace filter.
Low refrigerant charge. Check for leaks, repair, and recharge.
Metering device or low side restricted. Remove source of restriction.
Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area. Reset thermostat.
Field-installed filter drier restricted. Replace.
VENTILATION FANS
#2 1 0 3 2 0 9 4 7
Routine Maintenance Belt and Bearing Maintenance for GB
Model
DANGER 1. Belts tend to stretch after a period of time. They
Disconnect and secure to the “off” position all should be checked periodically for wear and
electrical power to the fan prior to inspection tightness. When replacing belts, use the same
or servicing. Failure to comply with this safety type as supplied with the unit.
precaution could result in serious injury or death. 2. Matched belts should always be used on units
DANGER with multi-groove pulleys.
Pour écarter les risques de blessure grave ou 3. For belt replacement, loosen the tensioning device
de mort, débrancher et verrouiller l’alimentation enough to allow removal of the belt by hand.
électrique en position « Arrêt » avant tout contrôle 4. Once installed, adjust belts as shown in
ou entretien. “Pre-Starting Checks.”
IMPORTANT 5. To ensure tightness, check pulley setscrews.
Uneven cleaning of the wheel will produce an out of Proper keys must be in keyways.
balance condition that will cause vibration in the fan. 6. Fan RPM should not be readjusted. Only use
WARNING pulleys of identical size and type when replacing
pulleys.
This unit should be made non-functional when
cleaning the wheel or housing (fuses removed, 7. Shaft bearings can be classified in two
disconnect locked off). groups: relubricating and non-relubricating. All
non-relubricating bearings on model GB fans
AVERTISSEMENT are factory lubricated and require no further
L’appareil doit être rendu non opérationnel lors lubrication under normal use (between -20º
du nettoyage de la turbine ou du caisson (fusibles to 180ºF (-29º to 82ºC) in a relatively clean
retirés, sectionneur verrouillé). environment).
8. On GB belt driven fans, the standard cast pillow
Greasing of motors is only intended when fittings are
block bearings are factory lubricated and are
provided. Many fractional horsepower motors are
provided with external grease fittings. Annual
permanently lubricated and should not be lubricated
lubrication is recommended, or more frequently
after installation. Motors supplied with grease fittings
if needed (See Table 2). Do not over-grease. Use
should be greased in accordance with manufacturers’
only one or two shots of lubricant with a hand
recommendations. Where motor temperatures do not
gun. Maximum hand gun rating is 40 psi. Rotate
exceed 104ºF (40ºC), the grease should be replaced
bearings during lubrication where good safety
after 2,000 hours of running time as a general rule.
practice permits. Caution should be employed to
Wheels require very little attention when moving prevent over packing or contamination.
clean air. Occasionally, oil and dust may accumulate
9. Grease fittings should be wiped clean. The unit
causing imbalance. When this occurs, the wheel and
should be in operation while lubricating. Extreme
housing should be cleaned to ensure smooth and safe
care should be used around moving parts.
operation.
10. Grease should be pumped in very slowly until a
All fasteners should be checked for tightness each
slight bead forms around the seal. A high grade
time maintenance checks are performed prior to
lithium base grease should be used. (See Table 3)
restarting unit.
11. During the first few months of operation,
A proper maintenance program will help these units
check bearing setscrews periodically to ensure
deliver years of dependable service.
tightness.
12. If unit is to be left idle for an extended period,
remove belts and store in a cool, dry place to
avoid premature belt failure.
®
Downblast Centrifugal Roof Exhaust 11
#2 1 0 3 2 0 9 4 7
DANGER Bearings (for belt drive fans only)
Bearings are the most critical moving part of the
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power fan and should be inspected at periodic intervals.
source can result in fire, shock or serious injury. Locking collars and setscrews, in addition to fasteners
attaching the bearings to the bearing plate, must be
DANGER checked for tightness. In a clean environment and
Pour écarter les risques d’incendie, de choc temperatures above 32ºF (0ºC) and below 200ºF
électrique ou de blessure grave, veiller à toujours (93ºC), fan shaft bearings with grease fittings should
débrancher, verrouiller et étiqueter la source de be lubricated semi-annually using a high-quality
courant avant l’installation ou l’entretien. lithium based grease. If unusual environmental
conditions exist, temperatures below 32ºF (0ºC) and
Routine Maintenance above 200ºF (93ºC), moisture or contaminants, more
frequent lubrication is required.
Once the fan has been put into operation, a periodic
maintenance program should be set up to preserve With the unit running, add grease very slowly with a
the reliability and performance of the fan. Items to be manual grease gun until a slight bead of grease forms
included in this program are belts, bearings, fasteners at the seal. Be careful not to unseat the seal by over
and setscrews, lubrication, and removal of dust and lubricating or using excessive pressure. Bearings
dirt. without grease fittings are lubricated for life.
3
#2 1 0 3 2 0 9 4 7
Thermostat Settings
This ensures your thermostat is installed properly and away from all heat sources, including
solar rays, light bulbs, and heat-producing appliances.
a minimum 2-foot clearance around the entire unit. If you have bushes or other plants
encroaching on the heat pump, trim them back.
I. PRELIMINARY INFORMATION
5) POWER WIRES HAVE BEEN SIZED AND INSTALLED PROPERLY TO THE UNIT.
10) SEALED ALL POWER AND CONTROL WIRES ENTRY INTO THE UNIT AND INSIDE THE BOX
III. START - UP
ELECTRICAL:
SUPPLY VOLTAGE: (L1 - L2): (L2 - L3): (L3 - L1):
PRESSURES:
CIRCUIT - 1
CIRCUIT - 2
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Centrifugal Upblast and Sidewall Exhaust AMCA Publication 410-96, Safety Practices for Users and
catalog provides additional information describing the Installers of Industrial and Commercial Fans, provides
equipment, fan performance, available accessories, and additional safety information. This publication can be
specification data. obtained from AMCA International, Inc. at www.amca.org.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com
14 479822 • Model G and GB, Rev. 4, December 2014 Copyright 2014 © Greenheck Fan Corporation
#2 1 0 3 2 0 9 4 7
3
#2 1 0 3 2 0 9 4 7
3
#2 1 0 3 2 0 9 4 7
Arabian Air Conditioning Company Limited
P.O.Box 9784, Riyadh 11423
Kingdom of Saudi Arabia
WARRANTY CERTIFICATE
serial number and Carrier Invoice reference is MANDATORY for Warranty claim.
Yours faithfully
Mohammed Shoaib
Sr. Sales Engineer
WARRANTY CERTIFICATE
This is to certify that the Greenheck Fans will be supplied under above Project
are covered by Greenheck special warranty which is as under.
Greenheck (Al Saadeh) warrants the equipment to be free from defects in material
and workmanship for a period of 24 months from the date of substantial
completion of project.
Any units or parts proven defective during the warranty period will be repaired or
replaced at our option.
1. FOR AC UNIT
2. FOR VENTILATION FANS
3
#2 1 0 3 2 0 9 4 7
Contact us
For support, contact our Call Center Agents.
Carrier Offices:
RIYADH
Tel: 012-2375000
Fax: 012-6917386
DAMMAM
Tel: 013-8577710
Fax: 013-8578834
MAKKAH
Tel: 012-5472230
Fax: 012-5472352
MADINAH
Tel: 014-8464163
Fax: 014-8464162
KHAMIS MUSHAIT
Tel: 017-2212270
HOFUF
Tel: 013-5822425
Fax: 013-5826272
#2 1 0 3 2 0 9 4 7
#2 1 0 3 2 0 9 4 7
P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 www.greenheck.com
3
SPARE PARTS LIST FOR PACKAGE AC UNIT
#2 1 0 3 2 0 9 4 7
Series Model Number Model Size Voltages Description Item Part Number Qty/Unit
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Fan Guard 30GT414209 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Filter, Air 20x20x2 KH01AA585 4
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Control Box Ch3,4 Double Circuit 48TMSSRMP-2910 1 SET
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 75va 400v Transformer W/breaker HT01BD602 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Phase Monitor (samco Part No.hk35ac002s) 48HG503588 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Power Distribution Block W/ Insulator (3 Pole) HY84DA022 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 CONTACTOR 3P,HONG FA XMCO-188.E 18AMP HN53TAA024NC 2
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Crank Case Heater 02-7736-03s 40w-480v HT32TC743 2
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Terminal Control Board HK50AA051 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Low Pressure Switch ,c1 HK02SB020 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Low Pressure Switch ,c2 HK02SB024 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 High Pressure Switch,c1 HK02SA420 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 High Pressure Switch,c2 HK02SA440 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Comp Plug C1 HY06KE005 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Comp Plug C2 HY06KE006 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Switch, Limit,temp-actuated, Manual Reset HH18HA199 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Motor Outdoor HD52GE382-HK-HK 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Motor, Indoor 400v-60hz HD58FE651S 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Terminal,block HY84DA011 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Wheel, Blower LA22LA125 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Shaft, Fan 50DK502898 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Bearing, Ball (BOA) 1" Shaft KT61DA080B 2
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Bracket Assy 48HG500422 2
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Compressor, (c1 C2) Hermatic Scroll GC30NB002 2
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Mount Assy, Motor 30GB406723 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Fan Propeller 4-blade LA01EW032S 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Pulley Motor KR11HY216 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Pulley, Blower KR11AZ002 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 V-belt Ax52 KR29AF052 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Core, Check Valve Spring Loaded (hi Flow) EC39EZ067 4
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Valve Body, Regrigerant Access (0.375 Hole) EC39EZ065 4
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 Header Assembly 48TM401170 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Filter Drier KH43LE102 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Fan Guard 30GT414209 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Filter, Air 20x20x2 KH01AA585 4
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Control Box 10t-12.5t Ch3,4 Double Circuit 48TMSSRMP-2910 1 SET
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 75va 400v Transformer W/breaker HT01BD602 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Phase Monitor (samco Part No.hk35ac002s) 48HG503588 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Power Distribution Block W/ Insulator (3pole) HY84DA022 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 CONTACTOR 3P,HONG FA XMCO-188.E 18AMP HN53TAA024NC 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Terminal Control Board HK50AA051 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Crank Case Heater 02-7733-03s 70w-480v HT32TC705 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Low Pressure Switch ,c1 HK02SB020 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Low Pressure Switch ,c2 HK02SB024 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 High Pressure Switch,c1 HK02SA420 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 High Pressure Switch,c2 HK02SA440 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Comp Plug C1 HY06KE005 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Comp Plug C2 HY06KE006 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Switch, Limit,temp-actuated, Manual Reset HH18HA199 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Motor, Indoor 400v-60hz HD60FE655S 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Motor, Outdoor 1hp HD52GE382-HK-HK 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Terminal,block HY84DA011 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Wheel, Blower LA22LA125 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Shaft, Fan 50DK502898 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Bearing, Ball (BOA) 1" Shaft KT61DA080B 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Bracket Assy 48HG500422 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Compressor, C2 Hermatic Scroll GC30NB004 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Compressor, C1 Hermatic Scroll GC30NB003 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Mount Assy, Motor 30GB406723 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Fan, Propeller 3blade 30dia 22'pitch LA01EW029S 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Pulley Motor KR11HY184 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Pulley, Blower KR11AJ912 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 V-belt Ax52 KR29AF052 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Core, Check Valve Spring Loaded (hi Flow) EC39EZ067 4
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Valve Body, Regrigerant Access (0.375 Hole) EC39EZ065 4
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Filter Drier KH43LE102 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Header Assembly 48TM401239 1
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 Header Assembly 48TM401007 1
50TCM 50TCMD12A2A1-0A0A0 12 400-3-60 CONTACTOR 3P,HONG FA XMCO-128.E 12AMPS HN53TA024NC 2
50TCM 50TCMD14A2A1-0A0A0 14 400-3-60 CONTACTOR 3P,HONG FA XMCO-128.E 12AMPS HN53TA024NC 2
#2 1 0 3FANS
SPARE PART LIST FOR VENTILATION 209 47
Parts List
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information
will assist the local Greenheck representative and the factory in providing service and replacement parts. Before
taking any corrective action, make certain unit is not capable of operation during repairs.
CAUTION ATTENTION
A fan manufactured with an explosion resistant La présence d’un moteur antidéflagrant sur un
motor does not certify the entire unit to be explosion ventilateur ne garantit pas que tout l’appareil est
proof. Refer to UL Listing Mark for the fans antidéflagrant. Pour connaître les emplois autorisés
approved usage. de l’appareil, voir son marquage de conformité UL.
Belt
Shaft Pulley
Motor Motor Pulley
Shock Bearings
Mounts Motor
Drive Frame
Hood Clip Assembly
Shroud
Shock Mounts
Fan Shaft
Birdguard Shroud Brace
Shroud
Wheel Birdguard
Vertical
Wheel Support
Shroud Brace
Conduit
Lower Chase
Curb Cap/ Windband Windband
Venturi
Vertical
Support Curb Cap/
Venturi
®
Downblast Centrifugal Roof Exhaust 13
#2 1 0 3 2 0 9 4 7
Parts List
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information
will assist the local Greenheck representative and the factory in providing service and replacement parts. Before
taking any corrective action, make certain unit is not capable of operation during repairs.
CAUTION ATTENTION
A fan manufactured with an explosion resistant La présence d’un moteur antidéflagrant sur un
motor does not certify the entire unit to be explosion ventilateur ne garantit pas que tout l’appareil est
proof. Refer to UL Listing Mark for the fans antidéflagrant. Pour connaître les emplois autorisés
approved usage. de l’appareil, voir son marquage de conformité UL.
1. Fan Panel
1
2. Propeller
3. Drive Frame Channel (2)
2 4. Motor /Bearing Plate
9 8
5. Motor
6. Motor Pulley
7. Shaft Pulley
8. Fan Shaft
9. Bearings (2)
10. Belt
4
10
Exhaust Supply
Airflow Airflow
3 5 6 7
1. Fan Panel
1 2. Propeller
11 3. Drive Frame Channel (2)
9 4. Motor Plate
4 8
5. Motor
7 6. Motor Pulley
2 7. Shaft Pulley
10 8. Fan Shaft
9. Bearings (2)
6
10. Belt
11. Bearing Plate
5
Exhaust Supply
Airflow Airflow
1. Fan Panel
2. Propeller
6 3. Drive Frame/Motor Support
2
4. Motor
5. Riser Blocks (4) - supply fan only
4 6. Shaft Extension - supply fan only
Exhaust Supply
Airflow Airflow
1 3 5
1. Fan Panel
1 2. Propeller
2 3. Drive Frame Channels (2)
4. Motor Plate
5. Motor
Exhaust Supply
Airflow Airflow
3 4 5
®®
Sidewall Propeller Fans 9
#2 1 0 3 2 0 9 4 7
3
#2 1 0 3 2 0 9 4 7