GENERAL CHARACTERISTICS
NO compromise!
Is a fact that, despite the chiller is selected to satisfy the cooling demand of the plant in worst conditions
(meaning highest ambient temperature possible during the cooling season and maximum demand of cooling
energy from the plant), in real operation the ambient temperature will be most of the time lower than the design
temperature and the cooling demand will be less than the maximum possible.
The indication of “how good a chiller is” cannot be given by full load efficiency energy ratio (EER) but a seasonal
energy efficiency ratio index is needed to proper represent actual operation.
The latest European regulations (entered into force on January 2018) are based on the same concept, setting
for Europe minimum efficiency levels based on seasonal operation.
Within the scope of the regulation two different application are identified:
• Comfort Cooling applications: seasonal efficiency index is Seasonal Energy Efficiency Ratio (SEER)
• Process Cooling application: seasonal efficiency index is Seasonal Energy Performance Ratio SEPR)
The calculation of the seasonal efficiency indexes is based on an average profile for European countries.
For comfort application SEER calculation, as defined in EN14825, considers a cooling season of 2600 hours.
Assuming 100% cooling demand at 35°C ambient temperature (design temperature) and 0% at 16°C (assumed
as Off temperature). Between 35°C and 16°C ambient the cooling demand is calculated based on a linear trend.
In the graph below the parameter (BIN and Load) for SEER calculation are represented together with the efficiency
of fix speed screw chiller and DAIKIN TZ C at each condition. Despite the efficiency at design condition is similar,
the efficiency of DAIKIN TZ C goes up to 130% over the efficiency of the fix speed chiller resulting in much lower
operating cost over the cooling season.
2
GENERAL CHARACTERISTICS
For process application SEPR calculation considers a full year operation (8760 hours). Assuming 100% cooling
demand at 35°C ambient temperature (design temperature) and 80% at 5°C (80% is minimum load required for
the process). Between 35°C and 5°C ambient the cooling demand is calculated following a linear trend.
In the graph below the parameter (BIN and Load) for SEPR calculation are represented together with the efficiency
of fix speed screw chiller and DAIKIN TZ C at each condition. Despite the efficiency at design condition is similar,
the efficiency of DAIKIN TZ C goes up to 125% over the efficiency of the fix speed chiller resulting in much lower
operating cost over the year.
For any application, comfort or process, DAIKIN TZ C achieve the highest efficiency and so the lowest operating
costs.
The EWA(H)(D)~TZ C range is available with 2 efficiency levels both with an extensive option list.
Outstanding reliability the TZ-C chillers are equipped with a rugged compressor design with advanced composite
compressor gate rotors material, a proactive control logic and are full factory- run-tested to optimized trouble-free
operation.
The compressor is driven by an inverter integrated on the compressor body and cooled by the refrigerant from the
chiller’s circuit. The inverter is designed and manufactured by DAIKIN for this specific application. It is the result
of years of experience in inverter application for compressors.
Superior control logic The MicroTech 4 controller provides an easy to use control environmental. The control
logic is designed to provide maximum efficiency, to continue operation in unusual operating conditions and to
provide a history of unit operation. One of the greatest benefits is the easy interface with LonWorks, Bacnet,
Ethernet TCP/IP or Modbus communications. Integrated sequencing control is provided allowing to connect
units (up to 4) operating as a single bigger chiller
Code requirements – Safety and observant of laws/directives Units are designed and manufactured in
accordance with applicable selections of the following:
Certifications Units are complying with European directives in force, concerning manufacturing and safety. On
request units can be produced complying with laws in force in non-European countries, and with other applications,
such as naval.
3
GENERAL CHARACTERISTICS
Compressor the compressor is semi-hermetic, single-screw type. Design and manufactured by DAIKIN, the
new single screw compressor is the result of years of experience and continuous investments in research and
development. Specifically, the new DAIKIN single screw compressor is optimized to operate with both R1234ze
and R134a refrigerant. The geometry of the compressor itself has been fully redesigned to achieve the highest
efficiency at full load (when the all the capacity of the chiller is required) as well as the highest part-load
efficiency (much frequent conditions) thanks to the Variable Frequency Drive (VFD) allowing continuous
modulation of compressor’s rotational speed.
The VFD, also design and manufactured by DAIKIN, is integrated in the compressor’s body and the electronics
inside is cooled by the refrigerant form the chiller’s circuit.
The heat generated by the VFD is dissipated trough an aluminum plate exchanger directly in contact with the
electronics. When temperature inside the VFD requires to be lowered some refrigerant is taken from the liquid
line of the and, after being expanded, it enters in the aluminum heatsink cooling the inverter electronics.
The cold vector is the refrigerant from the chiller, which is not only very effective in remove the heat from the
VFD, but it is also always available when the cooling is required.
All the components and the connections of the VFD have been specifically engineered to operate properly with
the vibration levels determined by the compressor operation. To prove the reliability and the resilience of the
VFD an extensive testing campaign has been carried out both in laboratory and on real chiller plant applications.
Most commonly used VFD are air cooled type. In this case the cooling vector is the air from the surroundings.
The capacity of the air to cool the VFD depends on his characteristics such as temperature and density. This are
influenced by the installation’s conditions such as altitude, ambient temperature (which could be affected also
by hot air recirculation phenomenon).
4
GENERAL CHARACTERISTICS
For this reason, according to the ambient condition, some restrictions must be considered for air cooled VFDs.
The power and so the current that the inverter can manage is subject to derating according temperature and
altitude as per the graphs below.
Some applications are provided with glycol cooled VFDs. In that cases the heat from the inverter is removed by
glycol mixture moving into a loop between the electrical panel (where the VFD components are) removing the
heat and rejecting that heat to the ambient trough a heat exchanger in contact with the ambient air. It is clear
also that the effectiveness of this system is influenced by the ambient conditions as well as the direct air-cooled
system (it is not possible to have the glycol coolant below the air temperature) with additional complications.
The glycol mixture is pushed trough the cooling loop by a dedicated pump which is a sensitive component
requiring dedicated maintenance. The glycol mixture quality must stay strictly within the parameters indicate
by the supplier otherwise the seals of the pump could be easily corroded.
In case of DAIKIN refrigerant cooled VFD the operation is not affected by the environment conditions such as
ambient temperature, altitude or air quality (presence of pollutant, dust or sand)
DAIKIN
Air Glycol
Technology Refrigerant
Cooled Cooled
Cooled
Influenced by environmental conditions
YES YES NO
(temperature, altitude, pollution)
External components needed for the VFD
YES YES NO
cooling
VFD cooling system needs dedicated
YES YES NO
maintenance
Massively introduced on the market back in 2013, the VFD developed by DAIKIN is, nowadays, successfully
applied in hundreds of chillers installations all over the world.
5
GENERAL CHARACTERISTICS
Refrigerant DAIKIN TZC is designed to operate with both R1234ze and R134a. Both are ecological refrigerant
with zero ODP (Ozone Depletion Potential) but with different GWP (Global Warming Potential) index. R1234ze
and R134a are Greenhouse gases, meaning that they absorb and emit radiant energy within the thermal infrared
range. The Greenhouse gases cause the well-known Greenhouse effect. One of the primary greenhouse gases
in the atmosphere is carbon dioxide. Basically, greenhouse gases (GHGs) warm the Earth by absorbing energy
and slowing the rate at which the energy escapes to space, acting like a blanket insulating the Earth. The Global
Warming Potential is a measure of how much energy the emissions of 1 ton of a gas will absorb over a given
period (usually 100 years is considered), relative to the emissions of 1 ton of carbon dioxide. The larger the
GWP, the more that a given GHG warms the Earth compared to carbon dioxide over that time.
The European Union aims to reduce the environmental impact of fluorinated gases via regulation. The first f-gas
regulation EC 842/2006 focused on reducing emissions mostly by preventing leaks in systems and enforcing
responsible end-of-life recovery and destruction of these gases. The European Union has recently published an
updated F-gas regulation (517/2014). This regulation entered into force from 1st January 2015, replacing the
previous version (842/2006) includes among the phase down of HFC refrigerants.
Considering the overall quantity of HFC supplied to Europe in 2015 (100%) the phase down program aims to reduce
that quantity down to 21% by 2030. Is important to note that: HFCs refrigerants are not banned but phased down.
DAIKIN TZC is available with both HFO and HFC refrigerant with same efficiency levels and options:
6
GENERAL CHARACTERISTICS
Additional information related to F-GAS Regulation (EU) No 517/2014 OF THE European Parliament
and of the Council of 16 April 2014 on fluorinated greenhouse gases and repealing Regulation (EC)
No 842/2006
Note: the refrigerant charge is subject to change. Refer to the unit nameplate for actual unit
refrigerant charge
7
GENERAL CHARACTERISTICS
Evaporator (Shell & Tube) The units are equipped with a direct expansion shell & tube evaporator with
refrigerant evaporating inside the tubes and water flowing in the shell. The tubes are enhanced for maximum
heat transfer and rolled into steel tube sheet and sealed.
The evaporators are single-pass on both refrigerant and water sides for pure counter-flow heat exchange and
low refrigerant pressure drops. Both attributes contribute to the heat exchanger effectiveness and total unit’s
outstanding efficiency.
The water side is designed for 10 bar of maximum operating pressure and is provided with vents and drain. The
external shell is covered with a 20mm closed cell insulation material and the evaporator water connections are
provided with Victaulic kit (as standard). Each evaporator has 2 circuits, one for each compressor and is
manufactured in accordance to European standards. Flow switch to detect water flow rate is available as option
(shipped loose). Strainers are available as option from the factory. Note: the installation of the strainer is
mandatory.
The reduced quantity of refrigerant allowed by using direct expansion type evaporator makes possible for the
unit to perform the pump down when stopped storing the refrigerant inside the condensing section. The same
is not possible for units equipped with flooded evaporator due to the much higher quantity of refrigerant inside
the chiller.
Electronic expansion valves the unit is equipped with the most advanced electronic expansion valves to
achieve precise control of refrigerant mass flow. As today’s system requires improved energy efficiency, tighter
temperature control, wider range of operating conditions and incorporate features like remote monitoring and
diagnostics, the application of electronic expansion valves becomes mandatory.
Electronic expansion valves possess unique features: short opening and closing time, high resolution, positive
shut-off function to eliminate use of additional solenoid valve, continuous modulation of mass flow without stress
in the refrigerant circuit and corrosion resistance stainless steel body.
Electronic expansion valves are typically working with lower ΔP between high-pressure and low-pressure side,
than a thermostatic expansion valve. The electronic expansion valve allows the system to work with low
condenser pressure (winter time) without any refrigerant flow problems and with a perfect chilled water leaving
temperature control. The economizer circuit is also controlled by an electronic expansion valve.
8
GENERAL CHARACTERISTICS
Condenser assembly the condenser assembly is composed of full aluminum heat exchangers and the new fan
designed by DAIKIN.
The condenser fans are propeller type with high efficiency design blades to maximize performances. The
material of the blades is glass-reinforced resin and each fan is protected by a guard. The advanced composite
material has been tested to withstand UV light, heat, and humidity corrosion in some of the most severe climates
in the world. Fan motors are internally protected from over temperature and are IP54. Insulation class F.
The fans are provided as standard with AC motors, with ON/OFF or INVERTER control according to the version
and the options selected. As option is possible to equip the unit with brushless motors for fans.
Refer to the option description chapter and price list.
Standard Chiller performances refers to the unit with free discharge (no additional pressure drops on the
condenser outlet), without ducts and in observance of the chiller installation prescriptions. As option is possible
to equip the unit with powerful fan’s motors to ensure proper airflow through the condenser coil with additional
pressure drops up to 200 Pa. Refer to Options chapter for more details.
9
GENERAL CHARACTERISTICS
Refrigerant circuit Each unit has 2 independent refrigerant circuits and each one includes:
• Compressor with integrated oil separator
• Refrigerant
• Evaporator
• Air Cooled Condenser
• Electronic expansion valve
• Discharge line shut off valve
• Sight glass with moisture indicator
• Filter drier
• Charging valves
• High pressure switch
• High pressure transducers
• Low pressure transducers
• Oil pressure transducer
• Suction temperature sensor
Electrical control panel Power and control are located in the main panel that is manufactured to ensure
protection against all weather conditions. The electrical panel is IP54 and (when opening the doors) internally
protected against possible accidental contact with live parts. The main panel is fitted with a main switch interlocked
door that shuts off power supply when opening.
Power Section The power section includes compressors and fans protection devices, fans starters and control
circuit power supply.
10
GENERAL CHARACTERISTICS
MicroTech 4 controller
The new MicroTech 4 controller is installed as standard in all Daikin chillers.
It gives the possibility to check the most relevant control parameters and modify unit set-points. A built-in display
shows unit operating status. Additionally, temperatures and pressures of water, refrigerant and air, programmable
values, set-points can be accessed based on a preset list of user profiles.
A sophisticated software with adaptive logic, selects the most energy efficient combination of compressors, EEXV
and fans to keep stable operating conditions to maximize unit energy efficiency and reliability. MicroTech 4 protects
critical components based on external signals from onboard sub-system (such as motor temperatures, refrigerant
and oil pressures and temperatures, correctness of phase sequence, pressure switches and freezing of heat
exchanger).
The input coming from high-pressure switches cuts all digital output from the controller in less than 50ms, as an
additional security for the equipment. Fast program cycle (less than 200ms) for a precise monitoring of the system
and sub-systems. Floating point calculations supported for increased accuracy in Pressure / Temperature
conversions.
11
GENERAL CHARACTERISTICS
System security
The following securities are available:
• phase monitor;
• low ambient temperature lock-out;
• freeze protection.
Regulation type
Proportional integral derivative regulation on the cold heat exchanger leaving water output probe.
MicroTech 4
MicroTech 4 built-in terminal has the following features:
• Liquid crystal display with white back lighting, supports Unicode fonts for multi-lingual;
• Key-pad consisting of 3 keys;
• Push’n’roll control for an increased usability;
• Flash memory to protect the data;
• Password access to modify the setting;
• Application security to prevent application tampering or hardware usability with third party applications;
• Alarm history memory to allow an easy fault analysis.
12
GENERAL CHARACTERISTICS
Nomenclature
13
OPTIONS
Phase monitor (opt. code 13 – provided as standard) Device that monitors input voltage and stops the
chiller in case of phase loss or wrong phase sequence.
20mm evaporator insulation (opt. code 29 – provided as standard) The external shell is covered with a
20mm closed cell insulation material.
Discharge line shut-off valve (opt. code 61 – provided as standard) Installed on the discharge port of
the compressor to facilitate maintenance operation.
Set point reset, demand limit and alarm from external device (opt. code 90 – provided as standard)
The options can be enabled on the unit controller:
Setpoint Reset: The leaving water temperature set-point can be overwritten with an external 4- 20mA, through
the ambient temperature, or through the evaporator water temperature ΔT.
The active setpoint is calculated applying a correction which is a function of ambient temperature (OAT). As
temperature drops below the Start Reset OAT (SROAT), LWT setpoint is gradually increased until OAT reaches
the Max Reset OAT value (MROAT). Beyond this value, the LWT setpoint is increased by the Max Reset (MR)
value.
Demand Limit: Chiller capacity can be limited through an external 4-20mA signal or via network.
Demand limit function allows the unit to be limited to a specified maximum load. Capacity limit level is defined
with an external 4-20 mA signal and linear relationship. 4 mA indicate maximum capacity available whereas 20
mA indicates minimum capacity available. With demand limit function is not possible shutdown the unit but only
unload it until minimum admissible capacity. Demand limit related setpoints available through this menu are listed
in the table below.
14
OPTIONS
Alarm from external device: The unit controller is able to receive an external alarm signal. The user can decide
whether this alarm signal will stop the unit or not.
Evaporator electric heater (opt. code 57) 125W electric heater, controlled by a thermostat (heater is
activated if water temperature is <4°C) and installed in the evaporator.
Fans circuit breakers (opt. code 96 – provided as standard) Safety devices that, added to the standard
protection devices, protect fan motors against overload and overcurrent.
NOTE: to achieve noise reduction at part load the unit must be equipped with a variable speed fans control (FANS
SPEED REGULATION -INVERTER, EC motors fans, 100 PA ESP, 200 ESP fans)
Time Scheduler
Unit On/Off can be managed automatically through the function Time Scheduler enabled when the parameter
Unit Enable is set to Scheduler 0. For each day of the week user can define six time slots and choose for each
time slot if the unit must be OFF or active and for the active mode choose which of the two setpoints to follow.
(refer to the User Manual for more details).
15
OPTIONS
M/S can:
• Control systems combining EWA(H)(D)~TZ (Daikin fix speed screw Air Cooled chiller) with EWAD~T-
(Daikin Inverter Screw Air Cooled chiller).
For all the above cases the option Intelligent Chiller Manager (iCM) Standard must be provided.
The option 143 Variable Primary Flow is not compatible with ICM Standard.
To operate with Variable Primary flow in multiple chiller Plants iCM Standard must be provided.
To operate with Variable Flow on based deltaT in multiple chiller Plants iCM Standard must be provided.
Standard chiller capacity control is based on the evaporating leaving water temperature. To keep the same control
in case of units connected in M/S an additional temperature sensor must be installed on the common line of the
hydraulic circuit and connected to the Master unit. The temperature sensor can be an NTC10K or PT1000. The
temperature sensor is not provided by the factory).
In case no additional probe is installed is possible to activate the control based on the entering water temperature.
Once set which unit has the role of master, the other(s) will operate as slave(s) based on the inputs provided by
the master.
16
OPTIONS
Options on request
Total Heat Recovery (opt. code 01) A plate to plate heat exchanger for each refrigerant circuit is installed
directly in series to the air condenser coil, thus, compressor discharged refrigerant is always flowing through the
heat recovery exchanger and warm water production is always available while the chiller is providing cooling.
A plate to plate heat exchanger for each refrigerant circuit is installed in series to the air condenser coil. There
is no switch nor solenoid valve in the circuit, thus compressor discharged refrigerant is always flowing through
the heat recovery exchanger and warm water production is always available while the chiller is providing cooling.
The amount of heat recovered is about the 80/85% of the total heat rejection of the chiller (the actual amount
of the available heat rejection recovered depends on the operating conditions). When heating capacity is required
the unit ‘s controller starts to manage the condensing pressure, according to the required set point for the hot
water, acting on the airflow for the condensing section. The heating available for heat recovery is a result of the
cooling operation. No heating is available when cooling is not requested.
17
OPTIONS
The Total heat recovery function operate according the following scheme:
The thermostat (filed supply) detects when heating energy is required from the user. Once the water
temperature to the HOT USER goes below the set-point, a signal (1) is sent to activate the heat recovery pump
(2) and to the unit controller (3) enabling the HEAT RECOVERY MODE. The unit controller modulates the valve
according the to the temperature entering the heat recovery exchanger. The valve must be positioned as
mixing valve. Once the controller switch to HEAT RECOVERY MODE it starts to compare the inlet temperature
to the plate heat exchanger with the set-point given to the unit controller; if the temperature goes below that
setpoint unit starts to manage the entering water temperature (8). The capacity of the unit is anyway managed
by the controller (7) based on the outlet temperature from the evaporator (6). The heating capacity is a
percentage of the whole heat rejection resulting from the chiller operation and is available only when cooling
capacity is requested at the same time.
The mixing valve must be installed to avoid cold water entering the heat recovery exchanger. The valve (not
provided by the factory) must a be a continuously modulated type. The signal for the modulation is provided
by the chiller (4) (0-10V signal). The modulation of the valve is based on the entering water temperature to
the heat recovery exchanger.
When heat recovery is ON the unit efficiency to consider is not the EER (Energy Efficiency Ratio) which refers
only to the cooling effect of the unit. With heat recovery the unit is also providing heating energy that otherwise
should still be provided by another source.
The Total Efficiency Ratio is defined as:
Total Heat Recovery (THR) option affects the cooling performances of the unit according the ambient
temperature and the hot water temperature requested. Check for the unit performances in the Chiller Selection
Software.
18
OPTIONS
Partial Heat Recovery (opt. code 03 – NOT AVAILABLE FOR EWAH~TZ-C units)
A plate to plate heat exchanger for each refrigerant circuit is installed in series to the air condenser coil. There
is no switch nor solenoid valve in the circuit, thus compressor discharged refrigerant is always flowing through
the heat recovery exchanger and warm water production is always available while the chiller is providing cooling.
The unit layout is similar to the one with OPT01; the plate heat exchanger placed at the compressor discharge
is smaller compare to the one used for total heat recovery and the heating capacity available is only the one
related to the over-heated vapor.
The amount of heat recovered is about the 15/20% (according to the operating conditions) of the total heat
rejection of the chiller. Heat recovery capability is subject to cooling load demand (if no cooling demand is
present then no heat recovery is available) and strongly affected by the ambient temperature and requested
hot water temperature. Differently from option Total Heat Recovery, the unit controller does not manage the
condensing temperature in partial heat recover operation. The heat recovery operation must be managed from
the plant manager that controls the pump on the recovery circuit. Also, when Partial Heat Recovery is ON the
efficiency of the chiller is represented by TER and not simply by EER.
Brine Version (opt. code 08) For operation with temperature at the outlet of the evaporator below 4°C, the
unit must operate with glycol mixture (with ethylene or propylene glycol) and the Brine Version option must be
selected. The option provides dedicated control function, optimized evaporator and additional insulation on heat
exchanger and piping.
Compressor suction insulation (opt. code 176) to improve aesthetics avoiding moisture on compressor’s
suction (coldest part).
Evaporator Victaulic KIT (opt. code 20) Victaulic kit includes the Victaulic joint and the counter pipe fitted
with Victaulic groove to be welded with the plant pipes.
Evaporator flange KIT (opt. code 21) The flange kit includes flange, counter-flange and gaskets, bolted
together with fasteners and nuts.
Suction line shut-off valve (opt. code 62) Installed on the suction port of the compressor to facilitate
maintenance operation.
SOUND PROOF SYSTEM (COMPRESSOR) (opt. code 76b) Selecting this option the unit is provided with
compressors enclosure for enhanced protection of the compressors, acoustic attenuation and improve aesthetics of
the unit. In addition to the compressor enclosure, a flexible joint is inserted on compressor suction line significantly
reduces the transmission of the vibration from the compressor to the chiller structure.
For information on sound performances for the unit with option 76b refer to Specification table or to Chiller Selection
Software
19
OPTIONS
E-coating microchannel coils (opt. code 139) As protection, a layer of an epoxy polymer is added on the
surface of the exchanger. The process consists in the complete immersion of the exchanger in the epoxy polymer
solution. An electric voltage applied to the exchanger causes a difference with the electrical charge of the polymer
molecules that, as result, are drawn to the metal. The thickness of the coating is controlled by the applied
voltage. The result is a uniform layer of epoxy polymers applied all over the exchanger surface. A final UV top-
coat treatment is applied on the coil surf
The treatment is recommended in all application where high risk of corrosion exist (e.g.: high polluted urban,
costal, industrial environments and their combinations).
In the table below, technical properties of the treatment are described:
20
OPTIONS
Unit guards (to cover unit access) (opt. code 140) Wire mesh that covers the access all around the unit
Side panels on coil ends (opt. code 141) Protection carter on both side of each condensing module.
Unit right water connection (opt. code 101) Provides water connection on the right side.
21
OPTIONS
Water filter - Victaulic connections (opt. code 115) to prevent damages to the water heat exchanger due
to the presence of particles in the water a filter must be installed.
With option 115 a water filter is shipped loose with the unit. Is customer responsibility to properly install and
maintain the water filter.
To be affective the filter must be installed at the entering of the unit;
DO NOT REVERSE the water inlet and outlet of the filter (see Installation notes for more details).
The inside taper filter cartridge is made of stainless steel 304, thickness 1.5 mm, holes diameter 5.5 mm, distance
between two holes 6.5mm, are per centum 64,4%.
Filter screen is made of 304, max passage 0.5 mm.
NOTE: the installation of the filter is mandatory either if supplied by DAIKIN or from third part supplier.
Proper filter cleaning and maintenance is key to ensure chiller operation.
The pressure drop across the water filter provided by DAIKIN are given by the following formula:
Connection diameter a b
[mm]
114 0.00417 1.954
140 0.00128 2.002
168 0.00065 1.928
219 0.00026 2.011
273 0.00009 1.974
Evaporator flow switch (opt. code 58) Paddle type. Supplied separately to be wired and installed on the
evaporator water piping (by the customer). The installation of the flow switch is mandatory.
22
OPTIONS
Is possible to equip the unit with a hydronic kit. There are 4 possible configurations:
The kit is completed with pressure gauge, safety valve, drain valve. The motor pump is protected by a circuit
breaker installed in control panel. The kit is assembled and wired to the control panel. The pipe and pump are
protected from freezing with an additional electrical heater.
Low lift version provides an average available head of about 100÷150 kPa or more at chiller standard conditions.
High lift version provides an average available head of about 200÷250 kPa or more at unit standard conditions.
Please refer to the relative graphs in the " Options (Technical data)" chapter.
Note: In case of unit equipped with hydronic kit on board selected to operate with over 30% of propylene glycol
mixture contact factory.
- Inverter kit for 1 centrifugal pump Low lift (opt. code 120e)
- Inverter kit for 1 centrifugal pump High lift (opt. code 120f)
- Inverter kit for 2 centrifugal pumps Low lift (opt. code 120g)
- Inverter kit for 2 centrifugal pumps High lift (opt. code 120h)
Note: The Inverter kit must be associated with the corresponding hydronic kit (opt. code 78/79/80/81).
- Control the pump speed via external input from Building Management System (BMS)
For this application, a 0-10V signal to control the pump speed must be provided from the plant manager according
to the specific control strategy of the plant. The water must be within the minimum and maximum value allowed
for the unit (refer to the Technical specifications and to the “Operating limit” chapter). The change in water flow
rate must not be exceed more than 10% of the design water flow rate per minute.
Thanks to the saving on pumping cost, the payback time for the Inverter Kit is approximately one year.
23
OPTIONS
- Control variable flow on primary loop based on chiller delta-T (available as standard for single chiller installation only)
Providing the unit with the inverter kit for the on-board pump it is possible to manage a variable water flow rate
for the primary loop. This function is available as standard when the hydronic kit plus inverter are selected.
The standard feature is applicable for single unit installation only. In case of multiple chillers installation an
additional control is needed.
The variable flow control is suitable for primary/secondary plant, cannot be used in primary plant only.
In a Primary-Secondary plant configuration a key component is the decoupler. The decoupler is always open (no
valve must be installed). The aim of the decoupler is to allows the primary and secondary pumps to operate at
different flow rates. This is necessary because the primary pumps and secondary pumps are managed differently
and so the primary and secondary flow rate are practically never the same. Specifically, the primary flow rate is
managed based on the chiller delta-T (Tout - Tin) the secondary flow rate is regulated to maintain the necessary
pressure differential in the secondary loop. The direction of the water flow through the decoupler must be always
from supply to return. To ensure this the primary flow rate must the secondary flow rate. If this condition is not
respected the warmer return water will flow backwards through the decoupler and raise the supply water
temperature. Due to the higher temperature of the supply water temperature the terminal unit control will open
the valves asking for higher water flow rate. The secondary pumps will speed up increasing even more the water
flow rate on secondary plant making the situation even worst (secondary flow rate >> primary flow rate). As result
there will be no control on the supply water temperature losing effectiveness of the cooling plant.
On the other side any excess in the primary flow, vs. secondary flow, flows through the decoupler from the supply
to the return mixing with the warmer return water. To reach this target is very important to have minimum pressure
drop in the decoupler that needs to be sized to reach a pressure drop that should not exceed 4÷5 kPa at the
minimum for the flow rate of the primary pump.
Activating the variable flow control the chiller will modulate the water flow rate based on the chiller delta.
When the secondary loop will reduce the water flow rate (because the plant load decrease), the water flow rate in
the decoupler (always from supply to return) increases. The return water temperature mixes with the supply water
from the decoupler reducing the water temperature the inlet temperature and so the delta-T on the chiller. As
consequence the chiller control reduce the speed of the pump, reducing the primary flow rate.
On the opposite, when the flow rate on secondary flow increases also the water temperature at the chiller inlet
increase (increasing the delta-T); therefore, the chiller control will increase the water flow rate.
24
OPTIONS
For unit installed in Primary/Secondary plants the option Variable Primary Flow is not applicable. In this case a
different a different control is required.
For different kind of water flow management iCM must be provided.
To operate in Primary/Secondary plants with variable flow in primary loop the iCM must be provided.
The option 143 can be selected only together with the other hydronic kit option (see the table below).
Note: the option 143 Variable Primary Flow (VPF) is intended for a single unit installation. In case of multiple units’
system in VPF plant iCM must be provided.
A bypass line (field supply) needs to be installed to guarantee that the minimum water flow of the unit is always
supplied (refer to the “Operating limit” chapter for indication on minimum water flow). The bypass valve will be an
ON/OFF normally closed valve controlled by the unit controller. In case the minimum water flow allowed is not
reached, the unit will command the valve to open the bypass line restoring the water flow above the minimum
value.
The unit with option 143 cannot manage external variable speed pumps. For such control iCM must be provided.
25
OPTIONS
Differential Pressure Transducers - shipped loose - (opt. code 144) to be installed in a specific point of
the plant, selected by the plant designer.
Compressors circuit breakers (opt. code 95) A safety device which ensures thermal and electrical protection
against motor overcurrent (overtemperature) and overload protection. Overcurrent protection is protection
against excessive currents or current beyond the acceptable current rating of equipment. It operates instantly
when the current exceeds the overcurrent imposed the overcurrent threshold. Short circuit is a type of
overcurrent. The breaker acts practically instantly when the current reaches the threshold value, while the
thermal relay reacts with a timing related to the percentage of over-load.
Energy meter (including current limit) (opt. code 16a) Device installed inside the control box that displays
all chiller electrical power parameters at line input such as line voltage and phase current, input active and
reactive power, active and reactive energy, including current limit option. An integrated RS485 module allows a
Modbus communication to an external BMS.
Current limit function allows to control unit power consumption taking current drawn below a specific limit.
Starting from the Current Limit Setpoint defined through the HMI or BAS communication, user can decrease the
real limit using an external 4-20mA signal as indicate in the graph below. With 20 mA real current limit is set to
Current Limit Setpoint, whereas with 4 mA signal the unit is unloaded until minimum capacity.
Ground fault relay (opt. code 102) To shut down the entire unit if a ground fault condition is detected.
Rapid restart (opt. code 110) Rapid Restart is the ideal solution for those application where we cannot afford
the loose of cooling such as data centers, health care facilities, process cooling …etc. For this kind of applications,
in case of a power failure, chiller equipment is required to restore the cooling supply to the system as fast as
possible. Standard unit (without the Rapid Restart option) will be starting within 310 seconds after the power is
restored and it will be reaching full load cooling capacity within 20 ÷ 25 minutes (obviously depending on the
load demand). Rapid Restart is allowing the chiller to start as fast as 30 seconds after power is restored and to
reach full load cooling capacity in less than 3 minutes from the unit restart.
For more details about this option please refer to the Control Manual.
With Rapid Restart option the unit controller is always powered by UPS unit and dedicated control logic allows
to achieve the full load capacity in short time.
26
OPTIONS
ModBus RTU MSTP (opt. code 180) The option enables the communication protocol Modbus RTU Master
BACNet MSTP (opt. code 181) The option enables the communication protocol BACnet MSTP
BACNet IP (opt. code 182) The option enables the communication protocol BACnet IP
High ambient kit (opt. code 142) The high ambient kit must be selected in case of installations where design
condition is at 46°C ambient temperature and above.
Since mechanical switches are derated based on their load and the operational temperature, in case of operation
at high ambient temperature, the unit is provided with oversized electrical equipment (e.g. main switch, fuses,
cables) with the aim to increase reliability and components operating life. In addition to oversized electrical
equipment other measures are taken to maximize the reliability and operating life of the components in the
electrical box, such as: enhanced ventilation (depending on the model), and sunshields.
NOTE: option 142 is not compatible with option 99a
27
OPTIONS
28
OPTIONS
In addition to the functionalities provided by Master/Slave with iCM Standard is possible to:
• Control mixed systems:
o Chiller + Heat Pump
o Chiller + multipurpose
• Manage manifolded pumps
• Manage the unit operation enhancing the system efficiency.
This functionality allows to further increase the system efficiency by setting different thresholds to share
the load among the units installed in the most efficient configuration.
All the information from the slave’s controller are available on the master unit’s controller.
29
OPTIONS
30
OPTIONS
The accuracy of the performance monitoring is -/+ 5% at nominal condition and -/+ 10% for all other conditions.
The performance monitoring system must be activated by selecting the opt. 186. As alternative all the information
provided by the Performance Monitoring system are available is chiller is connected on Daikin On Site.
The subscription to DoS includes the visualization of above parameters in a dedicated dashboard.
Installation options
Rubber anti vibration mounts (opt. code 75) Supplied separately, these are positioned under the base of
the unit during installation. Ideal to reduce the vibrations when the unit is floor mounted.
Spring anti vibration mounts (opt. code 77) Supplied separately, these are positioned under the base of the
unit during installation. Ideal for dampening vibrations for installation on roofs and metallic structures.
Other options
Transport kit (opt. code 71)
31
OPTIONS
Applications
DAIKIN TZ C range can be applied to supply chilled water or brine mixture in a wide range of temperatures at
different ambient conditions. A proper chiller selection is key to achieve effective and reliable system operation.
The unit must be selected according to the specific requirements for the project. Do not intentionally oversize the
unit at design condition to ensure cooling capacity. An oversized chiller will be subject to frequent compressors
cycling leading to inefficient operation.
In case an oversized system is required for the project, propose two smaller chillers connected in ICM Standard
control.
Some application could require water flow rate through the exchanger out of the allowed limits.
The limits for the water flow rate are defined as follow:
Where:
NOTE: the direction of the flow must be always from supply to return. With the flow in the opposite direction, the
chilled water supply temperature in the secondary loop will rise to unacceptable levels.
32
OPTIONS
If only the entering water temperature is outside the limit the previous scheme can be applied (single decoupler)
paying attention to fix the proper water flow rate on primary circuit and dimensioning the decoupler accordingly.
Most of the chiller installation requires, in addition to chilled water, also heated water. The hot water can be used
to post eat air in AHU’s, for preparation of Sanitary Hot Water, and many other applications.
As explained in the option description, the heating is available only when the chiller is providing chilled water; for
this reason, the evaluation of the actual heating capacity available requires also the information on the cooling load.
In case of multiple chillers plant involving heat recovery chillers and standard chillers a proper plant configuration
can be used to better exploit the heat recovery capability to enhance the system efficiency.
33
OPTIONS
With external BMS or using the set-point reset function is possible to modulate the cooling capacity to the one
corresponding to the actual heating need. The extra cooling capacity which cannot be delivered by the heat recovery
chiller, will be transferred to the standard chillers in the production loop. This will optimize the energy usage of the
entire chiller plant and the heat recovery operation will be limited to exactly the heating need.
34
OPTIONS
Compare to previous layout (heat recovery chiller in parallel positioned on distribution side) the Side stream
configuration allows to control the heat recovery chiller on the hot energy needed, without effect on the supply
water temperature. To optimized system operation the heat recovery chiller should be selected based on the heating
capacity at full load. For the heat recovery chiller in this application the cooling capacity represents the side effect
of the heating operation. The cooling only chiller in the production line must be able to provide the extra cooling
capacity needed when minimum heating capacity is required. In case cooling load required is much higher than the
heating load a cheaper and affective solution could be to use of a water to water heat pump installed Side stream
on the cooling loop.
The heat pump selected based on the heating capacity will modulate the capacity according the heating load.
35
OPTIONS
In case of units of same sizes there is no practical reason to assign different priorities to the units, while in case of
system combining unit with different sizes or VFD screw chillers (DAIKIN TZC) with fix speed screw chillers (DAIKIN
T-B) to optimize the efficiency it may be needed. For this situation in possible to assign priorities to the units
connected
The thermostat control for DAIKIN units is by default on the Evaporator Leaving Water Temperature (ELWT).
In iCM Standard system the default thermostat control is also on the leaving water temperature. To keep this
function an additional temperature sensor must be installed and connected to the master unit. on the common
line of the hydraulic circuit and connected to the Master unit. The temperature sensor can be an NTC10K or
PT1000. The temperature sensor is not provided by the factory.
As alternative is possible to enable the thermostat control on Evaporating Entering Water Temperature (EEWT). In
this case there is no need of additional temperature sensor.
36
OPTIONS
Once chosen the control method (based on ELWT or EEWT) is possible to manage the thermostat control from the
HMI interface on the Master units.
For detailed description of all the settings refer to the user manual.
The Threshold parameter allows to assign a load threshold that each unit must reach before starting a new chiller.
The default value is 60%, is possible to set value from 30% up to 100%. Lower the threshold, higher will be the
number of the active chillers sharing equally the cooling demand, while with threshold at 100% the chiller will
operate in pure staging. Each chiller needs to run at 100% before to start the next chiller. With this setting the
number of active chillers is minimized.
The below graphs show a schematic of the sharing and staging operation. The example is based on a system with
3 TZ C units of same capacity (no priority assigned).
With the threshold at 30%, the first chiller starts at 17°C, as the required load increases the chiller charges until it
reaches the 30% of his capacity (which happens at 18°C). Since the 1 chiller has reached the load threshold, the
second chiller starts. The first chiller keeps the capacity at 30% while the second chillers charges until it also reaches
the 30 % of the load (in the example occurs at 21°C). Than also the third chiller is starts. The others keep the
capacity at 30% until also the third chiller reaches the 30% capacity. From that point the chillers charge all together,
sharing equally the required load up to 100%.
Whit this strategy the number of active chillers is maximized, and the chillers operate most of the time at part load.
37
OPTIONS
Setting the load threshold at 100% the system controls will be pure staging. The next unit is not started until the
units already running have reached 100% of their capacity. With this setting the number of units ON is minimized.
The evaluation of the optimum threshold value should consider different factors such as:
• Chiller type (VFD or fixed speed) and so their part load efficiency
• Number of units involved and sizes (all same size or different sizes)
• Eventual assigned priorities
• Cold loop layout (primary/secondary or only primary) and management (fix or variable water flow rate)
Another important aspect to be evaluated is the load required over the climatic profile of the specific installation.
The graph below shows a typical energy profile required for comfort cooling application.
38
OPTIONS
The same cooling profile con be represented over the temperatures, together with the indication of how many hours
each temperature recurs during the year.
From the above graph is possible to evaluate how the system will operate and so, identify the most recurring
condition. Knowing how the cooling load is distributed throughout the season is possible to set the system reaching
the highest frequency possible for the most recurring condition.
To better understand we can try three different sequencing strategies:
The plant considered is for 3 units of same size 1 MW each. The pumps on primary plant are fixed speed Each chiller
enable the related pump when is called to start. Pressure drop on primary loop equal to 100 kPa with the 3 chillers
ON.
The below graph shows the trend of the power input for the pumps on the primary loop according to the number
of active chillers
39
OPTIONS
The following graph and table show the efficiency trend and the resulting energy consumption over the cooling
season for the different threshold values
40
OPTIONS
The efficiency trend over the temperature shows how the different thresholds used for the ICM Standard sequencing
gives different results. The energy consumption over the full cooling season for the primary plant (chillers + primary
pumps) reduces from 738646 kWh down to 651813 kWh modifying the threshold.
Same components (chillers and pumps) gives much lower energy consumption, and so lower running costs, just
setting the right threshold.
From going from 100% to 60% of threshold the increase in efficiency in noticeable, while going down from 60 to
30% the difference in much lower. This difference is strongly affected by the pumping energy. In case of higher
pressure drops on primary loop the difference would be even lower or in favor of the 60%. While a system with
variable flow would give higher benefits to a configuration with 30% threshold.
A proper evaluation of the pumping energy costs is key to find the best threshold set.
Many additional factors can be considered to achieve even higher energy savings like:
41
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 101 101 102 103 104 105
Sound Pressure @ 1 m (1) (9) dB(A) 80 80 80 81 82 82
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 120 130 141 150 175
42
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 106 107 105 106 107 108
Sound Pressure @ 1 m (1) (9) dB(A) 83 84 83 83 84 85
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 200 220 200 220 250 270
43
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 120 130 141 150 175
44
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 102 103 102 102 103 104
Sound Pressure @ 1 m (1) (9) dB(A) 79 80 79 79 80 80
Sound Power + opt76b (1) (8) dB(A) 100 101 100 100 101 101
Sound Pressure @ 1 m + opt76b (1) (9) dB(A) 77 78 77 77 78 78
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 200 220 250 270
45
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 120 130 141 150 175
46
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 200 220 250 270
47
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 130 141 175 200 220
48
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 250 270
49
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 130 141 175 200 220
50
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 250 270
51
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 130 141 175 200 220
52
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 250 270
53
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 102 103 104 104 105 105
Sound Pressure @ 1 m (1) (9) dB(A) 80 81 82 81 82 82
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 175 200 200 220 250
54
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270 270
55
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 100 100 101 101 101 102
Sound Pressure @ 1 m (1) (9) dB(A) 77 78 78 78 79 79
Sound Power + opt76b (1) (8) dB(A) 99 99 100 100 100 100
Sound Pressure @ 1 m + opt76b (1) (9) dB(A) 77 77 77 77 77 77
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 175 200 200 220 250
56
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270 270
57
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 175 200 200 220 250
58
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270 270
59
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 200 220 200 220 250
60
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270
61
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 200 220 200 220 250
62
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270
63
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 101 101 102 103 104 105
Sound Pressure @ 1 m (1) (9) dB(A) 80 80 80 81 82 82
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 120 130 141 150 175
64
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 106 107 105 106 107 108
Sound Pressure @ 1 m (1) (9) dB(A) 83 84 83 83 84 85
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 200 220 250 270
65
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 120 130 141 150 175
66
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 102 103 102 102 103 104
Sound Pressure @ 1 m (1) (9) dB(A) 79 80 79 79 80 80
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 200 220 250 270
67
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 120 130 141 150 175
68
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 200 220 250 270
69
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 130 141 175 200 220
70
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 250 270
71
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 130 141 175 200 220
72
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 250 270
73
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 120 130 141 175 200 220
74
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2
Refrigerant type / GWP - R1234ze(E) / GWP = 7
Refrigerant Charge (11) kg 200 220 250 270
75
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 102 103 104 104 105 105
Sound Pressure @ 1 m (1) (9) dB(A) 80 81 82 81 82 82
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 175 200 200 220 250
76
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270 270
77
TECHNICAL SPECIFICATIONS
Sound Power (1) (8) dB(A) 100 100 101 101 101 102
Sound Pressure @ 1 m (1) (9) dB(A) 77 78 78 78 79 79
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 175 200 200 220 250
78
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270 270
79
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 175 200 200 220 250
80
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270 270
81
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430 NA
Refrigerant Charge (11) kg 175 200 220
82
TECHNICAL SPECIFICATIONS
Evaporator type -
Water flow rate (1) l/s
Evaporator pressure drop (1) (7) kPa NA
Evaporator water volume (8) lt
Minimum water rate (6) l/s
Fan type -
Fan diameter mm
Fan rotational speed RPM
Fan motor / control - NA
Number of fans n
Power input fans kW
Air flow (10) l/s
Refrigerant circuits n
Refrigerant type / GWP - NA
Refrigerant Charge (11) kg
Compressor type -
Capacity control -
Oil charge lt
Casing material -
Color -
Unit length mm
Unit width mm NA
Unit height mm
Unit weight - shipping kg
Unit weight - operation kg
Water connection size mm
Water connection type -
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Minimum capacity for the unit operating at Standard Rating Conditions: Operating Ambient Temperature 35°C, Evaporator, water outlet 7°C
(3) Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable
flow.
(4) the seasonal space cooling energy efficiency ηs,c is calculated as defined in Regulation (EU) 2016/2281 the seasonal energy efficiency ratio SEER divided by
the conversion coefficient CC (2.5), corrected by contributions accounting for temperature control (0.03).
(5) Seasonal energy performance Ratio as defined in Regulation (EU) 2016/2281 for a high temperature process chiller at standard rating conditions defined in
EN14511:2
(6) minimum flow rate to be reached in variable water flow system (not managed by the unit controller BMS) with unit operating at minimum load.
(7) not including filter pressure drop. The installation of the filter is mandatory.
(8) sound power level measured in accordance to ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to
EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C
(9) sound pressure level measured in accordance to ISO3744, referred to unit operating at Standard Rating Conditions for Air to water chillers according to
EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C
(10) referred to unit with free discharge on condenser fans.
(11) data subject to change. Refer to unit’s name plate for actual value.
83
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2
Refrigerant type / GWP - NA R134a / GWP = 1430
Refrigerant Charge (11) kg 200 220 250
84
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270
85
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2 2 2 2 2 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 175 200 220 200 220 250
86
TECHNICAL SPECIFICATIONS
Refrigerant circuits n 2
Refrigerant type / GWP - R134a / GWP = 1430
Refrigerant Charge (11) kg 270
87
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 408,6 433,3 493,5 521,5 549,9 579,6
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 56 56 64 72 80 88
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
88
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 612,7 668,8 718,8 780,9 848,9 934,8
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 96 104 96 104 112 120
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
89
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 408,6 433,3 493,5 521,5 549,9 579,6
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 56 56 64 72 80 88
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
90
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 612,7 668,8 718,8 780,9 848,9 934,8
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 96 104 96 104 112 120
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
91
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 414,9 446,8 505,2 529,7 554,4 581,0
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 36,4 36,4 41,6 46,8 52,0 57,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
92
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 611,1 667,2 736,4 796,5 863,9 952,0
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 62,4 67,6 62,4 67,6 72,8 78,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
93
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 373,9 431,3 459,1 513,1 544,2 604,8
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 36,4 41,6 46,8 57,2 62,4 67,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
94
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 660,3 717,4 778,2 848,9
Current
Compressor starting
Variable Frequency Drive
method
Max. running current
(6) A 388 419 451 484
Compressor #1
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
95
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 373,9 431,3 459,1 513,1 544,2 604,8
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 36,4 41,6 46,8 57,2 62,4 67,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
96
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 660,3 717,4 778,2 848,9
Current
Compressor starting
Variable Frequency Drive
method
Max. running current
(6) A 388 419 451 484
Compressor #1
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
97
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 374,9 432,6 460,2 514,2 545,4 606,0
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 36,4 41,6 46,8 57,2 62,4 67,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
98
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 670,1 725,0 783,7 853,8
Current
Compressor starting
Variable Frequency Drive
method
Max. running current
(6) A 388 419 451 484
Compressor #1
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
99
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 646,5 691,1 733,0 813,9 884,0 962,8
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 88 88 96 96 104 112
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
100
ELECTRICAL SPECIFICATIONS
101
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 646,5 691,1 733,0 813,9 884,0 962,8
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 88 88 96 96 104 112
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
102
ELECTRICAL SPECIFICATIONS
103
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 659,2 708,5 748,1 853,7 922,8 1000
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 57,2 57,2 62,4 62,4 67,6 72,8
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
104
ELECTRICAL SPECIFICATIONS
105
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 608,8 647,1 686,1 735,8 806,6 874,7
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6 2,6 2,6 4 4 4
current per fan
Total fans running
(6) A 57,2 62,4 67,6 62,4 67,6 72,8
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
106
ELECTRICAL SPECIFICATIONS
107
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 612,3 651,0 689,6 762,5 834,0 901,3
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 2,6
current per fan
Total fans running
(6) A 57,2 62,4 67,6 62,4 67,6 72,8
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
108
ELECTRICAL SPECIFICATIONS
109
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 383,7 408,6 465,1 489,5 514,2 540,2
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 29,4 29,4 33,6 37,8 42,0 46,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
110
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 569,5 622,1 676,2 734,7 799,1 881,5
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 50,4 54,6 50,4 54,6 58,8 63,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
111
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 383,7 408,6 465,1 489,5 514,2 540,2
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 29,4 29,4 33,6 37,8 42,0 46,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
112
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 569,5 622,1 676,2 734,7 799,1 881,5
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 50,4 54,6 50,4 54,6 58,8 63
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
113
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 391,3 423,1 478,2 499,3 520,8 544,1
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 14,0 14,0 16,0 18,0 20,0 22,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
114
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 570,9 623,7 695,9 752,6 816,7 901,3
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 24,0 26,0 24,0 26,0 28,0 30,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
115
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 350,3 404,3 428,9 476,3 504,1 561,4
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 14,0 16,0 18,0 22,0 24,0 26,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
116
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 614,8 668,0 724,9 791,7
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 50,4 54,6 58,8 63,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor
heat exchanger inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
117
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 350,3 404,3 428,9 476,3 504,1 561,4
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 14,0 16,0 18,0 22,0 24,0 26,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
118
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 614,8 668,0 724,9 791,7
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 50,4 54,6 58,8 63,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor
heat exchanger inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
119
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 351,3 405,7 430,0 477,4 505,4 562,6
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 14,0 16,0 18,0 22,0 24,0 26,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
120
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 629,6 681,3 736,6 803,4
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 24,0 26,0 28,0 30,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor
heat exchanger inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
121
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 607,3 652,0 690,3 771,8 838,4 913,5
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 46,2 46,2 50,4 50,4 54,6 58,8
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
122
ELECTRICAL SPECIFICATIONS
123
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 607,3 652,0 690,3 771,8 838,4 913,5
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 2,1
current per fan
Total fans running
(6) A 46,2 46,2 50,4 50,4 54,6 58,8
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
124
ELECTRICAL SPECIFICATIONS
125
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A NA 690,6 757,6 821,8
Current
Max. running
(3) A 1085 1124 1218
current
Max. current for
(4) A NA 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A NA 2,1
current per fan
Total fans running
(6) A 50,4 54,6 58,8
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 440 480 521
NA
Compressor #1
Max. running
current (6) A 440 480 521
Compressor #2
Short circuit
(6) kA 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
126
ELECTRICAL SPECIFICATIONS
127
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 622,0 671,3 707,6 812,7 878,4 952,3
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 22,0 22,0 24,0 24,0 26,0 28,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
128
ELECTRICAL SPECIFICATIONS
129
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 571,7 606,7 642,4 NA
Current
Max. running
(3) A 918 939 994
current
Max. current for
(4) A 1010 1033 1093 NA
wire sizing
Maximum starting
(5) A 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0 NA
current per fan
Total fans running
(6) A 22,0 24,0 26,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388
NA
Compressor #1
Max. running
current (6) A 370 367 388
Compressor #2
Short circuit
(6) kA 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
130
ELECTRICAL SPECIFICATIONS
131
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 575,3 610,6 646,0 721,7 789,8 853,8
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 1,0
current per fan
Total fans running
(6) A 22,0 24,0 26,0 24,0 26,0 28,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
132
ELECTRICAL SPECIFICATIONS
133
ELECTRICAL SPECIFICATIONS
EWAH~TZ- SS C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes 710 770 880 940 990 H10
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 408,6 433,3 493,5 521,5 549,9 579,6
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 56 56 64 72 80 88
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 1000 1000 1000 1250 1250 1250
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x300 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
134
ELECTRICAL SPECIFICATIONS
EWAH~TZ- SS C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes C11 C12 C13 C14 C15 C16
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 612,7 668,8 718,8 780,9 848,9 934,8
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 96 104 96 104 112 120
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1600 1600 1600 1600 2000 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
135
ELECTRICAL SPECIFICATIONS
EWAH~TZ- SL C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes 710 770 880 940 990 H10
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 408,6 433,3 493,5 521,5 549,9 579,6
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 56 56 64 72 80 88
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 1000 1000 1000 1250 1250 1250
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x300 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
136
ELECTRICAL SPECIFICATIONS
EWAH~TZ- SL C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes C11 C12 C13 C14 C15 C16
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 612,7 668,8 718,8 780,9 848,9 934,8
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 96 104 96 104 112 120
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1600 1600 1600 1600 2000 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
137
ELECTRICAL SPECIFICATIONS
EWAH~TZ- SR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes 710 770 880 940 990 H10
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 398,0 420,3 480,1 507,9 536,5 565,6
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 51,8 51,8 59,2 66,6 74,0 81,4
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 1000 1000 1000 1250 1250 1250
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x300 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
138
ELECTRICAL SPECIFICATIONS
EWAH~TZ- SR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes C11 C12 C13 C14 C15 C16
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 598,5 653,5 698,7 759,6 827,1 910,6
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 88,8 96,2 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1600 1600 1600 1600 2000 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
139
ELECTRICAL SPECIFICATIONS
EWAH~TZ- XS C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes 670 780 840 950 C10 C11
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 357,1 414,6 444,9 504,9 538,3 597,8
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 51,8 59,2 66,6 81,4 88,8 96,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 1000 1000 1000 1250 1250 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x300 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
140
ELECTRICAL SPECIFICATIONS
EWAH~TZ- XS C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes C12 C13 C14 C15
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 636,5 692,6 752,5 821,6
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 88,8 96,2 103,6 111
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
141
ELECTRICAL SPECIFICATIONS
EWAH~TZ- XL C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes 670 780 840 950 C10 C11
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 357,1 414,6 444,9 504,9 538,3 597,8
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 51,8 59,2 66,6 81,4 88,8 96,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 1000 1000 1000 1250 1250 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x300 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
142
ELECTRICAL SPECIFICATIONS
EWAH~TZ- XL C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes C12 C13 C14 C15
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 636,5 692,6 752,5 821,6
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
143
ELECTRICAL SPECIFICATIONS
EWAH~TZ- XR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes 670 780 840 950 C10 C11
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 358,1 416 446,1 506,1 539,7 599,1
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 51,8 59,2 66,6 81,4 88,8 96,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 1000 1000 1000 1250 1250 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x300 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
144
ELECTRICAL SPECIFICATIONS
EWAH~TZ- XR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes C12 C13 C14 C15
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 638,9 694,8 755 824,1
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
145
ELECTRICAL SPECIFICATIONS
EWAD~TZ- SS C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes H11 H12 H13 C15 C16 H17
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 648,6 693,5 736,0 816,4 887,1 963,0
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 88 88 96 96 104 112
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1600 1600 1600 2000 2000 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm² 3x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
146
ELECTRICAL SPECIFICATIONS
EWAD~TZ- SS C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes H18 H19
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances min/max % -10 / +10
147
ELECTRICAL SPECIFICATIONS
EWAD~TZ- SL C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes H11 H12 H13 C15 C16 H17
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 646,5 691,1 733,0 813,9 884,0 962,8
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - D.O.L.
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 88 88 96 96 104 112
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1600 1600 1600 2000 2000 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm² 3x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
148
ELECTRICAL SPECIFICATIONS
EWAD~TZ- SL C + OPT142B – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) ON OFF FANS
MODEL notes H18 H19
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances min/max % -10 / +10
149
ELECTRICAL SPECIFICATIONS
EWAD~TZ- SR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes H11 H12 H13 C15 C16 H17
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 630,3 673,6 715,5 789,1 857,9 936,5
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 81,4 81,4 88,8 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1600 1600 1600 2000 2000 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm² 3x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
150
ELECTRICAL SPECIFICATIONS
EWAD~TZ- SR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes H18 H19
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances min/max % -10 / +10
151
ELECTRICAL SPECIFICATIONS
EWAD~TZ- XS C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes C11 C12 H12 C14 C15 H16
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 586,8 628,2 668,7 708,8 777,5 844,4
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 81,4 88,8 96,2 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1600 1600 1600 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
152
ELECTRICAL SPECIFICATIONS
EWAD~TZ- XS C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes H17
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances min/max % -10 / +10
153
ELECTRICAL SPECIFICATIONS
EWAD~TZ- XR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes C11 C12 H12 C14 C15 H16
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances
% -10 / +10
min/max
Nominal Running
(1) A 588,1 629,7 670,1 711,2 779,8 847,0
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,7
current per fan
Total fans running
(6) A 81,4 88,8 96,2 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1600 1600 1600 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
154
ELECTRICAL SPECIFICATIONS
EWAD~TZ- XR C + OPT142C – HIGH AMBIENT KIT (OPERATION ABOVE 46°C) BRS FANS
MODEL notes H17
Phases n 3
Frequency Hz 50
Voltage (2) V 400
Voltage Tolerances min/max % -10 / +10
155
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 404,6 428,8 488,6 516,4 544,4 573,8
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 51,8 51,8 59,2 66,6 74,0 81,4
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
156
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 606,4 662,1 711,4 773,1 840,7 925,9
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 88,8 96,2 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
157
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 404,6 428,8 488,6 516,4 544,4 573,8
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 51,8 51,8 59,2 66,6 74,0 81,4
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
158
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 606,4 662,1 711,4 773,1 840,7 925,9
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 88,8 96,2 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
159
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 404,4 428,6 488,2 516,2 544,1 573,5
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 51,8 51,8 59,2 66,6 74,0 81,4
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
160
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 606,1 661,8 710,9 772,6 840,1 925,3
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 88,8 96,2 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
161
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 364,6 422,8 452,9 512,8 546,3 606,5
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 51,8 59,2 66,6 81,4 88,8 96,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
162
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 650,4 706,8 767,0 836,9
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat
exchanger inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
163
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 364,6 422,8 452,9 512,8 546,3 606,5
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 51,8 59,2 66,6 81,4 88,8 96,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
164
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 650,4 706,8 767,0 836,9
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
165
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 364,4 422,6 452,7 512,5 546,0 606,2
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 51,8 59,2 66,6 81,4 88,8 96,2
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
166
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 650,0 706,4 766,5 836,4
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 88,8 96,2 103,6 111,0
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat
exchanger inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
167
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 640,1 684,5 726,1 805,6 875,3 953,6
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 81,4 81,4 88,8 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
168
ELECTRICAL SPECIFICATIONS
169
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 640,1 684,5 726,1 805,6 875,3 953,6
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 81,4 81,4 88,8 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
170
ELECTRICAL SPECIFICATIONS
171
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 663,7 710,0 752,1 841,5 912,8 992,0
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - Inverter driven motor
method
Max running
(6) A 4
current per fan
Total fans running
(6) A 88 88 96 96 104 112
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
172
ELECTRICAL SPECIFICATIONS
173
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 597,1 638,3 679 725,2 795,2 862,6
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 81,4 88,8 96,2 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
174
ELECTRICAL SPECIFICATIONS
175
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 597,1 638,3 679 725,2 795,2 862,6
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 3,70
current per fan
Total fans running
(6) A 81,4 88,8 96,2 88,8 96,2 103,6
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
176
ELECTRICAL SPECIFICATIONS
177
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 423,5 445,7 508,9 540,6 572,9 605,8
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 77 77 88 99 110 121
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
178
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 642,2 701,0 741,8 806,7 877,6 964,8
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 132 143 132 143 154 165
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
179
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 423,5 445,7 508,9 540,6 572,9 605,8
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 77 77 88 99 110 121
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
180
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 642,2 701,0 741,8 806,7 877,6 964,8
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 132 143 132 143 154 165
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
181
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 423,7 446,0 509,3 541,0 573,3 606,1
Current
Max. running
(3) A 609 640 717 763 811 869
current
Max. current for
(4) A 670 704 789 839 892 956
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 77 77 88 99 110 121
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 246 262 291 308 326 345
Compressor #1
Max. running
current (6) A 246 262 291 308 326 345
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
182
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 642,6 701,4 742,4 807,2 878,2 965,5
Current
Max. running
(3) A 924 1032 1029 1119 1198 1226
current
Max. current for
(4) A 1016 1135 1132 1231 1318 1349
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 132 143 132 143 154 165
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 415 419 451 484 518
Compressor #1
Max. running
current (6) A 367 415 419 451 484 518
Compressor #2
Main switch size (6) A 1250 1250 1600 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
183
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 383,6 445,0 478,9 546,4 583,5 646,7
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 77 88 99 121 132 143
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
184
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 682,2 742,0 805,6 878,5
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Compressor starting
Variable Frequency Drive
method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
185
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 383,6 445,0 478,9 546,4 583,5 646,7
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 77 88 99 121 132 143
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
186
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 682,2 742,0 805,6 878,5
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 132 143 154 165
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat
exchanger inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
187
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 383,9 445,3 479,2 546,7 583,8 647,0
Current
Max. running
(3) A 588 625 693 754 836 936
current
Max. current for
(4) A 647 688 762 829 920 1030
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 77 88 99 121 132 143
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 236 248 276 291 326 367
Compressor #1
Max. running
current (6) A 236 248 276 291 326 367
Compressor #2
Main switch size (6) A 800 800 1000 1000 1250 1250
Terminal
(6) - Cables Cables Bars Bars Bars Bars
connection
Cable per phase (6) - 2x240 mm² 2x240 mm² 2x300 mm² 2x300 mm² 2x400 mm² 2x400 mm²
Short circuit
(6) kA 20 20 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
188
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 682,7 742,5 806,2 879,1
Current
Max. running
(3) A 967 1042 1132 1157
current
Max. current for
(4) A 1064 1146 1245 1273
wire sizing
Maximum starting
(5) A 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 132 143 154 165
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 388 419 451 484
Compressor #1
Max. running
current (6) A 388 419 451 484
Compressor #2
Cable per phase (6) - 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
189
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 670,6 713,8 759,1 832,1 905,1 987,1
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 121 121 132 132 143 154
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
190
ELECTRICAL SPECIFICATIONS
191
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 670,6 713,8 759,1 832,1 905,1 987,1
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 121 121 132 132 143 154
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
192
ELECTRICAL SPECIFICATIONS
193
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 663,8 710,1 752,2 841,6 912,9 992,1
Current
Max. running
(3) A 913 969 1027 1165 1205 1301
current
Max. current for
(4) A 1004 1066 1130 1282 1326 1431
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 121 121 132 132 143 154
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 367 388 411 480 521 562
Compressor #1
Max. running
current (6) A 367 388 411 480 521 562
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 2000
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 3x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
194
ELECTRICAL SPECIFICATIONS
195
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 628,4 673,5 717,7 754,6 827,1 897,7
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 121 132 143 132 143 154
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
196
ELECTRICAL SPECIFICATIONS
197
ELECTRICAL SPECIFICATIONS
Nominal Running
(1) A 597,1 638,3 679,0 725,2 795,2 862,6
Current
Max. running
(3) A 918 939 994 1085 1124 1218
current
Max. current for
(4) A 1010 1033 1093 1194 1236 1340
wire sizing
Maximum starting
(5) A 0 0 0 0 0 0
current
Fan starting
(6) - EC Brushless Motor
method
Max running
(6) A 5,50
current per fan
Total fans running
(6) A 121 132 143 132 143 154
current
Compressor
Variable Frequency Drive
starting method
Max. running
current (6) A 370 367 388 440 480 521
Compressor #1
Max. running
current (6) A 370 367 388 440 480 521
Compressor #2
Main switch size (6) A 1250 1250 1250 1600 1600 1600
Terminal
(6) - Bars Bars Bars Bars Bars Bars
connection
Cable per phase (6) - 2x400 mm² 2x400 mm² 2x400 mm² 2x500 mm² 2x500 mm² 2x500 mm²
Short circuit
(6) kA 25 25 25 25 25 25
current Icw 1 sec.
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger
inlet water temperature 12°C, outlet water temperature 7°C. Fouling factor = 0
(2) Voltage unbalance between phases must be within ± 3%.
(3) Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
(4) Based on minimum allowed voltage → Max. current for wire sizing = Max. Running current x 1,1
(5) In case of inverter driven compressor, the starting current is zero
(6) It may change in case of unit with options or customized unit. Refer to dedicated unit’s wiring diagram.
198
ELECTRICAL SPECIFICATIONS
199
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
200
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
201
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
202
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
203
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
204
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
205
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
206
SOUND LEVELS
NOTE: with exception of OPT76b Sound proof system (COMPRESSOR) the other options from Price List have no impact on sound performances
Customized selection made to meet specific project’s requirements could lead to change in sound performances. Refer to the customized
selection for specific data.
Despite "Sound power" and "Sound pressure" both share the same unit of measure, the decibel (dB), and the
term "sound level" is commonly substituted for each they represent two distinct characteristics of sound.
Sound power is the acoustical energy emitted by the sound source. it is an absolute value and is not affected by
the environment.
Sound pressure is a pressure disturbance in the atmosphere whose intensity is influenced not only by the strength
of the source, but also by the surroundings and the distance from the source to the receiver.
Although dB is commonly used when referring to measuring sound, humans do not hear all frequencies equally. In
order to account for this, corrections have been created to give a loudness measurement that takes into account
how the human ear actually perceives sound. The most common of these corrections is the “A” weighting (different
weights are applied at different frequencies). Values that have been corrected using the “A” weighting system are
shown using units of dB(A). Values not corrected to account for human hearing are written using units of dB. The
sound spectrum in octave band is reported in dB while the overall value of Sound power and pressure are in dB(A).
To calculate the sound pressure at different distances from the chiller the generic calculation of sound power from
sound pressure is as follows:
𝑳𝒑 = 𝑳𝒘 − 𝟏𝟎 ∗ 𝐥𝐨𝐠 𝟏𝟎 𝑨𝒅
Where Ad is the surface around the chiller calculated at the specific distance d
207
SOUND LEVELS
208
SOUND LEVELS
209
SOUND LEVELS
210
SOUND LEVELS
211
SOUND LEVELS
212
OPERATING LIMITS
The above graphic represents a guideline about the operating limits of the range. Please refer to the latest
Chiller Selection Software (CSS) for real operating limits working conditions for specific model and
configuration.
For operation with EWLT below 4°C, the unit must operate with glycol mixture.
The glycol percentage must be provided according to the minimum ELWT needed.
213
OPERATING LIMITS
The above graphic represents a guideline about the operating limits of the range. Please refer to the latest
Chiller Selection Software (CSS) for real operating limits working conditions for specific model and
configuration.
For operation with EWLT below 4°C, the unit must operate with glycol mixture.
The glycol percentage must be provided according to the minimum ELWT needed.
214
OPERATING LIMITS
EWA(H)(D)~TZC chiller is design for outdoor installation with free discharge on the condenser inlet/outlet.
All data are declared considering the unit installed without any additional pressure drop for the condenser
air flow and in compliancy with the installation prescriptions.
Any additional pressure resistance added on the condenser air flow will cause the reduction of the air flow
and so a derating of the condenser performance. The different performance of the condenser reflects in a
loss of cooling capacity and increased compressor power input.
Within certain limit is possible to add pressure resistance on the condenser discharge of the standard unit.
The additional pressure resistance is referred to the standard air-flow (refer to the Specification tables for
the air flow rate for the specific unit).
Example: APR = 30 Pa for unit EWAHC11TZSSC2 means that the 30 Pa are referred to 121728 l/s.
Below a graphic representation of the
In the following tables are indicated the correction factors for cooling capacity, compressor power input
and max operating temperature according different levels of Additional Pressure Resistance (A.P.R.).
215
OPERATING LIMITS
Minimum glycol percentage for low air ambient temperature to prevent freezing of
the hydraulic circuit
In presence of glycol in the water system the performance will be affected. Refer to the selection software. All
machine protection systems, such as antifreeze, and low-pressure protection will need to be adjusted in
accordance to the type and percentage of the glycol.
Elevation above sea level [m] 0 300 600 900 1200 1500 1800
barometric pressure [mbar] 1013 977 942 908 875 843 812
Cooling capacity correction factors 1 0,993 0,986 0,979 0,973 0,967 0,96
Power input correction factors 1 1,005 1,009 1,015 1,021 1,026 1,031
Maximum operating altitude is 1800 m above sea level.
Contact factory if the unit has to be installed 1000 m above the sea level.
For each model please, refer to minimum water flow rate indicate din technical specifications tables.
216
OPERATING LIMITS
Operating limits for Storage Environmental conditions must be within the following limits:
- Minimum ambient temperature: -20°C
- Maximum ambient temperature: 57°C
- Maximum R.H.: 95% not condensing
Storage below the minimum temperature may cause damage to components. Storage above the maximum
temperature causes opening of safety valves.
Storage in condensing atmosphere may damage electronic components.
Water treatment Before putting the unit into operation, clean the water circuit. Dirt, scales, corrosion
debits and other material can accumulate inside the heat exchanger and reduce its heat exchanging capacity.
Pressure drop can increase as well, thus reducing water flow. Proper water treatment therefore reduces the risk
of corrosion, erosion, scaling, etc. The most appropriate water treatment must be determined locally, according
to the type of system and water characteristics. The manufacturer is not responsible for damage to or
malfunctioning of equipment caused by failure to treat water or by improperly treated water.
Water-glycol mixture with the passing of time decays and it gives rise to acid products that can start corrosion
processes. Also, the degradation of products in the water-glycol mixture may allow biological proliferation and
thus bacteria formation can give rise to corrosion. For these reasons’ glycol has to be used with suitable corrosion
inhibitors.
The corrosion inhibitors have a lifespan (1 or 2 years) so it is important to periodically verify the percentage of the
water-glycol mixture
Inhibitors may become insufficient due to “top ups” of water in the circuit (if water is added to the mixture due to
low level, the percentage of glycol must remain as per requirements therefore the correct % of glycol should also
be integrated.
The parameters to be checked regularly are the antifreeze concentration and the pH of water-glycol mixture
217
OPERATING LIMITS
Heat recovery Units may be optionally equipped with heat recovery system. This system is made by a
water-cooled heat exchanger located on the compressors discharge pipe and a dedicated management of
condensing pressure. There is a plate to plate heat exchanger for each circuit. Check on unit drawing the
position of Heat recovery heat exchangers.
The heat recovery exchangers are not manifolded on water side. All hydraulic connection must be done on job
site. The water connections of recovery exchangers are threated. Check on unit drawing for the size of the
connection.
Is strongly recommended to install a 3-ways valve on the heat recovery loop. The valve, not provided by
factory, acts as a mixing valve, managed by the unit controller based on the temperature of the water entering
the heat exchangers avoiding excessively cold water to enters.
This to ensure that the compressor operate within allowed temperatures range. Minimum water temperature
to ensure proper chiller operation is 25°C.
NOTE: It is a responsibility of plant designer and chiller installer to guarantee the respect of this value by
using the recirculating bypass valve or other systems.
The flow switch must be installed on the heat recovery water loop. Pump, valve, flow switch and manifold are not
provided by the factory.
218
OPERATING LIMITS
Is possible to operate with variable flow rate on heat recovery. The control for the pump speed (not provided by
the factory) can be done to keep constant the delta-T on heat recovery loop.
In this case isolating valve must be installed on each heat recovery exchanger to avoid that water passes through
a heat recovery exchanger while the related compressor is OFF. The state of the isolating valve must be linked to
the state of the compressor.
NOTE: flow switch must be set to detect the minim flow for the circuit.
series model THR - water volume [lt] series model THR - water volume [lt]
710 22,3 H11 36,5
EWAD~TZ X-S/R C EWAD~TZ S-S/L/R C
219
OPERATING LIMITS
Configuration of the hydronic kit with pump pushing fluid in the evaporator:
220
OPERATING LIMITS
Configuration of the hydronic kit with suction pump from the evaporator:
221
OPERATING LIMITS
222
OPERATING LIMITS
EWAH~TZ S S/L/R C-
Single pump – Low lift
223
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the pressure
drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
224
OPERATING LIMITS
EWAH~TZ S S/L/R C-
225
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water
temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the pressure
drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
226
OPERATING LIMITS
EWAH~TZ S S/L/R C-
227
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water
temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the pressure
drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
228
OPERATING LIMITS
EWAH~TZ S S/L/R C-
229
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the pressure
drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
230
OPERATING LIMITS
EWAH~TZ X S/L/R C-
Single pump – Low lift
231
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the pressure
drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
232
OPERATING LIMITS
EWAH~TZ X S/L/R C-
Single pump – High lift
233
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
234
OPERATING LIMITS
EWAH~TZ X S/L/R C-
235
OPERATING LIMITS
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
236
OPERATING LIMITS
EWAH~TZ X S/L/R C-
Dual pump – High lift
237
OPERATING LIMITS
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water
temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the pressure
drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
238
OPERATING LIMITS
EWAD~TZ S S/L/R C-
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
239
OPERATING LIMITS
EWAD~TZ S S/L/R C-
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
240
INSTALLATION NOTES
EWAD~TZ S S/L/R C-
Dual pump – Low lift
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
241
INSTALLATION NOTES
EWAD~TZ S S/L/R C-
Dual pump – High Lift
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
242
INSTALLATION NOTES
EWAD~TZ X S/R C-
Single pump – Low Lift
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
243
INSTALLATION NOTES
EWAD~TZ X S/R C-
Single pump – High Lift
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
244
INSTALLATION NOTES
EWAD~TZ X S/R C-
Dual pump – Low Lift
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
245
INSTALLATION NOTES
EWAD~TZ X S/R C-
Dual pump – High Lift
Available
Pump Pump Water Evaporator Filter water
Motor Pump water
motor motor Power Insulation flow pressure pressure head @
ref. power current PN protecti head @ std
models supply class rate drop drop std
curve input on condition (3)
(5) (1) (1) (2) condition
(1) (4)
(1) Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet
water temperature 12°C, outlet water temperature 7°C.
(2) The pressure drops for the filter are referred to the one provided by DAIKIN as option (option code 115). In case of filter provided by third party supplier the
pressure drop in the table must not be considered.
(3) Total head of the pump.
(4) Available head external to the unit (already including the pressure drop in the exchanger and in the filter (if opt 115 is selected)
(5) Refer to 400 V power supply
The above data are referred to the unit without additional optional.
In case of unit with opt. 08, 154, 187 refer the selection sheet for the actual pressure drops.
The above data are referred the unit installed in compliancy with installation prescription.
All the data are subject to change without notice. For updated information on project base refer to Chiller Selection Software and unit nameplate.
246
INSTALLATION NOTES
Warning Installation and maintenance of the unit must be performed only by qualified personnel who have
knowledge with local codes and regulations, and experience with this type of equipment. Must be avoided the
unit installation in places that could be considered dangerous for all the maintenance operations.
Handling Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull
the unit from anything other than the base frame. Never allow the unit to fall during unloading or moving as this
may result in serious damage. To lift the unit, rings are provided in the base frame of the unit. Spreader bar and
cables should be arranged to prevent damage to cabinet.
Location The units are produced for outdoor installation on roofs, floors or below ground level on condition that
the area is free from obstacles for the passage of the condenser air. The unit should be positioned on solid
foundations and perfectly leveled; in the case of installation on roofs or floors, it may be advisable to arrange
the use of suitable weight distribution beams. When the units are installed on the ground, a concrete base at
least 250 mm wider and longer than the unit’s footprint should be laid. Furthermore, this base should withstand
the unit weight mentioned in the technical data table.
Space requirements Each side of the unit must be accessible after installation for periodic service.
The following pictures shows you minimum recommended clearance requirements for service activities.
• A at least 1500 mm
• B at least 1800 mm
• C between 1800 and 3600 mm. To be checked on unit drawings.
These clearances ensure proper space to perform all possible maintenance activities and replacing of unit’s
components.
NOTE: Installations with different (lower) clearances around the unit should be subjected and
approved by local service referent.
The units are air-cooled, then it is important to respect minimum distances which guarantee the best ventilation
of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in cooling
capacity and an increase in electricity consumption.
To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the
condenser heat transfer surface.
Two conditions must be avoided to achieve the best performance: warm air recirculation and coil starvation. Both
these conditions cause an increase of condensing pressures that results in reductions in unit efficiency and
capacity.
247
INSTALLATION NOTES
For single chiller installation in proximity of a wall the following indications are recommended:
If H lower than chiller height and L must be at least 3 m no impact on chiller performances.
If H lower than chiller height and/or L shorter than 3 m chiller operation could be affected according to wind
direction, ambient temperature. In such situation a proper analysis should be carried out to evaluate the impact on
chiller operation considering all the specific boundary conditions.
Information on nominal air-flow are indicated in Technical specification tables.
The indicated airflow corresponds to an air velocity on condenser coil of ≈ 2.7 m/s.
The walls have the same height of the chillers; ambient temperature = 46°C
In this due to the wind direction air recirculation will occur lading to air condensing pressure.
As result of this installation the impact on cooling capacity can be estimated in - 5% (avg. depending on unit size)
on the catalog data.
248
INSTALLATION NOTES
with walls having the same height of the chillers. The space between the chillers must be at least 1500 mm to
ensure space to operate on the electrical panel. In this situation the impact on performances is the same of the
previous.
The walls have the same height of the chillers; ambient temperature = 35°C;
The air temperature entering the second chiller is higher due to the mix with the exhaust air from 1th chiller in
following the wind direction. The impact on the cooling capacity of the second chiller can be estimated in
approximately -8% (avg. depending on unit size) on the catalog data.
249
INSTALLATION NOTES
The above examples are intended as general guidelines and no comprehensive of all possible plant configuration
and operating conditions.
In case of critical installation (not compliant with the advised clearances) should be analyzed by plant designer
and proper to evaluate the impact on chiller operation and identify possible countermeasures.
250
INSTALLATION NOTES
Water piping
The water system must have:
251
TECHNICAL SPECIFICATIONS
General The chiller will be designed and manufactured in accordance with the following European directives:
• Construction of pressure vessel 2014/68/EU
• Machinery Directive 2006/42/EC
• Low Voltage 2014/35/EU
• Electromagnetic Compatibility 2014/30/EU
• Electrical & Safety codes EN 60204–1
• Manufacturing Quality Standards UNI – UNI EN ISO 14001
To avoid any losses, the unit will be tested at full load in the factory (at the nominal working conditions and
water temperatures). The chiller will be delivered to the job site completely assembled and charged with
refrigerant and oil.
The installation of the chiller must comply with the manufacturer’s instructions for rigging and handling
equipment.
The unit will be able to start up and operate (as standard) at full load with:
- outside air temperature from ............... °C to ............... °C
- evaporator leaving fluid temperature between ............... °C and ............... °C
-
Refrigerant HFO R1234ze(e) , HFC R134a
Operating voltage range should be 400V ±10%, 3ph, 50Hz, voltage unbalance maximum 3%, without neutral
conductor and shall only have one power connection point.
Unit description Chiller shall include two or three independent refrigerant circuits, semi-hermetic type
rotary single screw compressors, electronic expansion device (EEXV), direct expansion ‘shell & tube’
evaporator, air-cooled condenser section made with aluminum Microchannel technology, R-134a
refrigerant, lubrication system, motor starting components, discharge line shut-off valve, control system
and all components necessary for a safe and stable unit operation.
Sound level and vibrations Sound power level shall not exceed ………dB(A). The sound power levels must be
rated in accordance to ISO 9614 and Sound Power rated according to ISO 3744 (other types of rating cannot
be used). Vibration on the base frame should not exceed 2 mm/s.
252
TECHNICAL SPECIFICATIONS
• The compressor shall be equipped with an electric oil-crankcase heater.
• Compressor shall be fully field serviceable. Compressor that must be removed and returned to the factory for
service shall be unacceptable.
Cooling capacity control system the chiller will have a microprocessor for the control of the compressor
capacity in order to continuously modulate the compressor’s
rotational speed.
• The unit capacity control shall be infinitely modulating between 100% and the minimum.
• The system shall control the unit based on the leaving evaporator water temperature that shall be controlled
by PID (Proportional Integral Derivative) logic.
Evaporator
The units shall be equipped with a direct expansion shell & tube evaporator with copper tubes rolled into steel
tube sheets.
The external shell shall insulate with flexible, closed cell polyurethane insulation material (20 -mm thick).
• The evaporator will have 2 circuits, one for each compressor and shall be single refrigerant pass.
• The water connections shall be VICTAULIC type connections as standard to ensure quick mechanical
disconnection between the unit and the hydronic network.
• The evaporator will be manufactured in accordance to PED approval.
• Flow switch on evaporator available as option (shipped loose).
• Water filter needs to be provided on the plant.
Condenser coil the condenser is made entirely of aluminum with flat tubes containing small channels.
Full - depth louvered aluminum fins a r e inserted between the tubes maximizing the heat exchange.
The Microchannel technology ensures the highest performance with the minimum surface for the exchanger.
The quantity of refrigerant is also reduced compared to Cu/Al condenser. Special treatments ensure resistance
to the corrosion by atmospheric agents extending the life time (available on request).
Condenser fans the condenser fans used in conjunction with the condenser coils, shall be propeller type
with aluminum-magnesium alloy blades for higher efficiencies. Each fan shall be protected by a fan guard.
• The air discharge shall be vertical, and each fan must be coupled to the electrical motor, supplied as standard
to IP54 and capable to work to ambient temperatures of - 20°C to + 65°C.
• The condenser fans shall have as a standard a thermally protection by internal thermal motor protection and
protected by circuit breaker installed inside the electrical panel as a standard.
Refrigerant circuit the unit shall have two or three independent refrigerant circuits.
The circuit shall include as standard: electronic expansion device piloted by unit’s microprocessor control,
compressor discharge shut-off valves, economizer circuit, sight glass with moisture indicator, replaceable filter
drier, charging valves, high pressure switch, high- and low-pressure transducers, oil pressure transducer and
insulated suction line.
Hydronic kit options (on request) The hydronic module shall be integrated in the chiller chassis without
increasing its dimensions and includes the following elements: centrifugal pump with motor protected by a
circuit breaker installed in control panel, water filling system with pressure gauge, safety valve, drain valve.
• The hydronic module shall be assembled and wired to the control panel.
• A choice of two pump types shall be available:
- in-line single pump
- in-line twin pumps.
Master / Slave the unit shall be able to operate in Master / Slave mode in order to be connected with other
similar unit (up to 4). The master unit shall manage the slaves connected in series on the hydraulic plant with the
aim of optimize the running hours of each compressor and to balance running hours.
iCM Standard the unit shall be able to control the primary loop system (for systems up to 4 chillers) allowing in
addition to the Master/Slave functionality also the capability to share the load among the unit according the optimal
condition and managing also the primary pumps integrated on the unit or external. In case of external pumps,
the control should be able to manage dedicated pumps as well as manifolded pumps including the stand-by pumps
if present.
Electrical control panel Power and control shall be located in the main panel that will be manufactured to
ensure protection against all weather conditions.
• The electrical panel shall be IP54 and (when opening the doors) internally protected against possible
accidental contact with live parts.
• The main panel shall be fitted with a main switch interlocked door that shuts off power supply when opening.
• The power section will include compressors and fans protection devices, fans starters and control.
253
TECHNICAL SPECIFICATIONS
Controller The controller will be installed as standard and it will be used to modify unit set-points and check
control parameters.
• A built-in display will shows chiller operating status plus temperatures and pressures of water, refrigerant
and air, programmable values, set-points.
• A sophisticated software with predictive logic, will select the most energy efficient combination of compressors,
EEXV and condenser fans to keep stable operating conditions to maximize chiller energy efficiency and reliability.
• The controller will be able to protect critical components based on external signals from its system (such as
motor temperatures, refrigerant gas and oil pressures, correct phase sequence, pressure switches and
evaporator). The input coming from the high pressure switch cuts all digital output from the controller in less
than 50ms, this will be an additional security for the equipment.
• Fast program cycle (200ms) for a precise monitoring of the system.
• Floating point calculations supported for increased accuracy in P/T conversions.
254