PFS Single Screw Water Cooled Chiller: Service Manual
PFS Single Screw Water Cooled Chiller: Service Manual
PFS Single Screw Water Cooled Chiller: Service Manual
Effective Time:2010.04
i
Content
1. General Description .................................................................................................................................................................. 4
2. Chiller Design Features ........................................................................................................................................................... 4
2.1 Chiller Design Features.............................................................................................................................................................. 4
2.2 Control Features ......................................................................................................................................................................... 4
3. Chiller Introduction .................................................................................................................................................................... 5
3.1 Main parts of chiller ................................................................................................................................................................... 5
3.2 Pipes of Chiller Unit .................................................................................................................................................................. 6
3.3 Electrical parts ........................................................................................................................................................................... 8
3.3.1 Moulded Case Circuit Breaker: See Fig 3-7.................................................................................................................... 8
3.3.2 Phase Monitor: Refer to Fig 3-8 ........................................................................................................................................ 9
3.3.3 CPU ....................................................................................................................................................................................... 9
3.3.4 Pressure sensor: Refer to Fig 3-10 ................................................................................................................................ 10
3.3.5 Temperature sensor .......................................................................................................................................................... 10
3.3.6 Capacity sensor ................................................................................................................................................................. 10
3.4 System Flow Chart................................................................................................................................................................... 11
3.5 Electrical Wiring Diagram ....................................................................................................................................................... 12
3.6 Chiller Electrical Parameters ................................................................................................................................................... 32
3.7 Chiller Protection Set Point ..................................................................................................................................................... 32
4. PFS Chiller Performance Data ............................................................................................................................................. 34
5. Chiller Control Logic Flow Charge..................................................................................................................................... 36
6. Installation ................................................................................................................................................................................ 42
6.1 Receiving and handling............................................................................................................................................................ 42
6.2 Chiller lifting............................................................................................................................................................................ 42
6.3 Chiller mounting instruction .................................................................................................................................................... 43
6.3.1 Chiller mounting flat .......................................................................................................................................................... 43
6.3.2 Vibration absorption request............................................................................................................................................ 44
6.4 Condenser and evaporator water piping................................................................................................................................... 45
6.4.1 Water quality ...................................................................................................................................................................... 45
6.4.2 Measuring device .............................................................................................................................................................. 45
6.4.2.1 Pressure gauge ................................................................................................................................................................... 45
6.4.2.2 Thermometer ...................................................................................................................................................................... 45
6.4.3 Control Device ................................................................................................................................................................... 45
6.5 Salty device .............................................................................................................................................................................. 46
7. Operation ................................................................................................................................................................................. 46
7.1 Operator responsibilities .......................................................................................................................................................... 46
7.2 Unit running range ................................................................................................................................................................... 46
7.2.1 Cooling Tower Fans control ............................................................................................................................................. 46
7.2.2 Cooling tower By-pass valve control .............................................................................................................................. 47
7.2.3 Cooled water flow adjustment ......................................................................................................................................... 47
7.2.4 Lower Cooled water temperature regulation ................................................................................................................. 47
7.3 System star up pre-check ......................................................................................................................................................... 47
7.3.1 Waterside............................................................................................................................................................................ 47
1
7.3.2 Unit ...................................................................................................................................................................................... 48
7.3.3 Electrical and control system ........................................................................................................................................... 48
7.3.4 Oil temperature .................................................................................................................................................................. 48
7.4 Start-up and shut-off operation ................................................................................................................................................ 48
7.4.1 Chiller test/ start-up ........................................................................................................................................................... 48
7.4.2 Start-up/Shut-off ................................................................................................................................................................ 49
7.4.2.1 Start-up............................................................................................................................................................................... 49
7.4.2.2 Shut-off .............................................................................................................................................................................. 49
7.4.2.3 Emergency stop .................................................................................................................................................................. 49
7.5 Main components ..................................................................................................................................................................... 49
7.5.1 Compressor ........................................................................................................................................................................ 49
7.5.1.1 Compressor main components (Only used for HSS4200 series compressor) .................................................................... 50
7.5.1.2 Compression process ......................................................................................................................................................... 50
7.5.1.3 Compressor capacity control.............................................................................................................................................. 51
7.5.2 Evaporator .......................................................................................................................................................................... 52
7.5.3 Condenser .......................................................................................................................................................................... 52
7.5.4 Oil separator....................................................................................................................................................................... 52
7.5.5 Expansion valve system ................................................................................................................................................... 53
7.5.6 Refrigerant injection solenoid valve ................................................................................................................................ 53
7.5.7 Lubrication .......................................................................................................................................................................... 53
8. Maintenance ............................................................................................................................................................................ 53
8.1 Operator responsibilities .......................................................................................................................................................... 53
8.2 Daily Inspection ....................................................................................................................................................................... 54
8.3 Schedule maintenance.............................................................................................................................................................. 54
8.4 Seasonal servicing.................................................................................................................................................................... 55
8.4.1 Annually star-up ................................................................................................................................................................. 55
8.4.2 Annual shutdown ............................................................................................................................................................... 55
8.5 Vessel cleaning ......................................................................................................................................................................... 55
8.7 Lubricant oil ............................................................................................................................................................................. 56
8.7.1 Lubricant oil inspection ..................................................................................................................................................... 56
8.7.2 Lubrication renewing......................................................................................................................................................... 56
8.7.3 Oil filter change .................................................................................................................................................................. 57
8.7.3.1 Oil filter replacement periods ............................................................................................................................................ 57
8.7.3.2 Oil filter replacement process ............................................................................................................................................ 57
8.8 Safety Valve ............................................................................................................................................................................. 58
8.9 Electrical and control ............................................................................................................................................................... 58
9. Touch screen operate ............................................................................................................................................................. 59
9.1 K-TP178 Control panel Operating manual for PFS.1 .............................................................................................................. 59
9.1.1 Mode ................................................................................................................................................................................... 61
9.1.2 System ................................................................................................................................................................................ 65
9.1.3 Reset ................................................................................................................................................................................... 67
9.1.4 Data ..................................................................................................................................................................................... 67
9.1.5 Set ....................................................................................................................................................................................... 69
9.1.6 Alarm ................................................................................................................................................................................... 79
2
9.2 K-TP178 Control panel Operating manual for PFS.2 .............................................................................................................. 81
9.2.1 Mode ................................................................................................................................................................................... 83
9.2.2 System ................................................................................................................................................................................ 88
9.2.3 Reset ................................................................................................................................................................................... 89
9.2.4 Data ..................................................................................................................................................................................... 89
9.2.5 Set ....................................................................................................................................................................................... 92
9.2.6 Alarm ................................................................................................................................................................................. 103
9.3 K-TP178 Control panel Operating manual for PFS.3 ............................................................................................................ 106
9.3.1 Mode ................................................................................................................................................................................. 108
9.3.2 System .............................................................................................................................................................................. 112
9.3.3 Reset ................................................................................................................................................................................. 114
9.3.4 Data ................................................................................................................................................................................... 114
9.3.5 Set ..................................................................................................................................................................................... 116
9.3.6 Alarm ................................................................................................................................................................................. 128
10. Fault diagnosis .................................................................................................................................................................... 130
10.1 Fault diagnostic table ........................................................................................................................................................... 130
10.2 Oil lose analysis ................................................................................................................................................................... 132
11. Chiller maintenance parts packet ..................................................................................................................................... 139
11.1 Chiller maintenance parts ..................................................................................................................................................... 139
11.2 Wearing parts ....................................................................................................................................................................... 139
3
1. General Description
With unique single screw compressor design, McQuay has gained many reputations since 1970‟s. As
the first manufacturer who uses R134a in chiller in the world, McQuay launched high efficiency &
environmental friendly screw chiller PFS and WPS.C.
4
3. Chiller Introduction
Operator
Control Cabinet
Touch Screen
1#Compressor 2#Compressor
Evaporator
Condenser
Float Valve EXV
Please refer catalogue or installation manual for the detail dimensions and parameters.
Oil Separator
Source Water
Inlet Pipe
Hot Water
Oultlet pipe
Source Water
Hot Water Inlet
Outlet Pipe
pipe
Figure 3-1
5
3.2 Pipes of Chiller Unit
Discharge pipe connect compressor and oil separator: Refer to Fig 3-2
Discharge pipes
Figure 3-2
Suction pipes of compressor: Refer to Fig 3-3 Suction pipes
Figure 3-3
6
Refrigerant feed line between condenser and evaporator Refer to Fig 3-4
Figure 3-4
Oil feed line between compressor & oil separator: Fig 3-5
Oil Feed Line
Figure 3-5
7
Oil return pipe connects middle of evaporator and suction pipe. See Fig 3-6.
Oil return pipe
Figure 3-6
Figure 3-7
8
3.3.2 Phase Monitor: Refer to Fig 3-8
Fig 3-8
Input side protection: Dynamic phase loss\Static phase loss\Phase revised\Phase
unbalance\overvoltage\under voltage
Load side protection:Dynamic phase loss\Static phase loss\phase unbalance
Power supply: 380(±10%)VA
3.3.3 CPU
Fig 3-9
9
Extension Module EM231
Fig 3-10
Discharge temperature sensor parameters: Output signal 4~20 mA, temperature range 0~100℃
Water temperature sensor parameters: Output signal 4~20 mA, temperature range -20~80℃
Capacity sensor parameters: Output signal 4~20 mA, adjusted range : 6400~32000℃
10
3.4 System Flow Chart
11
3.5 Electrical Wiring Diagram
12
13
14
15
16
17
Below drawing is PFS.2 wiring diagram
18
19
20
21
22
23
Below drawings are PFS.3 wiring diagram:
24
25
26
27
28
29
30
31
3.6 Chiller Electrical Parameters
relation
relation.Capacity sensor
adjusted in site
5 Motor overheat protector Energized @2700-3200Ω 25℃-100-200Ω Test the resistance value
Suction Pressure: Set point scope is 180~500kPa; Pre-alarm will be energized when the pressure is
lower than it. Factory default value is 210kPa.
Discharge pressure: Set point scope is 800~2200kPa; Pre-alarm will be energized when the pressure
is higher than it. Factory default set point is 1600kPa.
Alarm: When alarm occurs, chiller will stop and alarm indicator light will be energized. Alarm can be
cleaned after settling the fault and pressing “alarm reset” bottom.
Discharge temperature: Set point scope is 50~100℃; Pre-alarm will be energized when the discharge
32
temperature is higher than it. For normal cooling mode, factory default setpoint is 70℃ and 90℃ for
heating mode.
Oil pressure differential: Setpoint scope is 100~800kPa; Pre-alarm will be energized when oil pressure
differential is lower than it. Factory default setpoint is 150 kPa.
Emergency stop temperature: In normal cooling mode, if chilled water outlet temperature is lower than
the emergency stop temperature set point, chiller will be tripped; setpoint scope is 1~5℃, factory
default setpoint is 3. In heating mode,
Chilled water flow switch time delay: When chilled water flow fluctuation time is longer than the
setpoint, alarm will be energized.Setpoint scope is 1~6 sec. Factory default is 2 sec.
Cooling water flow switch time delay: If cooling water flow fluctuates beyond the set point time during
chiller running, chiller will be tripped. Set point scope is 1~6 sec, default is 2 sec.
Discharge supper heat alarm time delay: If discharge superheat temperature doesn‟t go above
pre-alarm\alarm setpoint within certain time, chiller will be tripped. Set point is 300~1800 sec, default is
450 sec.
33
4. PFS Chiller Performance Data
Power Input kW 63.2 75.9 82.9 129.2 141.8 156.2 163.3 170.4
Evap Water Flow l/s 18.0 21.9 24.6 36.0 39.9 43.7 46.4 49.2
Evap Pressure Drop 24.5 34.2 24.9 27.9 30.7 36.9 47.6 48.8
kPa
Cond Water Flow l/s 22.5 27.3 30.8 45.0 49.8 54.6 58.0 61.5
Cond Pressure Drop 36.8 29.7 30.5 35.7 36.8 44.4 51.7 58.6
kPa
Type R134a
Refrigerant Charge 215 215 215 315 315 315 350 350
kg
Brand McQuay
Oil
Charge L 74 74 74 85 85 85 85 85
34
OD of Evap. Pipe (mm) φ168 φ168 φ168 φ219 φ219 φ219 φ219 φ219
OD of Cond.Pipe (mm) φ168 φ168 φ168 φ219 φ219 φ219 φ219 φ219
Shipment Weight kg 3670 3701 3744 5512 5551 5576 5846 5883
Operation Weight kg 3924 3971 4032 5935 5990 6028 6323 6374
Comp Inrush Current A 316.6 316.6 316.6 316.6 316.6 316.6 316.6 316.6
Chiller Inrush Current A 316.6 316.6 316.6 438.9. 456.2 457.2 467.5 467.3
Evap Water Flow l/s 54.6 58.5 62.3 66.2 69.0 71.8 74.5
Evap Pressure Drop kPa 80.1 75.6 82.0 86.2 86.1 81.0 85.6
Cond Water Flow l/s 68.2 73.1 77.9 82.8 86.2 89.7 93.2
Cond Pressure Drop kPa 79.0 78.1 81.5 79.7 75.4 79.2 83.9
Starter Y-Δ
35
Qty. 1 1 1 1 1 1 1
Type R134a
Refrigerant
Charge kg 400 470 495 495 495 565 565
Brand McQuay
Oil
Charge L 145 145 145 145 174 174 174
OD of Evap. Pipe (mm) φ219 φ219 φ219 φ219 φ219 φ219 φ219
Comp Inrush Current A 316.6 316.6 316.6 316.6 316.6 316.6 316.6
Chiller Inrush Current A 560.9 577.9 595.6 595.4 605.5 616.7 616.5
L×W×H mm 4308×1980×2278
Note:
a Cooling capacities in above table are based on below condition:
b Chilled water outlet temp 7℃;chilled water flowrate 0.172 m3/(h·kW);
c Cooling water inlet temp 30℃; Cooling water flowrate 0.215 m3/(h·kW);
d Evaporator side fouling factor 0.018m2·℃/kW, condenser side fouling factor 0.044m2·℃/kW;
e Power supply: 380V/3P/50Hz;
f Allowable power supply fluctuation (voltage): within ±10%;
g PFS110.1-PFS150.1 are not in AHRI550/590 certified scope.
Chiller startup
36
Start
Close the
main switch
Power light is on
NO Alarm/error YES
ON
Eliminate
the alarm
ALARM
OFF
Clear the
history alarm
The unit is
ready to start
37
Ready to start
BMS BMS
STOP
start singal Mode
Singal Screw
Remote Remote Chiller Control
Switch ON Start Mode
Chilled water
No chilled water flow alarm NO flow switch
closed or not
Chiller Start
Indicator Light On
YES
Press Compressor Switch SA1~SA3
Lead-lag Balance
1st Startup Comp is "1# Comp";
2nd Startup Comp is "2# Comp";
3ed Startup Comp is "3# Comp";
YES
Evap.Temp>Startup
Waiting NO Delta T(2°) YES Wait for load
YES
Note:
Cooling mode:Startup Delta T= Evap. water temp - Evap water temp setpoint;
Heating mode:Startup Delta T= Cond. water temp - Cond water temp setpoint.
38
Lead compressor start-up
Ready
YES
30S
If
another comp
Only one runs NO is put in YES
running
YES ?
YES
YES NO 1# is faulty
The
capacity YES
Unload NO is unloaded under
30S 10%
2# starts up
YES
Wait for 30S
YES
Capacity
Unload alarm NO of lead-comp is YES
minimun
?
△-conversion Receive △
failure alarm NO feedback signal
YES YES
15S
lag-comp delay
NO
60s
YES
39
Lag compressor start-up
Start
Start time
NO
is done
#2 / #3
Unload NO unload below
30S Min Capacity
YES
30S
If YES
the capacity
Unload failure NO of #2/3 unload YES
the minimum
#2/#3 Y start
Main contactor is closed
Time
Y contactor is closed
Heaters are OFF
Oil supply valve is ON
Oil drain valve is ON
△conversion Receive △
alarm NO feedback signal
40
Compressor stop
Schedule opreating
YES
Compressor unload
Compressor to less than
NO
unload for 30S Min Capacity
YES
Compressor unload
Unload failure alarm NO to less than YES
Min Capacity
Unit stop
Indicator light off
41
6. Installation
The unit (and any item that shipped with it) should be checked immediately upon receipt to check well
found or not. Confirm the unit and accessories are accord to the customer order and request, confirm
the model follow the nameplate. Check the damage of the unit especially parts and piping and fill out
the receiving report. Notify forwarder in case the unit sustains any damage, and submit formal claim
request in writing.
Wooden skid must be used during chiller lifting and moving into position to prevent damaging the
bottom part of the
f
chiller; wooden skid is not suggested to remove during moving and lifting. Cable or
chain with rigging hooks is recommended to lift chiller via marked lifting holes, also you can directly lift
by frapping lifting holes in evaporator and condenser with cable or chain. But cabinet and other
components should be protected during direct lifting.
Lifting Unit by lifting chain reference as below:
42
PFS280.2-PFS350.2 1573 658 1200 3000
PFS370.3-PFS510.3 2257 714 1200 3600
Note:
Make sure an even and slow speed when lifting and translation
Drain should be fully concerned of the base construction and around it. The base must be higher than
the floor, and waterproof treatment is need. Also illuminance must be fully concerned to convenient to
maintain and operate.
The unit mounting base construction and each model mounting diagram is as below:
M – M Section
W1 W2
W4 W3
Chiller electrical
panel direction
43
Model A B C D E
Model F G H J Bolts
Base should make use of concrete C25, thickness in accordance with the drawing, and pour twice for embedded bolts concrete
Earthwork excavation should get approval by related bureau before next procedure.
A. Neoprene vibration pads should be located under the corners of the unit to prevent the vibration
pass to the base, the pads location as below:
● ●
● ●
Base
Bolts
Vibration Pad
B. Spring Insulation. McQuay can provide spring insulation as request. The location as below:
44
Please install the spring insulation follow the letter on it.
● Unit circuit water quality (Evaporator and condenser inlet water) should accord with GB50050-95,
“Code for Design of Industrial Recirculating Cooling Water Treatment”
● Recirculating water in open system of the unit should keep the PH value in range of 7.0-9.0, and
the calcium ion content must lower than 200mg/L.
Recommend using 0.4-class & 200-dial pressure gauge, Specific reference to the water pressure of
the water system, it is recommended to use the same access to water pressure gauge.
6.4.2.2 Thermometer
Water inspects device must be installed on both inlet and outlet piping of the unit, as water flow switch,
water DP switch, and wiring to the controller. The standard device is water flow switch and supplied by
user, McQuay can provide it in accessories under request.
45
6.5 Salty device
Set a deflate valve on the peak point of the water system, the valve can be manual or automatically
controlled.
Water inspects device must be installed on both inlet and outlet piping of the unit, as water flow switch,
water DP switch, and wiring to the controller. The standard device is water flow switch.
Install check valve on the evaporator and condenser pipe between the unit and the pipe system; Install
flexible connectors or metal tubes to reduce vibration on the piping.
Impurity in the water system will block the heat exchange and cause deposit. Filter must install before
the pumps.
If the ambient may be below 0, increase in anti-freeze to protect the unit's operation is proposed
7. Operation
Operator of PFS/WPS.C must be familiar with Water system, electrical and refrigeration knowable, If
necessary (The initial startup of the chiller), McQuay service personnel will advice the proper operating
procedures.
The optimize condenser water inlet for PFS is 24~35℃,High ECWT will course capacity reduce and
compressor power increase; Low ECWT will course low compressor oil feed pressure, compressor
has difficulty to load, and may not load to 100%. The compressor running life may be reduced under a
long period of low oil pressure
If customer needs running the unit at an low ambient temperature condition, raise the Condensation
Pressure is need by some key imperatives:
The most efficiency method is using VSD or multiple stages cooling tower fan control. The user can set
the on/off temperature setpoint at each stage.
46
7.2.2 Cooling tower By-pass valve control
Use the by-pass valve to control the entry water flow of the cooling tower manually or automatically to
keep the temperature of the Mix-water.
Keep the CEWT constant; change the condenser entering water flow to control the condensation
temperature.
The following steps should be carried out prior to starting of the chiller:
7.3.1 Waterside
Check all condenser/evaporator inlet/outlet water piping connections; ensure all connections are
connected according to the factory certified chiller drawing;
Check all the Evaporator/condenser inlet/outlet temperature sensor location and wiring ensure the
connection fastened and temp display correct. If temp display is not correct, use “System Setting”
page functions to calibrate;
Open all water valves, start up the water pump, and leak check all flanges connecting of water pipes.
Vent the air of both Evaporator and condenser;
47
Check the pressure drop on both evaporator/condenser water sides, check the motion of water flow
switch or pressure differential switch is correct.
7.3.2 Unit
Open valves list below: Liquid line check valve, Oil line check valve, Evaporator oil return check valve,
Liquid level control check valve, and Liquid injection check valve.
Disconnect the chiller main breaker; check all wiring contractor to the chiller control cabinet
Check the power supply, the voltage fluctuate range should not exceed 10% of the rated voltage on
nameplate, and the voltage balance not exceed 2%.
Check the power capacity if it is enough to staring the chiller and running it at full load.
Ensure all cables and safety devices comply with the chiller‟s requirements. Check the chiller wiring
diagram for all wiring connections, such as the connections for remote on/off, condenser pump and
cooling tower fan.
Close all circuit to the main power supply and circuit breakers and turn the chiller emergency stop
button clockwise to power up the chiller control panel and electric heater.
Ensure the oil temperature higher than 40℃, or 15℃ higher than ambient temperature
The compressor test should be carried out of the first time of startup. Choose the “Test” mode, do 3
seconds and 16 seconds test.
3-second test: Check the rotation of each compressor through analyzing the difference between
discharge and suction pressure. If no PD increase means a wrong wiring, should check and re-wiring.
16-second test: Check the transition of the star-delta starter.
3, 16-second test: Check if there is any abnormal noise when compressor is operating.
Check and resolve all problems and re-energize the control panel. Check all the settings in the chiller
48
“Setting” pages follow the actual requirement, choose the “Local” mode, set the LEWT, If the pumps
are not interlocking with the chiller controls, check if the condenser and chilled water pumps have been
turned on, Finally, turn the compressor on.
If the compressor cannot reach full load, check whether high pressure is two times of low pressure, if is,
check the compressor can be load to 100% by manual or not. If the compressor can not load to full
load, please adjust the compressor capacity upper/lower limit settings based on the real valve.
7.4.2 Start-up/Shut-off
Three running modes can be selected, they are “Use Local”, “Use Schedule” and “Use Remote”, user
can choose one mode in the control panel, once one mode selected, others are ignored.
7.4.2.1 Start-up
7.4.2.2 Shut-off
If “Use Local”, press the stop button on “Operate” page, the compressor will unload automatically and
shut-off. If “Use Schedule”, the unit will stop follow the pre-set schedule. If “Use Remote”, the chiller
will shut-off once get a remote signal.
A red button located on the control panel is emergency stop; press the button to stop the chiller when
chiller failure happens.
7.5.1 Compressor
WPS.C PFS unit use HSS series semi-hermetic single screw compressor.
49
7.5.1.1 Compressor main components (Only used for HSS4200 series compressor)
Suction:
50
Compress:
Discharge:
PFS/WPS.C compressor use capacity slide valve to control the exhaust volume, the capacity sensor
measure the displacement of the slide valve from 0-100%, respectively presented 25-100% exhaust
volume.
The compressor capacity is controlled by chilled water outlet temperature PID algorithm. When ELWT
is lower than setpoint, unload solenoid valve is energized, high pressure oil enters the piston chamber,
at this time the combined force of high oil pressure and spring sufficiently overcomes the differential
pressure to make slide valve move to unload, then spring force reduces, finally it achieves to balance
without energizing load/unload solenoid valve. Whereas, when CLWT is higher than setpoint, load
solenoid valve is energized, oil in piston chamber reduces, the combined force of high oil pressure and
spring is lower than differential pressure, the capacity slide valve moves to unload.
51
Load/Unload principle scheme:
7.5.2 Evaporator
The evaporator of PFS is flood type, refrigerant in the shell circuit and water in tubes. The copper tube
outside dimension is 19mm with both sides enhanced treatment. 2-pass design, the refrigerant vapor
enters compressor from top of evaporator, PFS suction pipe is connected to compressor with Victaulic
while WPS.C using flange.
7.5.3 Condenser
The condenser is under the oil separator, refrigerant vapor is condensed here and sub-cooled, and the
copper tube OD is 19mm with both sides enhanced treatment, 2-pass design.
The mixture of refrigerant and oil discharged from the compressor flow through the discharge pipe,
52
and enter the oil separator. The oil separated and the gas enters the condenser.
The expansion valve is directly controlled by a refrigerant level sensor placed on the condenser (a ball
type float valve). The system controls the refrigerant liquid level, to grant an adequate operation of the
expansion valve completely flooding the integrated sub-cooling section of the shell-and-tube
condenser. PFS/WPS.C unit uses SV type float valve and PMFH type servo-controlled valve
manufactured by Danfoss. When the liquid level in the float rises the float orifice opens. This brings
about a rise in the pressure across the servo and PMFH opens allowing more refrigerant flow, and vice
versa as the liquid level in the float drops. Manual override of PMFH is possible with the installation of
solenoid valve type EVM fitted in S ll. When EVM opens, it allows the servo pressure to control the
operation of the PMFH; when the chiller is under high evaporator pressure, EVM closes to override the
operation of the PMFH (PMFH closes) to prevent more refrigerant from flowing into the evaporator, to
lower the evaporator pressure.
The low temperature refrigerant gas cools down the motor, control the motor temperature nearby an
optimized set point. Once system considers motor wirings need cool-down due to high discharge
temperature, controller will make liquid injection solenoid valve open, liquid refrigerant enters into
compressor to cool down.
7.5.7 Lubrication
8. Maintenance
To ensure the unit is in good running condition, regular inspection should be done follow the list below.
If necessary, calibrate the pressure and temperature display in the system “Setting” page.
53
job conditions)
2 Low pressure Check LP sensor Pressure guage 230-350KPa
3 Oil pressure Check OP Pressure guage 10-50KPa lower than HP
Star-rotor bearing ○
Star rotor △ ○
motor △ △ △ △
solenoid valve △ △
Suction filter △ △ △ △ ○
Oil filter △ △ △ △ ○
Oil ○ ○
Noted:△Inspect ○change
54
8.4 Seasonal servicing
Megger test should be taken before start the chiller (380V voltage test the insulation for the unit, the
resistance must higher than 20MΩ ). Fasten all contactors, on power the unit at least 4 hours before
running to ensure the oil temperature can reach 40℃ or 15℃ higher than ambient.
Close the liquid supply valve, running the unit till low pressure alarm shut off.
Disconnect the main power supply; disconnect the circuit breaker in control panel. Prevent oil heater
energized or star up the unit suddenly.
Drain off the water in the heat exchanger to prevent the long term water flow to corrosion the heat
exchanger; meanwhile prevent the ice to rupture the tubes in winter when the ambient temperature
below 0.
Because of the open loop water system, the heat exchange tubes are easy to deposit, and decrease
the heat exchange efficiency and cooling capacity, increase the compressor power consumption.
Demineralized water is recommended. Normally the tube cleaning works should be done annually, if
use polluted water, cleaning must be more frequently. The tubes are inner helix groove, and must use
circumrotate cleaning equipment to clean the tubes.
Based on checking result to confirm the cleaning period and water disposal is propriety. Check the
water temperature sensor on inlet/outlet piping, if corrosion, replace it, if deposit, clean it.
Noted:
● Before starting, preparing work should be done in advance, separate the piping system from
other equipment.
● After the cleaning by chemical agent, the tubes should be flushed by a mass of water to dilute
remaining chemical medicament, till the PH value around 6-8.
● Special brush should be used during the cleaning to avoid the damage of scratching or breaking
the tubes, liner brush is forbidden.
55
8.7 Lubricant oil
If the PFS unit repeating shut off by lower oil level alarm, it is likely to show an insufficient oil
charge; also maybe the system is in the process of oil reclaim:
1. Running the unit for one hour and a half, check the oil level is rising or not;
2. Re-start the unit and running at normal condition, if still low oil level alarm, means insufficient oil
charge, uses the oil charge valve at the bottom of the oil separator to charge.
3. Make sure the unit is shut off when charge oil to make the work easy. Even though the unit is
shut off but still under positive pressure, oil pump by manual or electrical is recommended.
4. Charge oil till the level reach the second scale line on eye sight glass on oil separator.
56
Note:
Oil can be pumped to the condenser with refrigerant. The oil should be separated and returned to the unit.
Excessive oil charge will decrease the unit efficiency. Over volume charge will decrease the heat exchange efficiency.
The HSS4200 single screw compressor is equipped with a high efficient filter for optimal filtration
(McQuay Wuhan, China Part No.M7348-188).A secondary filter is installed in the supply oil piping
The main oil filter of the compressor should be inspected after the first 1000 hours of operation and
every 4000 hours thereafter. Should the compressor stops on „Load‟ alarm, check the oil filter pressure
drop.
Use a pressure gauge to check the discharge pressure P1 and filter outlet pressure P2 of the
compressor as shown in the Figure below. Should the pressure difference between P1 and P2 exceed
100 kPa, replace the oil filter
● Suction pressure adds 1000kPa based on original setting in “Sensor Calibration” page when
chiller is running;
● Shut-off the check valve at the bottom of the condenser, running till low pressure alarm to shut
down.
57
● Remove the oil filter flange cover;
● Remove the old oil filter core under appreciably positive pressure;
● New O ring is recommended before fix the new oil filter core. Oil the O ring first and fix the filter,
make sure the system is under positive pressure otherwise should vent out the air with some
refrigerant.
Note:
Change the setting back after the replacement; open the check valve at the bottom of Condenser.
The safety valve (NPT1) purges excessive refrigerant when over pressure condition occurs. Therefore,
the following maintenance must be carried out to ensure that it is working properly:
Dismantle the gas discharge adaptor at the opening of the pressure relief valve, inspect the
valve carefully and check for corrosion, rust, dust built-up, fouling and leakage. Perform this
inspect at least once a year.
In case of corrosion or any foreign substance built-up, remove all refrigerant and oil, and
replace the safety valve.
If the unit is installed in a corrosive environment or the safety valve discharges gas into a corrosive
environment, the inspection frequency should be increased.
Familiarity with the wiring diagram and the chiller system prior to carrying out maintenance on the
58
electrical system. Maintenance of the electrical system involves the general requirement of keeping
contacts clean and connections tight and checking per month.
Control cabinet must be on power more than 1 hour during the long term shut off season, to
prevent the moisture.
Warning:
If the wiring is not follow the diagram, the quality guarantee will be lapse. Fuse disconnect or circuit breaker tripped means short circuit or
overload. Before re-start the compressor or change the fuse, should find out the fault and fix. The control panel must be maintained by
experienced electrical engineer.
Prolegomenon
PFS utilizes known K-TP 178 touch screen as the main human interface to offer operator easy
operation and maintenance. This manual will direct operator on how to view, set, and control PFS
chillers via K-TP178.
Note: The [Data] button will change to [Display] by pressing other buttons except [Set]
59
Control Mode
Select
Manual Operation
Mode
Output Test
Compressor Test
Hardware
Information
System
Screen Setup
Reset alarm
Reset
Chiller Information
Data Compressor
Information
Capacity Slide
Calibration
System Setup
Chiller Capacity
PID Setup
Set
Alarm Setup
Schedule Setup
Page
Sensor Offsets
Active Alarm
Alarm
Alarm History
60
9.1.1 Mode
Mode interface contains 4 sub-screens: control mode select, manual operation, output test and
compressor test.
9.1.1.1 Control mode settings
Four control modes available on McQuay PFS, see below detailed table:
Mode Description
Remote To control chiller on/off by remote PC or other devices away from chiller plant room.
Local To control chiller on/off by chiller operating touch screen.
Schedule To control chiller on/off by pre-set time schedule, refer to section9.1. 5.6.
Pre-start testing, allow unit to check wiring and output prior start, refer to section
Test
9.1.1.3 and 9.1.1.4
The following interface will be displayed by pressing “Mode” button in the main interface.
Note 1: Only McQuay authorized operator has the rights to operate.
Note2: Program for Australia chillers will pop-out an input dialogue by pressing [Mode] button. It offers
two level user names and codes protection with different authorities. See below table:
Table 9.1.2 User identification
User Description
name
Admin Administrator has full rights to view, operate and change settings.
User Only allowed to view and operate, cannot change set points.
61
Figure 9.1.2 Log on interface
After log on, interface will direct you into the mode selection screen.
Only one control mode could be selected each time, and a selection has to be made before start the
unit. Once one mode is pressed the button will reverse, for example press [Ignore local], then the
button will auto change to [Use local].
Figure 9.1.3 Control Mode Select interface
Ignore Local/Use local Press this button to disable/enable local control (on/off) of the chiller.
Ignore Remote/Use remote Press this button to disable/enable local control (on/off) of the chiller.
Ignore Schedule/Use Enable/disable chiller auto start according to preset time schedule.
Schedule
Ignore Test/Use test Enable/disable test mode of the chiller.
62
9.1.1.2 Manual operation
The following interface will be displayed as follows by pressing [Operate] in the mode interface:
Figure 9.1.4 Start/Stop interface
Display the countdown time lag to allow chiller starts (from the moment of power
Wait time
bringing in to chiller starts).
Capacity Display the current running % load.
Start/ Stop Press [Start] for start of the unit and [Stop] for shutoff of the unit.
63
Figure 9.1.5 Output Test interface
To test for chiller internal control wiring, switch between the ON/OFF button (on the [Unit Output Test]
menu as shown in above figure) for the control parameter and check the corresponding LED on the
controller block inside the compressor control cabinet. Refer to the chiller wiring diagram for the
corresponding LED address.
Caution: The test of oil feed valve is not allowed when the high/low pressure is not built up to
prevent oil back to the oil separator from the compressor oil chamber
Press “Operate” button to return to [Manual operating] menu.
9.1.1.4 Compressor test
Press the [Compressor Test] button to the following compressor testing screen. Prior to bringing the
chiller into actual operation, the compressor testing function lets the operator to perform test on the
64
compressor
Figure 9.1.6 Compressor Test interface
Press this button to perform a three-second running test on this chiller; the main
3S Test
purpose is to check compressor running rotation.
Press this button to perform a sixteen-second running test on this chiller, the main
16S Test
purpose is to check compressor abnormal noise, starter wye-delta transition, etc.
Displays the difference between discharge and suction pressure for compressor. A
Lift Press correct compressor rotation determined by a positive „Lift Press‟ value, otherwise a
negative value is displayed.
Press [operate] button or [output test] button to return to previous menu screen.
Note: compressor test can only be performed when control mode [use test] is selected.
9.1.2 System
65
Figure 9.1.7 Information of the touch screen
66
9.1.3 Reset
9.1.4 Data
In this section will provide chiller information such as temps, pumps and compressor information to
view the operating condition of the chiller.
9.1.4.1 Chiller information
The following interface will be displayed as follows by pressing [Data] in the main interface:
Figure 9.1.9 Chiller information
Displays the active set point of leaving water temperature of the evaporator,
Active Set point
Active set point=Local spt + Remote CHW offset, refer to section 5.1.
Lvg Evap Displays the leaving water temperature of the evaporator.
Ent Evap Displays the entering water temperature of the evaporator.
Lvg Cond Displays the leaving water temperature of the condenser.
Ent Cond Displays the entering water temperature of the condenser.
Cooling Call When displays Call means the Remote switch is on, and No Call means it is
Received off.
Evap Pump Displays running hours and start times of the chilled water pump.
Hrs/Starts
Cond Pump Displays running hours and start times of the cooled water pump.
Hrs/Starts
67
9.1.4.2 Compressor information
Press lower right [Comp] on above menu will switch the interface to compressor information to display
compressor temp and pressure in real time.
Figure 9.1.10 Compressor Information interface
Displays the value differential between the discharge temperature and the
Disch Superht
compressor‟s saturated discharge temperature.
Disch Temp Displays the real-time discharge temperature.
Saturated Cond T The corresponding saturation temperature of the discharge pressure.
Displays countdown waiting time of start, and the chiller will be allowed to
Wait Time
start only after the waiting-time is 0. Refer to section 1.2
Hours Displays the total operating time of the compressor.
Starts Displays the total starts of the compressor.
Press [Temp] button to return to previous chiller information menu.
68
9.1.5 Set
Note: Only the [Set] button pressed doesn’t change [Data] to [Display]
9.1.5.1 System setting
Press the [Set] button on the main tool bar for system settings. A window will pop up prompting for
Username and Password. All system settings (except leaving chilled water set point) are password
protected.
Figure 9.1.11 System setup
Set leaving evaporator water temperature in the 3 to 15℃ range via human
Local Spt
interface touch screen. Factory default setting is 7℃.
Setting the offset value by remote analog signal(4-20mA) in the range of
Remote CHW
0-10℃.Factory default setting is 0℃.
offset
Active set point=Local spt+Remote CHW offset.
The temperature difference between the actual leaving chilled water
Start DT temperature and the user set point. Chiller starts when [Start DT] exceeds a
user preset value in the 1 to 5℃ range. Default factory setting is 2℃
The temperature difference between the actual leaving chilled water
temperature and the user setpoint. Chiller shuts down when [Shutdn DT]
Stop DT
falls below a user preset value in the -3 to -0.5℃ range. Default factory
setting is -2℃
Sat Cond Setpoint Corresponding saturated condenser temp of discharge pressure settings
69
for the control of condenser water modulating valve or condenser water
VFD pumps. the arrange is 20-35℃.Default factory setting is 25℃.
The set point of the Pulldown Rate of chilled water with the range of
Pulldown Rate
0.1-2℃/minute, factory default setting is 0.2℃/minute.
Sets the minimum capacity that the chiller can unload to. Default factory
Min Capacity
setting is 10% but adjustable in 5%-50% range.
Modbus ID Sets machine Modbus address if multiple chiller control system applied.
Note:[Remote CHW offset] is used only for Australia chillers.
Active Set point=Local Spt+Remote CHW offset
9.1.5.2 Chiller capacity PID setup
To accurately control the capacity (related to chilled water temperature) and condenser water
temperature, PFS chiller temperature controller uses PID (Proportional, Integral, Differential) algorithm
in controlling the temperature. PID controller compares the actual temperature (feedback from sensor
reading) to the desired control temperature (setpoint); an error signal found by subtracting the
measured quantity from the setpoint is feedbacked to the PID controller. The PID controller computes
and sends a “corrective signal” (otherwise known as a “corrective value”) to the actuators based on:
the magnitude of the error (“P” = proportional), the sum of all previous errors (“I” = integral) and
anticipate future error from the rate of change of the error (“D” = differential). A “corrective action” is
performed by the actuator such that the error signal is reduced. The new output will be sent back to the
sensor again to find the new error signal (e). The looping of error feedback and corrective action
continues until the actual output is equal to the setpoint.
However, just simply by adding these three values (P, I and D) together would not compute the
“corrective value”, each of these 3 values needs to be multiplied by a constant, known as “gain”.
Corrective value (u) is equal to the proportional gain (KP) times the magnitude of the error (P), plus the
integral gain (KI) times the integral of the error (I), plus the differential gain (KD) times the differential of
the error (D). See the following equations:
u = KP(P) + KI(I) + KD(D)
Proportional gain, expressed in degree (oC), has the effect of reducing the rise time (response time)
and steady-state error when it is increased. (Note: steady-state error is the difference between the
70
actual temperature and the setpoint when the actual temperature has settled down to a constant
value).
Integral gain, expressed in seconds, has the effect of eliminating the steady-state error, however the
tradeoff is longer settling time which means more time is needed for the PID controller to adjust the
actual temperature back to the setpoint.
Differential gains, expressed in seconds, helps to improve the responsiveness and stability of the
temperature control by sensing the rate of rise or falls of system temperature and minimizes overshoot
or undershoot. Therefore, larger differential gain means that rate of error is evaluated longer so that
overshoot is minimized and PID controller will take lesser time to adjust the actual temperature back to
the setpoint (shorter settling time).
Effects of each of gains are summarized in the table shown below.
Table9.1.3 Effects on increasing PID gains
PID Gain Rise Time Overshoot Settling Time Steady State Error
Small
Kd Decrease Decrease Small Change
Change
The following are explanations for another two user adjustable parameters in PID settings.
Sample – Sampling period, the time taken to take a reading of the controlled parameter (in our case,
the output temperature)
Period – Output period, the time taken to feedback the error signal to the PID controller
NOTE: Correlations as shown in above Table 9.3.3 may not be exactly accurate, because Kp,
Ki, and Kd are dependent of each other. In fact, changing one of these variables can change the
effect of the other two. For this reason, the table should only be used as a reference and user
assumes all responsibility on changing the PID settings, and McQuay takes no responsibility
should the performance of the chiller be compromised.
71
Figure 9.1.12 PID interface
Sets the proportional gain of the controller in the 0.01 to 5 range. Default
Gain
factory setting is 0.8.
Sets the sampling rate of the controller in the 10 to 90 seconds range.
Sample
Default factory setting is 30 seconds.
Sets the integral time of the controller in the 200 to 9000 seconds range.
Integral
Default factory setting is 300 seconds.
Sets the differential value of the controller in the 5 to 120 seconds range.
Differential
Default factory setting is 15 seconds.
Sets the controller output period in the 2 to 60 seconds range. Default factory
Period
setting is 2 seconds.
Sets the time of load/unload solenoid valve energized in one output period,
Pulse Time
default factory setting for loading is 0.3S and unloading 0.4S.
72
Figure 9.1.13 Alarm Setup
Sets the compressor suction pressure alarm value in the 180 to 500 kPa
range. Warning light on the control cabinet lit up, LCD displays alarm
Suct P Alarm
message and machine shuts down when suction pressure falls below the
setpoint. Default factory setting is 180 kPa.
Sets the compressor discharge pressure pre-alarm value in the 800 to 1200
Dis.P Pre-Alarm kPa range. Alarm light on the control cabinet flashes, LCD displays alarm
message and machine unloads when discharge pressure exceeds the
73
setpoint. Default factory setting is 950 kPa.
Sets the compressor discharge pressure alarm value in the 800 to 1200 kPa
range. Alarm light on the control cabinet lit up, LCD displays alarm message
Dis.P alarm
and machine shuts down when discharge pressure exceeds the setpoint.
Default factory setting is 1000 kPa.
Alarm will be given when the oil pressure differential is lower than this value,
Oil DP Alarm
the set value is 100-800 kPa, and that of the factory is 100 kPa
74
Figure 9.1.14 Spring piston of the capacity sensor
Demand limit control mode, can be shift from [local] to [remote] by press
Demand Reset
drop-down menu.
Sets the maximum cooling load the unit can produce. can be set at the
Demand Limit local and remote mode, ranges from 50% to 100% with a factory default
setting 100%.
75
9.1.5.5 CDS WTR Flow PID Setup
Condenser water flow PID is to sense refrigerant saturated condenser temp corresponding to
discharge pressure (refer to section5.1 system setting-Sat. cond temp) and after PID calculation, send
the analogue output to modulate condenser water flow valve or VFD pumps.
Figure 9.1.16 CDS WTR Flow PID Setup interface
Sets the proportional gain of the controller in the 0.01 to 5 range. Default
Gain
factory setting is 0.4.
Sets the sampling rate of the controller in the 10 to 90 seconds range.
Sample
Default factory setting is 10 seconds.
Sets the integral time of the controller in the 200 to 3000 seconds range.
Integral
Default factory setting is 300 seconds.
Sets the differential value of the controller in the 5 to 120 seconds range.
Differential
Default factory setting is 15 seconds.
Sets the controller output period in the 2 to 60 seconds range. Default factory
Period
setting is 10 seconds.
Sets the lower limit of analog signal to control device of condenser
AO Low Level modulation valve or VFD pumps in range of 6400-32000, factory default
setting is 6400.
Sets the upper limit of analog signal to control device of condenser
AO High Level
modulation valve or VFD pumps in range of 6400-32000, factory default
76
setting is 32000.
Note: Change of above settings may cause interference or abnormal control malfunction, consult
McQuay service engineer before change.
9.1.5.6 Schedule
A 7-day, 24-hours („HOUR:MINUTE‟) programmable start/stop schedule of the chiller can be
programmed through the „Schedule settings‟ screen by pressing the [Schedule] button. Press the
[Next] or [Previous] button to switch between pages.
Figure 9.1.17 Schedule set
Chiller will run as per user-set schedule when the [use schedule] function is enabled on the „Mode
Select‟ screen (refer to section 1.1 Control mode selection).
77
9.1.5.7 Sensor offset
The „Sensor Offset‟ setting menu enables user to correct any differences between the actual
pressure/temperature and the sensor reading. Press the [Sensor Off.] button to enter the „Sensor
Offset‟ menu to add correctional factors to the temp/pressure values as read by sensors 1. This is
explained using the following formula.
Should there be no differences between the sensor reading and the actual temperature/pressure, the
correctional factor is zero.
Please note that the „Sensor offset‟ setting does not calibrate the sensor, but adds a correctional factor
to the value of the sensor as read by the chiller microprocessor, such that the value can be corrected.
Figure 9.1.19 Sensor offset
Adds a leaving chilled water temperature correctional factor in the range of -9.9 to
Evap L-T
9.9 ℃.Default factory setting is 0℃.
Adds an entering chilled water temperature correctional factor in the range of -9.9 to
Evap E-T
9.9 ℃. Default factory setting is 0℃.
Adds a leaving condenser water temperature correctional factor in the range of -9.9
Cond L-T
to 9.9 ℃. Default factory setting is 0℃.
78
Adds a discharge pressure correctional factor in the range of -9.9 to 9.9 ℃.
Dis T
Default factory setting is 0 ℃.
Adds a discharge temperature correctional factor in the range of -999 to 999 kPa.
Dis.P
Default factory setting is 0 kPa.
Adds a suction pressure correctional factor in the range of -999 to 999 kPa. Default
Suct. P
factory setting is 0 kPa.
Adds a oil pressure correctional factor in the range of -999 to 999 kPa. Default
Oil Press
factory setting is 0 kPa.
9.1.6 Alarm
In case of alarm, the compressor will shut off and alarm light lit up. To restart the compressor after
problem has been rectified, press the [clear] button located on the main menu.
The following is a list of the alarms:
1. Discharge superheat pre-alarm/alarm;
2. Suction pressure pre-alarm/alarm;
3. Discharge pressure pre-alarm/alarm;
4. Phase sequence protection alarm;
5. Evap Freeze Protect;
6. Cond Water Flow switch alarm;
7. Evap Water Flow switch alarm;
8. Oil level switch alarm;
9. Oil DP alarm;
10. Discharge T alarm;
11. Low pressure switch alarm;
12. High pressure switch alarm;
13. Motor overheat alarm;
14. Motor overload alarm;
15. Wye-delta transition fault;
16. Unloading fault;
Press the [Alarm] button in the main tool bar for active alarm and alarm history.
79
Figure 9.1.20 Active Alarms interface
80
9.2 K-TP178 Control panel Operating manual for PFS.2
Prolegomenon
PFS utilizes known K-TP 178 touch screen as the main human interface to offer operator easy
operation and maintenance. This manual will direct operator on how to view, set, and control PFS
chillers via K-TP178.
Figure 9.2.1 main interface
Note: The [Data] button will change to [Display] by pressing other buttons except [Set]
81
Control Mode Select
Manual Operation
Mode
Output Test
Compressor Test
Hardware
Information
System
Screen Setup
Reset alarm
Reset
Chiller Information
Data Compressor
Information
Capacity Slide
Calibration
System Setup
Sensor Offsets
Active Alarm
Alarm
Alarm History
82
9.2.1 Mode
Mode interface contains 4 sub-screens: control mode select, manual operation, output test and
compressor test.
9.2.1.1 Control mode settings
Four control modes available on McQuay PFS, see below detailed table:
Table 9.2.1 Control mode select
Mode Description
Remote To control chiller on/off by remote PC or other devices away from chiller plant room.
Local To control chiller on/off by chiller operating touch screen.
Schedule To control chiller on/off by pre-set time schedule, refer to section 9.2.5.6.
Pre-start testing, allow unit to check wiring and output prior start, refer to section
Test
9.2.1.3 and 9.2.1.4
The following interface will be displayed by pressing “Mode” button in the main interface.
Note 1: Only McQuay authorized operator has the rights to operate.
Note2: Program for Australia chillers will pop-out an input dialogue by pressing [Mode] button. It offers
two level user names and codes protection with different authorities. See below table:
Table 9.2.2 User identification
83
After log on, interface will direct you into the mode selection screen.
Only one control mode could be selected each time, and a selection has to be made before start the
unit. Once one mode is pressed the button will reverse, for example press [Ignore local], then the
button will auto change to [Use local].
Figure 9.2.3 Control Mode Select interface
Ignore Local/Use local Press this button to disable/enable local control (on/off) of the chiller.
Ignore Remote/Use Press this button to disable/enable local control (on/off) of the chiller.
remote
Ignore Schedule/Use Enable/disable chiller auto start according to preset time schedule.
Schedule
84
Figure 9.2.4 Start/Stop interface
Start/ Stop Press [Start] for start of the unit and [Stop] for shutoff of the unit.
Load Press this button to increase compressor load.
Unload Press this button to decrease compressor load.
Press this button to interchange between Auto and Manual mode. During Auto
mode, chiller‟s control automatically adjusts its capacity according to field
condition. During Manual mode, the chiller capacity can be adjusted manually
Auto/Manual
by pressing the [Load] and [Unload] buttons. When one mode is selected,
chiller will operate under the selected mode until a change is made by the
operator.
Soft switch for Compressor #1. Press this button will change the display
between “C1 Auto” and “C1 stop”. When “C1 Auto” mode displayed,Comp 1
will operate automatically according to control logic settings. By pressing [C1
Auto] this button will change to “C1 stop” which means compressor 1 will be
C1 Auto/C1 Stop compulsively switched off. This switch has a priority on controlling compressor
starts- compressor can not start again if not pressing this button to “C1 Auto”.
Note: Only dual compressor PFS has compressor soft switch as there is no
dry contact hard switch on control panel. PFS.1 and PFS.3 unit have dry
contact switch on control panel so this soft switch is not required.
C2 Auto/C2 Stop The same as C1 Auto/C1 Stop.
85
Press “Mode” button to return to the [Control mode select] menu.
9.2.1.3 Output test
The following interface will be displayed as follows by pressing [Output Test] in the Control Mode
Select interface. This menu enables user to test chiller internal control wiring connection to the
following parameters.
Figure 9.2.5 Output Test interface
Feed oil Oil feed solenoid valve, both1#&2# (1# denotes Comp 1, 2# denotes Comp 2)
Return oil Oil return solenoid valve,both1#&2#.
Load Compressor loading solenoid valve, both1#&2#.
86
Tower Cooling tower fan.
Evap Pump Chilled water pump.
Cond Pump Condenser water pump.
3S Test Press this button to perform a three-second running test on this chiller; the main
purpose is to check compressor running rotation, both1#&2# .(1# denotes Comp 1,
2# denotes Comp 2).
87
16S Test Press this button to perform a sixteen-second running test on this chiller, the main
purpose is to check compressor abnormal noise, starter wye-delta transition, etc.
both1#&2#.
Lift Press Displays the difference between discharge and suction pressure for compressor. A
correct compressor rotation determined by a positive „Lift Press‟ value, otherwise a
negative value is displayed.
Press [operate] button or [output test] button to return to previous menu screen.
Note: compressor test can only be performed when control mode [use test] is selected.(Refer to 1.1 )
9.2.2 System
88
Figure 9.2.8 Screen Setup interface
9.2.3 Reset
9.2.4 Data
In this section will provide chiller information such as temps, pumps and compressor information to
view the operating condition of the chiller
9.2.4.1 Chiller information
The following interface will be displayed as follows by pressing [Data] in the main interface:
89
Figure 9.2.9 Chiller information
90
Figure 9.2.10 Compressor Information interface
Displays the value differential between the discharge temperature and the
Disch Superht
compressor‟s saturated discharge temperature.
Disch Temp Displays the real-time discharge temperature.
Saturated Cond T The corresponding saturation temperature of the discharge pressure.
91
pressure.
Capacity Displays the operating capacity of the compressor.
Displays countdown waiting time of start, and the chiller will be allowed to
Wait Time
start only after the waiting-time is 0. Refer to section 1.2
9.2.5 Set
Note: Only the [Set] button pressed doesn’t change [Data] to [Display]
9.2.5.1 System setting
Press the [Set] button on the main tool bar for system settings. A window will pop up prompting for
Username and Password. All system settings (except leaving chilled water set point) are password
protected.
Figure 9.2.11 System setup
Remote CHW offset Setting the offset value by remote analog signal(4-20mA) in the range of
92
0-10℃.Factory default setting is 0℃.
Active set point=Local spt+Remote CHW offset.
The temperature difference between the actual leaving chilled water
Start DT temperature and the user set point. Chiller starts when [Start DT] exceeds
a user preset value in the 1 to 5℃ range. Default factory setting is 2℃
The temperature difference between the actual leaving chilled water
temperature and the user setpoint. Chiller shuts down when [Shutdn DT]
Stop DT
falls below a user preset value in the -3 to -0.5℃ range. Default factory
setting is -2℃
93
sensor again to find the new error signal (e). The looping of error feedback and corrective action
continues until the actual output is equal to the setpoint.
However, just simply by adding these three values (P, I and D) together would not compute the
“corrective value”, each of these 3 values needs to be multiplied by a constant, known as “gain”.
Corrective value (u) is equal to the proportional gain (KP) times the magnitude of the error (P), plus the
integral gain (KI) times the integral of the error (I), plus the differential gain (KD) times the differential of
the error (D). See the following equations:
u = KP(P) + KI(I) + KD(D)
Proportional gain, expressed in degree (oC), has the effect of reducing the rise time (response time)
and steady-state error when it is increased. (Note: steady-state error is the difference between the
actual temperature and the setpoint when the actual temperature has settled down to a constant
value).
Integral gain, expressed in seconds, has the effect of eliminating the steady-state error, however the
tradeoff is longer settling time which means more time is needed for the PID controller to adjust the
actual temperature back to the setpoint.
Differential gains, expressed in seconds, helps to improve the responsiveness and stability of the
temperature control by sensing the rate of rise or falls of system temperature and minimizes overshoot
or undershoot. Therefore, larger differential gain means that rate of error is evaluated longer so that
overshoot is minimized and PID controller will take lesser time to adjust the actual temperature back to
the setpoint (shorter settling time).
Effects of each of gains are summarized in the table shown below.
Table9.2.3 Effects on increasing PID gains
PID Gain Rise Time Overshoot Settling Time Steady State Error
The following are explanations for another two user adjustable parameters in PID settings.
Sample – Sampling period, the time taken to take a reading of the controlled parameter (in our case,
the output temperature)
94
Period – Output period, the time taken to feedback the error signal to the PID controller
NOTE: Correlations as shown in above may not be exactly accurate, because K p, Ki, and Kd are
dependent of each other. In fact, changing one of these variables can change the effect of the
other two. For this reason, the table should only be used as a reference and user assumes all
responsibility on changing the PID settings, and McQuay takes no responsibility should the
performance of the chiller be compromised.
Sets the proportional gain of the controller in the 0.01 to 5 range. Default
Gain
factory setting loading is is 0.8 and unloading 0.6.
Sets the sampling rate of the controller in the 10 to 90 seconds range.
Sample
Default factory setting is 30 seconds.
Sets the integral time of the controller in the 200 to 9000 seconds range.
Integral
Default factory setting is 300 seconds.
Sets the differential value of the controller in the 5 to 120 seconds range.
Differential
Default factory setting is 15 seconds.
Sets the controller output period in the 2 to 60 seconds range. Default factory
Period
setting is 4 seconds.
Sets the time of load/unload solenoid valve energized in one output period,
Pulse Time
default factory setting for loading is 0.3S and unloading 0.4S.
95
9.2.5.3 Alarm setup
This menu will provide access of change alarm settings. McQuay PFS offers two kinds of alarms:
Pre-alarm: When pre-alarm occurs, machine will not necessarily automatically shut-off but alarm light
on control cabinet will flash and LCD displays the pre-alarm message.
Alarm: When alarm occurs, machine will auto shut off and alarm light on control cabinet will lit up
continuously, meanwhile LCD displays the alarm message.
Press [Alarm Setup] button to enter following screen.
Figure 9.2.13 Alarm Setup
96
Sets the compressor suction pressure alarm value in the 180 to 500 kPa
range. Warning light on the control cabinet lit up, LCD displays alarm
Suct P Alarm
message and machine shuts down when suction pressure falls below the
setpoint. Default factory setting is 180 kPa.
Sets the compressor discharge pressure pre-alarm value in the 800 to 1200
kPa range. Alarm light on the control cabinet flashes, LCD displays alarm
Dis.P Pre-Alarm
message and machine unloads when discharge pressure exceeds the
setpoint. Default factory setting is 950 kPa.
Sets the compressor discharge pressure alarm value in the 800 to 1200 kPa
range. Alarm light on the control cabinet lit up, LCD displays alarm message
Dis.P alarm
and machine shuts down when discharge pressure exceeds the setpoint.
Default factory setting is 1000 kPa.
Alarm will be given when the oil pressure differential is lower than this value,
Oil DP Alarm
the set value is 100-800 kPa, and that of the factory is 100 kPa
Timing delay of evaporator chilled water flow/PD switch alarm, setting
EDP Delay
ranges from 2S to 6S, factory default setting is 5S.
Timing delay of condenser cooling water flow/PD switch alarm, setting
CDP Delay
ranges from 2S to 6S, factory default setting is 5S.
9.2.5.4 Cap. Offset
Below figure shows an enlarged view of spring piston of the capacity sensor. Imagine the piston move
horizontally along the dotted square (along point A and B) as the capacity modulation valve pushes the
tip of spring piston. Point A and B correspond to 100% and 0% compressor load, respectively.
Referring to Figure 14, a positional value is given to point A (upper limit) and B (lower limit). Factory
default setting for point A (100% load) and B (0% load) is 32000 and 6400, respectively. The capacity
sensor might need to be calibrated if point A shift to point A‟, which represents a new setting on the
position value for 0% compressor load (the same explanation goes for point B‟).
Capacity calibration menu (by pressing the [Cap. Offset] button) allows user to recalibrate the
positional value for point A and B. For example, when compressor stops, (which represents 0%
compressor load) the „Active‟ value shows the actual positional value of the transducer (point B‟, which
97
correspond to 0% load) which should be the same for the „Lower Limit‟ value (point B). Should the
„Lower Limit‟ value differ from the „Active‟ value, set the „Lower Limit‟ value according to the „Active‟
value.
Figure 9.2.14 spring piston of the capacity sensor
98
Active Displays the current actual positional value of capacity sensor.
Sets the positional lower limit value of the transducer (Point A), factory
Lower Lim
default setting is 6400. Setting range 6400-32000.
Sets the positional upper limit value of the transducer (Point B), factory
Upper Lim
default setting is 32000. Setting range 6400-32000.
Demand limit control mode, can be shift from [local] to [remote] by press
Demand Limit drop-down menu. A 0-10V/4-20MA current signal will be sent to CPU to limit
the capacity if [remote] been selected.
Sets the maximum cooling load the unit can produce. can be set at the local
Dmd Capacity Spt and remote mode, ranges from 50% to 100% with a factory default setting
100%.
Press button [next] on the [Capacity Slide Calibration] interface will go into the [Demand Limit Setup]
interface.
Press button [previous] on the [Demand Limit Setup] interface will go into the [Capacity Slide
Calibration] interface.
9.2.5.5 CDS WTR Flow PID Setup
Condenser water flow PID is to sense refrigerant saturated condenser temp corresponding to
discharge pressure (refer to section5.1 system setting-Sat. cond temp) and after PID calculation, send
the analogue output to modulate condenser water flow valve or VFD pumps.
99
Figure 9.2.16 CDS WTR Flow PID Setup interface
Sets the proportional gain of the controller in the 0.01 to 5 range. Default
Gain
factory setting is 0.4.
Sets the sampling rate of the controller in the 10 to 90 seconds range. Default
Sample
factory setting is 10 seconds.
Sets the integral time of the controller in the 200 to 3000 seconds range.
Integral
Default factory setting is 300 seconds.
Sets the differential value of the controller in the 5 to 120 seconds range.
Differential
Default factory setting is 15 seconds.
Sets the controller output period in the 2 to 60 seconds range. Default factory
Period
setting is 10 seconds.
Sets the lower limit of analog signal to control device of condenser modulation
AO Low Level
valve or VFD pumps in range of 6400-32000, factory default setting is 6400.
Sets the upper limit of analog signal to control device of condenser modulation
AO High Level
valve or VFD pumps in range of 6400-32000, factory default setting is 32000.
Note: Change of above settings may cause interference or control malfunction, consult McQuay
service engineer before change.
9.2.5.6 Schedule
A 7-day, 24-hours („HOUR:MINUTE‟) programmable start/stop schedule of the chiller can be
programmed through the „Schedule settings‟ screen by pressing the [Schedule] button. Press the
100
[Next] or [Previous] button to switch between pages.
Figure 9.2.17 Schedule set
Chiller will run as per user-set schedule when the [use schedule] function is enabled on the „Mode
Select‟ screen (refer to section 1.1 Control mode selection).
9.2.5.7 Sen. offset
The „Sensor Offset‟ setting menu enables user to correct any differences between the actual
pressure/temperature and the sensor reading. Press the [Sensor Off.] button to enter the „Sensor
Offset‟ menu to add correctional factors to the temp/pressure values as read by sensors 1. This is
explained using the following formula.
Adds a leaving chilled water temperature correctional factor in the range of -9.9 to
Lvg Evap
9.9 ℃.Default factory setting is 0℃.
Adds an entering chilled water temperature correctional factor in the range of -9.9 to
Ent Evap
9.9 ℃. Default factory setting is 0℃.
Lvg Cond Adds a leaving condenser water temperature correctional factor in the range of -9.9
102
to 9.9 ℃. Default factory setting is 0℃.
Adds an entering condenser water temperature correctional factor in the range of
Ent Cond
-9.9 to 9.9 ℃. Default factory setting is 0℃.
Adds a discharge pressure (Comp 1 )correctional factor in the range of -9.9 to
1# Dis T
9.9 ℃. Default factory setting is 0 ℃.
9.2.6 Alarm
In case of alarm, the compressor will shut off and alarm light lit up. To restart the compressor after
problem has been rectified, press the [clear] button located on the main menu.
The following is a list of the alarms:
1. Discharge superheat pre-alarm/alarm;
2. Suction pressure pre-alarm/alarm;
3. Discharge pressure pre-alarm/alarm;
4. Phase sequence protection alarm;
5. Evap Freeze Protect;
6. Cond Water Flow switch alarm;
7. Evap Water Flow switch alarm;
8. Oil level switch alarm;
9. 1# ,2# Oil DP alarm;
10.1# ,2# Discharge T alarm;
103
11. 1# ,2# Low pressure switch alarm;
12. 1# ,2# High pressure switch alarm;
13. 1# ,2# Motor overheat alarm;
14. 1# ,2# Motor overload alarm;
15. 1# ,2# Transition fault;
16. 1# ,2# Unload fault;
Press the [Alarm] button in the main tool bar for active alarm and alarm history.
Figure 9.2.20 Active Alarms interface
104
Figure 9.2.21 Alarm History interface
Note: Alarm history is saved in touch screen memory not in CPU226, thus once power off; all the alarm
histories will be cleared and will not be shown on screen anymore.
105
9.3 K-TP178 Control panel Operating manual for PFS.3
Prolegomenon
PFS utilizes known K-TP 178 touch screen as the main human interface to offer operator easy
operation and maintenance. This manual will direct operator on how to view, set, and control PFS
chillers via K-TP178.
Note for Compressor nomenclature: Facing control panel, from left side to right side compressor #1,
#2 and #3 respectively.
Figure 9.3.1 main interface
Note: The [Data] button will change to [Display] by pressing other buttons except [Set]
106
Control Mode Select
Manual Operation
Mode
Output Test
Compressor Test
Hardware
Information
System
Screen Setup
Chiller Information
Data Compressor
Information
Capacity Slide
Calibration
System Setup
Sensor Offsets
Active Alarm
Alarm
Alarm History
107
9.3.1 Mode
Mode interface contains 4 sub-screens: control mode select, manual operation, output test and
compressor test.
9.3.1.1 Control mode settings
Four control modes available on McQuay PFS, see below detailed table:
Table 9.3.1 Control mode select
Mode Description
Remote To control chiller on/off by remote PC or other devices away from chiller plant room.
Local To control chiller on/off by chiller operating touch screen.
Schedule To control chiller on/off by pre-set time schedule, refer to section 9.3.5.6.
Pre-start testing, allow unit to check wiring and output prior start, refer to section
Test
9.3.1.3 and 9.3.1.4
The following interface will be displayed by pressing “Mode” button in the main interface.
Note 1: Only McQuay authorized operator has the rights to operate.
Note2: Program for Australia chillers will pop-out an input dialogue by pressing [Mode] button. It offers
two level user names and codes protection with different authorities. See below table:
Table 9.3.2 User identification
108
After log on, interface will direct you into the mode selection screen.
Only one control mode could be selected each time, and a selection has to be made before start the
unit. Once one mode is pressed the button will reverse, for example press [Ignore local], then the
button will auto change to [Use local].
Figure 9.3.3 Control Mode Select interface
Ignore Local/Use local Press this button to disable/enable local control (on/off) of the chiller.
Ignore Remote/Use Press this button to disable/enable local control (on/off) of the chiller.
remote
Ignore Schedule/Use Enable/disable chiller auto start according to preset time schedule.
Schedule
109
Figure 9.3.4 Manual Operation interface
110
Figure 9.3.6 Output Test interface 2
Two liquid feed valves. PFS.3 unit has a main liquid line and a supplemental
Liquid 1&2
liquid line, each line equips a solenoid valve.
To test for chiller internal control wiring, switch between the ON/OFF button (on the [Unit Output Test]
menu as shown in above figure) for the control parameter and check the corresponding LED on the
controller block inside the compressor control cabinet. Refer to the chiller wiring diagram for the
corresponding LED address.
Caution: To prevent oil back to the oil separator from the compressor oil chamber, the test of
oil feed valve is not allowed when the high/low pressure differential is not built up
Press [Operate] button to return to [Manual operating] menu.
111
9.3.1.4 Compressor test
Press the [Compressor Test] button to the following compressor testing screen. Prior to bringing the
chiller into actual operation, the compressor testing function lets the operator to perform test on each
compressor individually.
Figure 9.3.7 Compressor Test interface
Press this button to perform a three-second test run on this chiller; the main
3S Test
purpose is to check compressor running rotation.
Press this button to perform a sixteen-second test run on this chiller; the main
16S Test
purpose is to check compressor abnormal noise, and starter wye-delta transition.
Displays the difference between discharge and suction pressure for compressor. A
Lift Press correct compressor rotation determined by a positive „Lift Press‟ value, otherwise a
negative value is displayed.
Press [operate] button or [output test] button to return to previous menu screen.
Note: compressor test can only be performed when control mode [use test] is selected.
9.3.2 System
112
Figure 9.3.8 Information of the touchscreen
113
9.3.3 Reset
9.3.4 Data
In this section will provide chiller information such as temps, pumps and compressor information to
view the operating condition of the chiller.
9.3.4.1 Chiller information
The following interface will be displayed as follows by pressing [Data] in the main interface:
Figure 9.3.10 Chiller Information
Displays the active set point of leaving water temperature of the evaporator,
Active Set point
Active set point=Local spt+Remote CHW offset, refer to section 5.1.
Lvg Evap Displays the leaving water temperature of the evaporator.
Ent Evap Displays the entering water temperature of the evaporator.
Lvg Cond Displays the leaving water temperature of the condenser.
Ent Cond Displays the entering water temperature of the condenser.
Cooling Call When displays Call means the Remote switch is on, and No Call means it is
Received off.
Evap Pump Displays running hours and start times of the chilled water pump.
Hrs/Starts
Cond Pump Displays running hours and start times of the cooled water pump.
Hrs/Starts
114
9.3.4.2 Compressor information
Press lower right [1#] [2#][3#]on above menu will switch the interface to compressor information to
display compressor temp and pressure in real time for each compressors.
Figure 9.3.11 Information interface by pressing 1#
115
Figure 9.3.13 Information interface by pressing 3#
Displays countdown waiting time of start, and the chiller will be allowed to
Wait Time
start only after the waiting-time is 0. Refer to section 1.2
Hours Displays the total operating time of the compressor.
Starts Displays the total starts of the compressor.
Press [Temp] button to return to previous chiller information menu.
9.3.5 Set
Note: Only the [Set] button pressed doesn’t change [Data] to [Display]
116
9.3.5.1 System setting
Press the [Set] button on the main tool bar for system settings. A window will pop up prompting for
Username and Password. All system settings (except for leaving chilled water set point) are password
protected.
Figure 9.3.14 System Setup
117
VFD pumps. the arrange is 20-35℃.Default factory setting is 25℃.
The set point of the Pulldown Rate of chilled water with the range of
Pulldown Rate
0.1-2℃/minute, factory default setting is 0.2℃/minute.
Sets the minimum capacity that the chiller can unload to. Default factory
Min Capacity
setting is 10% but adjustable in 5%-50% range.
Modbus ID Sets machine Modbus address if multiple chiller control system applied.
Note:[Remote CHW offset] is used only for Australia chillers.
Active Set point=Local Spt+Remote CHW offset
9.3.5.2 Chiller capacity PID setup
To accurately control the capacity (related to chilled water temperature) and condenser water
temperature, PFS chiller temperature controller uses PID (Proportional, Integral, Differential) algorithm
in controlling the temperature. PID controller compares the actual temperature (feedback from sensor
reading) to the desired control temperature (setpoint); an error signal found by subtracting the
measured quantity from the setpoint is feedbacked to the PID controller. The PID controller computes
and sends a “corrective signal” (otherwise known as a “corrective value”) to the actuators based on:
the magnitude of the error (“P” = proportional), the sum of all previous errors (“I” = integral) and
anticipate future error from the rate of change of the error (“D” = differential). A “corrective action” is
performed by the actuator such that the error signal is reduced. The new output will be sent back to the
sensor again to find the new error signal (e). The looping of error feedback and corrective action
continues until the actual output is equal to the setpoint.
However, just simply by adding these three values (P, I and D) together would not compute the
“corrective value”, each of these 3 values needs to be multiplied by a constant, known as “gain”.
Corrective value (u) is equal to the proportional gain (KP) times the magnitude of the error (P), plus the
integral gain (KI) times the integral of the error (I), plus the differential gain (KD) times the differential of
the error (D). See the following equations:
u = KP(P) + KI(I) + KD(D)
Proportional gain, expressed in degree (oC), has the effect of reducing the rise time (response time)
and steady-state error when it is increased. (Note: steady-state error is the difference between the
actual temperature and the setpoint when the actual temperature has settled down to a constant
118
value).
Integral gain, expressed in seconds, has the effect of eliminating the steady-state error, however the
tradeoff is longer settling time which means more time is needed for the PID controller to adjust the
actual temperature back to the setpoint.
Differential gains, expressed in seconds, helps to improve the responsiveness and stability of the
temperature control by sensing the rate of rise or falls of system temperature and minimizes overshoot
or undershoot. Therefore, larger differential gain means that rate of error is evaluated longer so that
overshoot is minimized and PID controller will take lesser time to adjust the actual temperature back to
the setpoint (shorter settling time).
Effects of each of gains are summarized in the table shown below.
Table 9.3.3 Effects on increasing PID gains
PID Gain Rise Time Overshoot Settling Time Steady State Error
The following are explanations for another two user adjustable parameters in PID settings.
Sample – Sampling period, the time taken to take a reading of the controlled parameter (in our case,
the output temperature)
Period – Output period, the time taken to feedback the error signal to the PID controller
NOTE: Correlations as shown in above Table 9.3.3 may not be exactly accurate, because Kp,
Ki, and Kd are dependent of each other. In fact, changing one of these variables can change the
effect of the other two. For this reason, the table should only be used as a reference and user
assumes all responsibility on changing the PID settings, and McQuay takes no responsibility
should the performance of the chiller be compromised.
119
Figure 9.3.15 PID interface
Sets the proportional gain of the controller in the 0.01 to 5 range. Default
Gain
factory setting is 0.8.
Sets the sampling rate of the controller in the 10 to 90 seconds range.
Sample
Default factory setting is 30 seconds.
Sets the integral time of the controller in the 200 to 9000 seconds range.
Integral
Default factory setting is 300 seconds.
Sets the differential value of the controller in the 5 to 120 seconds range.
Differential
Default factory setting is 15 seconds.
Sets the controller output period in the 2 to 60 seconds range. Default
Period
factory setting for loading is 6 seconds and unloading 4 seconds.
Sets the time of load/unload solenoid valve energized in one output period,
Pulse Time
default factory setting for loading is 0.3S and unloading 0.4S.
120
Figure 9.3.16 Alarm Setup
Sets the compressor suction pressure alarm value in the 180 to 500 kPa
range. Warning light on the control cabinet lit up, LCD displays alarm
Suct P Alarm
message and machine shuts down when suction pressure falls below the
setpoint. Default factory setting is 180 kPa.
Sets the compressor discharge pressure pre-alarm value in the 800 to 1200
Dis.P Pre-Alarm kPa range. Alarm light on the control cabinet flashes, LCD displays alarm
message and machine unloads when discharge pressure exceeds the
121
setpoint. Default factory setting is 950 kPa.
Sets the compressor discharge pressure alarm value in the 800 to 1200 kPa
range. Alarm light on the control cabinet lit up, LCD displays alarm message
Dis.P alarm
and machine shuts down when discharge pressure exceeds the setpoint.
Default factory setting is 1000 kPa.
Alarm will be given when the oil pressure differential is lower than this value,
Oil DP Alarm
the set value is 100-800 kPa, and that of the factory is 100 kPa
Timing delay of evaporator chilled water flow/PD switch alarm, setting ranges
EDP Delay
from 2S to 6S, factory default setting is 5S.
Timing delay of condenser cooling water flow/PD switch alarm, setting
CDP Delay
ranges from 2S to 6S, factory default setting is 5S.
122
Figure 9.3.17 Spring piston of the capacity sensor
123
Sets the positional lower limit value of the transducer (Point A), factory
Lower Lim
default setting is 6400. Setting range 6400-32000.
Sets the positional upper limit value of the transducer (Point B), factory
Upper Lim
default setting is 32000. Setting range 6400-32000.
Demand limit control mode, can be shift from [local] to [remote] by press
Demand Limit
drop-down menu.
Sets the maximum cooling load the unit can produce. can be set at the local
Demand Capacity
and remote mode, ranges from 50% to 100% with a factory default setting
Spt
100%.
Sets the proportional gain of the controller in the 0.01 to 5 range. Default
Gain
factory setting is 0.4.
Sets the sampling rate of the controller in the 10 to 90 seconds range. Default
Sample
factory setting is 10 seconds.
Sets the integral time of the controller in the 200 to 3000 seconds range.
Integral
Default factory setting is 300 seconds.
124
Sets the differential value of the controller in the 5 to 120 seconds range.
Differential
Default factory setting is 15 seconds.
Sets the controller output period in the 2 to 60 seconds range. Default factory
Period
setting is 10 seconds.
Sets the lower limit of analog signal to control device of condenser modulation
AO Low Level
valve or VFD pumps in range of 6400-32000, factory default setting is 6400.
Sets the upper limit of analog signal to control device of condenser modulation
AO High Level
valve or VFD pumps in range of 6400-32000, factory default setting is 32000.
Note: Change of above settings may cause interference or abnormal control malfunction, consult
McQuay service engineer before change.
9.3.5.6 Schedule
A 7-day, 24-hours („HOUR:MINUTE‟) programmable start/stop schedule of the chiller can be
programmed through the „Schedule settings‟ screen by pressing the [Schedule] button. Press the
[Next] or [Previous] button to switch between pages.
Figure 9.3.21 Schedule set
125
Figure 9.3.22 Continues
Chiller will run as per user-set schedule when the [use schedule] function is enabled on the „Mode
Select‟ screen(refer to section 1.1 Control mode selection ).
9.3.5.7 Sensor offset
The „Sensor Offset‟ setting menu enables user to correct any differences between the actual
pressure/temperature and the sensor reading. Press the [Sensor Off.] button to enter the „Sensor
Offset‟ menu to add correctional factors to the temp/pressure values as read by sensors1. This is
explained using the following formula.
Should there be no differences between the sensor reading and the actual temperature/pressure, the
correctional factor is zero.
Please note that the „Sensor offset‟ setting does not calibrate the sensor, but adds a correctional factor
to the value of the sensor as read by the chiller microprocessor, such that the value can be corrected.
126
Figure 9.3.23 Sensor offset interface 1
Adds a leaving chilled water temperature correctional factor in the range of -9.9 to
Evap L-T
9.9 ℃.Default factory setting is 0℃.
Adds an entering chilled water temperature correctional factor in the range of -9.9 to
Evap E-T
9.9 ℃. Default factory setting is 0℃.
Adds a leaving condenser water temperature correctional factor in the range of -9.9
Cond L-T
to 9.9 ℃. Default factory setting is 0℃.
127
Default factory setting is 0 ℃.
Adds a discharge temperature correctional factor in the range of -999 to 999 kPa.
Dis.P
Default factory setting is 0 kPa.
Adds a suction pressure correctional factor in the range of -999 to 999 kPa. Default
Suct. P
factory setting is 0 kPa.
Adds a oil pressure correctional factor in the range of -999 to 999 kPa. Default
Oil Press
factory setting is 0 kPa.
9.3.6 Alarm
In case of alarm, the compressor will shut off and alarm light lit up. To restart the compressor after
problem has been rectified, press the [clear] button located on the main menu.
The following is a list of the alarms:
1. Discharge superheat pre-alarm/alarm
2. Suction pressure pre-alarm/alarm;
3. Discharge pressure pre-alarm/alarm
4. Phase sequence protection alarm;
5. Evap Freeze Protect;
6. No Cond Water Flow Fault;
7. No Evap Water Flow Fault;
8. Oil level switch alarm;
9. 1# ,2# ,3# Oil DP alarm;
10. 1# ,2# ,3# Discharge T alarm;
11. 1# ,2#,3# Low pressure switch alarm;
12. 1# ,2# ,3# High pressure switch alarm;
13. 1# ,2# ,3# Motor overheat alarm;
14. 1# ,2# ,3# Motor overload alarm;
15. 1# ,2# ,3# Transition fault;
16. 1# ,2# ,3# Unload fault;
Press the [Alarm] button in the main tool bar for active alarm and alarm history.
128
Figure 9.3.25 Active Alarms interface
129
10. Fault diagnosis
02. High pressure switch alarm High pressure sensor failure Comp shut off
temperature.
temperature.
indication error
130
low 2 Low oil temperature.
fast.
07. Phase sequence protection 1 Incorrect power connection. Unit shut off
09. Wye-Delta transfer failure The triangle contactor node failure Comp shut off
alarm
10. Comp low oil PD alarm 1 Cond water temp too low Comp shut off
11. Chilled water loss of flow 1 Low chilled water flow. Unit shut off & Pump
12. Condenser water loss of 1 Low condenser water flow. Unit shut off
131
10.2 Oil lose analysis
Follow below process to check the unit when PFS, WPS.C oil loss:
132
133
134
135
136
137
138
11. Chiller maintenance parts packet
139
19 Main controller/UL508 PLC/CPU226 PFS E8211163
20 Discharge flange gasket PFS T3312053
21 Oil filter core F4 compressor M7384-188
140