Vc-Hca 1
Vc-Hca 1
>
> Features
| Superior Switching Performance
Switching a vacuum makes for rapid breaking.
Rapid build-up of the dielectric strength ensures safety breaking.
The fuse mounted type also provides for protection against short-circuit currents.
| Optimum Design
Optimized structure and mechanism complement frequent switching.
| Low Surge
Special WCAg contact limits the chopping current up to 1A to protect the load from high surge.
| High Reliability
Rigid insulation frame and operating mechanism offer high reliability, especially for safety and quality assurance.
| Customer Convenience
Light weight and compact size enable easy installation with high efficiency in space.
Optimum design makes maintenance convenient.
>
> Operation and Application
| Continuously Energized Type
Having longer mechanical life time than a latched type, more suitable for frequent switching.
When the transformer for controlling power fails to supply power due to accidents, continuously energized type protects the
loads by tripping automatically.
| Latched Type
Latched type keeps the closing condition without the supply of power, so it is suitable for the system which has unstable
power or the load which requires automatic closing with power.
With the separate tripping circuit, DC control voltage is recommended for stable power supply. When AC control voltage is
used, the CTD(condesor trip device) should be installed.
6
◀ 5
7
8
▶
1 ▶
9
1 ▶
◀
◀ 3 2 ▶
◀ 3
2 ▶
◀ 4
◀ 4
> Ratings
>
Operating Continuously energized 32C� 34C� 62C� 64C� 82C� 84C� 32C� 34C� 62C� 64C� 82C� 84C�
method Latched 32L� 34L� 62L� 64L� 82L� 84L� 32L� 34L� 62L� 64L� 82L� 84L�
Rated current (A) 200 400 200 400 200 400 200 400 200 400 200 400
J 33 J 35 H 433) H 463)
>
> Technical Data
| Operating Time and Current
[ CLOSED condition ]
� ▶ � ▶
� �
◀ � ◀ �
▶
� ▶ � ▶
�
� ▶ �
◀
� ▶
◀ � ◀ �
◀ �
� ▶ � ▶
[ OPEN condition ]
◀ � ▶
� ▶
◀ �
◀ �
� ▶ ◀ �
� ▶
� ▶
▶Closing ▶Opening
When the closing coil(� ) is energized, the moving core(� ) �Continuously energized type: When the closing coil(� ) is
moves to the closing coil and compresses the opening de-energized by the OFF signal, the opening spring(� ) is
spring(� ). At the same time the pressing plate(� ), which is released to the OPEN condition.
fixed on the main shaft(� ), pushes the charging spring(� ),
�Latched type: When the opening coil is energized by the
so the movable stem of the vacuum interrupter(� ) is moved
OFF siginal or the opening button is pushed, the latch
up to make the CLOSED condition.
device(� ) is released and the opening spring(� ) lets the
�Continuously energized type: When the moving core(� ) moving core(� ) move to the OPEN condition.
moves, the auxiliary switch(� ) leads the control power to During a power failure, the trip button or condensor trip
resistance(� ) and reduces the current of the closing coil(� ). device(CTD) of the latched type also enable the opening of
the contactor.
�Latched type: When the contactor is closed, the latch device
(� ) of the contactor fixs the moving core(� ) mechanically
and keeps the closed condition. Then the control power is
removed.
>
> Technical Data
| Interlock Function
Case Principle Release
it cannot be drawn-in from test The interlock pin of the contactor, which is
When the position to connection position inserted in the TEST/CONNECTION hole of Open the contactor and draw in/out to
contactor
cradle, mechanically prevents the contactor required position.
is closed, it cannot be drawn-out from
connection position to test position from moving.
▶Interlock Mechanism
▶Interlock Release
Stopper
| Fuse
▶without Fuse Holder Type
The breaking current of without fuse type is limited, so a circuit breaker should be installed in the upper circuit of the line side.
In the case of draw-out types, the fuse holder connection part is replaced by a bus-bar. When it is required, the fuse holder
can be installed under our instruction.
▶Fuse Selection
※ - This table is based on SIBA catalogue, and is for the 3-phase motor with starting time max. 15 seconds and starting frequency 2 times per hour.
- SIBA recommends choosing the next highest voltage range in the condensor load.
- Please contact us for the further details of application data.
| Operating Condition
▶ Altitude : less than 1,000m A.S.L(above sea level)
Multiply the impuIse and the withstand voltage in accordance with the following correction factor (k) for high locations.
Applied altitude 1,000m 1,500m 2,000m 2,500m 3,000m
Correction factor (k) 1.0 1.05 1.1 1.15 1.2
▶ Special conditions
Please contact us for information on special cases like seashore use, corrosive chemical environments, and so on.
>
> Accessories
| Standard Accessories
Control lead cable (1.2m) Manual closing handle for latched type
| Additional Option
▶Electrical Interlock
▶Potential Transformer
▶Condensor Trip Device
Order code HCAS0012 HCAS0013
When the latched type vacuum contactor is
used in AC control voltage, the condensor Rated input voltage AC110V AC220V
trip device should be installed inside the Ordinary charging voltage DC145V DC290V
3.6/7.2kV contactor as an internal option. Ordinary current DC2A
For 12kV contactor, it should be installed Frequency 50/60Hz
in switchgear. Applied standard IEC 60694/KSC 4611
▶Terminal Connection
1,2: Input power(AC) / 5,6: Closing power(DC) / 5,7: Trip power
3.6/7.2kV DC Control
3.6/7.2kV AC Control
12kV
Option
[ 3.6/7.2kV ] [ 12kV ]
※ �Vza, Vzb: Control Switch �R: Resistor �CC: Closing Coil �Aux. Switch: Auxiliary Switch �X: Relay
�TC: Trip Coil �CTD: Condensor Trip Device �SCU: Control Unit �S8, S9: Internal Position Switch
>
> Dimensions
(Unit: mm)
Dimension Y
200A 400A
25 32
(Unit: mm)
Dimension A
200A 400A
25 32
(Unit: mm)
Dimension A
200A 400A
25 32
(Unit: mm)
(Unit: mm)
>
> Dimensions
(Unit: mm)
(Unit: mm)
(Unit: mm)
(Unit: mm)
(Unit: mm)
(Unit: mm)
>
> Dimensions
(Unit: mm)
(Unit: mm)
(Unit: mm)
(Unit: mm)
12kV Draw-out type, E1/F1 cradle without fuse holder / with single fuse holder
(Unit: mm)
12kV Draw-out type, M1 cradle without fuse holder / with single fuse holder
>
> Order Information
HCA 6 4 C D 4
Model Rated Rated Operating Structure Control
Code Name
Code Voltage
Code Current
Code Method
Code Code
Contactor Fuse Holder Voltage
HCA HCA 3 3.6kV 2 200A Continuously F Fixed type up to 12kV - 1 DC110V
C Energized
6 7.2kV 4 400A A Fixed type up to 12kV Single 2 DC220V
8 12kV L Latched J Fixed type up to 7.2kV Double 3 AC110V
B Draw-out type up to 12kV - 4 AC220V
D Draw-out type up to 12kV Single
H Draw-out type up to 7.2kV Double
HCA32CF 4000000 3.6kV Fixed type HCA32LF 4000000 AF 3.6kV Fixed type
without fuse holder, without fuse holder,
HCA62CF 4000000 7.2kV 200A AC220V, HCA62LF 4000000 AF 7.2kV 200A AC220V,
No cradle, No cradle, No fuse holder,
HCA82CF 4000000 12kV No fuse holder HCA82LF 4000000 BF1) 12kV AC220V CTD
HCA32CD 4F16000 3.6kV Draw-out type HCA32LD 4F16000 AF 3.6kV Draw-out type
with single fuse holder, with single fuse holder,
HCA62CD 4F16000 7.2kV 200A AC220V, HCA62LD 4F16000 AF 7.2kV 200A AC220V,
F1 cradle, F1 cradle, No fuse,
HCA82CD 4F1600A 12kV No fuse HCA82LD 4F16000 BF1) 12kV AC220V CTD
HCA32CD 4M16000 3.6kV Draw-out type HCA32LD 4M16000 AF 3.6kV Draw-out type
with single fuse holder, with single fuse holder,
HCA62CD 4M16000 7.2kV 200A AC220V, HCA62LD 4M16000 AF 7.2kV 200A AC220V,
M1 cradle, M1 cradle, No fuse,
HCA82CD 4M1600A 12kV No fuse HCA82LD 4M16000 BF1) 12kV AC220V CTD
VC V2
HCA34CF 4000000 3.6kV Fixed type HCA34LF 4000000 AF 3.6kV Fixed type
without fuse holder, without fuse holder,
HCA64CF 4000000 7.2kV 400A AC220V, HCA64LF 4000000 AF 7.2kV 400A AC220V,
No cradle, No cradle, No fuse holder,
HCA84CF 4000000 12kV No fuse holder HCA84LF 4000000 BF1) 12kV AC220V CTD
HCA34CD 4F16000 3.6kV Draw-out type HCA34LD 4F16000 AF 3.6kV Draw-out type
with single fuse holder, with single fuse holder,
HCA64CD 4F16000 7.2kV 400A AC220V, HCA64LD 4F16000 AF 7.2kV 400A AC220V,
F1 cradle, F1 cradle, No fuse,
HCA84CD 4F1600A 12kV No fuse HCA84LD 4F16000 BF1) 12kV AC220V CTD
HCA34CD 4M16000 3.6kV Draw-out type HCA34LD 4M16000 AF 3.6kV Draw-out type
with single fuse holder, with single fuse holder,
HCA64CD 4M16000 7.2kV 400A AC220V, HCA64LD 4M16000 AF 7.2kV 400A AC220V,
M1 cradle, M1 cradle, No fuse,
HCA84CD 4M1600A 12kV No fuse HCA84LD 4M16000 BF1) 12kV AC220V CTD
M1 6000 AMAP
Fuse Application
Code Cradle Code Code Additional Option
Fuse Holder Fuse Specification Application Mounting
00 N/A (for Fixed type) 0000 - - AE 3.6/7.2kV
CTD, AC110V
E1 without Shutter 6000 Single up to 250A, 192mm BE 12kV Latched type,
AF 3.6/7.2kV AC control
F1 with Insulation Shutter 3.6/7.2kV 315/355A, CTD, AC220V
600A Single BF 12kV Inside
M1 with Metal Shutter and Bushing 12kV, 292mm of
AL 3.6/7.2kV
with Metal Shutter, Bushing 600B Double 3.6/7.2kV, 192mm Electrical Interlock Draw-out type contactor
T1 BL 12kV
and Earthing Switch 600C Single 442mm AM 3.6/7.2kV
Fuse Melting Detector for Fuse
※ Fuse is not included. BM 12kV
AP 3.6/7.2kV
Position Switch Draw-out type Cradle
BP 12kV
T1 Potential Transformer, 3.6kV x 1EA
T3 Potential Transformer, 7.2kV x 1EA Inside
3.6/7.2kV All of
T4 Potential Transformer, 3.6kV x 2EA contactor
T6 Potential Transformer, 7.2kV x 2EA
| Spare Parts
Code Specification Category Code Specification Category
HCAS0001 Counter (5 digit) HCAS6032 Fuse - 7.2kV/31.5A/63kA, 192mm, 1EA (SIBA)
HCAS0002 Manual closing handle (for latched type) HCAS6040 Fuse - 7.2kV/40A/63kA, 192mm, 1EA (SIBA)
HCAS0003 Latch device (DC110V) HCAS6050 Fuse - 7.2kV/50A/63kA, 192mm, 1EA (SIBA)
HCAS0004 Latch device (DC220V) HCAS6063 Fuse - 7.2kV/63A/63kA, 192mm, 1EA (SIBA)
HCAS0005 Fuse melting detector (3.6/7.2kV) HCAS6080 Fuse - 7.2kV/80A/63kA, 192mm, 1EA (SIBA)
HCAS0006 Position indicator (3.6/7.2kV) HCAS6100 Fuse - 7.2kV/100A/63kA, 192mm, 1EA (SIBA)
HCAS0007 Closing coil (DC110/220V, 3.6/7.2kV, 1EA)1) HCAS6125 Fuse - 7.2kV/125A/63 kA, 192mm, 1EA (SIBA)
HCAS0008 Closing coil (DC110/220V, 12kV, 1EA)1) HCAS6160 Fuse - 7.2kV/160A/63kA, 192mm, 1EA (SIBA)
HCAS0009 Potential transformer (7.2kV/200VA) HCAS6200 Fuse - 7.2kV/200A/50kA, 192mm, 1EA (SIBA)
HCAS0011 Potential transformer (3.6kV/200VA) HCAS6250 Fuse - 7.2kV/250A/50kA, 192mm, 1EA (SIBA)
HCAS0012 Condenser trip device (AC110V) HCAS6315 Fuse - 7.2kV/315A/50kA, 292mm, 1EA (SIBA)
HCAS0013 Condenser trip device (AC220V) HCAS6355 Fuse - 7.2kV/355A/50kA, 292mm, 1EA (SIBA)
HCAS0015 Control lead cable (length 1.5m, 3.6/7.2kV) HCAS7006 Fuse - 12kV/6.3A/63kA, 292mm, 1EA (SIBA)
VC V8 VC V8
HCAS0016 Control lead cable (length 2.0m, 3.6/7.2kV) HCAS7010 Fuse - 12kV/10A/63kA, 292mm, 1EA (SIBA)
HCAS0019 Fuse holders for single type (3.6/7.2kV, 1EA)1) HCAS7016 Fuse - 12kV/16A/63kA, 292mm, 1EA (SIBA)
HCAS0020 Fuse holders for double type (3.6/7.2kV,1EA)1) HCAS7020 Fuse - 12kV/20A/63kA, 292mm, 1EA (SIBA)
HCAS0018 Fuse holders for single type (12kV, 1EA)1) HCAS7025 Fuse - 12kV/25A/63kA, 292mm, 1EA (SIBA)
HCAS0021 Isolating contact (3.6/7.2kV, 200A) HCAS7032 Fuse - 12kV/32A/63kA, 292mm, 1EA (SIBA)
HCAS0022 Isolating contact (3.6/7.2kV, 400A) HCAS7040 Fuse - 12kV/40A/63kA, 292mm, 1EA (SIBA)
HCAS0023 Isolating contact (12kV, 400A) HCAS7050 Fuse - 12kV/50A/63kA, 292mm, 1EA (SIBA)
HVC00704 Vacuum interrupter (7.2kV, 400A) HCAS7063 Fuse - 12kV/63A/63kA, 292mm, 1EA (SIBA)
HVC01204 Vacuum interrupter (12kV, 400A) HCAS7080 Fuse - 12kV/80A/63kA, 292mm, 1EA (SIBA)
HCAS6006 Fuse - 7.2kV/6.3A/63kA, 192mm, 1EA (SIBA) HCAS7100 Fuse - 12kV/100A/63kA, 292mm, 1EA (SIBA)
HCAS6010 Fuse - 7.2kV/10A/63kA, 192mm, 1EA (SIBA) HCAS7125 Fuse - 12kV/125A/63kA, 292mm, 1EA (SIBA)
HCAS6020 Fuse - 7.2kV/20A/63kA, 192mm, 1EA (SIBA) HCAS7160 Fuse - 12kV/160A/63kA, 292mm, 1EA (SIBA)
HCAS6025 Fuse - 7.2kV/25A/63kA, 192mm, 1EA (SIBA) HCAS7200 Fuse - 12kV/200A/50kA, 292mm, 1EA (SIBA)
※ - 442mm fuse is applicable to 12kV vacuum contactor, but not supplied by HHI.
1) 2EA is required for 1set of vacuum contactor.
2) 6EA is required for 1set of vacuum contactor.